tekmar 423 User Manual

- Data Brochure
Universal Reset Module 423
D 423
08/07
1
Information
Brochure
Choose controls
to match
application
2
Application
Brochure
Design your
mechanical
applications
3
Rough-in
Rough-in
instructions
Wiring
wiring
4
Wiring
Brochure
Wiring and
installation of
specific control
5
Data
Brochure
Control settings
and sequence of
operation
6
Job
Record
Record settings &
wiring details for
future reference
Introduction
The Universal Reset Module 423 provides outdoor reset to a hydronic heating system in order to maximize comfort and efficiency. The 423 can operate two on / off boilers or two modulating boilers. The 423 can override the outdoor reset water temperature to provide Domestic Hot Water or Setpoint operations. The 423 can operate four outdoor reset water temperatures, up to three of these water temperatures can be mixing water temperatures. To operate a mixing device, a Mixing Expansion Module must be connected to the 423 for each mixing water temperature.
Features:
tN4 Compatible
Four tN4 Buses
Up to One Boiler and Three Mixing Water
Temperatures
Two On-Off or Modulating Boilers
Equal Run Time Rotation
Powered Pump Outputs
DHW Operation
Optional DHW Sensor
Setpoint Operation
Stage1/ Stage 2/
Boil Enbl Setp Enbl
50
51 52 53
Meets Class B: Canadian
H7010A
ICES & FCC Part 15 Made in Canada
Boil Sens Sup / Ret Off / DHW Sensor Off / tekmar Stager Boilers On-Off / Mod Off / Rotation
Test
/
Powered Outputs 24 V (ac)
8 VA 1 VA
72 73 74
71
DHW 24 V (ac)
Vlv
R
54 55
Menu
Item
75
DHW Setpoint
Demand Demand
Mod2 (dc)Mod1 (dc)
57 58 59 60 6156
76 77 78
CCtN4
tN4
Boiler
Universal Reset Module 423
C2 tN4 tN4
123
62 63
C3C1+–C+–
6564
Demands: 20 - 260 V (ac) Relay Rating: 115 V (ac) 5 A
79 80 81 82
DHW Primary
DHW
Com
Boil Com70Out
66 67
tektra 1006-01
NPump N
68 69
Do not apply power
Pump
tN4
10 A max
1 of 36 © 2007 D 423 - 08/07
Table of Contents
Boil Sens Sup / Ret Off / DHW Sensor Off / tekmar Stager Boilers On-Off / Mod Off / Rotation
/
Table of Contents ...........................................................2
Display and DIP Switches ..............................................2
Dip Switch Settings ................................................2
Access Level ...........................................................3
Display and Symbols Description............................4
User Interface ........................................................5
Display Menus ................................................................6
View Menu ..............................................................6
Adjust Menu ............................................................ 8
Miscellaneous Menu ............................................. 15
Testing the Control ....................................................... 16
Sequence of Operation ................................................. 18
®
tekmarNet
4 Communication ............................... 18
Outdoor Reset ...................................................... 18
Boiler Temperature Control .................................. 21
tekmar Stager Operation ......................................23
Boil Enable ............................................................24
Zone Load Shedding ............................................24
Mixing Operation .................................................. 24
Domestic Hot Water Temperature Operation ....... 25
DHW with Low Temperature Boilers .....................27
Setpoint Temperature Operation ...........................28
Pump Operation ....................................................29
Pump Exercising ................................................... 29
Error Messages ............................................................ 31
Warranty .......................................................................36
Display and DIP Switches
Dip Switch Settings
Set the DIP switch settings prior to making adjustments to the control through the user interface. Setting the DIP switches determines which menu items are displayed in the user interface.
If you change a DIP switch setting while the control is powered up, the LCD display returns to the View Menu.
Lock / Unlock
Use the Lock / Unlock DIP switch to lock and unlock the Access Level of the 423 and all connected tN4 devices, including tN4 thermostats. For details, see “Access Level”.
Once locked, the access level in all devices cannot be
viewed or changed.
To determine if the control is currently locked a small
segment representing a padlock is viewed in the bottom right hand corner of the display.
To unlock the Access Level, set the DIP switch to
Unlock.
To lock the Access Level, set the DIP switch to Lock.
Stage1/ Stage 2/
Boil Enbl Setp Enbl
50
51 52 53
Meets Class B: Canadian
H7010A
ICES & FCC Part 15 Made in Canada
Test
/
Boil Sens Sup / Ret Off / DHW Sensor Off / tekmar Stager Boilers On-Off / Mod Off / Rotation
Powered Outputs 24 V (ac)
8 VA 1 VA
72 73 74
71
DHW 24 V (ac)
Vlv
DHW
CCtN4
C3C1+–C+–
C2 tN4 tN4
tN4
Boiler
57 58 59 60 6156
Universal Reset Module 423
123
62 63
Mod2 (dc)Mod1 (dc)
54 55
Menu
Item
75
76 77 78
DHW Setpoint
Demand Demand
R
6564
66 67
tektra 1006-01
Demands: 20 - 260 V (ac) Relay Rating: 115 V (ac) 5 A
79 80 81 82
DHW Primary
NPump N
Com
Boil Com70Out
68 69
Do not apply power
tN4
Pump
10 A max
© 2007 D 423 - 08/07 2 of 36
Boiler Sup / Ret
Off / DHW Sensor
Use the Boiler Sensor Supply / Return DIP switch to select the location of the boiler sensor.
If the boiler sensor is located on the supply, this DIP
switch should be set to Sup. The 423 is the control that determines the boiler water temperature. Set the boiler’s aquastat at least 20°F (11.0°C) higher than the Boiler Maximum setting.
If the 423 provides a heat demand to an external boiler
control, this DIP switch must be set to Ret. Install the boiler sensor on the return side of the boiler loop. The boiler’s operating temperature is controlled by its aquastat, or an external boiler reset control.
Boil On-Off / Mod
The Boil On-Off / Mod DIP switch selects whether the control operates an On-Off boiler or the firing rate of a Modulating boiler.
If set to Boil On-Off, the control operates up to two
On-Off boilers.
If set to Mod, the control operates up to two Modulating
boilers.
Off / tekmar Stager
Use the Off / DHW Sensor DIP switch when a tekmar sensor is be connected to the 423 in order to operate a DHW storage tank.
If a tekmar sensor is installed for DHW, set to DHW
Sensor. When the Off / DHW Sensor DIP switch is set to DHW Sensor, a regular DHW aquastat cannot be used.
If a tekmar sensor is not installed for DHW, set to Off.
Off / Rotation
Use the Off / Rotation DIP switch when the Equal Run Time Rotation feature is to be used. This feature changes the firing order of the boilers in order to maintain a similar amount of running time on each boiler.
If Equal Run Time Rotation is required, set the Off /
Rotation DIP switch to Rotation.
If Equal Run Time Rotation is not required, set to Off.
Use the Off / tekmar Stager DIP switch when a tekmar staging control is be connected to the 423 in order to operate multiple boilers. A tekmar stager may include Boiler Controls 264, 265, and 268.
If a tekmar Stager is installed, set to tekmar Stager. The
423 will then provide the stager with a target temperature via a 0-10 V (dc) signal. When the Off / tekmar Stager DIP switch is set to tekmar Stager, the Boiler Sensor DIP switch must be set to Sup.
If a tekmar Stager is not installed, set to Off.
Access Level
The Access Level restricts the number of Menus, Items, and Adjustments that can be accessed by the user. The Access Level setting is found in the Miscellaneous (MISC) Menu. Select the appropriate access level for the people who work with the control on a regular basis.
There are two Access Level settings:
Installer (InS): This is the factory default setting. This
access level is sufficient for the normal set up of the control.
Advanced (Ad): All of the control settings are available
to the user.
In the following menu tables, the access level the item is visible in is shown in the access column.
3 of 36 © 2007 D 423 - 08/07
Display
Menu Field
Displays the
current menu
Status Field
Displays the current
status of the control’s
inputs, outputs and
operation. Most symbols
in the status field are only visible when the
VIEW Menu is selected
Symbols Description
PUMP
Displays when the primary pump is in operation.
Item Field
Displays an abbreviated name of the selected item
Number Field
Displays the current value of the selected item
BOILER DEMAND
Displays when a Boiler Demand is present.
BURNER
Displays when the Stage 1 or Stage 2 contacts are closed.
LOCK
Displays when the access levels are locked.
WARNING
Displays when an error exists.
COMMUNICATION BUS
Displays when tN4 thermostats are connected.
DHW PUMP OR VALVE
Displays when the DHW Pump or DHW Valve is in operation.
°F, °C, %, HOURS, MINUTES
Units of measurement.
MIX 1 DEMAND
Displays when a Mix 1 Demand is present.
MIX 2 DEMAND
Displays when a Mix 2 Demand is present.
MIX 3 DEMAND
Displays when a Mix 3 Demand is present.
DHW DEMAND
Displays when a DHW Demand is present.
SETPOINT DEMAND
Displays when a Setpoint Demand is present.
DEVICE OUTPUT SCALE
Displays the output of the modulating boiler(s) or the variable speed injection pump.
© 2007 D 423 - 08/07 4 of 36
User Interface
Use the User Interface available on the Liquid Crystal Display (LCD) to setup and monitor the operation of the system. Use the four push buttons to the left of the LCD (Menu, Item, Up, Down) to select settings. As you enter settings, record the settings in the Job Record J 423.
Menu
The menus display in the Menu Field at the top left side of the LCD. Three menus are available: View, Adjust, and Miscellaneous.
To select a menu, press and release the Menu button.
Item
In each menu, a group of items can be selected. The abbreviated name of the selected item displays in the Item field of the LCD display.
To view the next available item, press and release the
Item button.
To view the previous item, hold down the Item button.
and press and release the Up button.
Adjusting a Setting
To adjust a setting
1. Select the appropriate menu using the Menu button.
2. Select the item using the Item button.
3. Use the Up or Down button to make the adjustment.
Default Item
To set the default item in the View Menu, display the
item for more than five seconds.
After navigating menus, the display reverts back to the default item after 60 seconds of button inactivity.
Back to View Menu
Continue to next Item
Continue to next Item
Continue to next Item
5 of 36 © 2007 D 423 - 08/07
Display Menus
View Menu (1 of 2)
Item Field Range Access Description
The View Menu items display the current operating temperatures and status information of the system.
VIEW MENU
-67 to 149°F
(-55.0 to 65.0°C)
-22 to 266°F
(-30.0 to 130.0°C)
– – –, 35 to 230°F
(– – –, 1.5 to 110.0°C)
-22 to 266°F
(-30.0 to 130.0°C)
– – –, 35 to 230°F
(– – –, 1.5 to 110.0°C)
InS
Ad
InS
Ad
Ad
InS
Ad
Ad
OUTDOOR SECTION B
Current outdoor air temperature as measured by the outdoor sensor.
MIX 1 SUPPLY SECTION B
Current Mix 1 supply water temperature as measured by the Mix 1 supply sensor.
Note: This item is only available when Bus 1, 2 or 3 is set to Mix 1.
MIX 1 TARGET SECTION B
The Mix 1 target is the temperature the control is currently trying to maintain at the Mix 1 supply sensor. “– – –” is displayed when no heat is required for Mix 1 zones.
Note: This item is only available when Bus 1, 2 or 3 is set to Mix 1.
MIX 2 SUPPLY SECTION B
Current Mix 2 supply water temperature as measured by the Mix 2 supply sensor.
Note: This item is only available when Bus 2 is set to Mix 2.
MIX 2 TARGET SECTION B
The Mix 2 target is the temperature the control is currently trying to maintain at the Mix 2 supply sensor. “– – –” is displayed when no heat is required for Mix 2 zones.
Note: This item is only available when Bus 2 is set to Mix 2.
-31 to 266°F
(-35.0 to 130.0°C)
– – –, 35 to 230°F
(– – –, 1.5 to 110.0°C)
Continued on next page.
© 2007 D 423 - 08/07 6 of 36
InS
Ad
Ad
MIX 3 SUPPLY SECTION B
Current Mix 3 supply water temperature as measured by the Mix 3 supply sensor.
Note: This item is only available when Bus 3 is set to Mix 3.
MIX 3 TARGET
The Mix 3 target is the temperature the control is currently trying to maintain at the Mix 3 supply sensor. “– – –” is displayed when no heat is required for Mix 3 zones.
Note: This item is only available when Bus 3 is set to Mix 3.
SECTION B
View Menu (2 of 2)
Item Field Range Access Description
-31 to 266°F
(-35.0 to 130.0°C)
– – –, 35 to 230°F
(– – –, 1.5 to 110.0°C)
-31 to 266°F
(-35.0 to 130.0°C)
-31 to 266°F
(-35.0 to 130.0°C)
InS
Ad
Ad
InS
Ad
InS
Ad
BOILER SUPPLY
Current boiler supply water temperature as measured by the boiler sensor.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup.
BOILER TARGET SECTION C
The boiler target is the temperature the control is currently trying to maintain at the boiler supply sensor. “– – –” is displayed when no heat is required for boiler zones.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup.
BOILER RETURN SECTION E
Current boiler return water temperature as measured by the boiler sensor.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Ret.
DHW SECTION H
Current DHW tank temperature as measured by the DHW sensor.
Note: This item is only available when the Off / DHW Sensor DIP Switch is set to DHW sensor.
SECTION B
VIEW MENU
0 to 100% Ad
0 to 100% Ad
0 to 999 hr
0 to 999 hr
InS
Ad
InS
Ad
BOILER 1 MODULATION SECTION C
Current percent modulation of the Boiler 1 burner.
Note: This item is only available when the Boiler On-Off / Mod DIP switch is set to Mod, the Boiler Sensor Sup / Ret DIP switch is set to Sup, and Boiler 1 is set to Auto.
BOILER 2 MODULATION SECTION C
Current percent modulation of the Boiler 2 burner.
Note: This item is only available when the Boiler On-Off / Mod DIP switch is set to Mod, the Boiler Sensor Sup / Ret DIP switch is set to Sup and Boiler 2 is set to Auto.
BOILER 1
The total running time of Boiler 1 since this item was last cleared. To clear this item, press the Up and Down buttons simultaneously while viewing this item.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup and Boiler 1 is set to Auto.
BOILER 2
The total running time of Boiler 2 since this item was last cleared. To clear this item, press the Up and Down buttons simultaneously while viewing this item.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup and Boiler 2 is set to Auto.
After the last item, the control returns to the first item in the menu.
7 of 36 © 2007 D 423 - 08/07
Adjust Menu (1 of 7)
The Adjust Menu items are the programmable settings used to operate the mechanical equipment.
Item Field
Range
boil, M1 (Mix 1), OFF
Default = boil
boil, M1 (Mix 1),
M2 (Mix 2), OFF
Default = boil
boil, M1 (Mix 1),
M3 (Mix 3), OFF
Default = boil
-60 to 45°F
(-51.0 to 7.0°C)
Default = 10°F
(-12.0°C)
Access Description
Ad
Ad
Ad
InS
Ad
BUS 1 SECTION C
Select the water temperature for tN4 Bus 1.
BUS 2 SECTION C
Select the water temperature for tN4 Bus 2.
Note: M1 is only available if Bus 1 is set to M1 (Mix 1).
BUS 3 SECTION C
Select the water temperature for tN4 Bus 3.
Note: M1 is only available if Bus 1 is set to M1 (Mix 1).
OUTDOOR DESIGN SECTION B
The design outdoor air temperature used in the heat loss calculations for the heating system. Typically set to the outdoor temperature of the coldest day of the year.
ADJUST MENU
Continued on next page.
1 HRF1 2 HRF2 3 Fancoil 4 Fin-tube Convector 5 Radiator 6 Baseboard
Default = 1
40 to 100°F
(4.5 to 38.0°C)
Default = 70°F (21.0°C)
70 to 220°F
(21.0 to 104.5°C)
Default = 120°F
(49.0°C)
InS
Ad
Ad
InS
Ad
MIX 1 TERMINAL SECTION B
The type of heating terminal units that are being used in Mix 1 zones.
Note: This item is only available when Bus 1 is set to Mix 1.
MIX 1 INDOOR
The design indoor air temperature used in the heat loss calculation for Mix 1 zones. Typically set to 70°F (21.0°C).
Note: This item is only available when Bus 1 is set to Mix 1.
MIX 1 DESIGN SECTION B
The supply water temperature required for the Mix 1 zones on the typical coldest day of the year.
Note: This item is only available when Bus 1 is set to Mix 1.
SECTION B
© 2007 D 423 - 08/07 8 of 36
Adjust Menu (2 of 7)
Item Field
Range
OFF, 40 to 150°F
(OFF, 4.5 to 65.5°C)
Default = OFF
80 to 220°F, OFF
(26.5 to 104.5°C, OFF)
Default = 140°F
(60.0°C)
30 to 230 seconds
Default = 105
1 HRF1 2 HRF2 3 Fancoil 4 Fin-tube Convector 5 Radiator 6 Baseboard
Default = 1
Access Description
MIX 1 MINIMUM
Ad
Ad
Ad
InS
Ad
The minimum allowed Mix 1 target temperature.
Note: This item is only available when Bus 1 is set to Mix 1.
MIX 1 MAXIMUM SECTION G
The maximum allowed Mix 1 target temperature.
Note: This item is only available when Bus 1 is set to Mix 1.
MIX 1 MOTOR SECTION G
The time that the Mix 1 actuating motor requires to operate from fully closed to fully open.
Note: This item is only available when Bus 1 is set to Mix 1 and the Mixing Expansion Module is set to Floating Action. Availability also depends on the type of mixing module used.
MIX 2 TERMINAL SECTION B
The type of heating terminal units that are being used in Mix 2 zones.
Note: This item is only available when Bus 2 is set to Mix 2.
SECTION G
ADJUST MENU
40 to 100°F
(4.5 to 38.0°C)
Default = 70°F (21.0°C)
70 to 220°F
(21.0 to 104.5°C)
Default = 120°F
(49.0°C)
OFF, 40 to 150°F
(OFF, 4.5 to 65.5°C)
Default = OFF
80 to 220°F, OFF
(26.5 to 104.5°C, OFF)
Default = 140°F
(60.0°C)
Ad
InS
Ad
Ad
Ad
MIX 2 INDOOR SECTION B
The design indoor air temperature used in the heat loss calculation for Mix 2 zones. Typically set to 70°F (21.0°C).
Note: This item is only available when Bus 2 is set to Mix 2.
MIX 2 DESIGN SECTION B
The supply water temperature required for the Mix 2 zones on the typical coldest day of the year.
Note: This item is only available when Bus 2 is set to Mix 2.
MIX 2 MINIMUM SECTION G
The minimum allowed Mix 2 target temperature.
Note: This item is only available when Bus 2 is set to Mix 2.
MIX 2 MAXIMUM SECTION G
The maximum allowed Mix 2 target temperature.
Note: This item is only available when Bus 2 is set to Mix 2.
Continued on next page.
9 of 36 © 2007 D 423 - 08/07
Adjust Menu (3 of 7)
Item Field
Range
30 to 230 seconds
Default = 105
1 HRF1 2 HRF2 3 Fancoil 4 Fin-tube Convector 5 Radiator 6 Baseboard
Default = 1
40 to 100°F
(4.5 to 38.0°C)
Default = 70°F (21.0°C)
70 to 220°F
(21.0 to 104.5°C)
Default = 120°F
(49.0°C)
Access Description
MIX 2 MOTOR
The time that the Mix 2 actuating motor requires to operate from fully closed to fully open.
Ad
InS
Ad
Ad
InS
Ad
Note: This item is only available when Bus 2 is set to Mix 2, and the Mixing Expansion Module is set to Floating Action. Availability also depends on the type of mixing module used.
MIX 3 TERMINAL SECTION B
The type of heating terminal units that are being used in Mix 3 zones.
Note: This item is only available when Bus 3 is set to Mix 3.
MIX 3 INDOOR SECTION B
The design indoor air temperature used in the heat loss calculation for Mix 3 zones. Typically set to 70°F (21.0°C).
Note: This item is only available when Bus 3 is set to Mix 3.
MIX 3 DESIGN SECTION B
The supply water temperature required for the Mix 3 zones on the typical coldest day of the year.
Note: This item is only available when Bus 3 is set to Mix 3.
SECTION G
ADJUST MENU
OFF, 40 to 150°F
(OFF, 4.5 to 65.5°C)
Default = OFF
80 to 220°F, OFF
(26.5 to 104.5°C, OFF)
Default = 140°F
(60.0°C)
30 to 230 seconds
Default = 105
Au (Auto)
OFF
Default = Au
Ad
Ad
Ad
InS
Ad
MIX 3 MINIMUM SECTION G
The minimum allowed Mix 3 target temperature.
Note: This item is only available when Bus 3 is set to Mix 3.
MIX 3 MAXIMUM SECTION G
The maximum allowed Mix 3 target temperature.
Note: This item is only available when Bus 3 is set to Mix 3.
MIX 3 MOTOR SECTION G
The time that the Mix 3 actuating motor requires to operate from fully closed to fully open.
Note: This item is only available when Bus 3 is set to Mix 3, and the Mixing Expansion Module is set to Floating Action. Availability also depends on the type of mixing module used.
BOILER 1 SECTION C
Selects Whether Boiler 1 is operational or not.
Note: This item is only available when the Boil Sensor Sup / Ret DIP Switch is set to Sup, and the tekmar stager DIP switch is set to OFF.
Continued on next page.
© 2007 D 423 - 08/07 10 of 36
Adjust Menu (4 of 7)
Item Field
Range
Au (Auto)
OFF
Default = Au
1 HRF1 2 HRF2 3 Fancoil 4 Fin-tube Convector 5 Radiator 6 Baseboard
Default = 4
40 to 100°F
(4.5 to 38.0°C)
Default = 70°F
(21.0°C)
70 to 220°F
(21.0 to 104.5°C)
Default = 180°F
(82.0°C)
Access Description
BOILER 2
InS
Ad
InS
Ad
Ad
InS
Ad
Selects whether Boiler 2 is operational or not.
Note: This item is only available when the Boil Sensor Sup / Ret DIP Switch is set to Sup, and the tekmar stager DIP switch is set to OFF.
BOILER TERMINAL SECTION B
The type of heating terminal units that are being used in boiler zones.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup.
BOILER INDOOR SECTION B
The design indoor air temperature used in the heat loss calculation for the boiler zones. Typically set to 70°F (21.0°C).
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup.
BOILER DESIGN SECTION B
The supply water temperature required for boiler zones on the typical coldest day of the year.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup.
SECTION C
ADJUST MENU
OFF, 80 to 180°F
(OFF, 26.5 to 82.0°C)
Default = 140°F
(60.0°C)
90 to 225°F, OFF
(32.0 to 107.0°C, OFF)
Default = 200°F
(93.5°C)
Au (Auto), 2 to 42°F
(Au, 1 to 23.5°C)
Default = Au
Au (Auto), 0.5 to
20.0 minutes
Default = Au
InS
Ad
Ad
Ad
Ad
BOILER MINIMUM
The minimum allowed boiler target temperature and boiler return protection temperature. Check the boiler manufacturer’s manual for recommend supply water temperatures.
BOILER MAXIMUM SECTION C
The maximum allowed boiler target temperature.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup and the tekmar stager DIP switch is set to OFF.
BOILER DIFFERENTIAL SECTION C
The temperature differential that the control is to use to cycle the boiler On and Off.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup and the tekmar stager DIP switch is set to OFF.
STAGE DELAY SECTION C
The minimum time delay between the operation of stages.
Note: This item is only available when the Boiler Sensor Sup / Ret DIP switch is set to Sup and the tekmar stager DIP switch is set to OFF.
SECTION
C
Continued on next page.
11 of 36 © 2007 D 423 - 08/07
Loading...
+ 25 hidden pages