READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.
THIS MANUAL IS USED BY QUALIFIED APPLIANCE TECHNICIANS ONLY.
HAIER DOES NOT ASSUME ANY RESPONSIBILITY FOR PROPERTY DAMAGE OR PERSONAL INJURY FOR IMPROPER SERVICE PROCEDURES DONE BY ONE UNQUALIFIED PERSON.
- 1 -
Haier air conditioner |
Edition: 20070116 |
CONTENTS
1. GENERAL INFORMATION............................................................... |
3 |
2. SPECIFICATION............................................................................... |
6 |
3. ELECTRICAL CONTROL.................................................................. |
8 |
4. THERMISTER RESISTANCE CHART............................................. |
30 |
5. TROUBLE SHOOTING.................................................................... |
40 |
6. PERFORMANCE CURVES DIAGRAM........................................... |
46 |
6.1 High drop and long pipe capacity modification curves…………………………......46 |
6.2.1Cooling capacity-temperature curves……………………………………………..47
6.2.2Heating capacity-temperature curves……………………………………………..49 6.3 Air outlet temp.-ambient temperature curves……………………………………….51
6.4.1 Cooling discharge pressure curves................................................................... |
53 |
6.4.2 Cooling suction pressure curves....................................................................... |
55 |
6.4.3 Heating discharge pressure curves................................................................... |
57 |
6.4.4 Heating suction pressure curves....................................................................... |
59 |
6.5 Sensible cooling value-temperature curves......................................................... |
61 |
6.6 Power consumption-temperature curves............................................................. |
63 |
6.7 Noise curves........................................................................................................ |
65 |
6.8 Compressor performance curves………………………………………………........66 |
|
7. WIRING DIAGRAM.......................................................................... |
68 |
8. SCHEMATIC DIAGRAM OF PCB.................................................... |
70 |
9. INSTALLATION................................................................................ |
72 |
- 2 -
Haier air conditioner |
Edition: 20070116 |
1. General information
This Service Manual describes the operation, disassembly, troubleshooting, and repair of Haier Room Air Conditioners, etc. It is intended for use by authorized services who troubleshoot and repair these units.
It is assumed that users of this manual are familiar with the use of tools and equipment used to troubleshoot and repair electrical, mechanical, and refrigeration systems; and understand the terminology used to describe and discuss them.
Haier urges you read and follow all safety precautions and warnings contained in this manual. Failure to comply with safety information may result in severe personal injury or death.
Related Publications
This is a base service manual, covering a range of similar models. It is intended to be used in conjunction with the Parts Manual and Technical Sheet covering specific model being serviced.
NOTE: General Precautions and Warnings
WARNING
To avoid risk of personal injury or death due to electrical shock, disconnect electrical power to unit before attempting to service the unit.
WARNING
To avoid risk of personal injury or death due to electrical shock, DO NOT, under any circumstances, alter the grounding plug .Air conditioner must be grounded at all times. Do not remove warning tag from power cord. If a two-prong (non-grounding) wall receptacle is encountered, contact a qualified electrician and have the receptacle replaced with a properly grounder wall receptacle in accordance with the National Electrical Code.
WARNING
To avoid risk of heat exposure, which may cause death or severe illness, air conditioner must be monitored when failures or shuts down.
WARNING
To avoid risk of personal injury or death due to electrical shock, grounding wires and wires colored like grounding wires are NOT to be used as current carrying conductors. The standard accepted color coding for ground wires is green or green with a yellow stripe. Electrical components such as the compressor and fan motor are grounded through an individual wire attached to the electrical component and to another part of the air conditioner. Grounding wires should not to be removed from individual components while servicing, unless the component is to be removed and replaced. It is extremely important to replace all removed grounding wires before completing service.
- 3 -
Haier air conditioner |
Edition: 20070116 |
MODEL: HSU-09HSA03/R2(DB)
Product Features
Healthy negative ionIntelligent airflow
Entire auto modeESF filter
Easy clean design
Main Specification
Cooling Capacity: 2400W
Power Input: 680W
Current Input:3.50A
EER:3.53
Heating Capacity: 2650W
Power Input:730W
Current Input: 3.8A
COP: 3.63
Air Volume(Indoor/outdoor): 400m3/h
Power Supply: 1PH/230V/ 50Hz
-4 -
Haier air conditioner |
Edition: 20070116 |
MODEL: HSU-12HSA03/R2(DB)
Product Features
Healthy negative ionIntelligent airflow
Entire auto modeESF filter
Easy clean design
Main Specification
Cooling Capacity: 3300W
Power Input: 1078W
Current Input: 4.9A
EER:3.06
Heating Capacity: 3600W
Power Input:1230W
Current Input: 5.4A
COP: 2.93
Air Volume(Indoor/outdoor): 450m3/h
Power Supply: 1PH/230V/ 50Hz
-5 -
Haier air conditioner |
Edition: 20070116 |
2. Specification
|
Item |
Unit |
HSU-09HSA03 |
HSU-12HSA03 |
|
|
/R2(DB) |
/R2(DB) |
|||
|
|
|
|||
|
|
|
|
|
|
Power |
|
PH, V, Hz |
1, 230, 50 |
1,230,50 |
|
|
|
|
|
|
|
Climate Type |
|
|
T1 |
T1 |
|
Starting Current |
|
A |
10 |
12 |
|
|
|
|
|
|
|
|
Cooling Capacity |
W |
2400 |
3300 |
|
|
Rated Power |
W |
680 |
1078 |
|
|
|
|
|
|
|
Cooling |
Rated Current |
A |
3.50 |
4.9 |
|
Max Power |
W |
870 |
1350 |
||
|
|||||
|
|
|
|
|
|
|
Max Current |
A |
3.8 |
6.0 |
|
|
EER |
W/W |
3.53 |
3.06 |
|
|
|
|
|
|
|
|
Heating Capacity |
W |
2650 |
3600 |
|
|
Rated Power |
W |
730 |
1230 |
|
|
|
|
|
|
|
Heating |
Rated Current |
A |
3.8 |
5.4 |
|
Max Power |
W |
1100 |
1480 |
||
|
|||||
|
Max Current |
A |
4.4 |
6.8 |
|
|
|
|
|
|
|
|
EER |
W/W |
3.63 |
2.93 |
|
Operating temp. |
Cooling |
|
18~46 |
18~46 |
|
range |
|
|
|
|
|
Heating |
|
-15~24 |
-15~24 |
||
|
H |
rpm |
1150 |
1300 |
|
Indoor fan Velocity |
|
|
|
|
|
M |
rpm |
950 |
950 |
||
|
L |
rpm |
740 |
740 |
|
|
|
|
|
|
|
Outdoor fan Velocity |
|
rpm |
710 |
800 |
|
Indoor Air Volume (High) |
m3 |
400 |
450 |
||
Max. pressure at warm side |
MPa |
4.15 |
4.15 |
||
Moisture Removal |
|
10-3m3/h |
0.83 |
1.2 |
|
Noise Level |
Indoor (H/M/L) |
dB(A) |
42/40/38 |
42/40/38 |
|
|
|
|
|
||
Outdoor |
dB(A) |
48 |
52 |
||
|
|||||
Indoor Weight |
Net |
Kg |
8.6 |
8.6 |
|
|
|
|
|
||
Gross |
Kg |
10.8 |
10.8 |
||
|
|||||
Outdoor Weight |
Net |
Kg |
31 |
33 |
|
|
|
|
|
||
Gross |
Kg |
34 |
36 |
||
|
|||||
|
|
|
|
|
|
Indoor Dimension |
Net |
mm |
760×182×285 |
760×182×285 |
|
Package |
mm |
837×282×312 |
837×282×312 |
||
|
|||||
|
|
|
|
|
|
Outdoor Dimension |
Net |
mm |
780×245×540 |
780×245×540 |
|
|
|
|
|
||
Package |
mm |
790×366×484 |
790×366×484 |
||
|
|||||
|
Manufacture |
|
TOSHIBA |
SANYO |
|
Compressor |
|
|
|
|
|
Type |
|
DA89X1C-20FZ |
C-6RZ092H1A |
||
|
|
|
|
|
|
|
Oil Charge |
ml |
370 |
320 |
|
|
|
- 6 - |
|
|
|
Haier air conditioner |
Edition: 20070116 |
|
||
|
|
|
|
|
|
|
Type |
|
R410A |
R410A |
|
|
|
|
|
|
|
Refrigerant |
Net Charge |
g |
800 |
1200 |
|
Charge if over standard pipe |
g/m |
12 |
12 |
|
|
|
|
||||
|
length |
|
|||
|
|
|
|
|
|
|
|
|
|
|
|
|
Liquid pipe Diameter |
mm |
6.35 |
6.35 |
|
Refrigerant Pipe |
Gas pipe Diameter |
mm |
9.52 |
12.7 |
|
|
|
|
|
|
|
Standard length |
m |
5 |
5 |
|
|
|
|
||||
|
|
|
|
|
|
|
Max length |
m |
15 |
15 |
|
Drain Hose |
Length |
mm |
2000 |
2000 |
|
|
|
|
|
|
|
Diameter |
mm |
16 |
16 |
|
|
|
|
||||
|
|
|
|
|
|
Drainage pipe material diameter |
mm |
16 |
16 |
|
|
Remote Controller Model |
|
YR-H04 |
YR-H04 |
|
|
|
|
|
|
|
|
Class of electric Shock Protection |
|
I |
I |
|
|
Class of Water Proof |
|
IP 24 |
IP 24 |
|
|
|
|
|
|
|
|
Power Cord (Model × Sectional Area) |
|
H05VV-F 3G2.5mm2 |
H05VV-F 3G2.5mm2 |
|
- 7 -
Haier air conditioner |
Edition: 20070116 |
3. Electrical control
. Scope of Application
This specification use for HSU-09/12HSA03/R2 DB frequency conversion air condition are manufactured by Haier air condition parent company. "Setting value" (express in parameter) in this specification means is a parameter that is stored in EEPROM. Refer to [EEPROM parameter table].
1. Chip pin definition
This controller adopts MOTROLA MC68HC908 AB32; Chip each pin definition as following:
1 |
PTC4 |
door switch |
2 |
IRQ |
|
3 |
RST |
over-zero detection |
|
|
|
4 |
PTF0/TACH2 |
remote control receiving |
5 |
PTF1/TACH3 |
SDA |
|
|
|
6 |
PTF2/TBCH2 |
SCL |
7 |
PTF3/TBCH3 |
Buzzer |
|
|
|
8 |
PTF4/TBCH0 |
Swing stepping motor A |
9 |
NC |
|
10 |
PTF7 |
Swing stepping motor D |
11 |
PTF5/TBCH1 |
Swing stepping motor B |
12 |
PTF6 |
Swing stepping motor C |
13 |
PTE0/TXD |
network output |
|
|
|
14 |
PTE1/RXD |
network output |
15 |
PTE2/TACH0 |
PG feedback |
|
|
|
16 |
PTE3/TACH1 |
PG output |
17 |
PTE4/SS |
fresh air |
18 |
PTE5/MISO |
negative ion output |
|
|
|
19 |
PTE6/MOSI |
self check/ decrease time |
20 |
PTE7/SPSCK |
empty |
21 |
VSS |
GND |
22 |
VDD |
VCC |
23 |
PTG0/KBD0 |
ultraviolet ray A |
24 |
PTG1/KBD1 |
empty |
|
|
|
25 |
PTG2/KBD2 |
empty |
26 |
PA0 selection panel 1 |
sliding stepping motor A |
|
|
|
27 |
PA1 high/low drive model |
sliding stepping motor B |
28 |
PA2 large/small model |
sliding stepping motor C |
|
|
|
29 |
PA3 A/B code selection |
sliding stepping motor D |
30 |
PA4 panel selection 2 |
pushup stepping motor A |
31 |
PA5 |
pushup stepping motor B |
|
|
- 8 - |
|
|
Haier air conditioner |
|
Edition: 20070116 |
|||
|
|
|
|
|
|
||
|
32 |
PA6 |
pushup stepping motor C |
|
|
||
|
33 |
PA7 |
pushup stepping motor D |
|
|
||
|
34 |
PTB0/ATD0 |
output outdoor communication |
|
|||
|
35 |
PTB1/ATD1 |
input outdoor communication |
|
|||
|
36 |
PTB2/ATD2 |
room temperature |
|
|
||
|
37 |
PTB3/ATD3 |
inner coil |
|
|
|
|
|
|
|
|
|
|||
|
38 |
PTB4/ATD4 |
swing left stepping motor D |
|
|||
|
39 |
PTB5/ATD5 |
swing left stepping motor C |
|
|||
|
|
|
|
|
|
||
|
40 |
PTB6/ATD6 |
swing left stepping motor B |
|
|
||
|
41 |
PTB7/ATD7 |
swing left stepping motor A |
|
|
||
|
42 |
PTD0 |
swing right stepping motor D |
|
|||
|
43 |
PTD1 |
swing right stepping motor C |
|
|||
|
44 |
VDDAREF |
VCC |
|
|
|
|
|
45 |
AVSS/VREFL |
GND |
|
|
|
|
|
46 |
PTD2 |
swing right stepping motor B |
|
|||
|
47 |
PTD |
swing right stepping motor A |
|
|||
|
|
|
|
|
|
||
|
48 |
PTH0/KBD3 |
central control input |
|
|
||
|
49 |
PTH1/KBD4 |
central control output |
|
|
||
|
|
|
|
|
|
|
|
|
50 |
PTD4/TBCLK |
empty |
|
|
|
|
|
51 |
PTD5 |
G/V LCS K health H heat |
|
|
||
|
52 |
PTD6/TACLK |
G/V WR K operation H dry |
|
|||
|
53 |
PTD7 |
G/V DA |
K power supply |
H cool |
|
|
|
54 |
VREFH |
VCC |
|
|
|
|
|
55 |
VDDA |
VCC |
|
|
|
|
|
56 |
VSSA |
GND |
|
|
|
|
|
57 |
CGMXFC |
|
|
|
|
|
|
58 |
OSC2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
59 |
OSC1 |
|
|
|
|
|
|
60 |
PTC0 |
emergency switch |
|
|
||
|
|
|
|
|
|
|
|
|
61 |
PTC1 |
empty |
K timer |
|
|
|
|
62 |
PTC2/MCLK |
G/V green light K green light H |
|
|||
|
operation |
|
|
|
|
||
|
|
|
|
|
|
|
|
|
63 |
PTC3 |
G/V blue light |
K blue light |
H timer |
|
|
|
64 |
PTC5 |
G/V red light |
K red light |
H health |
|
II. Temperature adjustment function
2.1 During temperature adjustment function, the operation frequency of outdoor unit will be based on indoor temperature and the set temperature.
When air capacity operates automatically; the indoor fan will be controlled on the basis of the requirements of temperature adjustment.
When the unit operates to make heat, the indoor wind unit will be controlled based on scrolling temperature.
- 9 -
Haier air conditioner |
Edition: 20070116 |
2.1.1 Standard of temperature sensor under indoor environment.
When the line is in short circuit or open circuit, the indicator light will be alarming and the indoor fan motor will be off. It will resume to the original state automatically after it returns normally, and operates as usual.
Short circuit:
Temperature: above 126 degrees,
Hex: Above F8H,
Value of Resistance: Below 0.65K, above 4.85V.
Normal temperature:
Temp: 25 degrees,
Hex: 40H,
Value of Resistance: 23K,
Voltage: 2.33V.
Power failure:
Temp: below -31 degrees,
Hex: below 08H,
Value of Resistance: Below 620K,
Voltage: Below 0.15V.
B parameter=4200
R (25degrees) =23K
2.1.2 Value of Resistance of indoor temperature sensor is ignored, when the heat mode is ON and the indoor fan is OFF, as well as after warm start indoor fan operate for 30 seconds. (in order to avoid affection of heat exchanger)
2.2 When frequency increase to holding frequency
In order to oil return fully during operating, the system will must keep some frequencies for a period of time.
|
Time Indication |
|
Frequency indication |
|
|
|
|
|
|
Drying in cool mode |
Heat |
|
Defrosting in heat mode |
Holding frequency |
|
|
|
|
|
60 seconds |
60 seconds |
|
30 seconds |
58Hz |
|
|
|
|
|
After Forced operation OFF at the start status, system will begin to control the temperature area.
2.3 Preset temperature correction
The preset temperature is corrected according to the operating mode, air capacity and forced operation status.
Only in the heat mode to correct the air capacity, confine to the low and middle speed of the air capacity.
Corrected value table for preset temperature:
- 10 -
|
|
Haier air conditioner |
Edition: 20070116 |
||
|
|
|
|
|
|
|
Mode |
Corrected contents |
Corrected variable |
Corrected |
|
|
parameter |
|
|||
|
|
|
|
|
|
|
|
Correct the operating mode |
ETBL0 |
4.67 |
|
|
|
|
|
|
|
|
|
Correct forced operating mode |
ETBL1 |
6 |
|
|
|
|
|
|
|
|
Heat |
When the air capacity is low to |
ETBL2 |
4.67 |
|
|
|
correct it |
|
||
|
|
|
|
|
|
|
|
When the air capacity is low to |
ETBL3 |
4.67 |
|
|
|
correct it |
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
Cool and |
Correct the operating mode |
ETBL4 |
-0.33 |
|
|
dry mode |
|
|
|
|
|
Correct the forced operating mode |
ETBL5 |
-4 |
|
2.4 Control the temperature the area
2.4.1 Deviation
Calculation the deviation of the temperature area, as following:
Heat: E= (remote control preset temperature + corrected value)-room temperature
Cool and dry: E=room temperature - (remote control preset temperature+ corrected value)
2.4.2 Compressor OFF OFF
When E is negative and |E|>?T:
|
Heat |
|
Cool |
||
|
|
|
|
|
|
?T |
TCHAHL |
0.67 |
TCHACL |
|
0.33 |
After ?T variation |
TCHAHH |
0.67 |
TCHACH |
|
1 |
?T variation condition |
When the system is start to operate, E=3.0 |
, |
The compressor will be stopped after detected continuously for 120 seconds.
After operation starts, when compressor turns off at the first time, based on the above conditions, the unit should operate according to ?T variable data. Between the time when compressor is off and restarts, the unit should operate on ?T starting data (Except dry) and operating mode is transferring. (Except the case that waiting unit is off). Compressor starts when the wrap E is larger than –?T. When compressor is operating and the set temperature by the remote control changes in the orientation that compressor is off, in addition, it is below –?T, compressor will be off.
2.4.3 Compressor operating
During the time when compressor is off, after waiting for 3 minutes, the deviation E is much larger
than- T +0.67 , compressor will start to operate.
2.4.4 DASH operation
When the system starts to operate or to switch the operation mode (except compressor first to off and then to on), when the compressor is on, the system will indicate the maximum frequency satisfied condition as following:
Cool |
deviate to 0 |
Dry |
deviate to G area |
Heat |
deviate to F area |
|
- 11 - |
Haier air conditioner |
Edition: 20070116 |
When the system is in test run, emergency operation, silencing operation mode, the DASH will be stopped.
2.4.5 Temperature adjustment section DASH operation condition in the different mode
2.4.6 Frequency in the different mode
In this area, the frequency (from indoor to outdoor) indication as following:
When the system is in the cool and dry mode, the frequencies between A area and B area are same. In the silencing operation mode, the frequencies between A-E area and F area are same.
|
Indication frequency |
Scope of |
Temperature |
|
|
frequency |
changing area |
Heating |
FQHOT [0—7] |
30-140Hz |
A—H |
Heat in Silence mode |
FQSHOT [0—2] |
30-72Hz |
F—H |
|
|
|
|
Dry |
FQDRY [0—7] |
30-98Hz |
B—H |
Cooling |
FQCOOL [0—7] |
30-98Hz |
B—H |
Cooling in silence mode |
FQSCOOL [0—2] |
30-64Hz |
F—H |
The maximum frequency is the maximum frequency value as above table.
The max or min frequency in the cool or heat mode is corresponding with the max or min frequency value as the above table.
2.4.7 Control frequency in the same area
The compressor operating by the identity frequency for 3minutes that its area has no change, the indication frequency will be changed.
The timer will be reset when you input the different frequency. The system’s temperature area have no change when the system operating by new frequency for 3 minutes, please changing its indication frequency (add FQUPH or FQUPL).
- 12 -
|
|
|
|
|
|
Haier air conditioner |
|
Edition: 20070116 |
||||
|
Controlling table in the identity area |
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Temperature change area |
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
A |
B |
|
C |
|
D |
E |
F |
G |
H |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Heat |
|
|
FQUP(2Hz) |
|
FQUP(2Hz) |
FQUP(2Hz) |
FQUP(1Hz) |
FQUP(1Hz) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Cool and dry |
|
|
FQUP(2Hz) |
|
FQUP(2Hz) |
FQUP(2Hz) |
FQUP(1Hz) |
FQUP(1Hz) |
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
FQUPH 2Hz |
FQUPL |
1Hz |
|
|
|
|
|
|
|
2.4.8 Air capacity decision when Air capacity is running automatically.
When air capacity is running automatically, based on temperature adjusting sections, you shift the switch for air capacity, namely, enhanced, middle, and weak.
When air capacity is running automatically, shown following air capacity table.
H---High M----Middle L---Low
|
|
Temperature adjustment section |
|
|
|
|
|||
|
A |
B |
C |
D |
E |
F |
G |
H |
I |
Heat |
H |
H |
H |
H |
H |
M |
L |
L |
SL |
|
|
|
|
|
|
|
|
|
O |
Cool |
|
H |
H |
H |
M |
M |
L |
L |
L |
Dry |
|
H |
M |
M |
M |
L |
L |
SLO |
SL |
|
|
|
|
|
|
|
|
|
O |
2.5 Defrost
When the high load precaution control operating, the priority is precaution control operating. Compressor is not off.
During the heat-making operation, communication of outdoor unit will deliver defrosting signal (I21=10), indoor unit will be based on defrosting controlling. It will continue until communication of outdoor unit delivers defrosting released signal (I21=01), indoor unit will be on heat-making operation directly. Air capacity will be of under the temperature controlling section of heat making.
2.6 Air capacity limited
During compressor operating, when the maximum speed of indoor fan be set middle or low speed, the upper limit of indication frequency shown respectively as following:
Frequency number of air capacity limit table:
|
Limiting frequency variable |
Limiting frequency |
|
|
|
Air capacity middle limit |
FQLIMMD |
90Hz |
Air capacity low limit |
FQLIMLO |
52Hz |
|
|
|
Upper and down limit of fresh |
FUPHEAL |
30Hz |
air capacity frequency |
|
|
Estimate the limiting frequency condition in heat mode; first, estimate it whether is the limiting frequency condition of set low fan or health fan. If there have set low fan, health fan or both of them, to
- 13 -
Haier air conditioner |
Edition: 20070116 |
correction the limit frequency according to the following condition:
Outdoor temperature condition |
Indication frequency |
|
||
011(20 |
more than) |
Low fan or health fan limited frequency |
48Hz |
|
|
|
|
|
|
010(15-20 |
) |
Low fan or health fan limited frequency |
50Hz |
|
|
|
|
+FUPHEA1 |
|
|
|
|
|
|
001(10-15 |
) |
Low fan or health fan limited frequency |
52Hz |
|
|
|
|
+FUPHEA2 |
|
000(10 |
downward) |
In general frequency |
|
. Indoor fan motor control
Objective revolutions:
|
|
|
|
+68 +6$5 '% |
+68 +6$5 '% |
|
|
|
|
|
YDULDEOH USP |
|
|
|
5RWDWH VSHHG YDULDEOH |
YDULDEOH USP |
|
|
:HDN |
)5307%/ |
|
|
|
|
|
|
|
|
|
|
6LOHQFLQJ 66/2 |
)5307%/ |
|
|
|
|
|
|
|
|
|
|
/RZ |
)5307%/ |
|
|
|
|
|
|
|
|
|
+HDWLQJ |
|
|
|
|
|
|
|
|
|
||
|
+LJK |
)5307%/ |
|
|
|
|
|
|
|
|
|
|
|
/RZ |
)5307%/ |
|
|
|
$XWRPDWLRQ |
|
|
|
|
|
|
|
|
|
|
|
|
+LJK |
)5307%/ |
|
|
|
|
|
|
|
|
|
:HDN |
)5307%/ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
6LOHQFLQJ 66/2 |
)5307%/ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
/RZ |
)5307%/ |
|
|
|
|
|
|
|
|
|
&RRO |
|
|
|
|
|
|
|
|
|
|
|
|
+LJK |
)5307%/ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
/RZ |
)5307%/ |
|
|
|
$XWRPDWLRQ |
|
|
|
|
|
|
|
|
|
|
|
|
+LJK |
)5307%/ |
|
|
|
|
|
|
|
|
|
/RZ |
)5307%/ |
|
|
|
|
|
|
|
|
|
$HUDWLRQ |
|
|
|
|
|
|
|
|
|
|
|
|
+LJK |
)5307%/ |
|
|
|
|
|
|
|
|
|
|
&RRO |
)5307%/ |
|
|
|
5DWLQJ |
|
|
|
|
|
|
|
|
|
|
|
|
+HDWLQJ |
)5307%/ |
|
|
|
|
|
|
|
|
|
When air capacity is set for controlling by hand; it is the revolution of (High + Low)/2.
When it runs automatically, it is the revolution of (automatically high + automatically low)/2. (No account the revolution when it doesn’t reach 10rpm)
3.1 Heat operation
3.1.1 Warm start
A, Control cool air during heating
Heat exchange temperature
- 14 -
Haier air conditioner |
Edition: 20070116 |
Based on the heat exchange temperature to control the indoor fan as the above shown.
1. When the heat exchange temperature rise, to distinguish the fan speed based on the heat exchange temperature:
The heat exchange temperature is less than 35.2 , the speed of fan motor is weak (for the first power on, when the system operating in heat mode or OFF the defrost mode, and when the heat exchange temperature is less than 25.2 , the fan motor will OFF; if the temperature is between 25.2 and
35.2, the fan motor will be weak speed operating);
The fan motor operating with low speed when heat exchange temperature is between 35.2 and 37
The heat exchange temperature is more than 37 , fan motor operating by the set speed.
2. When drop of the heat exchange temperature, to distinguish the fan speed based on the heat exchange temperature:
The fan motor operating with low speed when heat exchange temperature is between 35.2 and
25.2;
The fan motor always operates with little-low speed when heat exchange temperature is less than
25.2. (for the first power on, when the system operating in heat mode or stopping the defrost mode,
and when the heat exchange temperature is between 25.2 and 16 , the fan motor will operating with weak speed; when the temperature is drop down to under16 , the fan motor will be stopped.
3. During the heat exchange temperature is rising fan speed is in the weak and low speed status, if the heat exchange temperature don’t return to previous value after 4 minutes, the fan speed will rise and continuously operating by the set temperature for 4 minutes, the system will adjustment the fan speed based on the heat exchange temperature;
4. When the heat exchange temperature is dropping down, the fan speed will go up to the set speed if the fan motor operate continuously by the low speed for more than 4 minutes.
- 15 -
Haier air conditioner |
Edition: 20070116 |
3.1.2 Compressor OFF and waiting for 3 minutes
1.The compressor is OFF (the flamestat is OFF), the air capacity will change from small to little small after 20 seconds (is SSLO in silence mode);
2.To heat operating in stand-by time (when the mode switch, the compressor will OFF), the air capacity keep to weak.
3. Power off by remote control then the indoor fan motor will OFF.
3.1.3 Compressor restart
It is set air capacity by remote control after the system warm start.
System will be based on the temperature to determine its ventilation.
Reference the control function in temperature area.
3.1.4 Defrosting operation
Fan motor is off after being low for 20 minutes.
The system received command from the outdoor unit communication I21=11 during low temperature and defrosting in heat mode to control the air capacity, it is the same with through the heat exchange temperature transducer go to warm start to control. (3-1-1).
After defrosting operation, if the compressor is on, the system will go to warm start to control the air capacity. If compressor is off, the air capacity is weak.
3.2 Cool operation
When set the air capacity is high, middle and low which represents its air capacity separately.
When air capacity is running on automatically, it is based on temperature.
Refer to Temperature adjustment Functions. reference 2-4-8
3.3 Dry operation
3.3.1 Compressor OFF and waiting for 3 minutes
When the compressor is OFF, the fan motor will stop.
It will switch to weak after wait for 3 minutes.
The compressor will change to ON after wait for 3 minutes, and it will in the on-control mode.
- 16 -
Haier air conditioner |
Edition: 20070116 |
3.3.2 Compressor ON
When the air capacity is set High, Middle and Low, the compressor will operate by the set mode. When the air capacity is set auto fan, the air capacity will be adjusted by the temperature.
. Enhanced operation
Enhanced operation will continue for 15 minutes.
Enhanced operation will finish if the operation is off or after 15 minutes.
Enhanced operation will finish when the status be changed.
Enhanced operation will finish if the unit enters the status of “silence”, operates normally or on-timer signal control.
In the auto mode, there are enhanced /silence function; the main unit operating is based on enhanced cool /silence function in the cool mode; the main unit operated by the enhanced heat/silence function in the heat mode; the main unit will operate is based on no-enhanced/silence function in the fan mode.
4.1 Enhanced heat
Modify the set temperature. It has temperature-adjustment function.
Air capacity will be automatic middle fan speed.
When operating for defrosting, outdoor unit will not receive the communication signal of enhanced operation. After operation for defrosting, the system will operate enhanced function only in the remaining time.
After enhanced operation continues for 15 minutes, compressor is forbidden to be OFF for 10 minutes. (Except the error)
4.2 Enhanced Cool
Modify the set temperature. It has temperature-adjustment function.
The high air capacity will be set for hand controlling.
- 17 -
Haier air conditioner |
Edition: 20070116 |
After compressor starts, it’s not on the low load protection within 3 minutes.
4.3No enhanced function for fan and defrosting mode.
.Silence operation
Send silence operation signal to outdoor unit.
5.1 Heating in the silence mode
When compressor is on, air capacity is SSLO.
When compressor is off, air capacity is SSLO within 20 seconds, and then it changes to be tenuity.
5.2 Cooling in the silence mode
Air capacity is SSLO.
5.3 No silence functions during dry operating and fan operating in the silence mode.
.Fresh air
After the system receives remote control command, the negative ion generator will be activated to emit the negative ion if the fan motor is operating.
When the fan motor is OFF, the negative ion generator will OFF.
When the negative ion generator is OFF, if the fresh air mode is ON, the fan motor operating again and the negative ion generator will ON automatically.
.Timer operating
Use the timer to time counting is according to the time difference between time clock and current time. During timer operating, the timer indicator light will light.
7.1 Timer off
When the timer is off, the character display of the panel running status does not change, once the timer time is time-up, its operating will OFF.
7.2Timer ON
When the timer is ON, the panel only displays the timer character, once the on-timer time, the system will operate start by the set mode.
- 18 -
Haier air conditioner |
Edition:20070116 |
7.3 Timer ON/OFF
The executing order is based on the direction from the board.
. Sleep operating
8.1 During cool/ dry operation, the fixed temperature will rise by 1 after it operates for 1 hour. After another hour the temperature will rise by another 1 . After 6 hours, the unit is off.
8.2 During heat-making operation, the fixed temperature will rise by 2 hours the temperature will rise by 2 . The temperature will rise by 1 3 hours, the unit is off.
after 1 hour. After another 2 after three hours. After the last
8.3 Indoor fan unit will be high fan before the unit is set for sleeping state. After it is set for sleeping state, fan speed indoors will change into middle fan speed. If indoor fan unit is middle fan speed before it is set for sleeping state, fan speed indoors will change into low fan after it is set for sleeping state. If indoor unit is low fan before it is set for sleeping state, fan speed indoors will keep the same.
. Automatic operation
The automatic operation is divided into automation and full automation by use the variant selection mode.
9.1 Automation operating mode:
Automation operating is on, MCU will select corresponding operation mode based on the room temperature to preserve the set temperature (set temperature is 23 in the heat mode; it is 26 in the cool mode).
For the first power on, if the indoor temperature T=23 the system will operate in the heat mode, T>23 operating in the cool mode.
The system will perform the heat program in the heat mode (set temperature is 23 ), when system temperature arrive at stop value of compressor, the compressor to off and waiting for 3 minutes; after the compressor stop continuance for 15 minutes, if the system detected the ventilation temperature is more than 23 , it will enter cool mode, or else it will continuously operate in the heat mode.
When enter the cool mode and the system operating in cool mode (set temperature 26 ), the compensation temperature contrast will be canceled automatically, when it arrive at the stop temperature of the compressor, the compressor to off and wait for 3 minutes; after the compressor stop continuously for 15 minutes, the system detected the ventilation temperature T=23 , then it will enter heat mode and automatically add the compensation temperature. or else it will continuously operate in the cool mode.
- 19 -
Haier air conditioner |
Edition:20070116 |
When the system switch from other mode to auto mode, if the operation status change (i.e. first determine and then operation), it will stop for 3 minutes and then determine temperature based on the indoor ventilation temperature.
9.2 Full-automation operation
After system is on and the operation mode will switches to auto mode, the system determine operating mode by the difference between current set temperature and the room temperature, and then operate in the determined mode. In the following selection condition, Tr indicate room temperature Ts indicate set temperature.
In First enter auto mode, select operating mode as following condition:
Tr=Ts-3 |
select cool mode |
Tr Ts-3 |
select heat mode |
When system enter the auto mode, the operation mode will switch between cool and heat according to change of the indoor temperature: if the unit operating in the cool mode, when system temperature arrive at stop value of compressor, the compressor to off and stop continuously for 15 minutes, and then to detect the room temperature, at this point, if Tr Ts-3 , then the system enter the heat mode, otherwise it will operate continuously in the cool mode; if the unit operating in the heat mode, when system temperature arrive at stop value of compressor, the compressor to off and stop continuously for 15 minutes, and then to detect the room temperature, at this point, if Tr Ts+3 , then the system enter the cool mode, otherwise it will operate continuously in the heat mode.
This mode has timer and sleep function, if the system enter the cool mode, then enter the cool+ sleep mode, if enter the heat mode then enter heat + sleep mode.
Select swing or sticking on one position for the fan blade, and fan speed including: low, middle, high and auto fan, you can select any one of them without control.
. Running-in
In the Running-in mode the indication frequency is 58Hz, the air capacity is enhanced.
Running-in is off after 30 minutes. When the system received the remote control signal in the running-in mode, the system will exit this mode.
No taking activities under low load protection.
. Low load protection controlling
The standard of heat alternating temperature sensor
B destiny=3700 R (25 degrees) =10KO
When it operates for coolness making or defrosting, low load protection will be taken based on Heat exchange temperature as the following picture shows
Controlling under low load protection
If selection model is GANGDAcommunication, the indoor unit have not this function.
- 20 -
Haier air conditioner |
Edition:20070116 |
Heat exchange temperature sensor format:
Fixed number B =3700 R (25 degree) =10KO
In Cool\Dry operation mode, the unit performs low load protection operating according to Heat exchange temperature as following figure show.
Low load protection control
When it is on running-in process, low load protection controlling will be ignored.
After enhanced cool operation start, release temporarily the low load protection control for 3 minutes. (THLH[3 2 1 0]= 7 4.6 2.2 -0.5 )
. High load protection control
If selection model is GANGDAcommunication, the indoor unit has not this function.
In heat operation mode, the unit performs high load protection operating according to Heat exchange temperature as following figure show:
When operating for heat, the unit is under high load controlling based on Heat exchange temperature as the following picture shows.
- 21 -
Haier air conditioner |
Edition: 20070116 |
High load protection activities are limited twice within 30 minutes, and then high load protection starts to be alarming.
When Heat exchange temperature doesn’t reach "THHEAT[2]", the unit will return to state of normal temperature area control .
The lesser value of High load frequency and area frequency is used for the operation data.
.low temperature treatment in the heat mode
If the case that four-direction valve couldn’t be switched, or the compressor restarts except the defrosting mode in the heat operation, if the temperature of heat exchanger keeps below "THHOTLTH" (-4.5 ) for "TMHOTLTH" 90 seconds , compressor will be off and wait for 3 minutes. Heat exchange temperature higher than "THHOTLTH" (-4.5 ) will reset.
.EEPROM control
When outdoor power on, if the value unconformity between total parameter of EEPROM and check sum, indication the EEPROM disorder.
Indoor received disorder signal of EEPROM from outdoor, indicating outdoor EEPROM disorder. Control and emergency operating does not be received.
Cancel it by power OFF only.
- 22 -
Haier air conditioner |
Edition: 20070116 |
. Error list record
It indicates nothing if error code has not is recorded.
Fault signal show for 10s to auto off.
Remote control only receives the ‘off’ signal. Based on the ‘on/off’ or off signal of remote control, the error list will stop show.
Have component of EEPROM, after power on again, the list will be recorded.
.Special function
1.Indoor unit single operating
a. Enter conditions The system be set high heat mode by remote control, set temperature is 30 , power on for the first time, press the sleep key 6 times in 7 seconds, the buzzer resound 6 times.
b.Enter indoor unit single operation mode, indoor unit processing as following program:
Indoor unit operating and communication in set mode it will not process communication signal of outdoor but send communication signal to outdoor continuously.
c. Exit condition Once the system received remote control off or emergency off signal, it will exit indoor single operation status; when power fault, once power on it will exit single operation mode.
During indoor single operating, simulation outdoor send following information to indoor:
Output frequency 58 Hz, error defrosting status is 17654=0001, 13=0,121=01, outdoor temperature elever K54=00, indoor heat exchange temperature fixed to 47degree.
2. Power failure compensation
a.enter condition press the sleep key 10 times in 7 seconds, the buzzer resound 4 times, simultaneity , store the current operation status into EEPROM of indoor unit.
b.Enter indoor unit power failure mode, indoor unit processing as following program:
Remote control the emergency signal, unit will operate according to the remote controller and emergency set status and store the current operation status into indoor EEPROM.
Main unit operating based on the panel set status and store the current operation status in EEPROM. Enter power failure compensation power restart, main send the current status and power failure compensation signal to indoor panel, once the panel received to reply information and keep power failure compensation bit.
c. exit condition Press the sleep key 10 times in 7 seconds, the buzzer resound 2 times.
d. Set timer and sleep at power failure compensation status; after power restart, the main unit memory status is ‘off’ status.
- 23 -
Haier air conditioner |
Edition: 20070116 |
2. Rating operating |
|
rating cool: |
|
a. G code enter condition high speed cool set temp. is 16 |
press temperature “-” key and set key |
together, enter mode after resound 2 times. |
|
b. then operate as following:
Enter rated frequency operation mode; panel shown cool status; in communication rated shown.
c. Exit condition Exit rated operate mode and enter remote control set status after received remote control signal.
middle capacity:
a. G code enter conditions High fan cool, set temp. is 16 , press 4 times continuantly in 7s Enter rated frequency operation; Panel show cool status; have ration in communication.
Reso Enter rated frequency operation; Panel show cool status; have ration in communication. Resound 5 times.
b. then operating as following: enter middle capacity rated frequency operating;
c. Exit condition Exit rated operate mode and enter remote control set status after received remote control signal.
min capacity cool
a. G code enters condition: remote control high fan cool, set temp. is 16 , press 8 times continuantly in 7s resound 7 times.
b. then operating as following: enter min capacity rated frequency operating; panel show cool status; have ration in communication.
Enter rated frequency operation; Panel show cool status; have ration in communication.
c. Exit condition Exit rated operate mode and |
|
rated heat: rating heat |
|
a. G code enter condition high speed cool set temp. is 16 |
press temperature “-” key and set key |
together, enter mode after resound 2 times. |
|
b. Then operation as following program: |
|
Panel show heat status; have ration in communication. |
|
Enter rated frequency operation; Panel show cool status; have ration in communication. c. Exit condition: enter remote control set status after received remote control signel.
middle capacity heat:
a. G code enters condition Remote control high fan heat, set temp. is 30.7 , press 4 times
continuantly in 7s |
resound 7 times. |
b. Then operation as following program: panel show cool status; have ration in communication. |
|
Enter rated frequency operation; Panel show cool status; have ration in communication. |
|
c. Exit condition |
Exit rated operate mode and enter remote control set status after received remote |
control signal. |
|
min capacity heat:
a. G code enters condition Remote control high fan heat, set temp. is 30 , press 8 times continuantly
- 24 -
Haier air conditioner |
Edition: 20070116 |
in 7s resound 7 times.
b. Then operation as following program: Enter min capacity rated frequency operation; panel show cool status; have ration in communication.
Enter rated frequency operation; Panel show cool status; have ration in communication.
c. Exit condition Exit rated operate mode and enter remote control set status after received remote control signal.
.Fault explain
LCD fault code
Indoor unit fault code
|
|
Fault code |
|
Contents |
|
Remark |
|
|
|
|
E1 |
|
Room temperature sensor fault |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
E2 |
|
Heat exchange sensor fault |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
E3 |
|
Total current Over Current |
|
Use in split unit |
|
|
|
|
E4 |
|
EEPROM error |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
E5 |
|
Cool icing |
|
|
|
|
|
|
E6 |
|
Reset |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
E7 |
|
Communication fault(between indoor and outdoor unit) |
|
|
|
|
|
|
E8 |
|
communication between panel and indoor unit |
|
|
|
|
|
|
E9 |
|
High load protection |
|
|
|
|
|
|
E10 |
|
Humidity Sensor |
|
|
|
|
|
|
E11 |
|
Stepping motor fault |
|
|
|
|
|
|
E12 |
|
High voltage static electricity apparatus |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
E13 |
|
Power off moment |
|
Heat overload |
|
|
|
|
E14 |
|
Indoor fan motor fault |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
E15 |
|
Central control fault |
|
|
|
|
|
|
E16 |
|
High voltage electrostatic dust collection fault |
|
|
|
|
|
|
E17 |
|
reserved |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
E18 |
|
reserved |
|
|
|
|
|
|
E19 |
|
reserved |
|
|
|
|
Outdoor unit fault code |
|
|
|
|
||||
|
|
|
|
|
|
|
||
|
Fault code |
|
Contents |
Remark |
|
|
||
|
F1 |
|
Module fault (overheat, over current, short circuit) |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
F2 |
|
No load |
|
|
|
|
|
|
F3 |
|
Communication fault |
|
|
|
|
|
|
|
|
|
|
|
|||
|
F4 |
|
Compressor overheat |
Ventilation |
temperature |
|||
|
|
|
|
|
protection |
|
|
|
|
F5 |
|
Total current Over Current |
|
|
|
|
|
|
|
|
- 25 - |
|
|
|
|
|
|
Haier air conditioner |
Edition: 20070116 |
|
|
|
|
|
|
|
F6 |
Ambient temperature Sensor fault |
|
|
|
F7 |
Heat exchange Sensor |
|
|
|
F8 |
Fan unusual start |
|
|
|
F9 |
PFC protection |
|
|
|
F10 |
Cool overload |
|
|
|
F11 |
Compressor rotor circuit fault |
|
|
|
|
|
|
|
|
F12 |
Outdoor EEPROM error |
|
|
|
F13 |
Compressor forced switching failure |
|
|
|
|
|
|
|
|
F14 |
Fan hall element fault |
|
|
|
F15 |
Fan IPM overheat |
|
|
|
F16 |
Fan over current |
|
|
|
F17 |
Single-chip microcomputer ROM badly |
|
|
|
F18 |
Power supply over voltage protection |
|
|
|
F19 |
Power supply under voltage protection |
|
|
|
F20 |
Pressure protection |
|
|
|
F21 |
Defrosting temperature Sensor unusual |
|
|
|
|
|
|
|
|
F22 |
AC current protection |
|
|
|
F23 |
DC current protection |
|
|
|
|
|
|
|
|
F24 |
CT broken line protection |
|
|
|
F25 |
Ventilation temperature Sensor |
|
|
|
F26 |
electron expansion valve fault |
|
|
|
F27 |
reserved |
|
|
|
F28 |
reserved |
|
|
|
F29 |
reserved |
|
|
Emergency switch
When power off, press emergency switch less 5s to start emergencies operating. When power off, Press the emergency switch in 5s-10s to start running-in.
When power off, continues Press the emergency switch in 10s-15s to indicate last fault. When power off, Press the emergency switch, the panel shown auto mode.
When power off, continues Press the emergency switch in 15s or at hand leave switch, unit don’t receive the remote control.
More than 15s, unit enter “Off” status
More than 15s, unit can received signal
During operating, press the emergency switch may be power off.
Occur unusual circumstance, press this switch to off or cancel the unusual mode. When occur fault, press this switch to off the fault indication.
During operating, occur normal or unusual circumstance (e.g. touch switch to short circuit) or in the fault status, press and continues emergency switch (pressing for a long time), the unit received signal also.
Failure list express mode:
Press switch for 10seconds, resound 3times, free it to enter fault list express mode; press switch for
- 26 -
Haier air conditioner |
Edition: 20070116 |
15s panel indicator extinguish, failure list express mode be canceled. Previous alarm information sent to display panel to indicate operating status. After 10s, cancel fault indicator (fault list indicator show for 10s only). During showing the fault status, don’t receive other signal.
In normal mode, nothing is shown only buzzer sound.
Air deflector control
20.1 Vertical swing
20.1.1During power on, the entire output parts act along close direction.
20.1.2Set position, after power restart and initialize, direct to remote control position.
20.1.3Louver position
Position1 |
position2 |
position3 |
position4 |
position5 |
position6 |
10º from level 25º from level 40º from level |
55º from level 70º from level cool45ºHeat 60º |
20.1.4 Dispose on swing of remote control.
20.1.4.1 The swing will move in the following direction when the unit is cool/ dry/ fan. Position 1 (Initial
position) |
---position 2 |
---position 3----position 4 |
-----position 5 |
-----position 6---. |
……circulating |
20.1.4.2 The swing will move in the following direction when the unit is making heat: |
|||||
Position |
5 (Initial |
position)----position 4 |
---- position 3 |
---position 2--- |
position 6 ----position |
5 ……circulating. |
|
|
|
|
20.1.5 Dispose on swing indoor.
20.1.5.1 The unit will execute according to board indication when the unit is cool/heat/ dry.
When it runs under automatic mode, the host unit will enter heat-making mode based on indicated position of the board. When it runs under automatic mode, host unit has no position (After receiving the mode of position 5, the unit will dispose the data based on position 4).
20.1.5.2 When operation is off.
When operation is off or timing is on, all-close output parts will move into close direction. When all-close output starts to operate, namely, it will move into open direction.
20.1.5.3 Trigger delay
During running-in, it is the standard position for cool mode. During emergency operating, by indoor to