T7415A / KTF20 / DKF20

CABLE-TYPE BULB TEMPERATURE SENSORS

Fig. 1. The KTF20

GENERAL

The T7415A//KTF2/DKF20 Cable-type Bulb Temperature Sensor can be used as

immersion sensors

return air sensors

The sensors can be employed for hot and cold water installations in the following control systems:

Excel 5000

MicroniK 200

MicroniK 100

Excel Classic

Excel Plus

High Performance Excel Plus

Excel EMC

or other systems using PT1000 or NTC 20kΩ temperature sensing elements.

PRODUCT DATA

FEATURES

PT1000 or NTC 20ktemperature sensing element

Wide sensing range

High accuracy

Models

OS no.

 

description

sensing range

T7415A1007

 

Cable-type Bulb PT1000

-20...+100 °C

 

Temperature Sensor

(-4...+212 °F)

 

 

T7415A1015

 

Cable-type Bulb PT1000

-20...+300 °C

 

Temperature Sensor

(-4...+572 °F)

 

 

KTF20

 

Cable-type Bulb NTC20kΩ

-20...+100 °C

 

Temperature Sensor

(-4...+212 °F)

 

 

DKF20

 

Cable-type Bulb NTC20kΩ

-20...+100 °C

 

Mean value Sensor

(-4...+212 °F)

 

 

KTF20-B

 

Bulk shipment of 50 KTF20

see above

SPECIFICATION

Nominal value

 

 

PT1000

1000 Ω at 0 °C

NTC20kΩ

20 kΩ at 25 °C

Accuracy

 

 

PT1000

IEC751 Class B

 

0.3 K +0.5% • |t| (t in °C)

NTC20kΩ

0.3 K at 25 °C

Sensitivity

 

 

PT1000

≈ 3.85 Ω / K

NTC20kΩ

≈ -934.5 Ω / K at 25 °C (non-linear)

Response time

τ0.5

 

immersion well app.

≈ 10 s

duct application

τ0.5

≈ 2 min at air velocity

of 1 m/s (3.3 ft/s)

Electrical connection

T7415A/KTF20

2 m cable, 2-core

DKF20

2 m cable, 3-core

Ambient Limits (wiring box)

Storage temperature

-25...+70 °C (-13…+158 °F)

Humidity

5…95% rh, non-condensing

Safety

IP64 as per EN 60529

Dimensions

see Fig. 2 on page 2

® U.S. Registered Trademark

 

EN0B-0362GE51 R0907

Copyright © 2007 Honeywell Inc. • All rights reserved

 

 

 

 