tekmar 423 User Manual

Page 1
- Data Brochure
Universal Reset Module 423
D 423
08/07
1
Information
Brochure
Choose controls
to match
application
2
Application
Brochure
Design your
mechanical
applications
3
Rough-in
Rough-in
instructions
Wiring
wiring
4
Wiring
Brochure
Wiring and
installation of
specific control
5
Data
Brochure
Control settings
and sequence of
operation
6
Job
Record
Record settings &
wiring details for
future reference
Introduction
The Universal Reset Module 423 provides outdoor reset to a hydronic heating system in order to maximize comfort and efficiency. The 423 can operate two on / off boilers or two modulating boilers. The 423 can override the outdoor reset water temperature to provide Domestic Hot Water or Setpoint operations. The 423 can operate four outdoor reset water temperatures, up to three of these water temperatures can be mixing water temperatures. To operate a mixing device, a Mixing Expansion Module must be connected to the 423 for each mixing water temperature.
Features:
tN4 Compatible
Four tN4 Buses
Up to One Boiler and Three Mixing Water
Temperatures
Two On-Off or Modulating Boilers
Equal Run Time Rotation
Powered Pump Outputs
DHW Operation
Optional DHW Sensor
Setpoint Operation
Stage1/ Stage 2/
Boil Enbl Setp Enbl
50
51 52 53
Meets Class B: Canadian
H7010A
ICES & FCC Part 15 Made in Canada
Boil Sens Sup / Ret Off / DHW Sensor Off / tekmar Stager Boilers On-Off / Mod Off / Rotation
Test
/
Powered Outputs 24 V (ac)
8 VA 1 VA
72 73 74
71
DHW 24 V (ac)
Vlv
R
54 55
Menu
Item
75
DHW Setpoint
Demand Demand
Mod2 (dc)Mod1 (dc)
57 58 59 60 6156
76 77 78
CCtN4
tN4
Boiler
Universal Reset Module 423
C2 tN4 tN4
123
62 63
C3C1+–C+–
6564
Demands: 20 - 260 V (ac) Relay Rating: 115 V (ac) 5 A
79 80 81 82
DHW Primary
DHW
Com
Boil Com70Out
66 67
tektra 1006-01
NPump N
68 69
Do not apply power
Pump
tN4
10 A max
1 of 36 © 2007 D 423 - 08/07
Page 2
Table of Contents
Boil Sens Sup / Ret Off / DHW Sensor Off / tekmar Stager Boilers On-Off / Mod Off / Rotation
/
Table of Contents ...........................................................2
Display and DIP Switches ..............................................2
Dip Switch Settings ................................................2
Access Level ...........................................................3
Display and Symbols Description............................4
User Interface ........................................................5
Display Menus ................................................................6
View Menu ..............................................................6
Adjust Menu ............................................................ 8
Miscellaneous Menu ............................................. 15
Testing the Control ....................................................... 16
Sequence of Operation ................................................. 18
®
tekmarNet
4 Communication ............................... 18
Outdoor Reset ...................................................... 18
Boiler Temperature Control .................................. 21
tekmar Stager Operation ......................................23
Boil Enable ............................................................24
Zone Load Shedding ............................................24
Mixing Operation .................................................. 24
Domestic Hot Water Temperature Operation ....... 25
DHW with Low Temperature Boilers .....................27
Setpoint Temperature Operation ...........................28
Pump Operation ....................................................29
Pump Exercising ................................................... 29
Error Messages ............................................................ 31
Warranty .......................................................................36
Display and DIP Switches
Dip Switch Settings
Set the DIP switch settings prior to making adjustments to the control through the user interface. Setting the DIP switches determines which menu items are displayed in the user interface.
If you change a DIP switch setting while the control is powered up, the LCD display returns to the View Menu.
Lock / Unlock
Use the Lock / Unlock DIP switch to lock and unlock the Access Level of the 423 and all connected tN4 devices, including tN4 thermostats. For details, see “Access Level”.
Once locked, the access level in all devices cannot be
viewed or changed.
To determine if the control is currently locked a small
segment representing a padlock is viewed in the bottom right hand corner of the display.
To unlock the Access Level, set the DIP switch to
Unlock.
To lock the Access Level, set the DIP switch to Lock.
Stage1/ Stage 2/
Boil Enbl Setp Enbl
50
51 52 53
Meets Class B: Canadian
H7010A
ICES & FCC Part 15 Made in Canada
Test
/
Boil Sens Sup / Ret Off / DHW Sensor Off / tekmar Stager Boilers On-Off / Mod Off / Rotation
Powered Outputs 24 V (ac)
8 VA 1 VA
72 73 74
71
DHW 24 V (ac)
Vlv
DHW
CCtN4
C3C1+–C+–
C2 tN4 tN4
tN4
Boiler
57 58 59 60 6156
Universal Reset Module 423
123
62 63
Mod2 (dc)Mod1 (dc)
54 55
Menu
Item
75
76 77 78
DHW Setpoint
Demand Demand
R
6564
66 67
tektra 1006-01
Demands: 20 - 260 V (ac) Relay Rating: 115 V (ac) 5 A
79 80 81 82
DHW Primary
NPump N
Com
Boil Com70Out
68 69
Do not apply power
tN4
Pump
10 A max
© 2007 D 423 - 08/07 2 of 36
Page 3
Boiler Sup / Ret
Off / DHW Sensor
Use the Boiler Sensor Supply / Return DIP switch to select the location of the boiler sensor.
If the boiler sensor is located on the supply, this DIP
switch should be set to Sup. The 423 is the control that determines the boiler water temperature. Set the boiler’s aquastat at least 20°F (11.0°C) higher than the Boiler Maximum setting.
If the 423 provides a heat demand to an external boiler
control, this DIP switch must be set to Ret. Install the boiler sensor on the return side of the boiler loop. The boiler’s operating temperature is controlled by its aquastat, or an external boiler reset control.
Boil On-Off / Mod
The Boil On-Off / Mod DIP switch selects whether the control operates an On-Off boiler or the firing rate of a Modulating boiler.
If set to Boil On-Off, the control operates up to two
On-Off boilers.
If set to Mod, the control operates up to two Modulating
boilers.
Off / tekmar Stager
Use the Off / DHW Sensor DIP switch when a tekmar sensor is be connected to the 423 in order to operate a DHW storage tank.
If a tekmar sensor is installed for DHW, set to DHW
Sensor. When the Off / DHW Sensor DIP switch is set to DHW Sensor, a regular DHW aquastat cannot be used.
If a tekmar sensor is not installed for DHW, set to Off.
Off / Rotation
Use the Off / Rotation DIP switch when the Equal Run Time Rotation feature is to be used. This feature changes the firing order of the boilers in order to maintain a similar amount of running time on each boiler.
If Equal Run Time Rotation is required, set the Off /
Rotation DIP switch to Rotation.
If Equal Run Time Rotation is not required, set to Off.
Use the Off / tekmar Stager DIP switch when a tekmar staging control is be connected to the 423 in order to operate multiple boilers. A tekmar stager may include Boiler Controls 264, 265, and 268.
If a tekmar Stager is installed, set to tekmar Stager. The
423 will then provide the stager with a target temperature via a 0-10 V (dc) signal. When the Off / tekmar Stager DIP switch is set to tekmar Stager, the Boiler Sensor DIP switch must be set to Sup.
If a tekmar Stager is not installed, set to Off.
Access Level
The Access Level restricts the number of Menus, Items, and Adjustments that can be accessed by the user. The Access Level setting is found in the Miscellaneous (MISC) Menu. Select the appropriate access level for the people who work with the control on a regular basis.
There are two Access Level settings:
Installer (InS): This is the factory default setting. This
access level is sufficient for the normal set up of the control.
Advanced (Ad): All of the control settings are available
to the user.
In the following menu tables, the access level the item is visible in is shown in the access column.
3 of 36 © 2007 D 423 - 08/07
Page 4
Display
Menu Field
Displays the
current menu
Status Field
Displays the current
status of the control’s
inputs, outputs and
operation. Most symbols
in the status field are only visible when the
VIEW Menu is selected
Symbols Description
PUMP
Displays when the primary pump is in operation.
Item Field
Displays an abbreviated name of the selected item
Number Field
Displays the current value of the selected item
BOILER DEMAND
Displays when a Boiler Demand is present.
BURNER
Displays when the Stage 1 or Stage 2 contacts are closed.
LOCK
Displays when the access levels are locked.
WARNING
Displays when an error exists.
COMMUNICATION BUS
Displays when tN4 thermostats are connected.
DHW PUMP OR VALVE
Displays when the DHW Pump or DHW Valve is in operation.
°F, °C, %, HOURS, MINUTES
Units of measurement.
MIX 1 DEMAND
Displays when a Mix 1 Demand is present.
MIX 2 DEMAND
Displays when a Mix 2 Demand is present.
MIX 3 DEMAND
Displays when a Mix 3 Demand is present.
DHW DEMAND
Displays when a DHW Demand is present.
SETPOINT DEMAND
Displays when a Setpoint Demand is present.
DEVICE OUTPUT SCALE
Displays the output of the modulating boiler(s) or the variable speed injection pump.
© 2007 D 423 - 08/07 4 of 36
Page 5
User Interface
Use the User Interface available on the Liquid Crystal Display (LCD) to setup and monitor the operation of the system. Use the four push buttons to the left of the LCD (Menu, Item, Up, Down) to select settings. As you enter settings, record the settings in the Job Record J 423.
Menu
The menus display in the Menu Field at the top left side of the LCD. Three menus are available: View, Adjust, and Miscellaneous.
To select a menu, press and release the Menu button.
Item
In each menu, a group of items can be selected. The abbreviated name of the selected item displays in the Item field of the LCD display.
To view the next available item, press and release the
Item button.
To view the previous item, hold down the Item button.
and press and release the Up button.
Adjusting a Setting
To adjust a setting
1. Select the appropriate menu using the Menu button.
2. Select the item using the Item button.
3. Use the Up or Down button to make the adjustment.
Default Item
To set the default item in the View Menu, display the
item for more than five seconds.
After navigating menus, the display reverts back to the default item after 60 seconds of button inactivity.
Back to View Menu
Continue to next Item
Continue to next Item
Continue to next Item
5 of 36 © 2007 D 423 - 08/07
Page 6
Display Menus
View Menu (1 of 2)
Item Field Range Access Description
The View Menu items display the current operating temperatures and status information of the system.
VIEW MENU
-67 to 149°F
(-55.0 to 65.0°C)
-22 to 266°F
(-30.0 to 130.0°C)
– – –, 35 to 230°F
(– – –, 1.5 to 110.0°C)
-22 to 266°F
(-30.0 to 130.0°C)
– – –, 35 to 230°F
(– – –, 1.5 to 110.0°C)
InS
Ad
InS
Ad
Ad
InS
Ad
Ad
OUTDOOR SECTION B
Current outdoor air temperature as measured by the outdoor sensor.
MIX 1 SUPPLY SECTION B
Current Mix 1 supply water temperature as measured by the Mix 1 supply sensor.
Note: This item is only available when Bus 1, 2 or 3 is set to Mix 1.
MIX 1 TARGET SECTION B
The Mix 1 target is the temperature the control is currently trying to maintain at the Mix 1 supply sensor. “– – –” is displayed when no heat is required for Mix 1 zones.
Note: This item is only available when Bus 1, 2 or 3 is set to Mix 1.
MIX 2 SUPPLY SECTION B
Current Mix 2 supply water temperature as measured by the Mix 2 supply sensor.
Note: This item is only available when Bus 2 is set to Mix 2.
MIX 2 TARGET SECTION B
The Mix 2 target is the temperature the control is currently trying to maintain at the Mix 2 supply sensor. “– – –” is displayed when no heat is required for Mix 2 zones.
Note: This item is only available when Bus 2 is set to Mix 2.
-31 to 266°F
(-35.0 to 130.0°C)
– – –, 35 to 230°F
(– – –, 1.5 to 110.0°C)
Continued on next page.
© 2007 D 423 - 08/07 6 of 36
InS
Ad
Ad
MIX 3 SUPPLY SECTION B
Current Mix 3 supply water temperature as measured by the Mix 3 supply sensor.
Note: This item is only available when Bus 3 is set to Mix 3.
MIX 3 TARGET
The Mix 3 target is the temperature the control is currently trying to maintain at the Mix 3 supply sensor. “– – –” is displayed when no heat is required for Mix 3 zones.
Note: This item is only available when Bus 3 is set to Mix 3.
SECTION B
Page 7
View Menu (2 of 2)
Item Field Range Access Description
-31 to 266°F
(-35.0 to 130.0°C)
– – –, 35 to 230°F
(– – –, 1.5 to 110.0°C)
-31 to 266°F
(-35.0 to 130.0°C)
-31 to 266°F
(-35.0 to 130.0°C)
InS
Ad
Ad
InS
Ad
InS
Ad
BOILER SUPPLY
Current boiler supply water temperature as measured by the boiler sensor.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup.
BOILER TARGET SECTION C
The boiler target is the temperature the control is currently trying to maintain at the boiler supply sensor. “– – –” is displayed when no heat is required for boiler zones.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup.
BOILER RETURN SECTION E
Current boiler return water temperature as measured by the boiler sensor.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Ret.
DHW SECTION H
Current DHW tank temperature as measured by the DHW sensor.
Note: This item is only available when the Off / DHW Sensor DIP Switch is set to DHW sensor.
SECTION B
VIEW MENU
0 to 100% Ad
0 to 100% Ad
0 to 999 hr
0 to 999 hr
InS
Ad
InS
Ad
BOILER 1 MODULATION SECTION C
Current percent modulation of the Boiler 1 burner.
Note: This item is only available when the Boiler On-Off / Mod DIP switch is set to Mod, the Boiler Sensor Sup / Ret DIP switch is set to Sup, and Boiler 1 is set to Auto.
BOILER 2 MODULATION SECTION C
Current percent modulation of the Boiler 2 burner.
Note: This item is only available when the Boiler On-Off / Mod DIP switch is set to Mod, the Boiler Sensor Sup / Ret DIP switch is set to Sup and Boiler 2 is set to Auto.
BOILER 1
The total running time of Boiler 1 since this item was last cleared. To clear this item, press the Up and Down buttons simultaneously while viewing this item.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup and Boiler 1 is set to Auto.
BOILER 2
The total running time of Boiler 2 since this item was last cleared. To clear this item, press the Up and Down buttons simultaneously while viewing this item.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup and Boiler 2 is set to Auto.
After the last item, the control returns to the first item in the menu.
7 of 36 © 2007 D 423 - 08/07
Page 8
Adjust Menu (1 of 7)
The Adjust Menu items are the programmable settings used to operate the mechanical equipment.
Item Field
Range
boil, M1 (Mix 1), OFF
Default = boil
boil, M1 (Mix 1),
M2 (Mix 2), OFF
Default = boil
boil, M1 (Mix 1),
M3 (Mix 3), OFF
Default = boil
-60 to 45°F
(-51.0 to 7.0°C)
Default = 10°F
(-12.0°C)
Access Description
Ad
Ad
Ad
InS
Ad
BUS 1 SECTION C
Select the water temperature for tN4 Bus 1.
BUS 2 SECTION C
Select the water temperature for tN4 Bus 2.
Note: M1 is only available if Bus 1 is set to M1 (Mix 1).
BUS 3 SECTION C
Select the water temperature for tN4 Bus 3.
Note: M1 is only available if Bus 1 is set to M1 (Mix 1).
OUTDOOR DESIGN SECTION B
The design outdoor air temperature used in the heat loss calculations for the heating system. Typically set to the outdoor temperature of the coldest day of the year.
ADJUST MENU
Continued on next page.
1 HRF1 2 HRF2 3 Fancoil 4 Fin-tube Convector 5 Radiator 6 Baseboard
Default = 1
40 to 100°F
(4.5 to 38.0°C)
Default = 70°F (21.0°C)
70 to 220°F
(21.0 to 104.5°C)
Default = 120°F
(49.0°C)
InS
Ad
Ad
InS
Ad
MIX 1 TERMINAL SECTION B
The type of heating terminal units that are being used in Mix 1 zones.
Note: This item is only available when Bus 1 is set to Mix 1.
MIX 1 INDOOR
The design indoor air temperature used in the heat loss calculation for Mix 1 zones. Typically set to 70°F (21.0°C).
Note: This item is only available when Bus 1 is set to Mix 1.
MIX 1 DESIGN SECTION B
The supply water temperature required for the Mix 1 zones on the typical coldest day of the year.
Note: This item is only available when Bus 1 is set to Mix 1.
SECTION B
© 2007 D 423 - 08/07 8 of 36
Page 9
Adjust Menu (2 of 7)
Item Field
Range
OFF, 40 to 150°F
(OFF, 4.5 to 65.5°C)
Default = OFF
80 to 220°F, OFF
(26.5 to 104.5°C, OFF)
Default = 140°F
(60.0°C)
30 to 230 seconds
Default = 105
1 HRF1 2 HRF2 3 Fancoil 4 Fin-tube Convector 5 Radiator 6 Baseboard
Default = 1
Access Description
MIX 1 MINIMUM
Ad
Ad
Ad
InS
Ad
The minimum allowed Mix 1 target temperature.
Note: This item is only available when Bus 1 is set to Mix 1.
MIX 1 MAXIMUM SECTION G
The maximum allowed Mix 1 target temperature.
Note: This item is only available when Bus 1 is set to Mix 1.
MIX 1 MOTOR SECTION G
The time that the Mix 1 actuating motor requires to operate from fully closed to fully open.
Note: This item is only available when Bus 1 is set to Mix 1 and the Mixing Expansion Module is set to Floating Action. Availability also depends on the type of mixing module used.
MIX 2 TERMINAL SECTION B
The type of heating terminal units that are being used in Mix 2 zones.
Note: This item is only available when Bus 2 is set to Mix 2.
SECTION G
ADJUST MENU
40 to 100°F
(4.5 to 38.0°C)
Default = 70°F (21.0°C)
70 to 220°F
(21.0 to 104.5°C)
Default = 120°F
(49.0°C)
OFF, 40 to 150°F
(OFF, 4.5 to 65.5°C)
Default = OFF
80 to 220°F, OFF
(26.5 to 104.5°C, OFF)
Default = 140°F
(60.0°C)
Ad
InS
Ad
Ad
Ad
MIX 2 INDOOR SECTION B
The design indoor air temperature used in the heat loss calculation for Mix 2 zones. Typically set to 70°F (21.0°C).
Note: This item is only available when Bus 2 is set to Mix 2.
MIX 2 DESIGN SECTION B
The supply water temperature required for the Mix 2 zones on the typical coldest day of the year.
Note: This item is only available when Bus 2 is set to Mix 2.
MIX 2 MINIMUM SECTION G
The minimum allowed Mix 2 target temperature.
Note: This item is only available when Bus 2 is set to Mix 2.
MIX 2 MAXIMUM SECTION G
The maximum allowed Mix 2 target temperature.
Note: This item is only available when Bus 2 is set to Mix 2.
Continued on next page.
9 of 36 © 2007 D 423 - 08/07
Page 10
Adjust Menu (3 of 7)
Item Field
Range
30 to 230 seconds
Default = 105
1 HRF1 2 HRF2 3 Fancoil 4 Fin-tube Convector 5 Radiator 6 Baseboard
Default = 1
40 to 100°F
(4.5 to 38.0°C)
Default = 70°F (21.0°C)
70 to 220°F
(21.0 to 104.5°C)
Default = 120°F
(49.0°C)
Access Description
MIX 2 MOTOR
The time that the Mix 2 actuating motor requires to operate from fully closed to fully open.
Ad
InS
Ad
Ad
InS
Ad
Note: This item is only available when Bus 2 is set to Mix 2, and the Mixing Expansion Module is set to Floating Action. Availability also depends on the type of mixing module used.
MIX 3 TERMINAL SECTION B
The type of heating terminal units that are being used in Mix 3 zones.
Note: This item is only available when Bus 3 is set to Mix 3.
MIX 3 INDOOR SECTION B
The design indoor air temperature used in the heat loss calculation for Mix 3 zones. Typically set to 70°F (21.0°C).
Note: This item is only available when Bus 3 is set to Mix 3.
MIX 3 DESIGN SECTION B
The supply water temperature required for the Mix 3 zones on the typical coldest day of the year.
Note: This item is only available when Bus 3 is set to Mix 3.
SECTION G
ADJUST MENU
OFF, 40 to 150°F
(OFF, 4.5 to 65.5°C)
Default = OFF
80 to 220°F, OFF
(26.5 to 104.5°C, OFF)
Default = 140°F
(60.0°C)
30 to 230 seconds
Default = 105
Au (Auto)
OFF
Default = Au
Ad
Ad
Ad
InS
Ad
MIX 3 MINIMUM SECTION G
The minimum allowed Mix 3 target temperature.
Note: This item is only available when Bus 3 is set to Mix 3.
MIX 3 MAXIMUM SECTION G
The maximum allowed Mix 3 target temperature.
Note: This item is only available when Bus 3 is set to Mix 3.
MIX 3 MOTOR SECTION G
The time that the Mix 3 actuating motor requires to operate from fully closed to fully open.
Note: This item is only available when Bus 3 is set to Mix 3, and the Mixing Expansion Module is set to Floating Action. Availability also depends on the type of mixing module used.
BOILER 1 SECTION C
Selects Whether Boiler 1 is operational or not.
Note: This item is only available when the Boil Sensor Sup / Ret DIP Switch is set to Sup, and the tekmar stager DIP switch is set to OFF.
Continued on next page.
© 2007 D 423 - 08/07 10 of 36
Page 11
Adjust Menu (4 of 7)
Item Field
Range
Au (Auto)
OFF
Default = Au
1 HRF1 2 HRF2 3 Fancoil 4 Fin-tube Convector 5 Radiator 6 Baseboard
Default = 4
40 to 100°F
(4.5 to 38.0°C)
Default = 70°F
(21.0°C)
70 to 220°F
(21.0 to 104.5°C)
Default = 180°F
(82.0°C)
Access Description
BOILER 2
InS
Ad
InS
Ad
Ad
InS
Ad
Selects whether Boiler 2 is operational or not.
Note: This item is only available when the Boil Sensor Sup / Ret DIP Switch is set to Sup, and the tekmar stager DIP switch is set to OFF.
BOILER TERMINAL SECTION B
The type of heating terminal units that are being used in boiler zones.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup.
BOILER INDOOR SECTION B
The design indoor air temperature used in the heat loss calculation for the boiler zones. Typically set to 70°F (21.0°C).
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup.
BOILER DESIGN SECTION B
The supply water temperature required for boiler zones on the typical coldest day of the year.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup.
SECTION C
ADJUST MENU
OFF, 80 to 180°F
(OFF, 26.5 to 82.0°C)
Default = 140°F
(60.0°C)
90 to 225°F, OFF
(32.0 to 107.0°C, OFF)
Default = 200°F
(93.5°C)
Au (Auto), 2 to 42°F
(Au, 1 to 23.5°C)
Default = Au
Au (Auto), 0.5 to
20.0 minutes
Default = Au
InS
Ad
Ad
Ad
Ad
BOILER MINIMUM
The minimum allowed boiler target temperature and boiler return protection temperature. Check the boiler manufacturer’s manual for recommend supply water temperatures.
BOILER MAXIMUM SECTION C
The maximum allowed boiler target temperature.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup and the tekmar stager DIP switch is set to OFF.
BOILER DIFFERENTIAL SECTION C
The temperature differential that the control is to use to cycle the boiler On and Off.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup and the tekmar stager DIP switch is set to OFF.
STAGE DELAY SECTION C
The minimum time delay between the operation of stages.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup and the tekmar stager DIP switch is set to OFF.
SECTION
C
Continued on next page.
11 of 36 © 2007 D 423 - 08/07
Page 12
Adjust Menu (5 of 7)
Item Field
Range
0:00 to 3:00 min
Default = 0:10 min
10 to 230 seconds
Default = 30 seconds
0 to 50%
Default = 0%
Access Description
BOILER FIRE DELAY
The time delay the control can expect between the relay contact closes to fire the boiler and when the
Ad
Ad
Ad
burner actually fires.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup, and the tekmar stager DIP switch is set to OFF.
BOILER MOTOR SECTION C
The amount of time required for the modulating actuating motor to fully open the gas valve or operate the fan speed from a stopped position to full speed.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup, the Boiler On-Off / Mod DIP switch is set to Mod and the tekmar stager DIP switch is set to OFF.
BOILER MINIMUM MODULATION SECTION C
The minimum percent modulation of the burner.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup, the Boiler On-Off / Mod DIP switch is set to Mod, and the tekmar stager DIP switch is set to OFF.
SECTION C
ADJUST MENU
Au (Auto),
5 to 30 min
Default = Au
OFF, Mb1 (Member 1), Mb2 (Member 2), Mb3 (Member 3), Mb4 (Member 4),
Default = OFF
OFF, 1 (parallel, no priority) 2 (parallel, priority) 3 (pri-sec, no priority) 4 (pri-sec, priority)
Default = 1
OFF, 70 to 190°F
(OFF, 21.0 to 87.5°C)
Default = 140°F
(60.0°C)
Ad
InS
Ad
InS
Ad
InS
Ad
CYCLE LENGTH
The cycle length to which all tN4 devices will synchronize.
SCHEDULE
Selects which network setback schedule the control will follow.
DHW MODE SECTION H
Selects the DHW mode of operation. This determines the operation of the primary pump in combination with the DHW Pump / Valve and whether or not DHW priority is required.
DHW (Occupied)
The temperature of the DHW tank during the Wake and Occupied periods.
Note: This item is only available when DHW Mode is set 1 through 4, and the Off / DHW Sensor DIP Switch is set to DHW Sensor.
SECTION H
Continued on next page.
© 2007 D 423 - 08/07 12 of 36
Page 13
Adjust Menu (6 of 7)
Item Field
Range
OFF, 70 to 190°F
(OFF, 21.0 to 87.5°C)
Default = OFF
1 to 42°F
(0.5 to 23.5°C)
Default = 6°F (3.0°C)
100 to 220°F
(38.0 to 104.5°C)
Default = 180°F
(82.0°C)
Access Description
DHW (UnOccupied)
The temperature of the DHW tank during the Sleep and Unoccupied periods.
Ad
Ad
Ad
Note: This item is only available when DHW Mode is set 1 through 4, the Off / DHW Sensor DIP Switch is set to DHW Sensor, and the Schedule Setting is set to Member 1, 2, 3 or 4.
DHW DIFFERENTIAL SECTION H
The temperature differential (swing up and down) of the DHW tank from the DHW setting.
Note: This item is only available when the DHW Sensor DIP switch is set to DHW, and the DHW Mode is set 1 through 4 and the DHW Sensor DIP is set to OFF.
DHW EXCHANGE (Occupied) SECTION H
The boiler supply temperature to the DHW heat exchanger during the Occupied and Wake periods.
Note: This item is only available when DHW Mode is set 1 through 4 and the DHW Sensor DIP is set to OFF.
SECTION H
ADJUST MENU
OFF, On
Default = OFF
OFF,
1 (parallel, no priority) 2 (parallel, priority) 3 (pri-sec, no priority) 4 (pri-sec, priority)
Default = 1
60 to 220°F
(15.5 to 104.5°C)
Default = 180°F
(82.0°C)
Ad
Ad
Ad
DHW EXCHANGE (UnOccupied) SECTION H
Selects whether the control should respond to DHW Demands during the Sleep and Unoccupied periods.
Note: This item is only available when DHW Mode is set 1 through 4 and the Schedule Setting is set to Member 1, 2, 3 or 4 and the DHW Sensor DIP is set to OFF.
SETPOINT MODE
Selects the Setpoint mode of operation. This determines the operation of the primary pump and whether or not priority is required.
SETPOINT (Occupied) SECTION J
The minimum boiler target temperature when a Setpoint Demand is present during the Wake and Occupied periods.
Note: This item is only available when Setpoint Mode is set 1 through 4.
SECTION J
Continued on next page.
13 of 36 © 2007 D 423 - 08/07
Page 14
Adjust Menu (7 of 7)
Item Field
Default = 70°F (21.0°C)
Range
OFF, On
Default = OFF
40 to 100°F, OFF
(4.5 to 38.0°C, OFF)
Access Description
Ad
InS
Ad
ADJUST MENU
40 to 100°F, OFF
(4.5 to 38.0°C, OFF)
Default = 60°F (15.5°C)
After the last item, the control returns to the first item in the menu.
Ad
SETPOINT (UnOccupied)
Selects whether or not a Setpoint Demand will be responded to during the Sleep and Unoccupied periods.
Note: This item is only available when Setpoint Mode is set 1 through 4 and the Schedule Setting is set to Member 1, 2, 3 or 4.
WWSD (Occupied) SECTION B
The system’s warm weather shut down temperature during the Wake and Occupied periods. The WWSD applies to the space heating loads only. It does not affect DHW or Setpoint heating loads.
WWSD (UnOccupied) SECTION B
The system’s warm weather shut down temperature during the Sleep and Unoccupied period.
Note: This item is only available when the Schedule Setting is set to Member 1, 2, 3 or 4.
SECTION J
© 2007 D 423 - 08/07 14 of 36
Page 15
Misc (Miscellaneous) Menu (1 of 1)
Item Field Range Access Description
InS (Installer)
Ad (Advanced)
InS
Ad
The Miscellaneous Menu Items set control and display options such as access level and temperature units.
ACCESS LEVEL
The access level of the control. The access column shows which items are visible in each access level.
Note: This item is only available when the Lock / Unlock DIP switch is set to Unlock.
MISC MENU
°F, °C
Default = °F
0 to 24 Ad
0 to 24 Ad
0 to 24 Ad
0 to 24 Ad
InS
Ad
UNITS
Select between Fahrenheit and Celsius temperature units.
BUS 1 DEVICES
Displays the number of devices on Bus 1.
Note: This item is only available when Bus 1 is set to boil or Mix 1.
BUS 2 DEVICES
Displays the number of devices on Bus 2.
Note: This item is only available when Bus 2 is set to boil, Mix 1 or Mix 2.
BUS 3 DEVICES
Displays the number of devices on Bus 3.
Note: This item is only available when Bus 3 is set to boil, Mix 1 or Mix 3.
BOILER BUS DEVICES
Displays the number of devices on the boiler bus.
OFF
SEL (Select)
423
After the last item, the control returns to the first item in the menu.
Ad
InS
Ad
15 of 36 © 2007 D 423 - 08/07
FACTORY DEFAULT
Loads the factory defaults when the Up and Down buttons are held down for 1 second.
TYPE
Displays the type number of this product. Hold the Up button to display the software version.
Page 16
Testing the Control
IF Bus 3 is set to M3 (Mix 3):
The control has a built-in test routine that tests the main control functions. The control continually monitors the sensors and displays an error message whenever a fault is found. The individual outputs and relays are tested using a test sequence.
Test Sequence
Each step in the test sequence lasts 10 seconds.
Start the test sequence by pressing the Test button.
Pause the test sequence by pressing the Test button
again. To advance to the next step, press the Test button again.
If the test sequence is paused for more than five minutes,
the control exits the entire test routine.
To advance to a particular step, repeatedly press and
release the Test button to display the appropriate device.
HAZARD
Access to the Test button requires the removal of the front cover and exposes hazardous voltage while the control is powered. Only trained, qualified and competent personnel should operate the Test button.
Step 7 The Mix 3 device ramps up to 100% over
10 seconds or according to the motor speed setting.
Step 8 The Mix 3 device ramps down to 0% over
10 seconds or according to the motor speed setting.
Step 9 The Mixing 3 pump on the Mixing Module
turns on for 10 seconds then shuts off.
Step 10 The primary pump turns on and remains on for
the rest of the test sequence.
IF Boil 1 is set to Au (Auto):
Step 11 The Stage 1 contact is closed to fire an on-off
boiler for 10 seconds or enable a modulating boiler.
IF the On-Off / Modulating DIP switch is set to Modulating or the tekmar Stager / Off DIP switch is set to tekmar Stager:
Step 12 The Mod 1 output ramps up to 100%.
Step 13 The Mod 1 output ramps down to 0%.
The Stage 1 contact is opened and the boiler is shut off.
Te s t
IF Bus 1 is set to M1 (Mix 1):
Step 1 The Mix 1 device ramps up to 100% over
10 seconds or according to the motor speed setting.
Step 2 The Mix 1 device ramps down to 0% over
10 seconds or according to the motor speed setting.
Step 3 The Mixing 1 pump turns on for 10 seconds
then shuts off.
IF Bus 2 is set to M2 (Mix 2):
Step 4 The Mix 2 device ramps up to 100% over
10 seconds or according to the motor speed setting.
Step 5 The Mix 2 device ramps down to 0% over
10 seconds or according to the motor speed setting.
Step 6 The Mixing 2 pump on the Mixing Module
turns on for 10 seconds then shuts off.
Press and Hold for 1 second
IF Boil 2 is set to Au (Auto):
Step 14 The Stage 2 contact is closed to fire an on-off
boiler for 10 seconds or enable a modulating boiler.
IF the On-Off / Modulating DIP switch is set to Modulating:
Step 15 The Mod 2 output ramps up to 100%.
Step 16 The Mod 2 output ramps down to 0%.
The Stage 2 contact is opened and the boiler
is shut off.
Step 17 If DHW MODE is set to 1 or 2, the primary
pump is shut off and the DHW Pump contact is closed.
If DHW MODE is set to 3 or 4, the primary
pump stays on and the DHW Pump contact is closed.
The control exits the test sequence.
If a device fails to operate during the test sequence, refer to the W 423 Wiring Brochure to check the operation of the control. If the control works properly, refer to any troubleshooting information supplied by the equipment manufacturer.
© 2007 D 423 - 08/07 16 of 36
Page 17
Max Heat
Zone Test
The control has a function called Max Heat. In this mode, the control turns on and operates the system up to the maximum set temperatures as long as there is a demand for heat. tN4 thermostats operate to meet the occupied setting +5°F (3°C). The control operates in this mode for up to 24 hours or until the Test button is pressed. Use this mode to run the circulators during system start-up to purge air from the piping.
The Mix 1, Mix 2 and Mix 3 Maximum settings are avail-
able in the Adjust Menu when in Max Heat.
HAZARD
Access to the Test button requires the removal of the front cover and exposes hazardous voltage while the control is powered. Only trained, qualified and competent personnel should operate the Test button.
Te s t
Press and Hold for 3 seconds
To enable Max Heat:
Press and hold the Test button for more than 3 seconds and less than 6 seconds.
If there is a demand for heat, the ‘TEST’ and ‘MAX’ segments are displayed on screen and the control will turn on all outputs for up to 24 hours.
If there is no demand for heat, the ‘TEST’ and ‘MAX’ segments are still displayed but no outputs are turned on until there is a demand for heat present.
To Cancel Max Heat:
Press the Test button to cancel Max Heat manually or wait 24 hours and the control will automatically leave the Max Heat mode.
In Zone Test mode, each tN4 device is individually turned on one at a time. The control tests each zone for up to 5 minutes of no button activity. Use this feature to purge air out of each zone and assist in troubleshooting.
HAZARD
Access to the Test button requires the removal of the front cover and exposes hazardous voltage while the control is powered. Only trained, qualified and competent personnel should operate the Test button.
Te s t
Press and Hold for 6 seconds
To enable Zone Test:
1. Press and hold the Test button for more than 6 seconds. The control displays ZN TEST OFF.
2. Press the Up button to change the display to ZN TEST ON. After 3 seconds, the boiler, all pumps, and the mixing valves are shut off.
3. The control operates stage one of the tN4 device with the lowest address number. Device number one of the boiler bus (b:01) has the lowest address number and device 24 of bus 3 (3:24) has the highest address number. All other tN4 zones are shut off.
4. Pressing the Up button will turn off stage 1, and turn on stage 2 of the same device (if that device has a second stage) or turn on stage 1 of the device with the next lowest address. The Down button can be pressed to move to a device with a lower address number. The Up and Down buttons will only move through devices on the same bus.
5. Press the Item button to switch busses. The Up and Down buttons can then be used to move through the devices and the heating stages of each device on the next bus.
6. To cancel the Zone Test, press the Test button. Once the Zone Test ends or is cancelled, the control resumes normal operation.
Tes t
Hold
for 6
seconds
Wait
3
seconds
Tes t
17 of 36 © 2007 D 423 - 08/07
Page 18
Sequence of Operation
tekmarNet®4 Communication Section A
tekmarNet®4 (tN4) communicates between tN4 devices
Outdoor Reset Module
(thermostats, Reset Module and Expansion Modules). Each tN4 device is connected to a tN4 communication bus using two wires. Each tN4 bus adjusts a single water temperature in the system using indoor temperature feedback. The Universal Reset Module 423 allows for four tN4 buses. This allows you to control a system with up to four separate water temperatures.
A system that has more than one tN4 bus is referred to as
The Universal Reset Module 423 is the system control for a hydronic heating system. The 423 operates a up to two heat sources such as boilers, up to three mixing devices, a domestic hot water tank, and responds to other heating requirements such as pool heating and snow melting. The 423 also coordinates and optimizes the operation of all the tN4 thermostats.
a tN4 network.
tN4 Thermostat
Network
Bus 1 Bus 2
The tN4 thermostat operates heating, cooling, and or ventilation equipment for a zone. Several tN4 thermostats may work in a group when operating a cooling system. Up
tekmarNet®4 Thermostats
Do not apply power
tN4
H7008B
/
Test
tN4
Menu
Item
Zone A1
Power
Zone Group Pump A
Zone A2
Zone Group Pump B
Zone A3
Zone B1
Zone B2
Zone B3
tekmarNet®4 Thermostats
to 24 tN4 thermostats can connect to a single tN4 bus.
Outdoor Reset Section B
In a heating system, the rate of heat supplied to the building must equal the rate of which heat is lost. If the two rates are not equal, the building will either cool off or over heat.
The rate of building heat loss depends mostly on the outdoor temperature. Outdoor Reset allows a hot water heating system to increase the water temperature, adding heat to the building, as the outdoor temperature drops. The rate at which the water temperature is changed is defined by the characterized heating curve.
Characterized Heating Curves
A characterized heating curve determines the amount the supply water temperature is raised for every 1° drop in outdoor air temperature. There is a characterized heating curve for each tN4 communication bus.
The characterized heating curve takes into account the type of terminal unit that the system is using. Since different types of heating terminal units transfer heat to a space using different proportions of radiation, convection and conduction, the supply water temperature must be controlled differently. Each tN4 bus is assigned a terminal unit setting that the control uses to vary the supply water temperature to suit to the terminal unit used. This improves the control of the air temperature in the building.
Indoor Temperature Feedback
Most buildings have internal heat gains due to people, passive solar heating and mechanical or electrical equipment. Likewise, wind loads cause a building to lose heat faster than during design conditions. If only the outdoor temperature is measured, the control cannot compensate for these internal heat gains or loses and the building may over or under heat. In order to maintain the most comfortable temperature, the control uses indoor temperature feedback from tN4 thermostats in order to adjust the water temperature on each tN4 bus on a continual basis.
© 2007 D 423 - 08/07 18 of 36
Page 19
Terminal Unit
There is a terminal unit setting for each tN4 bus. The Terminal Unit setting is found in the Adjust Menu.
Hydronic Radiant Floor (1)
Terminal type 1 is a heavy, or high mass, hydronic radiant floor system. This type of a hydronic radiant floor is embedded in either a thick concrete or gypsum pour. This heating system has a large thermal mass and is slow acting.
Hydronic Radiant Floor (2)
Terminal type 2 is a light, or low mass, hydronic radiant floor system. Most commonly, this type of radiant heating system is either attached to the bottom of a wood sub floor, suspended in the joist space, or sandwiched between the subfloor and the surface. This type of radiant system has a relatively low thermal mass and responds faster than a high mass system.
Radiator (5)
Terminal type 5 is a radiator terminal unit has a large heated surface that is exposed to the room. A radiator provides heat to the room through radiant heat transfer and natural convection.
Baseboard (6)
Terminal type 6 is a baseboard terminal unit is similar to a radiator, but has a low profile and is installed at the base of the wall. The proportion of heat transferred by radiation from a baseboard is greater than that from a fin-tube convector.
Fancoil (3)
Terminal type 3 is a fancoil terminal unit or air handling unit (AHU) consisting of a hydronic heating coil and either a fan or blower. Air is forced across the coil at a constant velocity by the fan or blower and is then delivered into the building space.
Fin–tube Convector (4)
Terminal type 4 is a convector terminal unit is made up of a heating element with fins on it. This type of terminal unit relies on the natural convection of air across the heating element to deliver heated air into the space. The amount of natural convection is dependant on the supply water temperature to the heating element and the room air temperature.
Outdoor Design Temperature
The outdoor design temperature is typically the coldest outdoor air temperature of the year. This temperature is used when doing the heat loss calculations for the building and is used to size the heating system equipment. If a cold outdoor design temperature is selected, the supply water temperature rises gradually as the outdoor temperature drops. If a warm outdoor design temperature is selected, the supply water temperature rises rapidly as the outdoor temperature drops.
The outdoor design setting is found in the Adjust Menu.
Warm Weather Shut Down (WWSD)
The Warm Weather Shut Down is the outdoor temperature at which hydronic heating is no longer required. The control closes mixing valves and variable speed pumps are not operated. The boiler operates only when a Domestic Hot Water (DHW) Demand or a Setpoint Demand is present.
The WWSD setting is found in the Adjust Menu.
19 of 36 © 2007 D 423 - 08/07
Page 20
Boiler Outdoor Reset
Mix 1, Mix 2 and Mix 3 Outdoor Reset
There is a water temperature and therefore a characterized heating curve for each communication bus. When using boiler temperature water to heat zones, the installer will be required to set a boiler characterized heating curve.
Boiler Terminal Unit Defaults
When a terminal unit is selected for boiler zones, the control loads default values for the boiler design, boiler maximum supply, and boiler minimum supply temperatures. The factory defaults can be changed to better match the installed system. Locate the Boiler Terminal Unit setting in the Adjust Menu.
Boiler Characterized Heating Curve
Boiler
Design
Terminal Unit
Outdoor
Design
Boiler
Indoor
Increasing Water Temperatures
Decreasing Outdoor Temperatures
Each tN4 communication bus operates on a separate water temperature. Therefore a separate characterized heating curve is required for Mix 1, Mix 2 and Mix 3.
Mix 1, 2 and 3 Terminal Unit Defaults
When a terminal unit is selected for Mix 1, 2, or 3, the control loads default values for the mix design, mix maximum supply, and mix minimum supply temperatures. The factory defaults can be changed to better match the installed system.
Locate the Mix 1, Mix 2 and Mix 3 terminal unit settings
in the Adjust Menu.
Mix Characterized Heating Curve
Mix
Terminal Unit
Outdoor
Design
Mix
Indoor
Decreasing Outdoor Temperatures
Design
Increasing Mix Temperature
Terminal Unit
High Mass Radiant (1)
Low Mass Radiant (2)
Fancoil (3)
Fin-Tube Convector (4)
Radiator (5)
Baseboard (6)
BOIL DSGN BOIL MAX BOIL MIN
120°F (49°C) 140°F (60°C) OFF
140°F (60°C) 160°F (71°C) OFF
190°F (88°C) 210°F (99°C) 140°F (60°C)
180°F (82°C) 200°F (93°C) 140°F (60°C)
160°F (71°C) 180°F (82°C) 140°F (60°C)
150°F (76°C) 170°F (77°C) 140°F (60°C)
Boiler Indoor Design
The boiler indoor design temperature is the indoor temperature the heating designer chose while calculating the heat loss for the boiler water heated zones. This temperature is typically 70°F (21.0°C). This setting establishes the beginning of the boiler characterized heating curve.
Locate the Boiler Indoor Design setting in the Adjust
Menu.
Boiler Design Temperature
The boiler design supply temperature is the boiler water temperature required to heat the zones on the typical coldest day of the year.
Locate the Boiler Design setting in the Adjust Menu.
Terminal Unit
High Mass Radiant (1)
Low Mass Radiant (2)
Fancoil (3)
Fin-Tube Convector (4)
Radiator (5)
Baseboard (6)
MIX DSGN MIX MAX MIX MIN
120°F (49°C) 140°F (60°C) OFF
140°F (60°C) 160°F (71°C) OFF
190°F (88°C) 210°F (99°C) 100°F (38°C)
180°F (82°C) 200°F (93°C) OFF
160°F (71°C) 180°F (82°C) OFF
150°F (76°C) 170°F (77°C) OFF
Mix 1, Mix 2 and Mix 3 Indoor Design
The Mix 1, Mix 2 and Mix 3 indoor design temperature is the indoor temperature the heating designer picked while calculating the heat loss for the building for the Mix 1, Mix 2, or Mix 3 water heated zones. This temperature is typically 70°F (21.0°C). This setting establishes the beginning of the Mix 1, Mix 2, or Mix 3 characterized heating curve.
Locate the Mix 1, Mix 2 and Mix 3 Indoor Design settings
in the Adjust Menu.
Mix 1, Mix 2, and Mix 3 Design Temperature
The Mix 1, Mix 2, and Mix 3 design supply temperature is the mix supply water temperature required to heat the zones when the outdoor temperature is as cold as the outdoor design temperature.
Locate the Mix 1, Mix 2 and Mix 3 Design settings in the
Adjust Menu.
© 2007 D 423 - 08/07 20 of 36
Page 21
Boiler Temperature Control Section C
B
o
i
l
W
a
t
e
r
T
e
m
p
e
r
a
t
u
r
e
B
o
i
l
W
a
t
e
r
T
e
m
p
e
r
a
t
u
r
e
The 423 is able to operate up to two on-off or modulating boiler as a heat source. For proper operation of the boilers, the 423 must be the only control that determines when the boilers are to fire. In this case, the boiler sensor should be located on the boiler supply pipe and the Boiler Sensor DIP switch is set to Supply.
*Important note: Each boiler operator, also known as an aquastat, remains in the burner circuit and acts as a secondary upper limit on the boiler temperature. Each boiler operator temperature setting must be adjusted above the 423’s Boiler Maximum setting in order to prevent short cycling of the boiler burner.
Boiler Target Temperature
The boiler target temperature is determined by connected tN4 devices or by a DHW or Setpoint Demand received by the control. The tN4 devices determine the highest water temperature required and then, requests this temperature on the tN4 Boiler Bus. The temperature request creates a Boiler Demand and this is indicated on the display. A DHW Demand and a Setpoint Demand have temperature settings to which the boilers are operated to meet and are able to override the tN4 bus temperature if required.
The control displays the temperature that it is currently trying to maintain as the boiler supply temperature in the View Menu. If the control does not presently have a requirement for heat, it does not show a boiler target temperature. Instead, “– – –” is displayed in the LCD.
Operation of the tN4 Buses
The 423 has four available tN4 communication buses. One bus is dedicated for a boiler water temperature. The three remaining buses (Bus 1, Bus 2 and Bus 3) can operate at either the boiler water temperatures or as up to three separate mixing water temperatures. The Bus 1, Bus 2 and Bus 3 items set the operation of each of these three buses.
Bus 2
Bus 2 is connected to a Zone manager via terminals 62 and 63. When Bus 2 is set to Boil, the tN4 thermostats connected to Bus 2 become part of the Boiler Bus. When Bus 2 is set to M1 (Mix 1), the tN4 thermostats connected to Bus 2 become part of Mix 1. When Bus 2 is set to M2 (Mix 2), a Mixing Expansion Module must be connected to Bus 2 and the tN4 thermostats connected to Bus 2 operate the Mixing Expansion Module to heat their zones.
Bus 3
Bus 3 is connected to a Zone manager via terminals 64 and 65. When Bus 3 is set to Boil, the tN4 thermostats connected to Bus 3 become part of the Boiler Bus. When Bus 3 is set to M1 (Mix 1), the tN4 thermostats connected to Bus 3 become part of Mix 1. When Bus 3 is set to M3 (Mix 3), a Mixing Expansion Module must be connected to Bus 3 and the tN4 thermostats connected to Bus 3 operate the Mixing Expansion Module to heat their zones.
Boiler Minimum
The boiler minimum is the lowest temperature that the control is allowed to use as a boiler target temperature. During mild conditions, if the control calculates a boiler target temperature that is below the Boiler Minimum setting, the boiler target temperature is adjusted to at least the Boiler Minimum setting. During this condition, if the boiler(s) is operating, the minimum segment is turned on in the display when viewing either the boiler supply temperature or the boiler target temperature. Set the Boiler Minimum setting to the boiler manufacturer’s recommended temperature.
Locate the Boiler Minimum setting in the Adjust Menu.
Boil MIN + ½ Boiler Differential
e
r
u
t
a
m
e
B
o
i
MIN segment on
T
r
e
t
l
a
W
r
e
p
Boil MIN– ½ Boiler Differential
Boil MIN
Boiler Bus
The boiler bus is connected to a Zone manager via terminals 58 and 59. tN4 thermostats or tN4 devices connected to the Boiler Bus operate the boiler directly in order to heat their zones. The boiler water temperature target will be determined based upon boiler outdoor reset and indoor feedback from the tN4 thermostats.
Bus 1
Bus 1 is connected to a Zone manager via the plug on the underside of the board. Additional Zone managers may be connected to bus 1 via terminals 60 and 61, When Bus 1 is set to Boil, the tN4 thermostats connected to Bus 1 become part of the Boiler Bus. When Bus 1 is set to M1 (Mix 1), a Mixing Expansion Module must be connected to Bus 1 and the tN4 thermostats connected to Bus 1 operate the Mixing Expansion Module to heat their zones.
Boiler Maximum
The boiler maximum is the highest temperature that the control is allowed to use as a boiler target temperature. If the control does target the Boiler Maximum setting, and the boiler temperature is near the boiler maximum temperature, the maximum segment will be displayed in the LCD while either the boiler target temperature or the boiler temperature is being viewed. At no time does the control operate the boiler(s) above 248°F (120.0°C).
Locate the Boiler Maximum setting in the Adjust Menu.
Boil MIN + ½ Boiler Differential
B
o
MAX
segment
on
21 of 36 © 2007 D 423 - 08/07
r
e
t
a
W
l
i
a
r
e
t
u
p
m
e
T
MAX
segment
r
e
Boil MIN – ½ Boiler Differential
on
Boil MAX
Page 22
Boiler Fire Delay
The Boiler Fire Delay is the time delay that occurs between the time that the control closes the boiler contact to fire the boiler and when the burner fires.
Locate the Boiler Fire Delay setting in the Adjust Menu.
Boiler Contact Closed
Fire Delay
Burner On
Auto Differential
In order to decrease temperature swings and increase boiler efficiency, the Auto Differential feature automatically changes the on / off differential of the boiler based on the heating load. As the load increases, the differential will decrease to minimize temperature swings. As the load decreases, the differential will increase to prevent short cycling.
Off
Time
On-Off Boiler(s) Operation
If the heat source is an On-Off Boiler(s), the Boil On-Off / Mod DIP switch must be set to On-Off.
Differential
An on / off heat source must be operated with a differential in order to prevent short cycling. With the control, either a fixed or an auto differential may be selected. The boiler differential is divided around the boiler target temperature. The first stage contact closes when the supply water temperature is 1/2 of the differential setting below the boiler target temperature. The second stage is operated if the first stage is unable to bring the supply water temperature up to the boiler target temperature at a reasonable rate. As the supply temperature reaches 1/2 of the differential above the boiler target temperature, the stages are staged off.
Locate the Boiler Differential setting in the Adjust Menu.
Differential = 10°F (6°C)
165°F (74°C)
160°F (71°C)
155°F (68°C)
Boiler
On
Boiler
On
Target + 1/2 Differential
Target
Target – 1/2 Differential
Fixed Differential
If the user desires to have a fixed differential, this is set using the Boiler Differential setting in the Adjust Menu.
Stage Delay
The Stage Delay is the minimum time delay between the firing of the first stage and the second stage. After this delay has expired the control can fire the second stage if it is required. This setting can be adjusted manually or set to an automatic setting. When the automatic setting is used, the control determines the best stage delay based on the operation of the system.
Locate the Stage Delay setting in the Adjust Menu.
Differential
Time
On
Heating Load
Modulating Boiler Operation
The 423 can operate up to two modulating boilers. This requires the use of the Mod 1 (dc) and Mod 2 (dc) outputs on the 423.
To operate modulating boilers, the Boil On-Off / Mod DIP switch must be set to Mod. The control operates each boiler by first closing the stage contact to allow the modulating boiler to go through the ignition sequence (the stage contact may not be required on all modulating boilers). Then, a 0-10 V (dc) analog signal is used to modulate the boiler firing rate from the Minimum Modulation setting using Proportional, Integral and Derivative (PID) logic in order to satisfy the boiler target temperature. The second stage is operated if the first stage is unable to bring the supply water temperature up to the boiler target temperature at a reasonable rate.
Modulating boilers require all the same settings as on-off boilers in addition to the settings below.
Modulating Boiler Differential
Modulating boilers must be operated with a differential while operating in low fire. The boiler differential is divided around the boiler target temperature. The boiler burner ignites at low fire when the supply water temperature is 1/2 of the Boiler Differential setting below the boiler target temperature. The boiler is shut off in low fire as the supply temperature reaches at least 1/2 of the differential above the boiler target temperature. With the control, either a fixed or an auto differential may be selected.
When the boilers are modulating above low fire, the differential does not apply. Instead, the modulation output signal is determined using Proportional, Integral and Derivative (PID) logic in order to satisfy the boiler target temperature.
© 2007 D 423 - 08/07 22 of 36
Page 23
Boiler Motor Speed
The Boiler Motor Speed is the amount of time the boiler requires to go from 0% modulation to 100% modulation.
Gas valve actuating motors have a design time from fully closed to fully open which can be found in the manufacturer’s manual. The Boiler Motor Speed should be set to this time.
The Boiler Motor Speed setting for a Variable Frequency Drive (VFD) is the amount of time required to go from a stopped position to 100% fan speed. Since a VFD has a very quick response rate, it may be necessary to increase the Motor Speed setting in order to increase the stability of the boiler modulation.
Locate the Boiler Motor Speed setting in the Adjust
Menu.
Minimum Modulation
The minimum modulation defines the minimum output signal from the control to the boiler burner. It is based on a percentage of the control’s output signal range.
The Minimum Modulation default setting is 0%.
For boilers with electronic operators, the boiler’s input signal range may not match the output signal range of the 423 control. The Minimum Modulation setting limits the control output range in order to match the boiler’s input range.
Locate the Boiler Minimum Modulation setting in the
Adjust Menu.
To calculate the Minimum Modulation, use the following formula:
For 0-10 V (dc):
Minimum Modulation =
0 V (dc) – Boiler’s Minimum Input Signal x 100%
0-10 V (dc)
Example:
A boiler requires a 1.8 V (dc) signal to fire the boiler at low fire. The boiler can be modulated to 10 V (dc) where it reaches high fire.
This means the boiler’s input signal range is 1.8 to 10 V (dc). The 423 control has an output signal range of 0-10 V (dc).
To make the two signal ranges the same, the Minimum Modulation required is:
Minimum Modulation =
0 V-1.8 V x 100% = 18%
0 V-10 V
10 V (dc)
Control
Range
Boiler
Range
18%
0 Vdc
1.8 V (dc)
tekmar Stager Operation Section D
In some cases, multiple boilers may be required. In these cases, the 423 allows for a connection to a tekmar Boiler Control 264, 265, or 268. The 423 uses the Mod1 (dc) modulating output to provide a 0-10 V (dc) signal to the external input terminals on the Boiler Control. The 423 controls the Boiler Control target temperature by changing the voltage signal. The Boiler Control responds to the boiler target by staging the multiple boilers. The following table can be used to convert a 0-10 V (dc) signal to a boiler target temperature:
Voltage (dc)
Boiler Target
012345678910
Off 50°F (10°C) 68°F (20°C) 86°F (30°C) 103°F (40°C) 121°F (50°C) 139°F (60°C) 157°F (70°C) 174°F (80°C) 192°F (90°C) 210°F (99°C)
To use the tekmar Staging operation, the following DIP switch settings are required:
1. Set the 423 Off / tekmar Stager DIP switch to tekmar Stager.
2. Set the 423 Boil Sup / Ret DIP switch to Sup.
3. Set the 423 Boil On-Off / Mod DIP switch to Mod.
The 423 boiler sensor must be located on the supply pipe leading from the boilers. On the Boiler Control 264, 265, or 268, the External Input / Stand Alone DIP switch must be set to External Input. Any domestic hot water (DHW) demands or Setpoint Demands in the system must connect to the 423 in order to allow for DHW or setpoint priority.
23 of 36 © 2007 D 423 - 08/07
Page 24
Boiler Enable and Setpoint Enable Section E
If the 423 is one of many controls that can call for heat to a single boiler or there is a boiler sequencer other than a tekmar Stager (Boiler Control 264, 265, 268), operating multiple boilers or multiple stages, then the boiler sensor must be located on the return pipe of the boiler(s).
When the sensor is located on the return, the 423 provides a boiler enable. The 423 no longer tries to control the boiler supply water temperature directly, but allows another operating control such as an aquastat to regulate the boiler supply temperature.
When there is a requirement for heat from the Mixing Expansion Modules connected to the 423, the Stage 1 / Boil Enbl contact closes.
When there is a DHW Demand, or a Setpoint Demand, the Stage 2 / Setp Enbl contact closes.
When the boiler sensor is located on the boiler return, the control is able to provide boiler return protection through the use of the Mixing Expansion Modules. This protects the boiler against sustained flue gas condensation and thermal shock.
*Important note: tN4 devices cannot be connected to the Boiler Bus while the Boiler Sensor DIP switch is set to Return.
To operate the control without a boiler sensor and prevent the control from displaying an error message, set the boiler sensor DIP switch to Return and power up the control without the boiler sensor connected.
The control operation will be similar to that as having the boiler sensor on the return except that boiler return protection is no longer provided.
Zone Load Shedding Section F
If the boiler temperature approaches the boiler minimum setting, the control can turn off certain high temperature zones in order to reduce the load on the boiler. This is known as Zone Load Shedding. Zones are shed in the following order:
1. The second stage of any 2-stage thermostats which have “BOIL” selected as their heat source in order of decreasing priority. Priority is determined by the address number of the thermostat (b:01 is the highest priority, 3:24 is the lowest priority).
2. The first stage of any thermostats on the boiler bus, again, in order of decreasing priority. The first stage of the highest priority thermostat (lowest address number) will not be shed unless there is also a setpoint or DHW call.
When the boiler supply temperature goes above the minimum setting, the control begins restoring the load by turning first stages back on in the reverse order that they were shed, followed by second stages in the reverse order that they were shed.
Mixing Operation Section G
The 423 has four tN4 communication buses. The first bus is dedicated for a boiler water temperature and is known as the Boiler Bus. The remaining buses can be selected to be either boiler or mixing depending on their individual Bus settings. When either Bus 1, Bus 2 or Bus 3 are set to be a separate mixing water temperature, a Mixing Expansion Module must be connected to that bus.
A Mixing Expansion Module is required in order to use each mixing temperature. The Mixing Expansion Module operates at the percent output that the 423 determines is required.
Each of the following settings must be set for each mixing water temperature.
Mixing Expansion Modules
A Mixing Expansion Module allows the control to reduce the boiler water temperature down to a lower water temperature. A Mixing Expansion Module when used with a boiler sensor also allows the control to protect the boiler from sustained flue gas condensation and thermal shock.
Variable Speed Injection
The control increases or decreases the power output to the circulator when there is a requirement for mixing. The circulator speed varies to maintain the correct mixed supply water temperature at the mix supply sensor. For correct sizing and piping of the variable speed injection circulator, refer to essay E 021. A visual indication of the current variable speed output is displayed in the LCD in the form of a bar graph while viewing the Mix Supply or Mix Target temperatures.
© 2007 D 423 - 08/07 24 of 36
Page 25
Floating Action
The control pulses the actuator motor open or close to maintain the correct supply water temperature at the mix supply sensor when there is a requirement for mixing. The mixing valve that the actuator is connected to can be either a 2-way, 3-way or 4-way valve. A visual indication as to whether the control is currently opening or closing the mixing valve is displayed in the LCD with the words OPN and CLS while viewing the Mix Supply or Mix Target temperatures.
Mix Minimum
A Mix Minimum temperature is set for each mixed water temperature. The Mix Minimum settings are the lowest temperature that the control is allowed to use as a mix target temperature. During mild conditions, if the control calculates a mix target temperature that is below the mix minimum setting, the mix target temperature is adjusted to match the mix minimum setting. During this condition, if the mixing supply temperature is near the mix minimum setting, the Min segment turns on in the LCD when either the mix target temperature or the mix supply temperature is being viewed.
Locate the Mix 1, Mix 2 and the Mix 3 Minimum settings
in the Adjust Menu.
Mix Maximum
A Mix Maximum temperature is set for each mixed water temperature. The Mix Maximum settings are the highest water temperature that the control is allowed to use as a mix target temperature. If the control does target the mix maximum setting, and the mix supply temperature is near the mix maximum temperature, the Max segment turns on in the LCD when either the mix target temperature or the mix supply temperature is viewed.
Locate the Mix 1, Mix 2 and the Mix 3 Maximum settings
in the Adjust Menu.
Boiler Minimum Protection
The control is capable of providing boiler protection from cold mixing system return water temperatures. If the boiler water temperature is cooler than the Boiler Minimum setting while the boiler is firing, the control reduces the output from the mixing devices. The mixing outputs are reduced at the same rate. Reducing the mixing output limits the amount of cool return water to the boiler and allows the boiler water temperature to recover. This feature can only be used if the boiler sensor is on the supply or on the return but is not available when the boiler sensor is not present.
Domestic Hot Water Temperature Operation Section H
DHW Demand
Powered DHW Demand
A powered DHW Demand may be used to provide heat to the DHW system. A DHW aquastat or setpoint control is used as a switch in the DHW Demand circuit. The control registers a DHW Demand when a voltage between 24 and 230 V (ac) is applied across the DHW Demand terminals (75 and 76).
The Off / DHW Sensor DIP must be set to Off.
DHW Sensor
A DHW Sensor may be used to provide heat to the DHW system. A DHW Sensor must be connected to the DHW Sensor terminals (66 and 67). Once the DHW sensor drops 1/2 of the DHW differential setting below the DHW setting, the control registers a DHW Demand.
The Off / DHW Sensor DIP must be set to DHW Sensor. Once the control detects a DHW Demand, the DHW Demand
segment turns on in the LCD.
DHW Differential
When using a DHW Sensor, a DHW Demand is registered when the DHW sensor drops 1/2 of the DHW Differential setting below the DHW setting. The DHW Demand is satisfied once the DHW Sensor rises 1/2 of the DHW Differential setting above the DHW setting.
Locate the DHW Differential setting in the Adjust
Menu.
Boiler Target Temperature
The boiler target temperature is at least as hot as the DHW Exchange setting (when using a Powered DHW Demand) or at least as hot as the DHW setting plus 40°F (22°C) (when using a DHW Sensor). The DHW Demand overrides the boiler reset target temperature, except when the boiler reset target is higher than the DHW target.
Locate the DHW Exchange setting in the Adjust
Menu.
25 of 36 © 2007 D 423 - 08/07
Page 26
DHW During UnOccupied
When using a Powered DHW Demand, the control has a DHW Exchange UnOccupied setting that allows the installer to select On or Off. When set to On, and the control receives a DHW Demand during an UnOccupied or Sleep period, the control continues operation of the DHW system as it would during the Occupied and Wake periods. When set to Off, the control can ignore a DHW Demand for the duration of the UnOccupied and Sleep periods.
When using a DHW Sensor, a second DHW temperature setting can be made for the UnOccupied or Sleep period.
DHW Mode and Priority Operation
The control has four different settings available for DHW Mode that affect pump operation. The required DHW Mode setting will depend on the piping arrangement of the DHW tank and whether or not priority for DHW is necessary. DHW Priority stops or limits the delivery of heat to the building heating system while the DHW tank calls for heat. This allows for quick recovery of the DHW tank.
Locate the DHW Mode setting in the Adjust Menu.
DHW MODE 1 - DHW in Parallel no Priority
When a DHW Demand is present, the DHW Pump and DHW Valve contacts close. The primary pump does not turn on, but may operate based on either Boiler or Mixing requirements or a Setpoint Demand.
It is assumed that the DHW Device will provide adequate flow through the heat exchanger and the boiler.
DHW MODE 2 - DHW in Parallel with Priority
When a DHW Demand is present, the DHW Pump and DHW Valve contacts close. The primary pump can operate when a Boiler Demand is present. If the boiler is unable to maintain the boiler target temperature, space heating zones are shut off sequentially using tN4 communication in order to provide priority to the DHW tank. This is known as zone load shedding.
It is assumed that the DHW device will provide adequate flow through the heat exchanger and the boiler.
Mode = 2
OFF
DHW Pump
Primary
Pump
DHW MODE 3 - DHW in Primary / Secondary no Priority
When a DHW Demand is present, the DHW Pump and DHW Valve contacts are closed and the primary pump is operated.
Mode = 3
DHW
Pump
Mode = 1
DHW Pump
Primary
Pump
Primary
Pump
DHW MODE 4 - DHW in Primary / Secondary with Priority
When a DHW Demand is present, the DHW Pump and Valve contacts are closed and the primary pump is operated. Priority over space heating zones is achieved by shutting off the zone pumps or zone valves through tN4 communication. This is known as zone load shedding.
Mode = 4
OFF
DHW
Pump
Primary
Pump
© 2007 D 423 - 08/07 26 of 36
Page 27
DHW Priority Override
DHW Post Purge
DHW Priority Override applies to DHW MODE 2 and 4. To prevent the building from cooling off too much or the possibility of a potential freeze up during DHW priority, the control limits the amount of time for DHW priority. As the outdoor air temperature becomes colder, the length of time that the control provides DHW priority is reduced. Once the allowed time for priority has elapsed, the control overrides the DHW priority and resumes space heating.
DHW Priority Override Time
Increasing Time
Decreasing Outdoor Air Temperature
After the DHW Demand is removed, the control performs a purge on the boiler. The control shuts off the boiler and continues to operate the DHW Pump and DHW Valve and the primary pump if applicable. This purges the residual heat from the boiler into the DHW tank. The control continues this purge for a maximum of four minutes or until the boiler supply water temperature drops 20°F (-6.5°C) below the boiler target temperature during the DHW operation. The control also stops the purge if the boiler supply temperature drops below the current boiler target temperature.
DHW Mixing Purge
After DHW operation, the boiler is extremely hot. At the same time, the heating zones may have cooled off considerably after being off for a period of time. When restarting the heating system after a DHW Demand with priority, the control shuts off the boiler and continues to operate the DHW Pump and DHW Valve while the primary pump is turned on. This allows some of the DHW return water to mix with the cool return water from the zones and temper the boiler return water.
Conditional DHW Priority
OFF
DHW
Pump
If the boiler supply temperature is maintained at or above the required temperature during DHW generation, this indicates that the boiler has enough capacity for DHW and possibly
Primary
Pump
heating as well. As long as the boiler supply temperature is maintained near the target, DHW and heating occurs simultaneously.
DHW with Low Temperature Boilers Section I
If DHW heating is to be incorporated into a low temperature system such as a radiant floor heating system, a mixing device is often installed to isolate the high DHW supply temperature from the lower system temperature. If a mixing device is not installed, high temperature water could be supplied to the low temperature system while trying to satisfy the DHW Demand. This may result in damage to the low temperature heating system.
The control is capable of providing DHW heating in such a system while minimizing the chance that the temperature in the heating system exceeds the design supply water temperature. In order to do this, the control must be set to DHW MODE 2 or DHW MODE 4 and Boil MIN must be set to OFF.
On a call for DHW, the control provides DHW priority by sending a message on the boiler temperature bus to the tN4 thermostats to shut off the heating zones for a period of time. The length of time is based on the outdoor air temperature as described in the DHW Priority Override section. However, if the DHW Demand is not satisfied within the allotted time, the boiler shuts off and the heat of the boiler is purged into the DHW tank. A DHW mixing purge occurs in order to reduce the boiler water temperature and once the boiler supply temperature is sufficiently reduced, the DHW Pump and DHW Valve contacts shut off. The heating system zones are allowed to turn on for a period of time to prevent the building from cooling off. After a period of heating, and if the DHW Demand is still present, the control shuts off the heating system and provides heat to the DHW tank once again.
27 of 36 © 2007 D 423 - 08/07
Page 28
Setpoint Temperature Operation Section J
Setpoint
The control can operate to satisfy the requirements of a setpoint load in addition to a space heating load and a DHW load. A setpoint load overrides the current outdoor reset temperature and WWSD setting in order to provide heat to the setpoint load.
Setpoint Demand
A Setpoint Demand is required in order for the control to provide heat to a setpoint load.
The control registers a Setpoint Demand when a voltage between 24 and 230 V (ac) is applied across the Setpoint Demand terminals (77 and 78). Once voltage is applied, the Setpoint Demand segment turns on in the LCD.
Boiler Target During Setpoint
The boiler target temperature during a Setpoint Demand is increased to at least the Setpoint setting. This temperature is maintained as long as the control has a Setpoint Demand.
Setpoint During UnOccupied
The control has a Setpoint UnOccupied setting that allows the installer to select On or Off. When set to On, and the control receives a Setpoint Demand during an UnOccupied or Sleep period, the control continues operation of the Setpoint system as it would during Occupied and Wake periods. When set to Off, the control can ignore a Setpoint Demand for the duration of the UnOccupied and Sleep periods.
Setpoint Mode 2 - Setpoint in Parallel with Priority
When a Setpoint Demand is present, the boiler is operated to maintain the setpoint target. The primary pump (P1) can operate when a Boiler Demand is present. If the boiler is unable to maintain the boiler target temperature, space heating zones are shut off sequentially using tN4 communication in order to provide priority for the setpoint load. This is known as zone load shedding.
It is assumed that the setpoint pump will provide adequate flow through the heat exchanger and the boiler.
Mode = 2
Setpoint
OFF
Primary
Pump
Setpoint Mode 3 – Setpoint in Primary / Secondary
Whenever a Setpoint Demand is present, the primary pump is turned on and the boiler is operated to maintain the setpoint target.
Mode = 3
Setpoint
Setpoint Modes
The Setpoint Mode determines the operation of the primary pump. The Setpoint Mode setting is found in the Adjust Menu.
Setpoint Mode 1 - Setpoint in Parallel
Whenever a Setpoint Demand is present, the boiler is operated to maintain the setpoint target. The primary pump does not turn on, but may operate based on either a Boiler, Mixing or a DHW Demand.
It is assumed that the Setpoint pump will provide adequate flow through the heat exchanger and the boiler.
Mode = 1
Setpoint
Primary
Pump
© 2007 D 423 - 08/07 28 of 36
Primary
Pump
Setpoint Mode 4 - Setpoint in Primary / Secondary with Priority
Whenever a Setpoint Demand is present, the primary pump is turned on and the boiler is operated to maintain the setpoint target. Space heating zones will be shut off using zone load shedding if the boiler is unable to maintain the boiler target temperature.
Mode = 4
Setpoint
OFF
Primary
Pump
Page 29
Setpoint Priority Override
Conditional Setpoint Priority
Setpoint Priority Override applies to SETPOINT MODE 2 and MODE 4. To prevent the building from cooling off too much or the possibility of a potential freeze up during setpoint priority, the control limits the amount of time for setpoint priority. As the outdoor air temperature becomes colder, the length of time the control provides setpoint priority is reduced. Once the allowed time for priority has elapsed, the control overrides the setpoint priority and resumes space heating.
If the boiler supply temperature is maintained at or above the required temperature during setpoint generation, this indicates that the boiler has enough capacity for setpoint and possibly heating as well. As long as the boiler target temperature is maintained, setpoint and heating occur at the same time.
Pump Operation Section K
Primary Pump
The primary pump is switched on in the following situations:
There is a Boiler Demand and that zone’s thermostat
has H1 Pump set to ON.
There is a Mix 1, Mix 2 or Mix 3 Demand.
There is a DHW Demand and the control is set to DHW
Mode 3 or 4.
The control is completing a DHW Purge.
There is a Setpoint Demand and the control is set to
Setpoint Mode 3 or Mode 4.
DHW Pump
The DHW Pump operates whenever there is a DHW Demand and the control is not in DHW Priority Override.
Pump Exercising Section L
The system control will exercise all pumps, mixing valves and hydronic zones (zone valves and zone pumps) for 10 seconds every three days to prevent seizure.
29 of 36 © 2007 D 423 - 08/07
Page 30
Error Messages
Local Errors and Device Errors
Error messages are used to indicate a problem somewhere in the system. There are two types of error messages: Local Errors and Device Errors.
A Local Error indicates an error specific to a device. For example, a thermostat with a sensor short circuit will show a Sensor Short Error on its display. No other devices will show this specific error (unless they also have a sensor short circuit).
A Device Error is used to indicate that there is a local error somewhere else on the system. For example, if a thermostat has a sensor short circuit, that thermostat will show a Local Error indicating specifically what the problem is. All other devices on the network will show Device Errors, indicating the address of the device with the Local Error. In other words, Device Errors are nothing more than pointers, showing you that there is a local error somewhere on the system and where to find it.
Error Priority
Only one error can be shown on a particular device at a time. If there is more than one error on the system, the highest priority error will be the one that is shown. The table on pages 22 and 23 lists error messages in order of high priority to low priority.
How to Locate an Error Message
If the warning symbol (flashing circle with exclamation mark) is visible on screen, this indicates that there is an error somewhere on the system. To view the error message, you must first put the control into the Advanced or Installer access level (available in MISC menu). When an error message is present, it is available as an item in the VIEW menu.
While in the View Menu, press the item button until the error message is displayed. You may have to advance through several View Menu items before the message is displayed.
If the error message is a Device Error (if “DEV” or “DEV ERR” is shown on screen), read the address shown and go to the device with that address. That device will have a Local Error indicating specifically what the problem is. When the problem is corrected, the error message will automatically clear.
Access Levels
In some cases, it is not desirable to let day-to-day users view error messages. In these cases, by lowering the access level of the thermostat or setpoint device to ‘User’ or lower, error messages cannot be seen in the View menu and the warning symbol only appears if there is a local error or a device error caused by a critical error on another device. If there is an error message on the system that you cannot find on a particular thermostat, make sure that the access level on that thermostat is set to Installer or Advanced.
Sensor Temperature Errors
If a control is unable to display a temperature due to a sensor malfunction or communication problem, the word “Err” is displayed in place of the temperature. This usually indicates that there is an error somewhere on the system but is not the actual error message. Keep looking through the View menu to find the actual error message.
Device is attempting to show supply temperature but cannot because of
sensor problem.
Keep pressing the Item button to find the actual
error message
Once error is corrected, the temperature can be
displayed
© 2007 D 423 - 08/07 30 of 36
Page 31
Error Messages (1 of 5)
Error Message Description
ADJUST ERROR
The control failed to read the Adjust Menu settings, and reloaded the factory default settings. Operation stops until you check all the Adjust Menu settings.
Note: To clear the error, the access level must be set to Advanced and the settings in the Adjust menu must be checked.
MISCELLANEOUS ERROR
The control failed to read the Miscellaneous Menu settings, and reloaded the factory default settings. Operation stops until you check all the Miscellaneous Menu settings.
Note: To clear the error, the access level must be set to Advanced and the settings in the Misc menu must be checked.
BOILER BUS ERROR
Communication has been lost on the Boiler Bus. Check the tN4, C and R wires for each tN4 device. Check the polarity of the C and R wires. Check for loose or broken wires. The error message self clears once the error condition is corrected.
BOILER BUS DEVICE LOST
Communication is lost to a tN4 device on the Boiler Bus. The number shown is the address of the lost device. The LCD on the lost device displays Bus Boil OPn. Ensure that there is power to the lost device. Trace the wires from the control to the lost device looking for loose or damaged wires. The error message self clears when the error condition is corrected.
Note: If you deliberately remove a tN4 device, hold the Up and Down buttons to clear the error.
BUS 1 ERROR
Communication has been lost on Bus 1. Check the tN4, C and R wires for each tN4 device. Check the polarity of the C and R wires. Check for loose or broken wires. The error message self clears once the error condition is corrected.
BUS 1 DEVICE LOST
Communication is lost to a tN4 device on Bus 1. The number shown is the address of the lost device. The LCD on the lost device displays Bus OPn. Ensure that there is power to the lost device. Trace the wires from the control to the lost device looking for loose or damaged wires. The error message self clears when the error condition is corrected.
Note: If you deliberately remove a tN4 device, hold the Up and Down buttons to clear the error.
BUS 2 ERROR
Communication has been lost on Bus 2. Check the tN4, C and R wires for each tN4 device. Check the polarity of the C and R wires. Check for loose or broken wires. The error message self clears once the error condition is corrected.
31 of 36 © 2007 D 423 - 08/07
Page 32
Error Messages (2 of 5)
Error Message Description
BUS 2 DEVICE LOST
Communication is lost to a tN4 device on Bus 2. The number shown is the address of the lost device. The LCD on the lost device displays Bus Boil OPn. Ensure that there is power to the lost device. Trace the wires from the control to the lost device looking for loose or damaged wires. The error message self clears when the error condition is corrected.
Note: If you deliberately remove a tN4 device, hold the Up and Down buttons to clear the error.
BUS 3 ERROR
Communication has been lost on Bus 3. Check the tN4, C and R wires for each tN4 device. Check the polarity of the C and R wires. Check for loose or broken wires. The error message self clears once the error condition is corrected.
BUS 3 DEVICE LOST
Communication is lost to a tN4 device on Bus 3. The number shown is the address of the lost device. The LCD on the lost device displays Bus Boil OPn. Ensure that there is power to the lost device. Trace the wires from the control to the lost device looking for loose or damaged wires. The error message self clears when the error condition is corrected.
Note: If you deliberately remove a tN4 device, hold the Up and Down buttons to clear the error.
MASTER DEVICE ERROR
Two tN4 buses are wired together. Check the tN4 bus wiring. The error message self clears once the error condition is corrected.
MIX 1 MODULE ERROR
The control lost communication with the Mixing Module or more than one Mixing Modules have been connected to the Mix 1 bus. Ensure that there is only one Mixing Module on the Mix 1 bus and that there is power to the Mixing Module. Trace the bus wires from the control to the Mixing Module looking for any loose or damaged wires. The error message self clears once the error condition is corrected.
MIX 2 MODULE ERROR
The control lost communication with the Mixing Module or more than one Mixing Modules have been connected to the Mix 2 bus. Ensure that there is only one Mixing Module on the Mix 2 bus and that there is power to the Mixing Module. Trace the bus wires from the control to the Mixing Module looking for any loose or damaged wires. The error message self clears once the error condition is corrected.
MIX 3 MODULE ERROR
The control lost communication with the Mixing Module or more than one Mixing Modules have been connected to the Mix 3 bus. Ensure that there is only one Mixing Module on the Mix 3 bus and that there is power to the Mixing Module. Trace the bus wires from the control to the Mixing Module looking for any loose or damaged wires. The error message self clears once the error condition is corrected.
© 2007 D 423 - 08/07 32 of 36
Page 33
Error Messages (3 of 5)
Error Message Description
MIXING EXPANSION MODULE CONFLICT
A Mixing Expansion Module is connected to the Boiler bus. The Mixing Expansion Module must be removed from the Boiler bus, or the bus must be changed to Mix 1, Mix 2, or Mix 3 in order to clear the error message. The error message self clears once the error condition is corrected.
MIX 1 SENSOR SHORT CIRCUIT
Due to a short circuit, the control failed to read the Mix 1 supply sensor. The Mix 1 Supply Sensor is connected to the Mixing Module. As a result, the control operates mixing device 1 at a fixed output as long as there is a call for heat. Locate and repair the problem as described in the Data Brochure D 070. The error message self clears once the error condition is corrected.
MIX 1 SENSOR OPEN CIRCUIT
Due to an open circuit, the control failed to read the Mix 1 supply sensor. The Mix 1 supply sensor is connected to the Mixing Module. The control operates the mixing device 1 at a fixed output as long as there is a call for heat. Locate and repair the problem as described in the Data Brochure D 070. The error message self clears once the error condition is corrected.
MIX 2 SENSOR SHORT CIRCUIT
Due to a short circuit, the control failed to read the Mix 2 supply sensor. The Mix 2 supply sensor is connected to the Mixing Module. The control operates the mixing device 2 at a fixed output as long as there is a call for heat. Locate and repair the problem as described in the Data Brochure D 070. The error message self clears once the error condition is corrected.
MIX 2 SENSOR OPEN CIRCUIT
Due to an open circuit, the control failed to read the Mix 2 supply sensor. The Mix 2 supply sensor is connected to the Mixing Module. The control operates the mixing device 2 at a fixed output as long as there is a call for heat. Locate and repair the problem as described in the Data Brochure D 070. The error message self clears once the error condition is corrected.
MIX 3 SENSOR SHORT CIRCUIT
Due to a short circuit, the control failed to read the Mix 3 supply sensor. The Mix 3 supply sensor is connected to the Mixing Module. The control operates the mixing device 3 at a fixed output as long as there is a call for heat. Locate and repair the problem as described in the Data Brochure D 070. The error message self clears once the error condition is corrected.
MIX 3 SENSOR OPEN CIRCUIT
Due to an open circuit, the control failed to read the Mix 3 supply sensor. The Mix 3 supply sensor is connected to the Mixing Module. The control operates the mixing device 3 at a fixed output as long as there is a call for heat. Locate and repair the problem as described in the Data Brochure D 070. The error message self clears once the error condition is corrected.
BOILER SENSOR SHORT CIRCUIT
Due to a short circuit, the control failed to read the boiler sensor. When there is a call for heat, the control no longer controls the boiler(s). Instead, the control provides a boiler enable to the boiler’s aquastat or boiler control until the sensor is repaired. The control will not operate the boiler contact if the Boil Minimum setting is less than 100°F (38.0°C). Locate and repair the problem as described in the Data Brochure D 070. The error message self clears once the error condition is corrected.
33 of 36 © 2007 D 423 - 08/07
Page 34
Error Messages (4 of 5)
Error Message Description
BOILER SENSOR OPEN CIRCUIT
Due to an open circuit, the control failed to read the boiler sensor. The control no longer controls the boiler. Instead, the control provides a boiler enable to the boiler’s aquastat or boiler control until the sensor is repaired. The control will not operate the boiler contact if the Boil Minimum setting is less than 100°F (38.0°C). Locate and repair the problem as described in the Data Brochure D 070. The error message self clears once the error condition is corrected
Note: If you deliberately remove the boiler sensor, set the Boiler Sensor Return / Supply DIP switch to Return. Power down for 10 seconds then restart the control.
OUTDOOR SENSOR SHORT CIRCUIT
Due to a short circuit, the control failed to read the outdoor sensor. As a result, the control assumes an outdoor temperature of 32°F (0.0°C) and continues operation. Locate and repair the problem as described in the Data Brochure D 070. The error message self clears once the error condition is corrected.
OUTDOOR SENSOR OPEN CIRCUIT
Due to an open circuit, the control failed to read the outdoor sensor. As a result, the control assumes an outdoor temperature of 32°F (0.0°C) and continues operation. Locate and repair the problem as described in the Data Brochure D 070. The error message self clears once the error condition is corrected.
DHW SHORT CIRCUIT
Due to a short circuit, the control failed to read the DHW sensor. As a result, the control no longer heats the DHW tank. Locate and repair the problem as described in the Data Brochure D 070. DHW tank heating will resume once the sensor problem is corrected. The error message self clears once the error condition is corrected.
DHW OPEN CIRCUIT
Due to an open circuit, the control failed to read the DHW sensor. As a result, the control no longer heats the DHW tank. Locate and repair the problem as described in the Data Brochure D 070. DHW tank heating will resume once the sensor problem is corrected. The error message self clears once the error condition is corrected.
DHW ERROR
A DHW Sensor and a DHW Demand have been applied at the same time. The DHW tank will not be heated until the DHW Demand signal is removed. The error message self clears once the error condition is corrected.
DEVICE SCHEDULE ERROR
The selected system schedule is no longer available. Either the system schedule master is no longer connected to the network or the system schedule number has been changed on the schedule master. The error message self clears once the error condition is corrected.
BOILER BUS AND RETURN SENSOR CONFLICT
There is a DIP switch settings conflict. The Boiler Sensor DIP Switch is set to Ret (Return) and there is a tN4 device on the Boiler bus. The error message clears once the tN4 device is removed from the Boiler bus or the DIP Switch is set to Sup (Supply).
© 2007 D 423 - 08/07 34 of 36
Page 35
Error Messages (5 of 5)
Error Message Description
tekmar STAGER SETTING CONFLICT
There is a DIP switch settings conflict. The tekmar Stager DIP switch is set to On and the Boiler Sensor DIP switch is set to Ret. Once the Boiler Sensor DIP switch is set to Sup or the tekmar Stager DIP switch is set to Off, the error message clears.
DEVICE ERROR AT ADDRESS #:# #
#:## is the address of the device with the error. The bus number displays before the colon, and the device number displays after. Go to the device with the address displayed.
Possible Addresses:
b:01 to b:24 - Device Error on Boiler Bus 1:01 to 1:24 - Device Error on Bus 1 2:01 to 2:24 - Device Error on Bus 2 3:01 to 3:24 - Device Error on Bus 3
35 of 36 © 2007 D 423 - 08/07
Page 36
Limited Warranty and Product Return Procedure
Limited Warranty The liability of tekmar under this warranty
is limited. The Purchaser, by taking receipt of any tekmar product (“Product”), acknowledges the terms of the Limited Warranty in effect at the time of such Product sale and acknowledges that it has read and understands same.
The tekmar Limited Warranty to the Purchaser on the Products sold hereunder is a manufacturer’s pass­through warranty which the Purchaser is authorized to pass through to its customers. Under the Limited War­ranty, each tekmar Product is warranted against defects in workmanship and materials if the Product is installed and used in compliance with tekmar’s instructions, ordi­nary wear and tear excepted. The pass-through warranty period is for a period of twenty-four (24) months from the production date if the Product is not installed during that period, or twelve (12) months from the documented date of installation if installed within twenty-four (24) months from the production date.
The liability of tekmar under the Limited Warranty shall be limited to, at tekmar’s sole discretion: the cost of parts and labor provided by tekmar to repair defects in materials and / or workmanship of the defective product; or to the exchange of the defective product for a warranty replace­ment product; or to the granting of credit limited to the origi­nal cost of the defective product, and such repair, exchange or credit shall be the sole remedy available from tekmar, and, without limiting the foregoing in any way, tekmar is not responsible, in contract, tort or strict product liability, for any other losses, costs, expenses, inconveniences, or damages, whether direct, indirect, special, secondary, inci­dental or consequential, arising from ownership or use of the product, or from defects in workmanship or materials, including any liability for fundamental breach of contract.
The pass-through Limited Warranty applies only to those defective Products returned to tekmar during the warranty period. This Limited Warranty does not cover the cost of the parts or labor to remove or transport the defective Product, or to reinstall the repaired or replacement Product, all such costs and expenses being subject to Purchaser’s agree­ment and warranty with its customers.
Any representations or warranties about the Products made by Purchaser to its customers which are different from or in excess of the tekmar Limited Warranty are the Purchaser’s sole responsibility and obligation. Purchaser shall indemnify and hold tekmar harmless from and against any and all claims, liabilities and damages of any kind or nature which arise out of or are related to any such repre­sentations or warranties by Purchaser to its customers.
The pass-through Limited Warranty does not apply if the returned Product has been damaged by negligence by per­sons other than tekmar, accident, fire, Act of God, abuse or misuse; or has been damaged by modifications, alterations or attachments made subsequent to purchase which have not been authorized by tekmar; or if the Product was not installed in compliance with tekmar’s instructions and / or the local codes and ordinances; or if due to defective instal­lation of the Product; or if the Product was not used in com­pliance with tekmar’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRAN­TIES, EXPRESS OR IMPLIED, WHICH THE GOVERNING LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE, INCLUDING, WITHOUT LIMITATION, IMPLIED WARRAN­TIES OF MERCHANTABILITY AND FITNESS FOR A PAR­TICULAR PURPOSE, DURABILITY OR DESCRIPTION OF THE PRODUCT, ITS NON-INFRINGEMENT OF ANY REL­EVANT PATENTS OR TRADEMARKS, AND ITS COMPLI­ANCE WITH OR NON-VIOLATION OF ANY APPLICABLE ENVIRONMENTAL, HEALTH OR SAFETY LEGISLATION; THE TERM OF ANY OTHER WARRANTY NOT HEREBY CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT IT SHALL NOT EXTEND BEYOND TWENTY-FOUR (24) MONTHS FROM THE PRODUCTION DATE, TO THE EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE GOVERNING LAW.
Product Warranty Return Procedure All Products that are believed to have defects in workmanship or materials must be returned, together with a written description of the defect, to the tekmar Representative assigned to the terri­tory in which such Product is located. If tekmar receives an inquiry from someone other than a tekmar Representative, including an inquiry from Purchaser (if not a tekmar Repre­sentative) or Purchaser’s customers, regarding a potential warranty claim, tekmar’s sole obligation shall be to provide the address and other contact information regarding the appropriate Representative.
tekmar Control Systems Ltd., Canada tekmar Control Systems, Inc., U.S.A.
Head Office: 5100 Silver Star Road Vernon, B.C. Canada V1B 3K4 (250) 545-7749 Fax. (250) 545 -0650 Web Site: www.tekmarcontrols.com
Product design, software and literature are Copyright © 2007 by: tekmar Control Systems Ltd. and tekmar Control Systems, Inc.
36 of 36
All specifications are subject to change without notice.
Printed in Canada. D 423 - 08/07.
Loading...