Setting the Switching Point

The interrelation between air speed and resistance change is not linear. In the lower range (low rates of flow) the change of resistance is very large. In the upper range, the change of resistance at identical changes in the rate of flow becomes increasingly smaller. When setting the switching point, it must first be determined what change is to be monitored, since some settings result in certain disadvantages. The following requirements must be taken into consideration:

Low change in the rate of flow in the high flow speed range: the switching point must be chosen very close to the measuring value of the normal flow, since the change of measuring values is very small when the rate of flow changes. Since the temperature compensation exhibits a certain amount of delay in comparison to the actual change of temperature, such a setting of the switching point is possible only with slow changes of temperature.

Low change in the rate of flow in the low flow speed range: the switching point may be selected at a greater distance from the measuring value of the normal rate of flow, since the changes of the measuring values are larger when the rate of flow changes. A change in temperature has no effect on the switching behavior.

Large change in the rate of flow: in most cases like this a simple yes/no statement is desired (e.g. ventilator running or ventilator stopped). Therefore, a larger safety margin may be selected, so that neither temperature changes nor turbulence have any influence on the switching behavior.

Commissioning of KSL..

 

Start-up bypass

 

 

 

Jumper set

= start-up bypass active for approx. 60 sec. Yellow LED „Time“ is on

Jumper not set

= start-up bypass inactive

Connection and commissioning must be performed by properly authorized and qualified personnel!

When commissioning and adjusting the devices, the following procedure is recommended:

Install and connect the flow controller in accordance with installation instructions and conditions.

Set jumper for start-up bypass, if required.

Set trimmer „Sensitivity“ to minimum sensitivity (left limit stop).

Connect mains voltage. The green LED lights up. If the jumper has been set, the start-up bypass procedure will be executed (approx. 60 sec.).

Set nominal rate of flow.

Slowly turn trimmer „Sensitivity“ clockwise until the yellow LED lights up and the signal output switches. In order to avoid erroneous switching at low changes of flow, turn the potentiometer slightly past the switching point.

To check the function of the flow controller, reduce or stop the flow.

The yellow LED will go off (output relay at RLSW4R is released).

The device is now set to function.

Trouble shooting

Problem

Possible Cause

Corrective Action

 

 

 

KSL... does not function at all

None or wrong mains voltage

Check mains voltage and connection

 

connected

 

 

 

 

KSL... does not detect flow

Sensor not installed correctly

Check installation conditions

 

 

 

KSL... exhibits changed tripping behavior

Sensor heavily contaminated by the

Carefully clean sensor with water

 

medium

 

 

 

 

KSL... switches at rapid temperature increase

Temperature gradient is outside of

Turn potentiometer „Sensitivity“ slightly

of the medium

technical specifications

further clockwise.

 

 

Check temperature gradient of the

 

 

system.

Should you have any further questions, please contact

TELEFON: 0 70 31 / 637-02 y FAX: 0 70 31 / 637-850 y INTERNET: http://www.honeywell.de/fema

BANKEN: Deutsche Bank AG Böblingen 05 / 89 200 (BLZ 600 700 70) y Volksbank Schönbuch eG 784 001 (BLZ 603 628 04) VORSTAND: Horst Bellwied, Regine Blickwede, Joachim Frosch, Wolfgang Fuchs, Horst Wild, Michael Löffler (stellv.)

VORSITZENDER DES AUFSICHTSRATES: Arnold Günther y SITZ: Offenbach am Main, Amtsgericht Offenbach am Main 5 HRB 6225

22.08.2001

Fema Regelgeräte

Honeywell AG

Böblinger Straße 17

D-71101 Schönaich

Airflow Controller

Operating Instructions for Airflow Controller

KSL..