Honeywell HZ432 TrueZONE Specification Sheet

5 (1)

HZ432 TrueZONE® Panel

SUBMITTAL SHEET

FEATURES

APPLICATION

The HZ432 TrueZONE® panel controls:

Single-stage, multi-stage, conventional, or heat pump heat/ cool HVAC equipment up to 3 stages of heat and 2 stages of cool;

Dual-fuel systems with up to 2 heat pump stages and 2 fossil fuel stages;

2, 3, or 4 zones and is expandable to 32 zones using wired thermostats with the optional TotalZone® Add-A-Zone panel;

2, 3, or 4 zones with wireless thermostats when used with the optional wireless adaptor.

Intuitive installer setup with easy-to-follow, digital display uses real language to guide installer through configuration

Universal application for any HVAC system using conventional thermostat wiring (R W Y G C etc.)

Standard checkout procedure ensures correct operation before leaving the job

Robust push terminals for up to two wires per terminal

Common-sense LEDs indicate stage of heat and damper state

Control of two or three wire dampers with open or closed logic

Variable-speed fan control lowers fan speed when one zone is calling for cooling

Discharge air temperature staging down-stages equipment when near high or low limit

Advanced dual-fuel operation changeover based on outdoor temp and duration of Y2 call

68-3071—01

Honeywell HZ432 TrueZONE Specification Sheet

HZ432 TRUEZONE® ZONE PANEL

SPECIFICATIONS

Input Ratings:

Voltage: 18-30 VAC 50/60 Hz powered by a transformer of 40

VA or more

Current Draw:

Zone Panel: 8.5 VA max. All VA specifications at 24 VAC.

Wiring:

 

18or 20-gauge solid (not stranded) wire

 

Humidity Ratings:

 

5% to 90% RH non-condensing

 

Temperature Ratings:

13.42

(341)

Shipping: -20° to 150°F (-29° to 66°C)

 

Operating: -40° to 165°F (-40° to 74°C)

 

Dimensions:

See Fig. 1.

Mounting:

Mounts with either 2 user-supplied screws at center line to mount onto 2 x 4, or with 4 screws at corners for wall mount.

Recommended Thermostats:

 

 

See Table 1.

8 (203)

1.86 (47)

 

 

Recommended Dampers:

 

M24797

See Tables 2 and 3.

Fig. 1. HZ432 TrueZONE panel dimensions in in. (mm).

For maximum number of dampers per zone see Table 4.

Accessories:

See Table 5.

Emissions:

Complies with FCC Class B, part 15 requirements.

Table 1. Recommended thermostats.

System

Non-programmable

Programmable

Single-Stage

TH5110D, TH3110D, T87N

TH8110U, TH6110D, TH4110D

 

 

 

Multi-Stage

TH5220D

TH8320U, TH8321U, TH6220D, YTH9421C

 

 

 

Heat-Pump

TH5220D (2H/1C only), TH3210D (2H/1C only),

TH8320U (up to 3H/2C), TH8321U (up to 3H/2C),

 

TH5320U* (up to 3H/2C)

TH6320U* (up to 3H/2C),TH6220D (2H/1C only),

 

 

TH4210D (2H/1C only), YTH9421C

 

 

 

Wireless

TH5320R

TH6320R

 

 

 

Commercial

 

TH7220U, TH8220U

 

 

 

Note: All versions of the model numbers listed above will work with the applications they are listed for. *This thermostat cannot control two stages of fossil fuel when in emergency heat mode.

Wireless adaptor required when used with wireless thermostats.

68-3071—01