Universal Reset Control 363
Mixing, Boiler & DHW
Mix Demand Boiler Demand
°
F
DHW Demand Setpoint Demand WWSD
1
2
Minimum
DH
Maximum
Item
R
NRTL/C
LR 58223
The Universal Reset Control 363 is a microprocessor based control designed to maximize the comfort and efficiency provided by a hydronic heating system. The control automatically adjusts the boiler and mixed loop water temperatures that are delivered to the heating system by using an outdoor reset. Outdoor reset increases the water temperature in the heating system as the outdoor temperature becomes colder. Outdoor reset also increases the energy efficiency of the heating system by not allowing more heat into the building than the building normally loses to the outside. Another benefit of outdoor reset is the reduction of indoor temperature swings - especially in the fall and spring months. The 363 can intelligently integrate indirect fired Domestic Hot Water (DHW) and tekmar zone controls into the heating system.

User Interface

Access Level(s) The tekmar Universal Mixing Control 363 has four access levels which are LTD (limited), USER, INST (Installer),
and ADV (advanced). This brochure only covers the LTD (Limited) and USER levels. Only qualified service people should make adjustments in the INST (Installer) and ADV (advanced) access levels.
Item Field
Displays an abbreviated name of the selected item
Menu Field
Displays the current menu
View Adjust Monitor
Schd Misc
Open Close
°F°
1
UnOcc
2
DHW
Aux
%
1
Number Field
Displays the current value of the selected item
Mix Demand Boiler Demand
C
min
sec
Ovr
DHW Demand
hr
Setpoint Demand WWSD
Minimum
!
Maximum
Status Field
Displays the current status of the control’s inputs, outputs and operation
Menu
Item
Buttons
Selects Menu,
{
Items and adjusts settings
The tekmar Universal Reset Control 363 has a Liquid Crystal Display (LCD) and four push buttons (
Menu, Item
, , ) which are used to view and adjust the settings.
Menu
Menu
button. By pressing and releasing the next available menu. Once a menu is selected, there will be a group of items that can be viewed within that menu.
Menu
button, the display will advance to the
Open
Close
Aux
UnOcc
Occ
Open / Close
Displays when the actuator is opening or closing the valve.
Mixing Device Output Scale
Shows output of injection pump or mixing valve. Arrows show
%
1
whether the output is increasing or decreasing.
Burner
Displays when the boiler relay is turned on.
Pump
1
2
Displays boiler pump 1 and/or mixing pump 2 is operating.
DHW Pump / Valve
DHW
Displays when the DHW pump or valve is on.
Storage Operation
Displays when the variable speed driven injection pump is drawing heat from the storage tank.
Boost
Displays when the control is in boost after setback.
UnOccupied Mode
Displays when control is in unoccupied mode.
Occupied Mode
Displays when the control is in occupied mode.
Item
The abbreviated name of the selected item will be displayed in the item field of the display. To view the next available item, press and release the reached the last available item in a menu, pressing and releasing the
Item
button. Once you have
Item
button will
return the display to the first item in the selected menu.
Adjust
To make an adjustment to a setting in the control, begin by selecting the appropriate menu using the use the
Additional information can be gained by observing the Status and Pointers fields of the LCD. The status field will indicate which of the control’s outputs are currently active. Most symbols in the status field are only visible when the View Menu is selected.
Menu
button. Then select the desired item using the
and/or button to make the adjustment.
Item
button. Finally,
1 of 4 Copyright © 1999 U 363 -06/99
Ovr
!
°
F, °C, sec,
min, hr
Override
Displays when the control is in override mode.
Warning
Displays when an error exists or a limit has been reached.
Lock - Unlock
Displays whether access levels are locked or unlocked.
°F, °C, sec, min, hr,
Units of measurement.
Pointer
Displays control operation as indicated by text.
Note: Depending on the settings the installer makes in the control, certain menu items may not appear.
Item
LTD
USER
Current outdoor air temperature as measured by the outdoor sensor. This is the default display for the control.
Target room air temperature. “— — —” denotes no heat is required. Will not display if RTU is connected.
Measured room air temperature at the indoor sensor. Will not display if RTU is connected.
Current mixed supply water temperature as measured by the mixing sensor.
Current boiler supply water temperature as measured by the boiler sensor.
Current storage tank water temperature as meassured by the storage tank sensor.
Target DHW tank temperature. This item can only be viewed if a tekmar sensor is used to measure the DHW tank temperature.
Current DHW tank temperature as measured by the DHW tank sensor.
363 View Menu
Range
-67 to 149˚F (-55 to 65˚C)
- - -, 35 to 100˚F (2 to 38˚C)
-58 to 167˚F (-50 to 75˚C)
-31 to 266˚F (-35 to 130˚C)
-31 to 266˚F (-35 to 130˚C)
-31 to 266˚F (-35 to 130˚C)
- - -, OFF, 70 to 190˚F (21 to 88˚C)
-31 to 266˚F (-35 to 130˚C)
Item
Occ
UnOcc
Occ
UnOcc
Occ
UnOcc
LTD
363
USER
The desired room air temperature during an Occupied period for mixing zone(s). Will not display if RTU is connected. In LTD access level, this setting can only be adjusted ±3°F (±1°C).
The desired room air temperature during an UnOccupied period for mixing zone(s). Will not display if RTU is connected.
The minimum temperature at the slab sensor, provided the control is not in Warm Weather Shut Down. This item can only be adjusted if a tekmar sensor is connected.
Mixing Water Temperature Setback. The amount that the mixing supply temperature will be reduced when the control is in an UnOccupied mode.
The desired room air temperature during an Occupied period for the boiler zones in the heating system. In LTD access level, this setting can only be adjusted ±3°F (±1°C).
The desired room air temperature during an UnOccupied period for
the boiler zone(s) in the heating system.
Boiler Water Temperature Setback. The amount that the boiler supply temperature will be reduced when the control is in an
UnOccupied mode.
The DHW storage tank’s temperature during the Occupied period. This item can only be adjusted if a tekmar sensor is used to measure
the DHW tank temperature.
The DHW storage tank’s temperature during the UnOccupied period.This item can only be adjusted if a tekmar sensor is used to measure the DHW tank temperature.
Adjust
Menu
Range
35 to 100˚F (2 to 38˚C)
35 to 100˚F (2 to 38˚C)
OFF, 35 to 120˚F (2 to 49˚C)
0 to 50˚F (0 to 28˚C)
35 to 100˚F (2 to 38˚C)
35 to 100˚F (2 to 38˚C)
0 to 50˚F (0 to 28˚C)
OFF, 70 to 190˚F (OFF, 21 to 88˚C)
OFF, 70 to 190˚F (21 to 88˚C)
The system’s warm weather shut down during the Occupied period.
Occ
UnOcc
Copyright © 1999 U 363 -06/99 2 of 4
The system’s warm weather shut down during the UnOccupied period.
35 to 100˚F, OFF (2 to 38˚C)
35 to 100˚F, OFF (2 to 38˚C)