Haier HSU-12HSA03-R2-DB, HSU-09HSA03-R2-DB User Manual

4.7 (3)
Haier HSU-12HSA03-R2-DB, HSU-09HSA03-R2-DB User Manual

Haier air conditioner

Edition: 20070116

Domestic

Air conditioner

HSU-09HSA03/R2(DB)

HSU-12HSA03/R2(DB)

CAUTION

READ THIS MANUAL CAREFULLY TO DIAGNOSE TROUBLE CORRECTLY BEFORE OFFERING SERVICE.

THIS MANUAL IS USED BY QUALIFIED APPLIANCE TECHNICIANS ONLY.

HAIER DOES NOT ASSUME ANY RESPONSIBILITY FOR PROPERTY DAMAGE OR PERSONAL INJURY FOR IMPROPER SERVICE PROCEDURES DONE BY ONE UNQUALIFIED PERSON.

- 1 -

Haier air conditioner

Edition: 20070116

CONTENTS

1. GENERAL INFORMATION...............................................................

3

2. SPECIFICATION...............................................................................

6

3. ELECTRICAL CONTROL..................................................................

8

4. THERMISTER RESISTANCE CHART.............................................

30

5. TROUBLE SHOOTING....................................................................

40

6. PERFORMANCE CURVES DIAGRAM...........................................

46

6.1 High drop and long pipe capacity modification curves…………………………......46

6.2.1Cooling capacity-temperature curves……………………………………………..47

6.2.2Heating capacity-temperature curves……………………………………………..49 6.3 Air outlet temp.-ambient temperature curves……………………………………….51

6.4.1 Cooling discharge pressure curves...................................................................

53

6.4.2 Cooling suction pressure curves.......................................................................

55

6.4.3 Heating discharge pressure curves...................................................................

57

6.4.4 Heating suction pressure curves.......................................................................

59

6.5 Sensible cooling value-temperature curves.........................................................

61

6.6 Power consumption-temperature curves.............................................................

63

6.7 Noise curves........................................................................................................

65

6.8 Compressor performance curves………………………………………………........66

7. WIRING DIAGRAM..........................................................................

68

8. SCHEMATIC DIAGRAM OF PCB....................................................

70

9. INSTALLATION................................................................................

72

- 2 -

Haier air conditioner

Edition: 20070116

1. General information

This Service Manual describes the operation, disassembly, troubleshooting, and repair of Haier Room Air Conditioners, etc. It is intended for use by authorized services who troubleshoot and repair these units.

It is assumed that users of this manual are familiar with the use of tools and equipment used to troubleshoot and repair electrical, mechanical, and refrigeration systems; and understand the terminology used to describe and discuss them.

Haier urges you read and follow all safety precautions and warnings contained in this manual. Failure to comply with safety information may result in severe personal injury or death.

Related Publications

This is a base service manual, covering a range of similar models. It is intended to be used in conjunction with the Parts Manual and Technical Sheet covering specific model being serviced.

NOTE: General Precautions and Warnings

WARNING

To avoid risk of personal injury or death due to electrical shock, disconnect electrical power to unit before attempting to service the unit.

WARNING

To avoid risk of personal injury or death due to electrical shock, DO NOT, under any circumstances, alter the grounding plug .Air conditioner must be grounded at all times. Do not remove warning tag from power cord. If a two-prong (non-grounding) wall receptacle is encountered, contact a qualified electrician and have the receptacle replaced with a properly grounder wall receptacle in accordance with the National Electrical Code.

WARNING

To avoid risk of heat exposure, which may cause death or severe illness, air conditioner must be monitored when failures or shuts down.

WARNING

To avoid risk of personal injury or death due to electrical shock, grounding wires and wires colored like grounding wires are NOT to be used as current carrying conductors. The standard accepted color coding for ground wires is green or green with a yellow stripe. Electrical components such as the compressor and fan motor are grounded through an individual wire attached to the electrical component and to another part of the air conditioner. Grounding wires should not to be removed from individual components while servicing, unless the component is to be removed and replaced. It is extremely important to replace all removed grounding wires before completing service.

- 3 -

Haier air conditioner

Edition: 20070116

MODEL: HSU-09HSA03/R2(DB)

Product Features

Healthy negative ionIntelligent airflow

Entire auto modeESF filter

Easy clean design

Main Specification

Cooling Capacity: 2400W

Power Input: 680W

Current Input:3.50A

EER:3.53

Heating Capacity: 2650W

Power Input:730W

Current Input: 3.8A

COP: 3.63

Air Volume(Indoor/outdoor): 400m3/h

Power Supply: 1PH/230V/ 50Hz

-4 -

Haier air conditioner

Edition: 20070116

MODEL: HSU-12HSA03/R2(DB)

Product Features

Healthy negative ionIntelligent airflow

Entire auto modeESF filter

Easy clean design

Main Specification

Cooling Capacity: 3300W

Power Input: 1078W

Current Input: 4.9A

EER:3.06

Heating Capacity: 3600W

Power Input:1230W

Current Input: 5.4A

COP: 2.93

Air Volume(Indoor/outdoor): 450m3/h

Power Supply: 1PH/230V/ 50Hz

-5 -

Haier air conditioner

Edition: 20070116

2. Specification

 

Item

Unit

HSU-09HSA03

HSU-12HSA03

 

/R2(DB)

/R2(DB)

 

 

 

 

 

 

 

 

Power

 

PH, V, Hz

1, 230, 50

1,230,50

 

 

 

 

 

Climate Type

 

 

T1

T1

Starting Current

 

A

10

12

 

 

 

 

 

 

Cooling Capacity

W

2400

3300

 

Rated Power

W

680

1078

 

 

 

 

 

Cooling

Rated Current

A

3.50

4.9

Max Power

W

870

1350

 

 

 

 

 

 

 

Max Current

A

3.8

6.0

 

EER

W/W

3.53

3.06

 

 

 

 

 

 

Heating Capacity

W

2650

3600

 

Rated Power

W

730

1230

 

 

 

 

 

Heating

Rated Current

A

3.8

5.4

Max Power

W

1100

1480

 

 

Max Current

A

4.4

6.8

 

 

 

 

 

 

EER

W/W

3.63

2.93

Operating temp.

Cooling

 

18~46

18~46

range

 

 

 

 

Heating

 

-15~24

-15~24

 

H

rpm

1150

1300

Indoor fan Velocity

 

 

 

 

M

rpm

950

950

 

L

rpm

740

740

 

 

 

 

 

Outdoor fan Velocity

 

rpm

710

800

Indoor Air Volume (High)

m3

400

450

Max. pressure at warm side

MPa

4.15

4.15

Moisture Removal

 

10-3m3/h

0.83

1.2

Noise Level

Indoor (H/M/L)

dB(A)

42/40/38

42/40/38

 

 

 

 

Outdoor

dB(A)

48

52

 

Indoor Weight

Net

Kg

8.6

8.6

 

 

 

 

Gross

Kg

10.8

10.8

 

Outdoor Weight

Net

Kg

31

33

 

 

 

 

Gross

Kg

34

36

 

 

 

 

 

 

Indoor Dimension

Net

mm

760×182×285

760×182×285

Package

mm

837×282×312

837×282×312

 

 

 

 

 

 

Outdoor Dimension

Net

mm

780×245×540

780×245×540

 

 

 

 

Package

mm

790×366×484

790×366×484

 

 

Manufacture

 

TOSHIBA

SANYO

Compressor

 

 

 

 

Type

 

DA89X1C-20FZ

C-6RZ092H1A

 

 

 

 

 

 

Oil Charge

ml

370

320

 

 

- 6 -

 

 

 

Haier air conditioner

Edition: 20070116

 

 

 

 

 

 

 

 

Type

 

R410A

R410A

 

 

 

 

 

 

 

Refrigerant

Net Charge

g

800

1200

 

Charge if over standard pipe

g/m

12

12

 

 

 

 

length

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid pipe Diameter

mm

6.35

6.35

 

Refrigerant Pipe

Gas pipe Diameter

mm

9.52

12.7

 

 

 

 

 

 

Standard length

m

5

5

 

 

 

 

 

 

 

 

 

 

Max length

m

15

15

 

Drain Hose

Length

mm

2000

2000

 

 

 

 

 

 

Diameter

mm

16

16

 

 

 

 

 

 

 

 

 

Drainage pipe material diameter

mm

16

16

 

Remote Controller Model

 

YR-H04

YR-H04

 

 

 

 

 

 

Class of electric Shock Protection

 

I

I

 

Class of Water Proof

 

IP 24

IP 24

 

 

 

 

 

 

Power Cord (Model × Sectional Area)

 

H05VV-F 3G2.5mm2

H05VV-F 3G2.5mm2

 

- 7 -

Haier air conditioner

Edition: 20070116

3. Electrical control

. Scope of Application

This specification use for HSU-09/12HSA03/R2 DB frequency conversion air condition are manufactured by Haier air condition parent company. "Setting value" (express in parameter) in this specification means is a parameter that is stored in EEPROM. Refer to [EEPROM parameter table].

1. Chip pin definition

This controller adopts MOTROLA MC68HC908 AB32; Chip each pin definition as following:

1

PTC4

door switch

2

IRQ

 

3

RST

over-zero detection

 

 

 

4

PTF0/TACH2

remote control receiving

5

PTF1/TACH3

SDA

 

 

 

6

PTF2/TBCH2

SCL

7

PTF3/TBCH3

Buzzer

 

 

 

8

PTF4/TBCH0

Swing stepping motor A

9

NC

 

10

PTF7

Swing stepping motor D

11

PTF5/TBCH1

Swing stepping motor B

12

PTF6

Swing stepping motor C

13

PTE0/TXD

network output

 

 

 

14

PTE1/RXD

network output

15

PTE2/TACH0

PG feedback

 

 

 

16

PTE3/TACH1

PG output

17

PTE4/SS

fresh air

18

PTE5/MISO

negative ion output

 

 

 

19

PTE6/MOSI

self check/ decrease time

20

PTE7/SPSCK

empty

21

VSS

GND

22

VDD

VCC

23

PTG0/KBD0

ultraviolet ray A

24

PTG1/KBD1

empty

 

 

 

25

PTG2/KBD2

empty

26

PA0 selection panel 1

sliding stepping motor A

 

 

 

27

PA1 high/low drive model

sliding stepping motor B

28

PA2 large/small model

sliding stepping motor C

 

 

 

29

PA3 A/B code selection

sliding stepping motor D

30

PA4 panel selection 2

pushup stepping motor A

31

PA5

pushup stepping motor B

 

 

- 8 -

 

 

Haier air conditioner

 

Edition: 20070116

 

 

 

 

 

 

 

32

PA6

pushup stepping motor C

 

 

 

33

PA7

pushup stepping motor D

 

 

 

34

PTB0/ATD0

output outdoor communication

 

 

35

PTB1/ATD1

input outdoor communication

 

 

36

PTB2/ATD2

room temperature

 

 

 

37

PTB3/ATD3

inner coil

 

 

 

 

 

 

 

 

 

 

38

PTB4/ATD4

swing left stepping motor D

 

 

39

PTB5/ATD5

swing left stepping motor C

 

 

 

 

 

 

 

 

40

PTB6/ATD6

swing left stepping motor B

 

 

 

41

PTB7/ATD7

swing left stepping motor A

 

 

 

42

PTD0

swing right stepping motor D

 

 

43

PTD1

swing right stepping motor C

 

 

44

VDDAREF

VCC

 

 

 

 

 

45

AVSS/VREFL

GND

 

 

 

 

 

46

PTD2

swing right stepping motor B

 

 

47

PTD

swing right stepping motor A

 

 

 

 

 

 

 

 

48

PTH0/KBD3

central control input

 

 

 

49

PTH1/KBD4

central control output

 

 

 

 

 

 

 

 

 

 

 

50

PTD4/TBCLK

empty

 

 

 

 

 

51

PTD5

G/V LCS K health H heat

 

 

 

52

PTD6/TACLK

G/V WR K operation H dry

 

 

53

PTD7

G/V DA

K power supply

H cool

 

 

54

VREFH

VCC

 

 

 

 

 

55

VDDA

VCC

 

 

 

 

 

56

VSSA

GND

 

 

 

 

 

57

CGMXFC

 

 

 

 

 

 

58

OSC2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

59

OSC1

 

 

 

 

 

 

60

PTC0

emergency switch

 

 

 

 

 

 

 

 

 

 

61

PTC1

empty

K timer

 

 

 

62

PTC2/MCLK

G/V green light K green light H

 

 

operation

 

 

 

 

 

 

 

 

 

 

 

 

63

PTC3

G/V blue light

K blue light

H timer

 

 

64

PTC5

G/V red light

K red light

H health

 

II. Temperature adjustment function

2.1 During temperature adjustment function, the operation frequency of outdoor unit will be based on indoor temperature and the set temperature.

When air capacity operates automatically; the indoor fan will be controlled on the basis of the requirements of temperature adjustment.

When the unit operates to make heat, the indoor wind unit will be controlled based on scrolling temperature.

- 9 -

Haier air conditioner

Edition: 20070116

2.1.1 Standard of temperature sensor under indoor environment.

When the line is in short circuit or open circuit, the indicator light will be alarming and the indoor fan motor will be off. It will resume to the original state automatically after it returns normally, and operates as usual.

Short circuit:

Temperature: above 126 degrees,

Hex: Above F8H,

Value of Resistance: Below 0.65K, above 4.85V.

Normal temperature:

Temp: 25 degrees,

Hex: 40H,

Value of Resistance: 23K,

Voltage: 2.33V.

Power failure:

Temp: below -31 degrees,

Hex: below 08H,

Value of Resistance: Below 620K,

Voltage: Below 0.15V.

B parameter=4200

R (25degrees) =23K

2.1.2 Value of Resistance of indoor temperature sensor is ignored, when the heat mode is ON and the indoor fan is OFF, as well as after warm start indoor fan operate for 30 seconds. (in order to avoid affection of heat exchanger)

2.2 When frequency increase to holding frequency

In order to oil return fully during operating, the system will must keep some frequencies for a period of time.

 

Time Indication

 

Frequency indication

 

 

 

 

 

Drying in cool mode

Heat

 

Defrosting in heat mode

Holding frequency

 

 

 

 

 

60 seconds

60 seconds

 

30 seconds

58Hz

 

 

 

 

 

After Forced operation OFF at the start status, system will begin to control the temperature area.

2.3 Preset temperature correction

The preset temperature is corrected according to the operating mode, air capacity and forced operation status.

Only in the heat mode to correct the air capacity, confine to the low and middle speed of the air capacity.

Corrected value table for preset temperature:

- 10 -

 

 

Haier air conditioner

Edition: 20070116

 

 

 

 

 

 

 

Mode

Corrected contents

Corrected variable

Corrected

 

 

parameter

 

 

 

 

 

 

 

 

Correct the operating mode

ETBL0

4.67

 

 

 

 

 

 

 

 

 

Correct forced operating mode

ETBL1

6

 

 

 

 

 

 

 

 

Heat

When the air capacity is low to

ETBL2

4.67

 

 

 

correct it

 

 

 

 

 

 

 

 

When the air capacity is low to

ETBL3

4.67

 

 

 

correct it

 

 

 

 

 

 

 

 

 

 

 

 

 

Cool and

Correct the operating mode

ETBL4

-0.33

 

 

dry mode

 

 

 

 

 

Correct the forced operating mode

ETBL5

-4

 

2.4 Control the temperature the area

2.4.1 Deviation

Calculation the deviation of the temperature area, as following:

Heat: E= (remote control preset temperature + corrected value)-room temperature

Cool and dry: E=room temperature - (remote control preset temperature+ corrected value)

2.4.2 Compressor OFF OFF

When E is negative and |E|>?T:

 

Heat

 

Cool

 

 

 

 

 

 

?T

TCHAHL

0.67

TCHACL

 

0.33

After ?T variation

TCHAHH

0.67

TCHACH

 

1

?T variation condition

When the system is start to operate, E=3.0

,

The compressor will be stopped after detected continuously for 120 seconds.

After operation starts, when compressor turns off at the first time, based on the above conditions, the unit should operate according to ?T variable data. Between the time when compressor is off and restarts, the unit should operate on ?T starting data (Except dry) and operating mode is transferring. (Except the case that waiting unit is off). Compressor starts when the wrap E is larger than –?T. When compressor is operating and the set temperature by the remote control changes in the orientation that compressor is off, in addition, it is below –?T, compressor will be off.

2.4.3 Compressor operating

During the time when compressor is off, after waiting for 3 minutes, the deviation E is much larger

than- T +0.67 , compressor will start to operate.

2.4.4 DASH operation

When the system starts to operate or to switch the operation mode (except compressor first to off and then to on), when the compressor is on, the system will indicate the maximum frequency satisfied condition as following:

Cool

deviate to 0

Dry

deviate to G area

Heat

deviate to F area

 

- 11 -

Haier air conditioner

Edition: 20070116

When the system is in test run, emergency operation, silencing operation mode, the DASH will be stopped.

2.4.5 Temperature adjustment section DASH operation condition in the different mode

2.4.6 Frequency in the different mode

In this area, the frequency (from indoor to outdoor) indication as following:

When the system is in the cool and dry mode, the frequencies between A area and B area are same. In the silencing operation mode, the frequencies between A-E area and F area are same.

 

Indication frequency

Scope of

Temperature

 

 

frequency

changing area

Heating

FQHOT [0—7]

30-140Hz

A—H

Heat in Silence mode

FQSHOT [0—2]

30-72Hz

F—H

 

 

 

 

Dry

FQDRY [0—7]

30-98Hz

B—H

Cooling

FQCOOL [0—7]

30-98Hz

B—H

Cooling in silence mode

FQSCOOL [0—2]

30-64Hz

F—H

The maximum frequency is the maximum frequency value as above table.

The max or min frequency in the cool or heat mode is corresponding with the max or min frequency value as the above table.

2.4.7 Control frequency in the same area

The compressor operating by the identity frequency for 3minutes that its area has no change, the indication frequency will be changed.

The timer will be reset when you input the different frequency. The system’s temperature area have no change when the system operating by new frequency for 3 minutes, please changing its indication frequency (add FQUPH or FQUPL).

- 12 -

 

 

 

 

 

 

Haier air conditioner

 

Edition: 20070116

 

Controlling table in the identity area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Temperature change area

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

 

C

 

D

E

F

G

H

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat

 

 

FQUP(2Hz)

 

FQUP(2Hz)

FQUP(2Hz)

FQUP(1Hz)

FQUP(1Hz)

 

 

 

 

 

 

 

 

 

 

 

 

 

Cool and dry

 

 

FQUP(2Hz)

 

FQUP(2Hz)

FQUP(2Hz)

FQUP(1Hz)

FQUP(1Hz)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FQUPH 2Hz

FQUPL

1Hz

 

 

 

 

 

 

 

2.4.8 Air capacity decision when Air capacity is running automatically.

When air capacity is running automatically, based on temperature adjusting sections, you shift the switch for air capacity, namely, enhanced, middle, and weak.

When air capacity is running automatically, shown following air capacity table.

H---High M----Middle L---Low

 

 

Temperature adjustment section

 

 

 

 

 

A

B

C

D

E

F

G

H

I

Heat

H

H

H

H

H

M

L

L

SL

 

 

 

 

 

 

 

 

 

O

Cool

 

H

H

H

M

M

L

L

L

Dry

 

H

M

M

M

L

L

SLO

SL

 

 

 

 

 

 

 

 

 

O

2.5 Defrost

When the high load precaution control operating, the priority is precaution control operating. Compressor is not off.

During the heat-making operation, communication of outdoor unit will deliver defrosting signal (I21=10), indoor unit will be based on defrosting controlling. It will continue until communication of outdoor unit delivers defrosting released signal (I21=01), indoor unit will be on heat-making operation directly. Air capacity will be of under the temperature controlling section of heat making.

2.6 Air capacity limited

During compressor operating, when the maximum speed of indoor fan be set middle or low speed, the upper limit of indication frequency shown respectively as following:

Frequency number of air capacity limit table:

 

Limiting frequency variable

Limiting frequency

 

 

 

Air capacity middle limit

FQLIMMD

90Hz

Air capacity low limit

FQLIMLO

52Hz

 

 

 

Upper and down limit of fresh

FUPHEAL

30Hz

air capacity frequency

 

 

Estimate the limiting frequency condition in heat mode; first, estimate it whether is the limiting frequency condition of set low fan or health fan. If there have set low fan, health fan or both of them, to

- 13 -

Haier air conditioner

Edition: 20070116

correction the limit frequency according to the following condition:

Outdoor temperature condition

Indication frequency

 

011(20

more than)

Low fan or health fan limited frequency

48Hz

 

 

 

 

010(15-20

)

Low fan or health fan limited frequency

50Hz

 

 

 

+FUPHEA1

 

 

 

 

 

001(10-15

)

Low fan or health fan limited frequency

52Hz

 

 

 

+FUPHEA2

 

000(10

downward)

In general frequency

 

. Indoor fan motor control

Objective revolutions:

 

 

 

 

+68 +6$5 '%

+68 +6$5 '%

 

 

 

 

 

YDULDEOH USP

 

 

 

5RWDWH VSHHG YDULDEOH

YDULDEOH USP

 

:HDN

)5307%/

 

 

 

 

 

 

 

 

 

6LOHQFLQJ 66/2

)5307%/

 

 

 

 

 

 

 

 

 

/RZ

)5307%/

 

 

 

 

 

 

 

 

+HDWLQJ

 

 

 

 

 

 

 

 

 

 

+LJK

)5307%/

 

 

 

 

 

 

 

 

 

 

/RZ

)5307%/

 

 

 

$XWRPDWLRQ

 

 

 

 

 

 

 

 

 

 

 

+LJK

)5307%/

 

 

 

 

 

 

 

 

 

:HDN

)5307%/

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6LOHQFLQJ 66/2

)5307%/

 

 

 

 

 

 

 

 

 

 

 

 

 

 

/RZ

)5307%/

 

 

 

 

 

 

 

 

&RRO

 

 

 

 

 

 

 

 

 

 

+LJK

)5307%/

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

/RZ

)5307%/

 

 

 

$XWRPDWLRQ

 

 

 

 

 

 

 

 

 

 

 

+LJK

)5307%/

 

 

 

 

 

 

 

 

 

/RZ

)5307%/

 

 

 

 

 

 

 

 

$HUDWLRQ

 

 

 

 

 

 

 

 

 

 

+LJK

)5307%/

 

 

 

 

 

 

 

 

&RRO

)5307%/

 

 

5DWLQJ

 

 

 

 

 

 

 

 

 

 

+HDWLQJ

)5307%/

 

 

 

 

 

 

 

 

When air capacity is set for controlling by hand; it is the revolution of (High + Low)/2.

When it runs automatically, it is the revolution of (automatically high + automatically low)/2. (No account the revolution when it doesn’t reach 10rpm)

3.1 Heat operation

3.1.1 Warm start

A, Control cool air during heating

Heat exchange temperature

- 14 -

Haier air conditioner

Edition: 20070116

Based on the heat exchange temperature to control the indoor fan as the above shown.

1. When the heat exchange temperature rise, to distinguish the fan speed based on the heat exchange temperature:

The heat exchange temperature is less than 35.2 , the speed of fan motor is weak (for the first power on, when the system operating in heat mode or OFF the defrost mode, and when the heat exchange temperature is less than 25.2 , the fan motor will OFF; if the temperature is between 25.2 and

35.2, the fan motor will be weak speed operating);

The fan motor operating with low speed when heat exchange temperature is between 35.2 and 37

The heat exchange temperature is more than 37 , fan motor operating by the set speed.

2. When drop of the heat exchange temperature, to distinguish the fan speed based on the heat exchange temperature:

The fan motor operating with low speed when heat exchange temperature is between 35.2 and

25.2;

The fan motor always operates with little-low speed when heat exchange temperature is less than

25.2. (for the first power on, when the system operating in heat mode or stopping the defrost mode,

and when the heat exchange temperature is between 25.2 and 16 , the fan motor will operating with weak speed; when the temperature is drop down to under16 , the fan motor will be stopped.

3. During the heat exchange temperature is rising fan speed is in the weak and low speed status, if the heat exchange temperature don’t return to previous value after 4 minutes, the fan speed will rise and continuously operating by the set temperature for 4 minutes, the system will adjustment the fan speed based on the heat exchange temperature;

4. When the heat exchange temperature is dropping down, the fan speed will go up to the set speed if the fan motor operate continuously by the low speed for more than 4 minutes.

- 15 -

Haier air conditioner

Edition: 20070116

3.1.2 Compressor OFF and waiting for 3 minutes

1.The compressor is OFF (the flamestat is OFF), the air capacity will change from small to little small after 20 seconds (is SSLO in silence mode);

2.To heat operating in stand-by time (when the mode switch, the compressor will OFF), the air capacity keep to weak.

3. Power off by remote control then the indoor fan motor will OFF.

3.1.3 Compressor restart

It is set air capacity by remote control after the system warm start.

System will be based on the temperature to determine its ventilation.

Reference the control function in temperature area.

3.1.4 Defrosting operation

Fan motor is off after being low for 20 minutes.

The system received command from the outdoor unit communication I21=11 during low temperature and defrosting in heat mode to control the air capacity, it is the same with through the heat exchange temperature transducer go to warm start to control. (3-1-1).

After defrosting operation, if the compressor is on, the system will go to warm start to control the air capacity. If compressor is off, the air capacity is weak.

3.2 Cool operation

When set the air capacity is high, middle and low which represents its air capacity separately.

When air capacity is running on automatically, it is based on temperature.

Refer to Temperature adjustment Functions. reference 2-4-8

3.3 Dry operation

3.3.1 Compressor OFF and waiting for 3 minutes

When the compressor is OFF, the fan motor will stop.

It will switch to weak after wait for 3 minutes.

The compressor will change to ON after wait for 3 minutes, and it will in the on-control mode.

- 16 -

Haier air conditioner

Edition: 20070116

3.3.2 Compressor ON

When the air capacity is set High, Middle and Low, the compressor will operate by the set mode. When the air capacity is set auto fan, the air capacity will be adjusted by the temperature.

. Enhanced operation

Enhanced operation will continue for 15 minutes.

Enhanced operation will finish if the operation is off or after 15 minutes.

Enhanced operation will finish when the status be changed.

Enhanced operation will finish if the unit enters the status of “silence”, operates normally or on-timer signal control.

In the auto mode, there are enhanced /silence function; the main unit operating is based on enhanced cool /silence function in the cool mode; the main unit operated by the enhanced heat/silence function in the heat mode; the main unit will operate is based on no-enhanced/silence function in the fan mode.

4.1 Enhanced heat

Modify the set temperature. It has temperature-adjustment function.

Air capacity will be automatic middle fan speed.

When operating for defrosting, outdoor unit will not receive the communication signal of enhanced operation. After operation for defrosting, the system will operate enhanced function only in the remaining time.

After enhanced operation continues for 15 minutes, compressor is forbidden to be OFF for 10 minutes. (Except the error)

4.2 Enhanced Cool

Modify the set temperature. It has temperature-adjustment function.

The high air capacity will be set for hand controlling.

- 17 -

Haier air conditioner

Edition: 20070116

After compressor starts, it’s not on the low load protection within 3 minutes.

4.3No enhanced function for fan and defrosting mode.

.Silence operation

Send silence operation signal to outdoor unit.

5.1 Heating in the silence mode

When compressor is on, air capacity is SSLO.

When compressor is off, air capacity is SSLO within 20 seconds, and then it changes to be tenuity.

5.2 Cooling in the silence mode

Air capacity is SSLO.

5.3 No silence functions during dry operating and fan operating in the silence mode.

.Fresh air

After the system receives remote control command, the negative ion generator will be activated to emit the negative ion if the fan motor is operating.

When the fan motor is OFF, the negative ion generator will OFF.

When the negative ion generator is OFF, if the fresh air mode is ON, the fan motor operating again and the negative ion generator will ON automatically.

.Timer operating

Use the timer to time counting is according to the time difference between time clock and current time. During timer operating, the timer indicator light will light.

7.1 Timer off

When the timer is off, the character display of the panel running status does not change, once the timer time is time-up, its operating will OFF.

7.2Timer ON

When the timer is ON, the panel only displays the timer character, once the on-timer time, the system will operate start by the set mode.

- 18 -

Haier air conditioner

Edition:20070116

7.3 Timer ON/OFF

The executing order is based on the direction from the board.

. Sleep operating

8.1 During cool/ dry operation, the fixed temperature will rise by 1 after it operates for 1 hour. After another hour the temperature will rise by another 1 . After 6 hours, the unit is off.

8.2 During heat-making operation, the fixed temperature will rise by 2 hours the temperature will rise by 2 . The temperature will rise by 1 3 hours, the unit is off.

after 1 hour. After another 2 after three hours. After the last

8.3 Indoor fan unit will be high fan before the unit is set for sleeping state. After it is set for sleeping state, fan speed indoors will change into middle fan speed. If indoor fan unit is middle fan speed before it is set for sleeping state, fan speed indoors will change into low fan after it is set for sleeping state. If indoor unit is low fan before it is set for sleeping state, fan speed indoors will keep the same.

. Automatic operation

The automatic operation is divided into automation and full automation by use the variant selection mode.

9.1 Automation operating mode:

Automation operating is on, MCU will select corresponding operation mode based on the room temperature to preserve the set temperature (set temperature is 23 in the heat mode; it is 26 in the cool mode).

For the first power on, if the indoor temperature T=23 the system will operate in the heat mode, T>23 operating in the cool mode.

The system will perform the heat program in the heat mode (set temperature is 23 ), when system temperature arrive at stop value of compressor, the compressor to off and waiting for 3 minutes; after the compressor stop continuance for 15 minutes, if the system detected the ventilation temperature is more than 23 , it will enter cool mode, or else it will continuously operate in the heat mode.

When enter the cool mode and the system operating in cool mode (set temperature 26 ), the compensation temperature contrast will be canceled automatically, when it arrive at the stop temperature of the compressor, the compressor to off and wait for 3 minutes; after the compressor stop continuously for 15 minutes, the system detected the ventilation temperature T=23 , then it will enter heat mode and automatically add the compensation temperature. or else it will continuously operate in the cool mode.

- 19 -

Haier air conditioner

Edition:20070116

When the system switch from other mode to auto mode, if the operation status change (i.e. first determine and then operation), it will stop for 3 minutes and then determine temperature based on the indoor ventilation temperature.

9.2 Full-automation operation

After system is on and the operation mode will switches to auto mode, the system determine operating mode by the difference between current set temperature and the room temperature, and then operate in the determined mode. In the following selection condition, Tr indicate room temperature Ts indicate set temperature.

In First enter auto mode, select operating mode as following condition:

Tr=Ts-3

select cool mode

Tr Ts-3

select heat mode

When system enter the auto mode, the operation mode will switch between cool and heat according to change of the indoor temperature: if the unit operating in the cool mode, when system temperature arrive at stop value of compressor, the compressor to off and stop continuously for 15 minutes, and then to detect the room temperature, at this point, if Tr Ts-3 , then the system enter the heat mode, otherwise it will operate continuously in the cool mode; if the unit operating in the heat mode, when system temperature arrive at stop value of compressor, the compressor to off and stop continuously for 15 minutes, and then to detect the room temperature, at this point, if Tr Ts+3 , then the system enter the cool mode, otherwise it will operate continuously in the heat mode.

This mode has timer and sleep function, if the system enter the cool mode, then enter the cool+ sleep mode, if enter the heat mode then enter heat + sleep mode.

Select swing or sticking on one position for the fan blade, and fan speed including: low, middle, high and auto fan, you can select any one of them without control.

. Running-in

In the Running-in mode the indication frequency is 58Hz, the air capacity is enhanced.

Running-in is off after 30 minutes. When the system received the remote control signal in the running-in mode, the system will exit this mode.

No taking activities under low load protection.

. Low load protection controlling

The standard of heat alternating temperature sensor

B destiny=3700 R (25 degrees) =10KO

When it operates for coolness making or defrosting, low load protection will be taken based on Heat exchange temperature as the following picture shows

Controlling under low load protection

If selection model is GANGDAcommunication, the indoor unit have not this function.

- 20 -

Haier air conditioner

Edition:20070116

Heat exchange temperature sensor format:

Fixed number B =3700 R (25 degree) =10KO

In Cool\Dry operation mode, the unit performs low load protection operating according to Heat exchange temperature as following figure show.

Low load protection control

When it is on running-in process, low load protection controlling will be ignored.

After enhanced cool operation start, release temporarily the low load protection control for 3 minutes. (THLH[3 2 1 0]= 7 4.6 2.2 -0.5 )

. High load protection control

If selection model is GANGDAcommunication, the indoor unit has not this function.

In heat operation mode, the unit performs high load protection operating according to Heat exchange temperature as following figure show:

When operating for heat, the unit is under high load controlling based on Heat exchange temperature as the following picture shows.

- 21 -

Haier air conditioner

Edition: 20070116

High load protection activities are limited twice within 30 minutes, and then high load protection starts to be alarming.

When Heat exchange temperature doesn’t reach "THHEAT[2]", the unit will return to state of normal temperature area control .

The lesser value of High load frequency and area frequency is used for the operation data.

.low temperature treatment in the heat mode

If the case that four-direction valve couldn’t be switched, or the compressor restarts except the defrosting mode in the heat operation, if the temperature of heat exchanger keeps below "THHOTLTH" (-4.5 ) for "TMHOTLTH" 90 seconds , compressor will be off and wait for 3 minutes. Heat exchange temperature higher than "THHOTLTH" (-4.5 ) will reset.

.EEPROM control

When outdoor power on, if the value unconformity between total parameter of EEPROM and check sum, indication the EEPROM disorder.

Indoor received disorder signal of EEPROM from outdoor, indicating outdoor EEPROM disorder. Control and emergency operating does not be received.

Cancel it by power OFF only.

- 22 -

Haier air conditioner

Edition: 20070116

. Error list record

It indicates nothing if error code has not is recorded.

Fault signal show for 10s to auto off.

Remote control only receives the ‘off’ signal. Based on the ‘on/off’ or off signal of remote control, the error list will stop show.

Have component of EEPROM, after power on again, the list will be recorded.

.Special function

1.Indoor unit single operating

a. Enter conditions The system be set high heat mode by remote control, set temperature is 30 , power on for the first time, press the sleep key 6 times in 7 seconds, the buzzer resound 6 times.

b.Enter indoor unit single operation mode, indoor unit processing as following program:

Indoor unit operating and communication in set mode it will not process communication signal of outdoor but send communication signal to outdoor continuously.

c. Exit condition Once the system received remote control off or emergency off signal, it will exit indoor single operation status; when power fault, once power on it will exit single operation mode.

During indoor single operating, simulation outdoor send following information to indoor:

Output frequency 58 Hz, error defrosting status is 17654=0001, 13=0,121=01, outdoor temperature elever K54=00, indoor heat exchange temperature fixed to 47degree.

2. Power failure compensation

a.enter condition press the sleep key 10 times in 7 seconds, the buzzer resound 4 times, simultaneity , store the current operation status into EEPROM of indoor unit.

b.Enter indoor unit power failure mode, indoor unit processing as following program:

Remote control the emergency signal, unit will operate according to the remote controller and emergency set status and store the current operation status into indoor EEPROM.

Main unit operating based on the panel set status and store the current operation status in EEPROM. Enter power failure compensation power restart, main send the current status and power failure compensation signal to indoor panel, once the panel received to reply information and keep power failure compensation bit.

c. exit condition Press the sleep key 10 times in 7 seconds, the buzzer resound 2 times.

d. Set timer and sleep at power failure compensation status; after power restart, the main unit memory status is ‘off’ status.

- 23 -

Haier air conditioner

Edition: 20070116

2. Rating operating

 

rating cool:

 

a. G code enter condition high speed cool set temp. is 16

press temperature “-” key and set key

together, enter mode after resound 2 times.

 

b. then operate as following:

Enter rated frequency operation mode; panel shown cool status; in communication rated shown.

c. Exit condition Exit rated operate mode and enter remote control set status after received remote control signal.

middle capacity:

a. G code enter conditions High fan cool, set temp. is 16 , press 4 times continuantly in 7s Enter rated frequency operation; Panel show cool status; have ration in communication.

Reso Enter rated frequency operation; Panel show cool status; have ration in communication. Resound 5 times.

b. then operating as following: enter middle capacity rated frequency operating;

c. Exit condition Exit rated operate mode and enter remote control set status after received remote control signal.

min capacity cool

a. G code enters condition: remote control high fan cool, set temp. is 16 , press 8 times continuantly in 7s resound 7 times.

b. then operating as following: enter min capacity rated frequency operating; panel show cool status; have ration in communication.

Enter rated frequency operation; Panel show cool status; have ration in communication.

c. Exit condition Exit rated operate mode and

 

rated heat: rating heat

 

a. G code enter condition high speed cool set temp. is 16

press temperature “-” key and set key

together, enter mode after resound 2 times.

 

b. Then operation as following program:

 

Panel show heat status; have ration in communication.

 

Enter rated frequency operation; Panel show cool status; have ration in communication. c. Exit condition: enter remote control set status after received remote control signel.

middle capacity heat:

a. G code enters condition Remote control high fan heat, set temp. is 30.7 , press 4 times

continuantly in 7s

resound 7 times.

b. Then operation as following program: panel show cool status; have ration in communication.

Enter rated frequency operation; Panel show cool status; have ration in communication.

c. Exit condition

Exit rated operate mode and enter remote control set status after received remote

control signal.

 

min capacity heat:

a. G code enters condition Remote control high fan heat, set temp. is 30 , press 8 times continuantly

- 24 -

Haier air conditioner

Edition: 20070116

in 7s resound 7 times.

b. Then operation as following program: Enter min capacity rated frequency operation; panel show cool status; have ration in communication.

Enter rated frequency operation; Panel show cool status; have ration in communication.

c. Exit condition Exit rated operate mode and enter remote control set status after received remote control signal.

.Fault explain

LCD fault code

Indoor unit fault code

 

 

Fault code

 

Contents

 

Remark

 

 

 

 

E1

 

Room temperature sensor fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E2

 

Heat exchange sensor fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E3

 

Total current Over Current

 

Use in split unit

 

 

 

E4

 

EEPROM error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E5

 

Cool icing

 

 

 

 

 

 

E6

 

Reset

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E7

 

Communication fault(between indoor and outdoor unit)

 

 

 

 

 

E8

 

communication between panel and indoor unit

 

 

 

 

 

 

E9

 

High load protection

 

 

 

 

 

 

E10

 

Humidity Sensor

 

 

 

 

 

 

E11

 

Stepping motor fault

 

 

 

 

 

 

E12

 

High voltage static electricity apparatus

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E13

 

Power off moment

 

Heat overload

 

 

 

E14

 

Indoor fan motor fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E15

 

Central control fault

 

 

 

 

 

 

E16

 

High voltage electrostatic dust collection fault

 

 

 

 

 

 

E17

 

reserved

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E18

 

reserved

 

 

 

 

 

 

E19

 

reserved

 

 

 

 

Outdoor unit fault code

 

 

 

 

 

 

 

 

 

 

 

 

Fault code

 

Contents

Remark

 

 

 

F1

 

Module fault (overheat, over current, short circuit)

 

 

 

 

 

 

 

 

 

 

 

 

 

F2

 

No load

 

 

 

 

 

F3

 

Communication fault

 

 

 

 

 

 

 

 

 

 

 

F4

 

Compressor overheat

Ventilation

temperature

 

 

 

 

 

protection

 

 

 

F5

 

Total current Over Current

 

 

 

 

 

 

 

- 25 -

 

 

 

 

 

 

Haier air conditioner

Edition: 20070116

 

 

 

 

 

 

F6

Ambient temperature Sensor fault

 

 

 

F7

Heat exchange Sensor

 

 

 

F8

Fan unusual start

 

 

 

F9

PFC protection

 

 

 

F10

Cool overload

 

 

 

F11

Compressor rotor circuit fault

 

 

 

 

 

 

 

 

F12

Outdoor EEPROM error

 

 

 

F13

Compressor forced switching failure

 

 

 

 

 

 

 

 

F14

Fan hall element fault

 

 

 

F15

Fan IPM overheat

 

 

 

F16

Fan over current

 

 

 

F17

Single-chip microcomputer ROM badly

 

 

 

F18

Power supply over voltage protection

 

 

 

F19

Power supply under voltage protection

 

 

 

F20

Pressure protection

 

 

 

F21

Defrosting temperature Sensor unusual

 

 

 

 

 

 

 

 

F22

AC current protection

 

 

 

F23

DC current protection

 

 

 

 

 

 

 

 

F24

CT broken line protection

 

 

 

F25

Ventilation temperature Sensor

 

 

 

F26

electron expansion valve fault

 

 

 

F27

reserved

 

 

 

F28

reserved

 

 

 

F29

reserved

 

 

Emergency switch

When power off, press emergency switch less 5s to start emergencies operating. When power off, Press the emergency switch in 5s-10s to start running-in.

When power off, continues Press the emergency switch in 10s-15s to indicate last fault. When power off, Press the emergency switch, the panel shown auto mode.

When power off, continues Press the emergency switch in 15s or at hand leave switch, unit don’t receive the remote control.

More than 15s, unit enter “Off” status

More than 15s, unit can received signal

During operating, press the emergency switch may be power off.

Occur unusual circumstance, press this switch to off or cancel the unusual mode. When occur fault, press this switch to off the fault indication.

During operating, occur normal or unusual circumstance (e.g. touch switch to short circuit) or in the fault status, press and continues emergency switch (pressing for a long time), the unit received signal also.

Failure list express mode:

Press switch for 10seconds, resound 3times, free it to enter fault list express mode; press switch for

- 26 -

Haier air conditioner

Edition: 20070116

15s panel indicator extinguish, failure list express mode be canceled. Previous alarm information sent to display panel to indicate operating status. After 10s, cancel fault indicator (fault list indicator show for 10s only). During showing the fault status, don’t receive other signal.

In normal mode, nothing is shown only buzzer sound.

Air deflector control

20.1 Vertical swing

20.1.1During power on, the entire output parts act along close direction.

20.1.2Set position, after power restart and initialize, direct to remote control position.

20.1.3Louver position

Position1

position2

position3

position4

position5

position6

10º from level 25º from level 40º from level

55º from level 70º from level cool45ºHeat 60º

20.1.4 Dispose on swing of remote control.

20.1.4.1 The swing will move in the following direction when the unit is cool/ dry/ fan. Position 1 (Initial

position)

---position 2

---position 3----position 4

-----position 5

-----position 6---.

……circulating

20.1.4.2 The swing will move in the following direction when the unit is making heat:

Position

5 (Initial

position)----position 4

---- position 3

---position 2---

position 6 ----position

5 ……circulating.

 

 

 

 

20.1.5 Dispose on swing indoor.

20.1.5.1 The unit will execute according to board indication when the unit is cool/heat/ dry.

When it runs under automatic mode, the host unit will enter heat-making mode based on indicated position of the board. When it runs under automatic mode, host unit has no position (After receiving the mode of position 5, the unit will dispose the data based on position 4).

20.1.5.2 When operation is off.

When operation is off or timing is on, all-close output parts will move into close direction. When all-close output starts to operate, namely, it will move into open direction.

20.1.5.3 Trigger delay

During running-in, it is the standard position for cool mode. During emergency operating, by indoor to

- 27 -