The Universal Reset Module 423 provides outdoor reset to a hydronic heating system in order to maximize comfort and
efficiency. The 423 can operate two on / off boilers or two modulating boilers. The 423 can override the outdoor reset
water temperature to provide Domestic Hot Water or Setpoint operations. The 423 can operate four outdoor reset water
temperatures, up to three of these water temperatures can be mixing water temperatures. To operate a mixing device, a
Mixing Expansion Module must be connected to the 423 for each mixing water temperature.
Features:
• tN4 Compatible
• Four tN4 Buses
• Up to One Boiler and Three Mixing Water
Temperatures
• Two On-Off or Modulating Boilers
• Equal Run Time Rotation
• Powered Pump Outputs
• DHW Operation
• Optional DHW Sensor
• Setpoint Operation
Stage1/ Stage 2/
Boil Enbl Setp Enbl
50
51 52 53
Meets Class B: Canadian
H7010A
ICES & FCC Part 15
Made in Canada
Boil Sens Sup / Ret
Off / DHW Sensor
Off / tekmar Stager
Boilers On-Off / Mod
Off / Rotation
Test
/
Powered
Outputs
24 V (ac)
8 VA1 VA
72 73 74
71
DHW24 V (ac)
Vlv
R
54 55
Menu
Item
75
DHWSetpoint
Demand Demand
Mod2 (dc)Mod1 (dc)
57 58 59 60 6156
76 77 78
CCtN4
tN4
Boiler
Universal Reset Module 423
C2 tN4tN4
123
62 63
C3C1+–C+–
6564
Demands: 20 - 260 V (ac)
Relay Rating: 115 V (ac) 5 A
Set the DIP switch settings prior to making adjustments
to the control through the user interface. Setting the DIP
switches determines which menu items are displayed in
the user interface.
If you change a DIP switch setting while the control is
powered up, the LCD display returns to the View Menu.
Lock / Unlock
Use the Lock / Unlock DIP switch to lock and unlock the Access
Level of the 423 and all connected tN4 devices, including
tN4 thermostats. For details, see “Access Level”.
• Once locked, the access level in all devices cannot be
viewed or changed.
• To determine if the control is currently locked a small
segment representing a padlock is viewed in the bottom
right hand corner of the display.
• To unlock the Access Level, set the DIP switch to
Unlock.
• To lock the Access Level, set the DIP switch to Lock.
Stage1/ Stage 2/
Boil EnblSetp Enbl
50
515253
Meets Class B: Canadian
H7010A
ICES & FCC Part 15
Made in Canada
Test
/
Boil Sens Sup / Ret
Off / DHW Sensor
Off / tekmar Stager
Boilers On-Off / Mod
Off / Rotation
Powered
Outputs
24 V (ac)
8 VA 1 VA
72 73 74
71
DHW 24 V (ac)
Vlv
DHW
CCtN4
C3C1+–C+–
C2 tN4tN4
tN4
Boiler
57 58 59 60 6156
Universal Reset Module 423
123
62 63
Mod2 (dc)Mod1 (dc)
54 55
Menu
Item
75
76 77 78
DHW Setpoint
Demand Demand
R
6564
66 67
tektra 1006-01
Demands: 20 - 260 V (ac)
Relay Rating: 115 V (ac) 5 A
Use the Boiler Sensor Supply / Return DIP switch to select
the location of the boiler sensor.
• If the boiler sensor is located on the supply, this DIP
switch should be set to Sup. The 423 is the control that
determines the boiler water temperature. Set the boiler’s
aquastat at least 20°F (11.0°C) higher than the Boiler
Maximum setting.
• If the 423 provides a heat demand to an external boiler
control, this DIP switch must be set to Ret. Install the
boiler sensor on the return side of the boiler loop.
The boiler’s operating temperature is controlled by its
aquastat, or an external boiler reset control.
Boil On-Off / Mod
The Boil On-Off / Mod DIP switch selects whether the
control operates an On-Off boiler or the firing rate of a
Modulating boiler.
• If set to Boil On-Off, the control operates up to two
On-Off boilers.
• If set to Mod, the control operates up to two Modulating
boilers.
Off / tekmar Stager
Use the Off / DHW Sensor DIP switch when a tekmar
sensor is be connected to the 423 in order to operate a
DHW storage tank.
• If a tekmar sensor is installed for DHW, set to DHW
Sensor. When the Off / DHW Sensor DIP switch is set
to DHW Sensor, a regular DHW aquastat cannot be
used.
• If a tekmar sensor is not installed for DHW, set to Off.
Off / Rotation
Use the Off / Rotation DIP switch when the Equal Run
Time Rotation feature is to be used. This feature changes
the firing order of the boilers in order to maintain a similar
amount of running time on each boiler.
• If Equal Run Time Rotation is required, set the Off /
Rotation DIP switch to Rotation.
• If Equal Run Time Rotation is not required, set to Off.
Use the Off / tekmar Stager DIP switch when a tekmar
staging control is be connected to the 423 in order to operate
multiple boilers. A tekmar stager may include Boiler Controls
264, 265, and 268.
• If a tekmar Stager is installed, set to tekmar Stager. The
423 will then provide the stager with a target temperature
via a 0-10 V (dc) signal. When the Off / tekmar Stager
DIP switch is set to tekmar Stager, the Boiler Sensor
DIP switch must be set to Sup.
• If a tekmar Stager is not installed, set to Off.
Access Level
The Access Level restricts the number of Menus, Items,
and Adjustments that can be accessed by the user. The
Access Level setting is found in the Miscellaneous (MISC)
Menu. Select the appropriate access level for the people
who work with the control on a regular basis.
There are two Access Level settings:
• Installer (InS): This is the factory default setting. This
access level is sufficient for the normal set up of the
control.
• Advanced (Ad): All of the control settings are available
to the user.
In the following menu tables, the access level the item is
visible in is shown in the access column.
Use the User Interface available on the Liquid Crystal Display
(LCD) to setup and monitor the operation of the system.
Use the four push buttons to the left of the LCD (Menu,
Item, Up, Down) to select settings. As you enter settings,
record the settings in the Job Record J 423.
Menu
The menus display in the Menu Field at the top left side
of the LCD. Three menus are available: View, Adjust, and
Miscellaneous.
• To select a menu, press and release the Menu button.
Item
In each menu, a group of items can be selected. The
abbreviated name of the selected item displays in the Item
field of the LCD display.
• To view the next available item, press and release the
Item button.
• To view the previous item, hold down the Item button.
and press and release the Up button.
Adjusting a Setting
To adjust a setting
1. Select the appropriate menu using the Menu button.
2. Select the item using the Item button.
3. Use the Up or Down button to make the adjustment.
Default Item
• To set the default item in the View Menu, display the
item for more than five seconds.
After navigating menus, the display reverts back to the
default item after 60 seconds of button inactivity.
The View Menu items display the current operating
temperatures and status information of the system.
VIEW MENU
-67 to 149°F
(-55.0 to 65.0°C)
-22 to 266°F
(-30.0 to 130.0°C)
– – –, 35 to 230°F
(– – –, 1.5 to 110.0°C)
-22 to 266°F
(-30.0 to 130.0°C)
– – –, 35 to 230°F
(– – –, 1.5 to 110.0°C)
InS
Ad
InS
Ad
Ad
InS
Ad
Ad
OUTDOOR SECTION B
Current outdoor air temperature as measured by the
outdoor sensor.
MIX 1 SUPPLY SECTION B
Current Mix 1 supply water temperature as measured
by the Mix 1 supply sensor.
Note: This item is only available when Bus 1, 2 or
3 is set to Mix 1.
MIX 1 TARGET SECTION B
The Mix 1 target is the temperature the control
is currently trying to maintain at the Mix 1 supply
sensor. “– – –” is displayed when no heat is required
for Mix 1 zones.
Note: This item is only available when Bus 1, 2 or
3 is set to Mix 1.
MIX 2 SUPPLY SECTION B
Current Mix 2 supply water temperature as measured
by the Mix 2 supply sensor.
Note: This item is only available when Bus 2 is set
to Mix 2.
MIX 2 TARGET SECTION B
The Mix 2 target is the temperature the control
is currently trying to maintain at the Mix 2 supply
sensor. “– – –” is displayed when no heat is required
for Mix 2 zones.
Note: This item is only available when Bus 2 is set
to Mix 2.
Current Mix 3 supply water temperature as measured
by the Mix 3 supply sensor.
Note: This item is only available when Bus 3 is set
to Mix 3.
MIX 3 TARGET
The Mix 3 target is the temperature the control
is currently trying to maintain at the Mix 3 supply
sensor. “– – –” is displayed when no heat is required
for Mix 3 zones.
Note: This item is only available when Bus 3 is set
to Mix 3.
SECTION B
Page 7
View Menu (2 of 2)
Item FieldRangeAccessDescription
-31 to 266°F
(-35.0 to 130.0°C)
– – –, 35 to 230°F
(– – –, 1.5 to 110.0°C)
-31 to 266°F
(-35.0 to 130.0°C)
-31 to 266°F
(-35.0 to 130.0°C)
InS
Ad
Ad
InS
Ad
InS
Ad
BOILER SUPPLY
Current boiler supply water temperature as measured
by the boiler sensor.
Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup.
BOILER TARGET SECTION C
The boiler target is the temperature the control
is currently trying to maintain at the boiler supply
sensor. “– – –” is displayed when no heat is required
for boiler zones.
Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup.
BOILER RETURN SECTION E
Current boiler return water temperature as measured
by the boiler sensor.
Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Ret.
DHW SECTION H
Current DHW tank temperature as measured by the
DHW sensor.
Note: This item is only available when the Off / DHW
Sensor DIP Switch is set to DHW sensor.
SECTION B
VIEW MENU
0 to 100%Ad
0 to 100%Ad
0 to 999 hr
0 to 999 hr
InS
Ad
InS
Ad
BOILER 1 MODULATION SECTION C
Current percent modulation of the Boiler 1 burner.
Note: This item is only available when the Boiler
On-Off / Mod DIP switch is set to Mod, the Boiler
Sensor Sup / Ret DIP switch is set to Sup, and
Boiler 1 is set to Auto.
BOILER 2 MODULATION SECTION C
Current percent modulation of the Boiler 2 burner.
Note: This item is only available when the Boiler
On-Off / Mod DIP switch is set to Mod, the Boiler
Sensor Sup / Ret DIP switch is set to Sup and Boiler 2
is set to Auto.
BOILER 1
The total running time of Boiler 1 since this item was
last cleared. To clear this item, press the Up and Down
buttons simultaneously while viewing this item.
Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup and Boiler 1
is set to Auto.
BOILER 2
The total running time of Boiler 2 since this item was
last cleared. To clear this item, press the Up and Down
buttons simultaneously while viewing this item.
Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup and Boiler 2
is set to Auto.
After the last item, the control returns to the first item in the menu.
The Adjust Menu items are the programmable settings
used to operate the mechanical equipment.
Item Field
Range
boil, M1 (Mix 1), OFF
Default = boil
boil, M1 (Mix 1),
M2 (Mix 2), OFF
Default = boil
boil, M1 (Mix 1),
M3 (Mix 3), OFF
Default = boil
-60 to 45°F
(-51.0 to 7.0°C)
Default = 10°F
(-12.0°C)
AccessDescription
Ad
Ad
Ad
InS
Ad
BUS 1 SECTION C
Select the water temperature for tN4 Bus 1.
BUS 2 SECTION C
Select the water temperature for tN4 Bus 2.
Note: M1 is only available if Bus 1 is set to M1
(Mix 1).
BUS 3 SECTION C
Select the water temperature for tN4 Bus 3.
Note: M1 is only available if Bus 1 is set to M1
(Mix 1).
OUTDOOR DESIGN SECTION B
The design outdoor air temperature used in the heat
loss calculations for the heating system. Typically
set to the outdoor temperature of the coldest day
of the year.
Note: This item is only available when Bus 1 is set
to Mix 1.
MIX 1 MAXIMUM SECTION G
The maximum allowed Mix 1 target temperature.
Note: This item is only available when Bus 1 is set
to Mix 1.
MIX 1 MOTOR SECTION G
The time that the Mix 1 actuating motor requires to
operate from fully closed to fully open.
Note: This item is only available when Bus 1 is set
to Mix 1 and the Mixing Expansion Module is set to
Floating Action. Availability also depends on the type
of mixing module used.
MIX 2 TERMINAL SECTION B
The type of heating terminal units that are being
used in Mix 2 zones.
Note: This item is only available when Bus 2 is set
to Mix 2.
SECTION G
ADJUST MENU
40 to 100°F
(4.5 to 38.0°C)
Default = 70°F (21.0°C)
70 to 220°F
(21.0 to 104.5°C)
Default = 120°F
(49.0°C)
OFF, 40 to 150°F
(OFF, 4.5 to 65.5°C)
Default = OFF
80 to 220°F, OFF
(26.5 to 104.5°C, OFF)
Default = 140°F
(60.0°C)
Ad
InS
Ad
Ad
Ad
MIX 2 INDOOR SECTION B
The design indoor air temperature used in the heat
loss calculation for Mix 2 zones. Typically set to
70°F (21.0°C).
Note: This item is only available when Bus 2 is set
to Mix 2.
MIX 2 DESIGN SECTION B
The supply water temperature required for the Mix 2
zones on the typical coldest day of the year.
Note: This item is only available when Bus 2 is set
to Mix 2.
MIX 2 MINIMUM SECTION G
The minimum allowed Mix 2 target temperature.
Note: This item is only available when Bus 2 is set
to Mix 2.
MIX 2 MAXIMUM SECTION G
The maximum allowed Mix 2 target temperature.
Note: This item is only available when Bus 2 is set
to Mix 2.
The time that the Mix 2 actuating motor requires to
operate from fully closed to fully open.
Ad
InS
Ad
Ad
InS
Ad
Note: This item is only available when Bus 2 is set
to Mix 2, and the Mixing Expansion Module is set
to Floating Action. Availability also depends on the
type of mixing module used.
MIX 3 TERMINAL SECTION B
The type of heating terminal units that are being
used in Mix 3 zones.
Note: This item is only available when Bus 3 is set
to Mix 3.
MIX 3 INDOOR SECTION B
The design indoor air temperature used in the heat
loss calculation for Mix 3 zones. Typically set to
70°F (21.0°C).
Note: This item is only available when Bus 3 is set
to Mix 3.
MIX 3 DESIGN SECTION B
The supply water temperature required for the Mix 3
zones on the typical coldest day of the year.
Note: This item is only available when Bus 3 is set
to Mix 3.
SECTION G
ADJUST MENU
OFF, 40 to 150°F
(OFF, 4.5 to 65.5°C)
Default = OFF
80 to 220°F, OFF
(26.5 to 104.5°C, OFF)
Default = 140°F
(60.0°C)
30 to 230 seconds
Default = 105
Au (Auto)
OFF
Default = Au
Ad
Ad
Ad
InS
Ad
MIX 3 MINIMUM SECTION G
The minimum allowed Mix 3 target temperature.
Note: This item is only available when Bus 3 is set
to Mix 3.
MIX 3 MAXIMUM SECTION G
The maximum allowed Mix 3 target temperature.
Note: This item is only available when Bus 3 is set
to Mix 3.
MIX 3 MOTOR SECTION G
The time that the Mix 3 actuating motor requires to
operate from fully closed to fully open.
Note: This item is only available when Bus 3 is set
to Mix 3, and the Mixing Expansion Module is set
to Floating Action. Availability also depends on the
type of mixing module used.
BOILER 1 SECTION C
Selects Whether Boiler 1 is operational or not.
Note: This item is only available when the Boil Sensor
Sup / Ret DIP Switch is set to Sup, and the tekmar
stager DIP switch is set to OFF.
Note: This item is only available when the Boil Sensor
Sup / Ret DIP Switch is set to Sup, and the tekmar
stager DIP switch is set to OFF.
BOILER TERMINAL SECTION B
The type of heating terminal units that are being
used in boiler zones.
Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup.
BOILER INDOOR SECTION B
The design indoor air temperature used in the heat
loss calculation for the boiler zones. Typically set to
70°F (21.0°C).
Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup.
BOILER DESIGN SECTION B
The supply water temperature required for boiler
zones on the typical coldest day of the year.
Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup.
SECTION C
ADJUST MENU
OFF, 80 to 180°F
(OFF, 26.5 to 82.0°C)
Default = 140°F
(60.0°C)
90 to 225°F, OFF
(32.0 to 107.0°C, OFF)
Default = 200°F
(93.5°C)
Au (Auto), 2 to 42°F
(Au, 1 to 23.5°C)
Default = Au
Au (Auto), 0.5 to
20.0 minutes
Default = Au
InS
Ad
Ad
Ad
Ad
BOILER MINIMUM
The minimum allowed boiler target temperature and
boiler return protection temperature. Check the boiler
manufacturer’s manual for recommend supply water
temperatures.
BOILER MAXIMUM SECTION C
The maximum allowed boiler target temperature.
Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup and the
tekmar stager DIP switch is set to OFF.
BOILER DIFFERENTIAL SECTION C
The temperature differential that the control is to use
to cycle the boiler On and Off.
Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup and the
tekmar stager DIP switch is set to OFF.
STAGE DELAY SECTION C
The minimum time delay between the operation of
stages.
Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup and the
tekmar stager DIP switch is set to OFF.
The time delay the control can expect between the
relay contact closes to fire the boiler and when the
Ad
Ad
Ad
burner actually fires.
Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup, and the
tekmar stager DIP switch is set to OFF.
BOILER MOTOR SECTION C
The amount of time required for the modulating actuating
motor to fully open the gas valve or operate the fan
speed from a stopped position to full speed.
Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup, the Boiler
On-Off / Mod DIP switch is set to Mod and the tekmar
stager DIP switch is set to OFF.
BOILER MINIMUM MODULATION SECTION C
The minimum percent modulation of the burner.
Note: This item is only available when the Boiler Sensor
Sup / Ret DIP switch is set to Sup, the Boiler On-Off /
Mod DIP switch is set to Mod, and the tekmar stager
DIP switch is set to OFF.
OFF,
1 (parallel, no priority)
2 (parallel, priority)
3 (pri-sec, no priority)
4 (pri-sec, priority)
Default = 1
OFF, 70 to 190°F
(OFF, 21.0 to 87.5°C)
Default = 140°F
(60.0°C)
Ad
InS
Ad
InS
Ad
InS
Ad
CYCLE LENGTH
The cycle length to which all tN4 devices will
synchronize.
SCHEDULE
Selects which network setback schedule the control
will follow.
DHW MODE SECTION H
Selects the DHW mode of operation. This determines
the operation of the primary pump in combination
with the DHW Pump / Valve and whether or not DHW
priority is required.
DHW (Occupied)
The temperature of the DHW tank during the Wake
and Occupied periods.
Note: This item is only available when DHW Mode
is set 1 through 4, and the Off / DHW Sensor DIP
Switch is set to DHW Sensor.
The temperature of the DHW tank during the Sleep
and Unoccupied periods.
Ad
Ad
Ad
Note: This item is only available when DHW Mode
is set 1 through 4, the Off / DHW Sensor DIP Switch
is set to DHW Sensor, and the Schedule Setting is
set to Member 1, 2, 3 or 4.
DHW DIFFERENTIAL SECTION H
The temperature differential (swing up and down) of
the DHW tank from the DHW setting.
Note: This item is only available when the DHW
Sensor DIP switch is set to DHW, and the DHW
Mode is set 1 through 4 and the DHW Sensor DIP
is set to OFF.
DHW EXCHANGE (Occupied) SECTION H
The boiler supply temperature to the DHW heat exchanger
during the Occupied and Wake periods.
Note: This item is only available when DHW Mode
is set 1 through 4 and the DHW Sensor DIP is set
to OFF.
SECTION H
ADJUST MENU
OFF, On
Default = OFF
OFF,
1 (parallel, no priority)
2 (parallel, priority)
3 (pri-sec, no priority)
4 (pri-sec, priority)
Default = 1
60 to 220°F
(15.5 to 104.5°C)
Default = 180°F
(82.0°C)
Ad
Ad
Ad
DHW EXCHANGE (UnOccupied) SECTION H
Selects whether the control should respond to
DHW Demands during the Sleep and Unoccupied
periods.
Note: This item is only available when DHW Mode
is set 1 through 4 and the Schedule Setting is set
to Member 1, 2, 3 or 4 and the DHW Sensor DIP is
set to OFF.
SETPOINT MODE
Selects the Setpoint mode of operation. This determines
the operation of the primary pump and whether or
not priority is required.
SETPOINT (Occupied) SECTION J
The minimum boiler target temperature when a
Setpoint Demand is present during the Wake and
Occupied periods.
Note: This item is only available when Setpoint Mode
is set 1 through 4.
After the last item, the control returns to the first item in the menu.
Ad
SETPOINT (UnOccupied)
Selects whether or not a Setpoint Demand will be
responded to during the Sleep and Unoccupied
periods.
Note: This item is only available when Setpoint Mode
is set 1 through 4 and the Schedule Setting is set to
Member 1, 2, 3 or 4.
WWSD (Occupied) SECTION B
The system’s warm weather shut down temperature
during the Wake and Occupied periods. The WWSD
applies to the space heating loads only. It does not
affect DHW or Setpoint heating loads.
WWSD (UnOccupied) SECTION B
The system’s warm weather shut down temperature
during the Sleep and Unoccupied period.
Note: This item is only available when the Schedule
Setting is set to Member 1, 2, 3 or 4.
Loads the factory defaults when the Up and Down
buttons are held down for 1 second.
TYPE
Displays the type number of this product. Hold the Up
button to display the software version.
Page 16
Testing the Control
•
•
•
•
IF Bus 3 is set to M3 (Mix 3):
The control has a built-in test routine that tests the main
control functions. The control continually monitors the
sensors and displays an error message whenever a fault
is found. The individual outputs and relays are tested using
a test sequence.
Test Sequence
Each step in the test sequence lasts 10 seconds.
• Start the test sequence by pressing the Test button.
• Pause the test sequence by pressing the Test button
again. To advance to the next step, press the Test
button again.
• If the test sequence is paused for more than five minutes,
the control exits the entire test routine.
• To advance to a particular step, repeatedly press and
release the Test button to display the appropriate
device.
HAZARD
Access to the Test button requires the removal of the
front cover and exposes hazardous voltage while the
control is powered. Only trained, qualified and competent
personnel should operate the Test button.
Step 7 The Mix 3 device ramps up to 100% over
10 seconds or according to the motor speed
setting.
Step 8 The Mix 3 device ramps down to 0% over
10 seconds or according to the motor speed
setting.
Step 9 The Mixing 3 pump on the Mixing Module
turns on for 10 seconds then shuts off.
Step 10 The primary pump turns on and remains on for
the rest of the test sequence.
IF Boil 1 is set to Au (Auto):
Step 11 The Stage 1 contact is closed to fire an on-off
boiler for 10 seconds or enable a modulating
boiler.
IF the On-Off / Modulating DIP switch is set to
Modulating or the tekmar Stager / Off DIP switch is
set to tekmar Stager:
Step 12 The Mod 1 output ramps up to 100%.
Step 13 The Mod 1 output ramps down to 0%.
The Stage 1 contact is opened and the boiler
is shut off.
Te s t
IF Bus 1 is set to M1 (Mix 1):
Step 1 The Mix 1 device ramps up to 100% over
10 seconds or according to the motor speed
setting.
Step 2 The Mix 1 device ramps down to 0% over
10 seconds or according to the motor speed
setting.
Step 3 The Mixing 1 pump turns on for 10 seconds
then shuts off.
IF Bus 2 is set to M2 (Mix 2):
Step 4 The Mix 2 device ramps up to 100% over
10 seconds or according to the motor speed
setting.
Step 5 The Mix 2 device ramps down to 0% over
10 seconds or according to the motor speed
setting.
Step 6 The Mixing 2 pump on the Mixing Module
turns on for 10 seconds then shuts off.
Press and Hold
for 1 second
IF Boil 2 is set to Au (Auto):
Step 14 The Stage 2 contact is closed to fire an on-off
boiler for 10 seconds or enable a modulating
boiler.
IF the On-Off / Modulating DIP switch is set to
Modulating:
Step 15 The Mod 2 output ramps up to 100%.
Step 16 The Mod 2 output ramps down to 0%.
The Stage 2 contact is opened and the boiler
is shut off.
Step 17 If DHW MODE is set to 1 or 2, the primary
pump is shut off and the DHW Pump contact
is closed.
If DHW MODE is set to 3 or 4, the primary
pump stays on and the DHW Pump contact is
closed.
The control exits the test sequence.
If a device fails to operate during the test sequence, refer
to the W 423 Wiring Brochure to check the operation
of the control. If the control works properly, refer to any
troubleshooting information supplied by the equipment
manufacturer.
The control has a function called Max Heat. In this mode,
the control turns on and operates the system up to the
maximum set temperatures as long as there is a demand
for heat. tN4 thermostats operate to meet the occupied
setting +5°F (3°C). The control operates in this mode for
up to 24 hours or until the Test button is pressed. Use this
mode to run the circulators during system start-up to purge
air from the piping.
• The Mix 1, Mix 2 and Mix 3 Maximum settings are avail-
able in the Adjust Menu when in Max Heat.
HAZARD
Access to the Test button requires the removal of the
front cover and exposes hazardous voltage while the
control is powered. Only trained, qualified and competent
personnel should operate the Test button.
Te s t
Press and Hold
for 3 seconds
To enable Max Heat:
Press and hold the Test button for more than 3 seconds
and less than 6 seconds.
If there is a demand for heat, the ‘TEST’ and ‘MAX’ segments
are displayed on screen and the control will turn on all
outputs for up to 24 hours.
If there is no demand for heat, the ‘TEST’ and ‘MAX’
segments are still displayed but no outputs are turned on
until there is a demand for heat present.
To Cancel Max Heat:
Press the Test button to cancel Max Heat manually or wait
24 hours and the control will automatically leave the Max
Heat mode.
In Zone Test mode, each tN4 device is individually turned
on one at a time. The control tests each zone for up to 5
minutes of no button activity. Use this feature to purge air
out of each zone and assist in troubleshooting.
HAZARD
Access to the Test button requires the removal of the
front cover and exposes hazardous voltage while the
control is powered. Only trained, qualified and competent
personnel should operate the Test button.
Te s t
Press and Hold
for 6 seconds
To enable Zone Test:
1. Press and hold the Test button for more than 6 seconds.
The control displays ZN TEST OFF.
2. Press the Up button to change the display to ZN TEST
ON. After 3 seconds, the boiler, all pumps, and the
mixing valves are shut off.
3. The control operates stage one of the tN4 device with the
lowest address number. Device number one of the boiler
bus (b:01) has the lowest address number and device
24 of bus 3 (3:24) has the highest address number. All
other tN4 zones are shut off.
4. Pressing the Up button will turn off stage 1, and turn on
stage 2 of the same device (if that device has a second
stage) or turn on stage 1 of the device with the next
lowest address. The Down button can be pressed to
move to a device with a lower address number. The Up
and Down buttons will only move through devices on
the same bus.
5. Press the Item button to switch busses. The Up and
Down buttons can then be used to move through the
devices and the heating stages of each device on the
next bus.
6. To cancel the Zone Test, press the Test button. Once
the Zone Test ends or is cancelled, the control resumes
normal operation.
tekmarNet®4 (tN4) communicates between tN4 devices
Outdoor Reset Module
(thermostats, Reset Module and Expansion Modules). Each
tN4 device is connected to a tN4 communication bus using
two wires. Each tN4 bus adjusts a single water temperature
in the system using indoor temperature feedback. The
Universal Reset Module 423 allows for four tN4 buses.
This allows you to control a system with up to four separate
water temperatures.
A system that has more than one tN4 bus is referred to as
The Universal Reset Module 423 is the system control for
a hydronic heating system. The 423 operates a up to two
heat sources such as boilers, up to three mixing devices,
a domestic hot water tank, and responds to other heating
requirements such as pool heating and snow melting. The
423 also coordinates and optimizes the operation of all the
tN4 thermostats.
a tN4 network.
tN4 Thermostat
Network
Bus 1Bus 2
The tN4 thermostat operates heating, cooling, and or
ventilation equipment for a zone. Several tN4 thermostats
may work in a group when operating a cooling system. Up
tekmarNet®4
Thermostats
Do not apply power
tN4
H7008B
/
Test
tN4
Menu
Item
Zone A1
Power
Zone Group Pump A
Zone A2
Zone Group Pump B
Zone A3
Zone B1
Zone B2
Zone B3
tekmarNet®4
Thermostats
to 24 tN4 thermostats can connect to a single tN4 bus.
Outdoor Reset Section B
In a heating system, the rate of heat supplied to the building
must equal the rate of which heat is lost. If the two rates are
not equal, the building will either cool off or over heat.
The rate of building heat loss depends mostly on the outdoor
temperature. Outdoor Reset allows a hot water heating
system to increase the water temperature, adding heat to
the building, as the outdoor temperature drops. The rate
at which the water temperature is changed is defined by
the characterized heating curve.
Characterized Heating Curves
A characterized heating curve determines the amount the
supply water temperature is raised for every 1° drop in
outdoor air temperature. There is a characterized heating
curve for each tN4 communication bus.
The characterized heating curve takes into account the
type of terminal unit that the system is using. Since different
types of heating terminal units transfer heat to a space using
different proportions of radiation, convection and conduction,
the supply water temperature must be controlled differently.
Each tN4 bus is assigned a terminal unit setting that the
control uses to vary the supply water temperature to suit
to the terminal unit used. This improves the control of the
air temperature in the building.
Indoor Temperature Feedback
Most buildings have internal heat gains due to people,
passive solar heating and mechanical or electrical equipment.
Likewise, wind loads cause a building to lose heat faster than
during design conditions. If only the outdoor temperature is
measured, the control cannot compensate for these internal
heat gains or loses and the building may over or under heat.
In order to maintain the most comfortable temperature,
the control uses indoor temperature feedback from tN4
thermostats in order to adjust the water temperature on
each tN4 bus on a continual basis.
There is a terminal unit setting for each tN4 bus. The
Terminal Unit setting is found in the Adjust Menu.
Hydronic Radiant Floor (1)
Terminal type 1 is a heavy, or high mass, hydronic radiant floor
system. This type of a hydronic radiant floor is embedded in
either a thick concrete or gypsum pour. This heating system
has a large thermal mass and is slow acting.
Hydronic Radiant Floor (2)
Terminal type 2 is a light, or low mass, hydronic radiant
floor system. Most commonly, this type of radiant heating
system is either attached to the bottom of a wood sub floor,
suspended in the joist space, or sandwiched between the
subfloor and the surface. This type of radiant system has
a relatively low thermal mass and responds faster than a
high mass system.
Radiator (5)
Terminal type 5 is a radiator terminal unit has a large heated
surface that is exposed to the room. A radiator provides
heat to the room through radiant heat transfer and natural
convection.
Baseboard (6)
Terminal type 6 is a baseboard terminal unit is similar to a
radiator, but has a low profile and is installed at the base
of the wall. The proportion of heat transferred by radiation
from a baseboard is greater than that from a fin-tube
convector.
Fancoil (3)
Terminal type 3 is a fancoil terminal unit or air handling
unit (AHU) consisting of a hydronic heating coil and either
a fan or blower. Air is forced across the coil at a constant
velocity by the fan or blower and is then delivered into the
building space.
Fin–tube Convector (4)
Terminal type 4 is a convector terminal unit is made up of
a heating element with fins on it. This type of terminal unit
relies on the natural convection of air across the heating
element to deliver heated air into the space. The amount
of natural convection is dependant on the supply water
temperature to the heating element and the room air
temperature.
Outdoor Design Temperature
The outdoor design temperature is typically the coldest
outdoor air temperature of the year. This temperature is
used when doing the heat loss calculations for the building
and is used to size the heating system equipment. If a cold
outdoor design temperature is selected, the supply water
temperature rises gradually as the outdoor temperature
drops. If a warm outdoor design temperature is selected,
the supply water temperature rises rapidly as the outdoor
temperature drops.
The outdoor design setting is found in the Adjust Menu.
Warm Weather Shut Down (WWSD)
The Warm Weather Shut Down is the outdoor temperature
at which hydronic heating is no longer required. The control
closes mixing valves and variable speed pumps are not
operated. The boiler operates only when a Domestic Hot
Water (DHW) Demand or a Setpoint Demand is present.
There is a water temperature and therefore a characterized
heating curve for each communication bus. When using
boiler temperature water to heat zones, the installer will be
required to set a boiler characterized heating curve.
Boiler Terminal Unit Defaults
When a terminal unit is selected for boiler zones, the
control loads default values for the boiler design, boiler
maximum supply, and boiler minimum supply temperatures.
The factory defaults can be changed to better match the
installed system. Locate the Boiler Terminal Unit setting
in the Adjust Menu.
Boiler Characterized Heating Curve
Boiler
Design
Terminal Unit
Outdoor
Design
Boiler
Indoor
Increasing Water Temperatures
Decreasing Outdoor Temperatures
Each tN4 communication bus operates on a separate water
temperature. Therefore a separate characterized heating
curve is required for Mix 1, Mix 2 and Mix 3.
Mix 1, 2 and 3 Terminal Unit Defaults
When a terminal unit is selected for Mix 1, 2, or 3, the control
loads default values for the mix design, mix maximum supply,
and mix minimum supply temperatures. The factory defaults
can be changed to better match the installed system.
• Locate the Mix 1, Mix 2 and Mix 3 terminal unit settings
in the Adjust Menu.
Mix Characterized Heating Curve
Mix
Terminal Unit
Outdoor
Design
Mix
Indoor
Decreasing Outdoor Temperatures
Design
Increasing Mix Temperature
Terminal Unit
High Mass Radiant (1)
Low Mass Radiant (2)
Fancoil (3)
Fin-Tube Convector (4)
Radiator (5)
Baseboard (6)
BOIL DSGNBOIL MAXBOIL MIN
120°F (49°C)140°F (60°C)OFF
140°F (60°C)160°F (71°C)OFF
190°F (88°C)210°F (99°C)140°F (60°C)
180°F (82°C)200°F (93°C)140°F (60°C)
160°F (71°C)180°F (82°C)140°F (60°C)
150°F (76°C)170°F (77°C)140°F (60°C)
Boiler Indoor Design
The boiler indoor design temperature is the indoor temperature
the heating designer chose while calculating the heat loss for
the boiler water heated zones. This temperature is typically
70°F (21.0°C). This setting establishes the beginning of
the boiler characterized heating curve.
• Locate the Boiler Indoor Design setting in the Adjust
Menu.
Boiler Design Temperature
The boiler design supply temperature is the boiler water
temperature required to heat the zones on the typical
coldest day of the year.
• Locate the Boiler Design setting in the Adjust Menu.
Terminal Unit
High Mass Radiant (1)
Low Mass Radiant (2)
Fancoil (3)
Fin-Tube Convector (4)
Radiator (5)
Baseboard (6)
MIX DSGNMIX MAXMIX MIN
120°F (49°C)140°F (60°C)OFF
140°F (60°C)160°F (71°C)OFF
190°F (88°C)210°F (99°C)100°F (38°C)
180°F (82°C)200°F (93°C)OFF
160°F (71°C)180°F (82°C)OFF
150°F (76°C)170°F (77°C)OFF
Mix 1, Mix 2 and Mix 3 Indoor Design
The Mix 1, Mix 2 and Mix 3 indoor design temperature is
the indoor temperature the heating designer picked while
calculating the heat loss for the building for the Mix 1, Mix 2,
or Mix 3 water heated zones. This temperature is typically
70°F (21.0°C). This setting establishes the beginning of
the Mix 1, Mix 2, or Mix 3 characterized heating curve.
• Locate the Mix 1, Mix 2 and Mix 3 Indoor Design settings
in the Adjust Menu.
Mix 1, Mix 2, and Mix 3 Design Temperature
The Mix 1, Mix 2, and Mix 3 design supply temperature is
the mix supply water temperature required to heat the zones
when the outdoor temperature is as cold as the outdoor
design temperature.
• Locate the Mix 1, Mix 2 and Mix 3 Design settings in the
The 423 is able to operate up to two on-off or modulating
boiler as a heat source. For proper operation of the boilers,
the 423 must be the only control that determines when the
boilers are to fire. In this case, the boiler sensor should be
located on the boiler supply pipe and the Boiler Sensor
DIP switch is set to Supply.
*Important note: Each boiler operator, also known as
an aquastat, remains in the burner circuit and acts as a
secondary upper limit on the boiler temperature. Each
boiler operator temperature setting must be adjusted above
the 423’s Boiler Maximum setting in order to prevent short
cycling of the boiler burner.
Boiler Target Temperature
The boiler target temperature is determined by connected
tN4 devices or by a DHW or Setpoint Demand received by
the control. The tN4 devices determine the highest water
temperature required and then, requests this temperature
on the tN4 Boiler Bus. The temperature request creates a
Boiler Demand and this is indicated on the display. A DHW
Demand and a Setpoint Demand have temperature settings
to which the boilers are operated to meet and are able to
override the tN4 bus temperature if required.
The control displays the temperature that it is currently trying
to maintain as the boiler supply temperature in the View
Menu. If the control does not presently have a requirement
for heat, it does not show a boiler target temperature.
Instead, “– – –” is displayed in the LCD.
Operation of the tN4 Buses
The 423 has four available tN4 communication buses. One
bus is dedicated for a boiler water temperature. The three
remaining buses (Bus 1, Bus 2 and Bus 3) can operate at
either the boiler water temperatures or as up to three separate
mixing water temperatures. The Bus 1, Bus 2 and Bus 3
items set the operation of each of these three buses.
Bus 2
Bus 2 is connected to a Zone manager via terminals 62
and 63. When Bus 2 is set to Boil, the tN4 thermostats
connected to Bus 2 become part of the Boiler Bus. When
Bus 2 is set to M1 (Mix 1), the tN4 thermostats connected
to Bus 2 become part of Mix 1. When Bus 2 is set to M2
(Mix 2), a Mixing Expansion Module must be connected to
Bus 2 and the tN4 thermostats connected to Bus 2 operate
the Mixing Expansion Module to heat their zones.
Bus 3
Bus 3 is connected to a Zone manager via terminals 64
and 65. When Bus 3 is set to Boil, the tN4 thermostats
connected to Bus 3 become part of the Boiler Bus. When
Bus 3 is set to M1 (Mix 1), the tN4 thermostats connected
to Bus 3 become part of Mix 1. When Bus 3 is set to M3
(Mix 3), a Mixing Expansion Module must be connected to
Bus 3 and the tN4 thermostats connected to Bus 3 operate
the Mixing Expansion Module to heat their zones.
Boiler Minimum
The boiler minimum is the lowest temperature that the
control is allowed to use as a boiler target temperature.
During mild conditions, if the control calculates a boiler target
temperature that is below the Boiler Minimum setting, the
boiler target temperature is adjusted to at least the Boiler
Minimum setting. During this condition, if the boiler(s) is
operating, the minimum segment is turned on in the display
when viewing either the boiler supply temperature or the
boiler target temperature. Set the Boiler Minimum setting
to the boiler manufacturer’s recommended temperature.
• Locate the Boiler Minimum setting in the Adjust Menu.
Boil MIN + ½ Boiler Differential
e
r
u
t
a
m
e
B
o
i
MIN segment on
T
r
e
t
l
a
W
r
e
p
Boil MIN– ½ Boiler Differential
Boil MIN
Boiler Bus
The boiler bus is connected to a Zone manager via terminals
58 and 59. tN4 thermostats or tN4 devices connected to
the Boiler Bus operate the boiler directly in order to heat
their zones. The boiler water temperature target will be
determined based upon boiler outdoor reset and indoor
feedback from the tN4 thermostats.
Bus 1
Bus 1 is connected to a Zone manager via the plug on the
underside of the board. Additional Zone managers may be
connected to bus 1 via terminals 60 and 61, When Bus 1 is
set to Boil, the tN4 thermostats connected to Bus 1 become
part of the Boiler Bus. When Bus 1 is set to M1 (Mix 1),
a Mixing Expansion Module must be connected to Bus 1
and the tN4 thermostats connected to Bus 1 operate the
Mixing Expansion Module to heat their zones.
Boiler Maximum
The boiler maximum is the highest temperature that the
control is allowed to use as a boiler target temperature. If
the control does target the Boiler Maximum setting, and the
boiler temperature is near the boiler maximum temperature,
the maximum segment will be displayed in the LCD while
either the boiler target temperature or the boiler temperature
is being viewed. At no time does the control operate the
boiler(s) above 248°F (120.0°C).
• Locate the Boiler Maximum setting in the Adjust Menu.
The Boiler Fire Delay is the time delay that occurs between
the time that the control closes the boiler contact to fire the
boiler and when the burner fires.
• Locate the Boiler Fire Delay setting in the Adjust Menu.
Boiler Contact Closed
Fire Delay
Burner On
Auto Differential
In order to decrease temperature swings and increase boiler
efficiency, the Auto Differential feature automatically changes
the on / off differential of the boiler based on the heating
load. As the load increases, the differential will decrease to
minimize temperature swings. As the load decreases, the
differential will increase to prevent short cycling.
Off
Time
On-Off Boiler(s) Operation
If the heat source is an On-Off Boiler(s), the Boil On-Off / Mod
DIP switch must be set to On-Off.
Differential
An on / off heat source must be operated with a differential
in order to prevent short cycling. With the control, either
a fixed or an auto differential may be selected. The boiler
differential is divided around the boiler target temperature.
The first stage contact closes when the supply water
temperature is 1/2 of the differential setting below the boiler
target temperature. The second stage is operated if the first
stage is unable to bring the supply water temperature up to
the boiler target temperature at a reasonable rate. As the
supply temperature reaches 1/2 of the differential above
the boiler target temperature, the stages are staged off.
•
Locate the Boiler Differential setting in the Adjust Menu.
Differential = 10°F (6°C)
165°F (74°C)
160°F (71°C)
155°F (68°C)
Boiler
On
Boiler
On
Target + 1/2 Differential
Target
Target – 1/2 Differential
Fixed Differential
If the user desires to have a fixed differential, this is set
using the Boiler Differential setting in the Adjust Menu.
Stage Delay
The Stage Delay is the minimum time delay between the
firing of the first stage and the second stage. After this
delay has expired the control can fire the second stage if it
is required. This setting can be adjusted manually or set to
an automatic setting. When the automatic setting is used,
the control determines the best stage delay based on the
operation of the system.
• Locate the Stage Delay setting in the Adjust Menu.
Differential
Time
On
Heating Load
Modulating Boiler Operation
The 423 can operate up to two modulating boilers. This
requires the use of the Mod 1 (dc) and Mod 2 (dc) outputs
on the 423.
To operate modulating boilers, the Boil On-Off / Mod DIP
switch must be set to Mod. The control operates each boiler
by first closing the stage contact to allow the modulating
boiler to go through the ignition sequence (the stage
contact may not be required on all modulating boilers).
Then, a 0-10 V (dc) analog signal is used to modulate the
boiler firing rate from the Minimum Modulation setting using
Proportional, Integral and Derivative (PID) logic in order
to satisfy the boiler target temperature. The second stage
is operated if the first stage is unable to bring the supply
water temperature up to the boiler target temperature at a
reasonable rate.
Modulating boilers require all the same settings as on-off
boilers in addition to the settings below.
Modulating Boiler Differential
Modulating boilers must be operated with a differential
while operating in low fire. The boiler differential is divided
around the boiler target temperature. The boiler burner
ignites at low fire when the supply water temperature is
1/2 of the Boiler Differential setting below the boiler target
temperature. The boiler is shut off in low fire as the supply
temperature reaches at least 1/2 of the differential above
the boiler target temperature. With the control, either a fixed
or an auto differential may be selected.
When the boilers are modulating above low fire, the differential
does not apply. Instead, the modulation output signal is
determined using Proportional, Integral and Derivative (PID)
logic in order to satisfy the boiler target temperature.
The Boiler Motor Speed is the amount of time the boiler
requires to go from 0% modulation to 100% modulation.
Gas valve actuating motors have a design time from fully closed
to fully open which can be found in the manufacturer’s manual.
The Boiler Motor Speed should be set to this time.
The Boiler Motor Speed setting for a Variable Frequency
Drive (VFD) is the amount of time required to go from a
stopped position to 100% fan speed. Since a VFD has a
very quick response rate, it may be necessary to increase
the Motor Speed setting in order to increase the stability
of the boiler modulation.
• Locate the Boiler Motor Speed setting in the Adjust
Menu.
Minimum Modulation
The minimum modulation defines the minimum output
signal from the control to the boiler burner. It is based on
a percentage of the control’s output signal range.
The Minimum Modulation default setting is 0%.
For boilers with electronic operators, the boiler’s input signal
range may not match the output signal range of the 423
control. The Minimum Modulation setting limits the control
output range in order to match the boiler’s input range.
• Locate the Boiler Minimum Modulation setting in the
Adjust Menu.
To calculate the Minimum Modulation, use the following
formula:
For 0-10 V (dc):
Minimum Modulation =
0 V (dc) – Boiler’s Minimum Input Signal x 100%
0-10 V (dc)
Example:
A boiler requires a 1.8 V (dc) signal to fire the boiler at
low fire. The boiler can be modulated to 10 V (dc) where
it reaches high fire.
This means the boiler’s input signal range is 1.8 to
10 V (dc). The 423 control has an output signal range of
0-10 V (dc).
To make the two signal ranges the same, the Minimum
Modulation required is:
Minimum Modulation =
0 V-1.8 V x 100% = 18%
0 V-10 V
10 V (dc)
Control
Range
Boiler
Range
18%
0 Vdc
1.8 V (dc)
tekmar Stager Operation Section D
In some cases, multiple boilers may be required. In these
cases, the 423 allows for a connection to a tekmar Boiler
Control 264, 265, or 268. The 423 uses the Mod1 (dc)
modulating output to provide a 0-10 V (dc) signal to the
external input terminals on the Boiler Control. The 423
controls the Boiler Control target temperature by changing
the voltage signal. The Boiler Control responds to the boiler
target by staging the multiple boilers. The following table
can be used to convert a 0-10 V (dc) signal to a boiler
target temperature:
To use the tekmar Staging operation, the following DIP
switch settings are required:
1. Set the 423 Off / tekmar Stager DIP switch to tekmar
Stager.
2. Set the 423 Boil Sup / Ret DIP switch to Sup.
3. Set the 423 Boil On-Off / Mod DIP switch to Mod.
The 423 boiler sensor must be located on the supply pipe
leading from the boilers. On the Boiler Control 264, 265,
or 268, the External Input / Stand Alone DIP switch must
be set to External Input. Any domestic hot water (DHW)
demands or Setpoint Demands in the system must connect
to the 423 in order to allow for DHW or setpoint priority.
If the 423 is one of many controls that can call for heat to
a single boiler or there is a boiler sequencer other than a
tekmar Stager (Boiler Control 264, 265, 268), operating
multiple boilers or multiple stages, then the boiler sensor
must be located on the return pipe of the boiler(s).
When the sensor is located on the return, the 423 provides
a boiler enable. The 423 no longer tries to control the
boiler supply water temperature directly, but allows another
operating control such as an aquastat to regulate the boiler
supply temperature.
When there is a requirement for heat from the Mixing Expansion
Modules connected to the 423, the Stage 1 / Boil Enbl contact
closes.
When there is a DHW Demand, or a Setpoint Demand, the
Stage 2 / Setp Enbl contact closes.
When the boiler sensor is located on the boiler return, the
control is able to provide boiler return protection through
the use of the Mixing Expansion Modules. This protects
the boiler against sustained flue gas condensation and
thermal shock.
*Important note: tN4 devices cannot be connected to
the Boiler Bus while the Boiler Sensor DIP switch is set
to Return.
To operate the control without a boiler sensor and prevent
the control from displaying an error message, set the boiler
sensor DIP switch to Return and power up the control
without the boiler sensor connected.
The control operation will be similar to that as having the
boiler sensor on the return except that boiler return protection
is no longer provided.
Zone Load Shedding Section F
If the boiler temperature approaches the boiler minimum
setting, the control can turn off certain high temperature
zones in order to reduce the load on the boiler. This is
known as Zone Load Shedding. Zones are shed in the
following order:
1. The second stage of any 2-stage thermostats which
have “BOIL” selected as their heat source in order of
decreasing priority. Priority is determined by the address
number of the thermostat (b:01 is the highest priority,
3:24 is the lowest priority).
2. The first stage of any thermostats on the boiler bus,
again, in order of decreasing priority. The first stage
of the highest priority thermostat (lowest address
number) will not be shed unless there is also a setpoint
or DHW call.
When the boiler supply temperature goes above the
minimum setting, the control begins restoring the load by
turning first stages back on in the reverse order that they
were shed, followed by second stages in the reverse order
that they were shed.
Mixing Operation Section G
The 423 has four tN4 communication buses. The first bus
is dedicated for a boiler water temperature and is known
as the Boiler Bus. The remaining buses can be selected to
be either boiler or mixing depending on their individual Bus
settings. When either Bus 1, Bus 2 or Bus 3 are set to be
a separate mixing water temperature, a Mixing Expansion
Module must be connected to that bus.
A Mixing Expansion Module is required in order to use
each mixing temperature. The Mixing Expansion Module
operates at the percent output that the 423 determines is
required.
Each of the following settings must be set for each mixing
water temperature.
Mixing Expansion Modules
A Mixing Expansion Module allows the control to reduce the
boiler water temperature down to a lower water temperature.
A Mixing Expansion Module when used with a boiler sensor
also allows the control to protect the boiler from sustained
flue gas condensation and thermal shock.
Variable Speed Injection
The control increases or decreases the power output
to the circulator when there is a requirement for mixing.
The circulator speed varies to maintain the correct mixed
supply water temperature at the mix supply sensor. For
correct sizing and piping of the variable speed injection
circulator, refer to essay E 021. A visual indication of the
current variable speed output is displayed in the LCD in
the form of a bar graph while viewing the Mix Supply or
Mix Target temperatures.
The control pulses the actuator motor open or close to
maintain the correct supply water temperature at the mix
supply sensor when there is a requirement for mixing.
The mixing valve that the actuator is connected to can be
either a 2-way, 3-way or 4-way valve. A visual indication
as to whether the control is currently opening or closing
the mixing valve is displayed in the LCD with the words
OPN and CLS while viewing the Mix Supply or Mix Target
temperatures.
Mix Minimum
A Mix Minimum temperature is set for each mixed water
temperature. The Mix Minimum settings are the lowest
temperature that the control is allowed to use as a mix
target temperature. During mild conditions, if the control
calculates a mix target temperature that is below the mix
minimum setting, the mix target temperature is adjusted
to match the mix minimum setting. During this condition,
if the mixing supply temperature is near the mix minimum
setting, the Min segment turns on in the LCD when either
the mix target temperature or the mix supply temperature
is being viewed.
• Locate the Mix 1, Mix 2 and the Mix 3 Minimum settings
in the Adjust Menu.
Mix Maximum
A Mix Maximum temperature is set for each mixed water
temperature. The Mix Maximum settings are the highest
water temperature that the control is allowed to use as a
mix target temperature. If the control does target the mix
maximum setting, and the mix supply temperature is near
the mix maximum temperature, the Max segment turns on
in the LCD when either the mix target temperature or the
mix supply temperature is viewed.
• Locate the Mix 1, Mix 2 and the Mix 3 Maximum settings
in the Adjust Menu.
Boiler Minimum Protection
The control is capable of providing boiler protection from
cold mixing system return water temperatures. If the boiler
water temperature is cooler than the Boiler Minimum
setting while the boiler is firing, the control reduces the
output from the mixing devices. The mixing outputs are
reduced at the same rate. Reducing the mixing output
limits the amount of cool return water to the boiler and
allows the boiler water temperature to recover. This feature
can only be used if the boiler sensor is on the supply or
on the return but is not available when the boiler sensor
is not present.
Domestic Hot Water Temperature Operation Section H
DHW Demand
Powered DHW Demand
A powered DHW Demand may be used to provide heat to
the DHW system. A DHW aquastat or setpoint control is
used as a switch in the DHW Demand circuit. The control
registers a DHW Demand when a voltage between 24 and
230 V (ac) is applied across the DHW Demand terminals
(75 and 76).
• The Off / DHW Sensor DIP must be set to Off.
DHW Sensor
A DHW Sensor may be used to provide heat to the DHW
system. A DHW Sensor must be connected to the DHW
Sensor terminals (66 and 67). Once the DHW sensor drops
1/2 of the DHW differential setting below the DHW setting,
the control registers a DHW Demand.
• The Off / DHW Sensor DIP must be set to DHW Sensor.
Once the control detects a DHW Demand, the DHW Demand
segment turns on in the LCD.
DHW Differential
When using a DHW Sensor, a DHW Demand is registered
when the DHW sensor drops 1/2 of the DHW Differential
setting below the DHW setting. The DHW Demand is satisfied
once the DHW Sensor rises 1/2 of the DHW Differential
setting above the DHW setting.
• Locate the DHW Differential setting in the Adjust
Menu.
Boiler Target Temperature
The boiler target temperature is at least as hot as the DHW
Exchange setting (when using a Powered DHW Demand)
or at least as hot as the DHW setting plus 40°F (22°C)
(when using a DHW Sensor). The DHW Demand overrides
the boiler reset target temperature, except when the boiler
reset target is higher than the DHW target.
When using a Powered DHW Demand, the control has a
DHW Exchange UnOccupied setting that allows the installer
to select On or Off. When set to On, and the control receives
a DHW Demand during an UnOccupied or Sleep period,
the control continues operation of the DHW system as it
would during the Occupied and Wake periods. When set to
Off, the control can ignore a DHW Demand for the duration
of the UnOccupied and Sleep periods.
When using a DHW Sensor, a second DHW temperature setting
can be made for the UnOccupied or Sleep period.
DHW Mode and Priority Operation
The control has four different settings available for DHW
Mode that affect pump operation. The required DHW Mode
setting will depend on the piping arrangement of the DHW
tank and whether or not priority for DHW is necessary. DHW
Priority stops or limits the delivery of heat to the building
heating system while the DHW tank calls for heat. This
allows for quick recovery of the DHW tank.
• Locate the DHW Mode setting in the Adjust Menu.
DHW MODE 1 - DHW in Parallel no Priority
When a DHW Demand is present, the DHW Pump and
DHW Valve contacts close. The primary pump does not
turn on, but may operate based on either Boiler or Mixing
requirements or a Setpoint Demand.
It is assumed that the DHW Device will provide adequate
flow through the heat exchanger and the boiler.
DHW MODE 2 - DHW in Parallel with Priority
When a DHW Demand is present, the DHW Pump and
DHW Valve contacts close. The primary pump can operate
when a Boiler Demand is present. If the boiler is unable
to maintain the boiler target temperature, space heating
zones are shut off sequentially using tN4 communication
in order to provide priority to the DHW tank. This is known
as zone load shedding.
It is assumed that the DHW device will provide adequate
flow through the heat exchanger and the boiler.
Mode = 2
OFF
DHW
Pump
Primary
Pump
DHW MODE 3 - DHW in Primary / Secondary no Priority
When a DHW Demand is present, the DHW Pump and
DHW Valve contacts are closed and the primary pump is
operated.
Mode = 3
DHW
Pump
Mode = 1
DHW
Pump
Primary
Pump
Primary
Pump
DHW MODE 4 - DHW in Primary / Secondary with Priority
When a DHW Demand is present, the DHW Pump and
Valve contacts are closed and the primary pump is operated.
Priority over space heating zones is achieved by shutting off
the zone pumps or zone valves through tN4 communication.
This is known as zone load shedding.
DHW Priority Override applies to DHW MODE 2 and 4.
To prevent the building from cooling off too much or the
possibility of a potential freeze up during DHW priority, the
control limits the amount of time for DHW priority. As the
outdoor air temperature becomes colder, the length of time
that the control provides DHW priority is reduced. Once the
allowed time for priority has elapsed, the control overrides
the DHW priority and resumes space heating.
DHW Priority Override Time
Increasing Time
Decreasing Outdoor Air Temperature
After the DHW Demand is removed, the control performs
a purge on the boiler. The control shuts off the boiler and
continues to operate the DHW Pump and DHW Valve and
the primary pump if applicable. This purges the residual heat
from the boiler into the DHW tank. The control continues
this purge for a maximum of four minutes or until the boiler
supply water temperature drops 20°F (-6.5°C) below the
boiler target temperature during the DHW operation. The
control also stops the purge if the boiler supply temperature
drops below the current boiler target temperature.
DHW Mixing Purge
After DHW operation, the boiler is extremely hot. At the same
time, the heating zones may have cooled off considerably
after being off for a period of time. When restarting the
heating system after a DHW Demand with priority, the
control shuts off the boiler and continues to operate the
DHW Pump and DHW Valve while the primary pump is
turned on. This allows some of the DHW return water to
mix with the cool return water from the zones and temper
the boiler return water.
Conditional DHW Priority
OFF
DHW
Pump
If the boiler supply temperature is maintained at or above the
required temperature during DHW generation, this indicates
that the boiler has enough capacity for DHW and possibly
Primary
Pump
heating as well. As long as the boiler supply temperature
is maintained near the target, DHW and heating occurs
simultaneously.
DHW with Low Temperature Boilers Section I
If DHW heating is to be incorporated into a low temperature
system such as a radiant floor heating system, a mixing
device is often installed to isolate the high DHW supply
temperature from the lower system temperature. If a mixing
device is not installed, high temperature water could be
supplied to the low temperature system while trying to
satisfy the DHW Demand. This may result in damage to
the low temperature heating system.
The control is capable of providing DHW heating in such a
system while minimizing the chance that the temperature
in the heating system exceeds the design supply water
temperature. In order to do this, the control must be set
to DHW MODE 2 or DHW MODE 4 and Boil MIN must be
set to OFF.
On a call for DHW, the control provides DHW priority by
sending a message on the boiler temperature bus to the
tN4 thermostats to shut off the heating zones for a period
of time. The length of time is based on the outdoor air
temperature as described in the DHW Priority Override
section. However, if the DHW Demand is not satisfied within
the allotted time, the boiler shuts off and the heat of the
boiler is purged into the DHW tank. A DHW mixing purge
occurs in order to reduce the boiler water temperature and
once the boiler supply temperature is sufficiently reduced,
the DHW Pump and DHW Valve contacts shut off. The
heating system zones are allowed to turn on for a period
of time to prevent the building from cooling off. After a
period of heating, and if the DHW Demand is still present,
the control shuts off the heating system and provides heat
to the DHW tank once again.
The control can operate to satisfy the requirements of a
setpoint load in addition to a space heating load and a
DHW load. A setpoint load overrides the current outdoor
reset temperature and WWSD setting in order to provide
heat to the setpoint load.
Setpoint Demand
A Setpoint Demand is required in order for the control to
provide heat to a setpoint load.
The control registers a Setpoint Demand when a voltage
between 24 and 230 V (ac) is applied across the Setpoint
Demand terminals (77 and 78). Once voltage is applied,
the Setpoint Demand segment turns on in the LCD.
Boiler Target During Setpoint
The boiler target temperature during a Setpoint Demand is
increased to at least the Setpoint setting. This temperature is
maintained as long as the control has a Setpoint Demand.
Setpoint During UnOccupied
The control has a Setpoint UnOccupied setting that allows
the installer to select On or Off. When set to On, and the
control receives a Setpoint Demand during an UnOccupied or
Sleep period, the control continues operation of the Setpoint
system as it would during Occupied and Wake periods. When
set to Off, the control can ignore a Setpoint Demand for the
duration of the UnOccupied and Sleep periods.
Setpoint Mode 2 - Setpoint in Parallel with Priority
When a Setpoint Demand is present, the boiler is operated
to maintain the setpoint target. The primary pump (P1)
can operate when a Boiler Demand is present. If the
boiler is unable to maintain the boiler target temperature,
space heating zones are shut off sequentially using tN4
communication in order to provide priority for the setpoint
load. This is known as zone load shedding.
It is assumed that the setpoint pump will provide adequate
flow through the heat exchanger and the boiler.
Mode = 2
Setpoint
OFF
Primary
Pump
Setpoint Mode 3 – Setpoint in Primary / Secondary
Whenever a Setpoint Demand is present, the primary
pump is turned on and the boiler is operated to maintain
the setpoint target.
Mode = 3
Setpoint
Setpoint Modes
The Setpoint Mode determines the operation of the primary
pump. The Setpoint Mode setting is found in the Adjust
Menu.
Setpoint Mode 1 - Setpoint in Parallel
Whenever a Setpoint Demand is present, the boiler is
operated to maintain the setpoint target. The primary pump
does not turn on, but may operate based on either a Boiler,
Mixing or a DHW Demand.
It is assumed that the Setpoint pump will provide adequate
flow through the heat exchanger and the boiler.
Setpoint Mode 4 - Setpoint in Primary / Secondary
with Priority
Whenever a Setpoint Demand is present, the primary
pump is turned on and the boiler is operated to maintain
the setpoint target. Space heating zones will be shut off
using zone load shedding if the boiler is unable to maintain
the boiler target temperature.
Mode = 4
Setpoint
OFF
Primary
Pump
Page 29
Setpoint Priority Override
•
•
•
•
•
Conditional Setpoint Priority
Setpoint Priority Override applies to SETPOINT MODE 2
and MODE 4. To prevent the building from cooling off
too much or the possibility of a potential freeze up during
setpoint priority, the control limits the amount of time for
setpoint priority. As the outdoor air temperature becomes
colder, the length of time the control provides setpoint
priority is reduced. Once the allowed time for priority has
elapsed, the control overrides the setpoint priority and
resumes space heating.
If the boiler supply temperature is maintained at or above
the required temperature during setpoint generation, this
indicates that the boiler has enough capacity for setpoint
and possibly heating as well. As long as the boiler target
temperature is maintained, setpoint and heating occur at
the same time.
Pump Operation Section K
Primary Pump
The primary pump is switched on in the following
situations:
• There is a Boiler Demand and that zone’s thermostat
has H1 Pump set to ON.
• There is a Mix 1, Mix 2 or Mix 3 Demand.
• There is a DHW Demand and the control is set to DHW
Mode 3 or 4.
• The control is completing a DHW Purge.
• There is a Setpoint Demand and the control is set to
Setpoint Mode 3 or Mode 4.
DHW Pump
The DHW Pump operates whenever there is a DHW Demand
and the control is not in DHW Priority Override.
Pump Exercising Section L
The system control will exercise all pumps, mixing valves and hydronic zones (zone valves and zone pumps) for 10 seconds
every three days to prevent seizure.
Error messages are used to indicate a problem somewhere in the system. There are two types of error messages: Local
Errors and Device Errors.
A Local Error indicates an error specific to a device. For example, a thermostat with a sensor short circuit will show a Sensor
Short Error on its display. No other devices will show this specific error (unless they also have a sensor short circuit).
A Device Error is used to indicate that there is a local error somewhere else on the system. For example, if a thermostat
has a sensor short circuit, that thermostat will show a Local Error indicating specifically what the problem is. All other
devices on the network will show Device Errors, indicating the address of the device with the Local Error. In other words,
Device Errors are nothing more than pointers, showing you that there is a local error somewhere on the system and where
to find it.
Error Priority
Only one error can be shown on a particular device at a time. If there is more than one error on the system, the highest
priority error will be the one that is shown. The table on pages 22 and 23 lists error messages in order of high priority to
low priority.
How to Locate an Error Message
If the warning symbol (flashing circle with exclamation mark) is visible on screen, this indicates that there is an error
somewhere on the system. To view the error message, you must first put the control into the Advanced or Installer access
level (available in MISC menu). When an error message is present, it is available as an item in the VIEW menu.
While in the View Menu, press the item button until the error message is displayed. You may have to advance through
several View Menu items before the message is displayed.
If the error message is a Device Error (if “DEV” or “DEV ERR” is shown on screen), read the address shown and go to the
device with that address. That device will have a Local Error indicating specifically what the problem is. When the problem
is corrected, the error message will automatically clear.
Access Levels
In some cases, it is not desirable to let day-to-day users view error messages. In these cases, by lowering the access level
of the thermostat or setpoint device to ‘User’ or lower, error messages cannot be seen in the View menu and the warning
symbol only appears if there is a local error or a device error caused by a critical error on another device. If there is an error
message on the system that you cannot find on a particular thermostat, make sure that the access level on that thermostat
is set to Installer or Advanced.
Sensor Temperature Errors
If a control is unable to display a temperature due to a sensor malfunction or communication problem, the word “Err” is
displayed in place of the temperature. This usually indicates that there is an error somewhere on the system but is not the
actual error message. Keep looking through the View menu to find the actual error message.
Device is attempting to
show supply temperature
but cannot because of
The control failed to read the Adjust Menu settings, and reloaded the factory default settings.
Operation stops until you check all the Adjust Menu settings.
Note: To clear the error, the access level must be set to Advanced and the settings in the
Adjust menu must be checked.
MISCELLANEOUS ERROR
The control failed to read the Miscellaneous Menu settings, and reloaded the factory default
settings. Operation stops until you check all the Miscellaneous Menu settings.
Note: To clear the error, the access level must be set to Advanced and the settings in the
Misc menu must be checked.
BOILER BUS ERROR
Communication has been lost on the Boiler Bus. Check the tN4, C and R wires for each tN4
device. Check the polarity of the C and R wires. Check for loose or broken wires. The error
message self clears once the error condition is corrected.
BOILER BUS DEVICE LOST
Communication is lost to a tN4 device on the Boiler Bus. The number shown is the address
of the lost device. The LCD on the lost device displays Bus Boil OPn. Ensure that there is
power to the lost device. Trace the wires from the control to the lost device looking for loose
or damaged wires. The error message self clears when the error condition is corrected.
Note: If you deliberately remove a tN4 device, hold the Up and Down buttons to clear the
error.
BUS 1 ERROR
Communication has been lost on Bus 1. Check the tN4, C and R wires for each tN4 device.
Check the polarity of the C and R wires. Check for loose or broken wires. The error message
self clears once the error condition is corrected.
BUS 1 DEVICE LOST
Communication is lost to a tN4 device on Bus 1. The number shown is the address of the
lost device. The LCD on the lost device displays Bus OPn. Ensure that there is power to the
lost device. Trace the wires from the control to the lost device looking for loose or damaged
wires. The error message self clears when the error condition is corrected.
Note: If you deliberately remove a tN4 device, hold the Up and Down buttons to clear the
error.
BUS 2 ERROR
Communication has been lost on Bus 2. Check the tN4, C and R wires for each tN4 device.
Check the polarity of the C and R wires. Check for loose or broken wires. The error message
self clears once the error condition is corrected.
Communication is lost to a tN4 device on Bus 2. The number shown is the address of the lost
device. The LCD on the lost device displays Bus Boil OPn. Ensure that there is power to the
lost device. Trace the wires from the control to the lost device looking for loose or damaged
wires. The error message self clears when the error condition is corrected.
Note: If you deliberately remove a tN4 device, hold the Up and Down buttons to clear the
error.
BUS 3 ERROR
Communication has been lost on Bus 3. Check the tN4, C and R wires for each tN4 device.
Check the polarity of the C and R wires. Check for loose or broken wires. The error message
self clears once the error condition is corrected.
BUS 3 DEVICE LOST
Communication is lost to a tN4 device on Bus 3. The number shown is the address of the lost
device. The LCD on the lost device displays Bus Boil OPn. Ensure that there is power to the
lost device. Trace the wires from the control to the lost device looking for loose or damaged
wires. The error message self clears when the error condition is corrected.
Note: If you deliberately remove a tN4 device, hold the Up and Down buttons to clear the
error.
MASTER DEVICE ERROR
Two tN4 buses are wired together. Check the tN4 bus wiring. The error message self clears
once the error condition is corrected.
MIX 1 MODULE ERROR
The control lost communication with the Mixing Module or more than one Mixing Modules
have been connected to the Mix 1 bus. Ensure that there is only one Mixing Module on the
Mix 1 bus and that there is power to the Mixing Module. Trace the bus wires from the control
to the Mixing Module looking for any loose or damaged wires. The error message self clears
once the error condition is corrected.
MIX 2 MODULE ERROR
The control lost communication with the Mixing Module or more than one Mixing Modules
have been connected to the Mix 2 bus. Ensure that there is only one Mixing Module on the
Mix 2 bus and that there is power to the Mixing Module. Trace the bus wires from the control
to the Mixing Module looking for any loose or damaged wires. The error message self clears
once the error condition is corrected.
MIX 3 MODULE ERROR
The control lost communication with the Mixing Module or more than one Mixing Modules
have been connected to the Mix 3 bus. Ensure that there is only one Mixing Module on the
Mix 3 bus and that there is power to the Mixing Module. Trace the bus wires from the control
to the Mixing Module looking for any loose or damaged wires. The error message self clears
once the error condition is corrected.
A Mixing Expansion Module is connected to the Boiler bus. The Mixing Expansion Module
must be removed from the Boiler bus, or the bus must be changed to Mix 1, Mix 2, or Mix 3
in order to clear the error message. The error message self clears once the error condition
is corrected.
MIX 1 SENSOR SHORT CIRCUIT
Due to a short circuit, the control failed to read the Mix 1 supply sensor. The Mix 1 Supply Sensor
is connected to the Mixing Module. As a result, the control operates mixing device 1 at a fixed
output as long as there is a call for heat. Locate and repair the problem as described in the
Data Brochure D 070. The error message self clears once the error condition is corrected.
MIX 1 SENSOR OPEN CIRCUIT
Due to an open circuit, the control failed to read the Mix 1 supply sensor. The Mix 1 supply
sensor is connected to the Mixing Module. The control operates the mixing device 1 at a fixed
output as long as there is a call for heat. Locate and repair the problem as described in the
Data Brochure D 070. The error message self clears once the error condition is corrected.
MIX 2 SENSOR SHORT CIRCUIT
Due to a short circuit, the control failed to read the Mix 2 supply sensor. The Mix 2 supply
sensor is connected to the Mixing Module. The control operates the mixing device 2 at a fixed
output as long as there is a call for heat. Locate and repair the problem as described in the
Data Brochure D 070. The error message self clears once the error condition is corrected.
MIX 2 SENSOR OPEN CIRCUIT
Due to an open circuit, the control failed to read the Mix 2 supply sensor. The Mix 2 supply
sensor is connected to the Mixing Module. The control operates the mixing device 2 at a fixed
output as long as there is a call for heat. Locate and repair the problem as described in the
Data Brochure D 070. The error message self clears once the error condition is corrected.
MIX 3 SENSOR SHORT CIRCUIT
Due to a short circuit, the control failed to read the Mix 3 supply sensor. The Mix 3 supply
sensor is connected to the Mixing Module. The control operates the mixing device 3 at a fixed
output as long as there is a call for heat. Locate and repair the problem as described in the
Data Brochure D 070. The error message self clears once the error condition is corrected.
MIX 3 SENSOR OPEN CIRCUIT
Due to an open circuit, the control failed to read the Mix 3 supply sensor. The Mix 3 supply
sensor is connected to the Mixing Module. The control operates the mixing device 3 at a fixed
output as long as there is a call for heat. Locate and repair the problem as described in the
Data Brochure D 070. The error message self clears once the error condition is corrected.
BOILER SENSOR SHORT CIRCUIT
Due to a short circuit, the control failed to read the boiler sensor. When there is a call for heat,
the control no longer controls the boiler(s). Instead, the control provides a boiler enable to
the boiler’s aquastat or boiler control until the sensor is repaired. The control will not operate
the boiler contact if the Boil Minimum setting is less than 100°F (38.0°C). Locate and repair
the problem as described in the Data Brochure D 070. The error message self clears once
the error condition is corrected.
Due to an open circuit, the control failed to read the boiler sensor. The control no longer controls
the boiler. Instead, the control provides a boiler enable to the boiler’s aquastat or boiler control
until the sensor is repaired. The control will not operate the boiler contact if the Boil Minimum
setting is less than 100°F (38.0°C). Locate and repair the problem as described in the Data
Brochure D 070. The error message self clears once the error condition is corrected
Note: If you deliberately remove the boiler sensor, set the Boiler Sensor Return / Supply DIP
switch to Return. Power down for 10 seconds then restart the control.
OUTDOOR SENSOR SHORT CIRCUIT
Due to a short circuit, the control failed to read the outdoor sensor. As a result, the control
assumes an outdoor temperature of 32°F (0.0°C) and continues operation. Locate and repair
the problem as described in the Data Brochure D 070. The error message self clears once
the error condition is corrected.
OUTDOOR SENSOR OPEN CIRCUIT
Due to an open circuit, the control failed to read the outdoor sensor. As a result, the control
assumes an outdoor temperature of 32°F (0.0°C) and continues operation. Locate and repair
the problem as described in the Data Brochure D 070. The error message self clears once
the error condition is corrected.
DHW SHORT CIRCUIT
Due to a short circuit, the control failed to read the DHW sensor. As a result, the control no
longer heats the DHW tank. Locate and repair the problem as described in the Data Brochure
D 070. DHW tank heating will resume once the sensor problem is corrected. The error message
self clears once the error condition is corrected.
DHW OPEN CIRCUIT
Due to an open circuit, the control failed to read the DHW sensor. As a result, the control no
longer heats the DHW tank. Locate and repair the problem as described in the Data Brochure
D 070. DHW tank heating will resume once the sensor problem is corrected. The error message
self clears once the error condition is corrected.
DHW ERROR
A DHW Sensor and a DHW Demand have been applied at the same time. The DHW tank
will not be heated until the DHW Demand signal is removed. The error message self clears
once the error condition is corrected.
DEVICE SCHEDULE ERROR
The selected system schedule is no longer available. Either the system schedule master is
no longer connected to the network or the system schedule number has been changed on
the schedule master. The error message self clears once the error condition is corrected.
BOILER BUS AND RETURN SENSOR CONFLICT
There is a DIP switch settings conflict. The Boiler Sensor DIP Switch is set to Ret (Return)
and there is a tN4 device on the Boiler bus. The error message clears once the tN4 device
is removed from the Boiler bus or the DIP Switch is set to Sup (Supply).
There is a DIP switch settings conflict. The tekmar Stager DIP switch is set to On and the
Boiler Sensor DIP switch is set to Ret. Once the Boiler Sensor DIP switch is set to Sup or the
tekmar Stager DIP switch is set to Off, the error message clears.
DEVICE ERROR AT ADDRESS #:# #
#:## is the address of the device with the error. The bus number displays before the colon,
and the device number displays after. Go to the device with the address displayed.
Possible Addresses:
b:01 to b:24 - Device Error on Boiler Bus
1:01 to 1:24 - Device Error on Bus 1
2:01 to 2:24 - Device Error on Bus 2
3:01 to 3:24 - Device Error on Bus 3
Limited Warranty The liability of tekmar under this warranty
is limited. The Purchaser, by taking receipt of any tekmar product
(“Product”), acknowledges the terms of the Limited Warranty in
effect at the time of such Product sale and acknowledges that it
has read and understands same.
The tekmar Limited Warranty to the Purchaser on the
Products sold hereunder is a manufacturer’s passthrough warranty which the Purchaser is authorized to
pass through to its customers. Under the Limited Warranty, each tekmar Product is warranted against defects
in workmanship and materials if the Product is installed
and used in compliance with tekmar’s instructions, ordinary wear and tear excepted. The pass-through warranty
period is for a period of twenty-four (24) months from the
production date if the Product is not installed during that
period, or twelve (12) months from the documented date
of installation if installed within twenty-four (24) months
from the production date.
The liability of tekmar under the Limited Warranty shall
be limited to, at tekmar’s sole discretion: the cost of parts
and labor provided by tekmar to repair defects in materials
and / or workmanship of the defective product; or to the
exchange of the defective product for a warranty replacement product; or to the granting of credit limited to the original cost of the defective product, and such repair, exchange
or credit shall be the sole remedy available from tekmar,
and, without limiting the foregoing in any way, tekmar is
not responsible, in contract, tort or strict product liability,
for any other losses, costs, expenses, inconveniences, or
damages, whether direct, indirect, special, secondary, incidental or consequential, arising from ownership or use of
the product, or from defects in workmanship or materials,
including any liability for fundamental breach of contract.
The pass-through Limited Warranty applies only to those
defective Products returned to tekmar during the warranty
period. This Limited Warranty does not cover the cost of the
parts or labor to remove or transport the defective Product,
or to reinstall the repaired or replacement Product, all such
costs and expenses being subject to Purchaser’s agreement and warranty with its customers.
Any representations or warranties about the Products
made by Purchaser to its customers which are different
from or in excess of the tekmar Limited Warranty are the
Purchaser’s sole responsibility and obligation. Purchaser
shall indemnify and hold tekmar harmless from and against
any and all claims, liabilities and damages of any kind or
nature which arise out of or are related to any such representations or warranties by Purchaser to its customers.
The pass-through Limited Warranty does not apply if the
returned Product has been damaged by negligence by persons other than tekmar, accident, fire, Act of God, abuse or
misuse; or has been damaged by modifications, alterations
or attachments made subsequent to purchase which have
not been authorized by tekmar; or if the Product was not
installed in compliance with tekmar’s instructions and / or
the local codes and ordinances; or if due to defective installation of the Product; or if the Product was not used in compliance with tekmar’s instructions.
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, WHICH THE GOVERNING
LAW ALLOWS PARTIES TO CONTRACTUALLY EXCLUDE,
INCLUDING, WITHOUT LIMITATION, IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, DURABILITY OR DESCRIPTION OF
THE PRODUCT, ITS NON-INFRINGEMENT OF ANY RELEVANT PATENTS OR TRADEMARKS, AND ITS COMPLIANCE WITH OR NON-VIOLATION OF ANY APPLICABLE
ENVIRONMENTAL, HEALTH OR SAFETY LEGISLATION;
THE TERM OF ANY OTHER WARRANTY NOT HEREBY
CONTRACTUALLY EXCLUDED IS LIMITED SUCH THAT
IT SHALL NOT EXTEND BEYOND TWENTY-FOUR (24)
MONTHS FROM THE PRODUCTION DATE, TO THE
EXTENT THAT SUCH LIMITATION IS ALLOWED BY THE
GOVERNING LAW.
Product Warranty Return Procedure All Products that
are believed to have defects in workmanship or materials
must be returned, together with a written description of the
defect, to the tekmar Representative assigned to the territory in which such Product is located. If tekmar receives an
inquiry from someone other than a tekmar Representative,
including an inquiry from Purchaser (if not a tekmar Representative) or Purchaser’s customers, regarding a potential
warranty claim, tekmar’s sole obligation shall be to provide
the address and other contact information regarding the
appropriate Representative.
tekmar Control Systems Ltd., Canada
tekmar Control Systems, Inc., U.S.A.
Head Office: 5100 Silver Star Road
Vernon, B.C. Canada V1B 3K4
(250) 545-7749 Fax. (250) 545 -0650
Web Site: www.tekmarcontrols.com