The Universal Reset Control 363 is a microprocessor based control designed to maximize the comfort and
efficiency provided by a hydronic heating system. The control automatically adjusts the boiler and mixed loop
water temperatures that are delivered to the heating system by using an outdoor reset. Outdoor reset increases
the water temperature in the heating system as the outdoor temperature becomes colder. Outdoor reset also
increases the energy efficiency of the heating system by not allowing more heat into the building than the
building normally loses to the outside. Another benefit of outdoor reset is the reduction of indoor temperature
swings - especially in the fall and spring months. The 363 can intelligently integrate indirect fired Domestic
Hot Water (DHW) and tekmar zone controls into the heating system.
User Interface
Access Level(s) The tekmar Universal Mixing Control 363 has four access levels which are LTD (limited), USER, INST (Installer),
and ADV (advanced). This brochure only covers the LTD (Limited) and USER levels. Only qualified service people should make
adjustments in the INST (Installer) and ADV (advanced) access levels.
Item Field
Displays an abbreviated
name of the selected item
Menu Field
Displays the
current menu
View
Adjust
Monitor
Schd
Misc
Open
Close
°F°
1
UnOcc
2
DHW
Aux
%
1
Number Field
Displays the current value
of the selected item
Mix Demand
Boiler Demand
C
min
sec
Ovr
DHW Demand
hr
Setpoint Demand
WWSD
Minimum
!
Maximum
Status Field
Displays the
current status of
the control’s
inputs, outputs
and operation
Menu
Item
Buttons
Selects Menu,
{
Items and adjusts
settings
The tekmar Universal Reset Control 363 has a Liquid Crystal Display (LCD) and
four push buttons (
Menu, Item
, , ) which are used to view and adjust the settings.
Menu
All of the items displayed by the control are organized into various menus. These menus
are listed on the left hand side of the display (Menu Field). To select a menu, use the
Menu
button. By pressing and releasing the
next available menu. Once a menu is selected, there will be a group of items that can
be viewed within that menu.
Menu
button, the display will advance to the
Open
Close
Aux
UnOcc
Occ
Open / Close
Displays when the actuator is
opening or closing the valve.
Mixing Device Output Scale
Shows output of injection pump
or mixing valve. Arrows show
%
1
whether the output is increasing
or decreasing.
Burner
Displays when the boiler relay is
turned on.
Pump
1
2
Displays boiler pump 1 and/or
mixing pump 2 is operating.
DHW Pump / Valve
DHW
Displays when the DHW pump or
valve is on.
Storage Operation
Displays when the variable speed
driven injection pump is drawing
heat from the storage tank.
Boost
Displays when the control is in
boost after setback.
UnOccupied Mode
Displays when control is in
unoccupied mode.
Occupied Mode
Displays when the control is in
occupied mode.
Item
The abbreviated name of the selected item will be displayed in the item field of the display.
To view the next available item, press and release the
reached the last available item in a menu, pressing and releasing the
Item
button. Once you have
Item
button will
return the display to the first item in the selected menu.
Adjust
To make an adjustment to a setting in the control, begin by selecting the appropriate
menu using the
use the
Additional information can be gained by observing the Status and Pointers fields of the
LCD. The status field will indicate which of the control’s outputs are currently active. Most
symbols in the status field are only visible when the View Menu is selected.
Menu
button. Then select the desired item using the
and/or button to make the adjustment.
Item
button. Finally,
1 of 4 Copyright © 1999 U 363 -06/99
Ovr
!
°
F, °C, sec,
min, hr
Override
Displays when the control is in
override mode.
Warning
Displays when an error exists or
a limit has been reached.
Lock - Unlock
Displays whether access levels
are locked or unlocked.
°F, °C, sec, min, hr,
Units of measurement.
Pointer
Displays control operation as
indicated by text.
Note: Depending on the settings the installer makes in the control, certain menu items may not appear.
Item
LTD
• •
•
• •
•
•
• •
•
• •
USER
Current outdoor air temperature as measured by the outdoor sensor.
This is the default display for the control.
Target room air temperature. “— — —” denotes no heat is required.
Will not display if RTU is connected.
Measured room air temperature at the indoor sensor. Will not display
if RTU is connected.
Current mixed supply water temperature as measured by the
mixing sensor.
Current boiler supply water temperature as measured by the boiler
sensor.
Current storage tank water temperature as meassured by the storage
tank sensor.
Target DHW tank temperature. This item can only be viewed if a
tekmar sensor is used to measure the DHW tank temperature.
Current DHW tank temperature as measured by the DHW tank
sensor.
363 View Menu
Range
-67 to 149˚F
(-55 to 65˚C)
- - -, 35 to 100˚F
(2 to 38˚C)
-58 to 167˚F
(-50 to 75˚C)
-31 to 266˚F
(-35 to 130˚C)
-31 to 266˚F
(-35 to 130˚C)
-31 to 266˚F
(-35 to 130˚C)
- - -, OFF, 70 to 190˚F
(21 to 88˚C)
-31 to 266˚F
(-35 to 130˚C)
Item
Occ
UnOcc
Occ
UnOcc
Occ
UnOcc
LTD
• •
•
•
•
• •
•
363
USER
The desired room air temperature during an Occupied period for
mixing zone(s). Will not display if RTU is connected. In LTD access
level, this setting can only be adjusted ±3°F (±1°C).
The desired room air temperature during an UnOccupied period for
mixing zone(s). Will not display if RTU is connected.
The minimum temperature at the slab sensor, provided the control
is not in Warm Weather Shut Down. This item can only be adjusted
if a tekmar sensor is connected.
Mixing Water Temperature Setback. The amount that the mixing
supply temperature will be reduced when the control is in an
UnOccupied mode.
The desired room air temperature during an Occupied period for the
boiler zones in the heating system.
In LTD access level, this setting can only be adjusted ±3°F (±1°C).
The desired room air temperature during an UnOccupied period for
•
the boiler zone(s) in the heating system.
Boiler Water Temperature Setback. The amount that the boiler supply
temperature will be reduced when the control is in an
•
UnOccupied mode.
The DHW storage tank’s temperature during the Occupied period.
This item can only be adjusted if a tekmar sensor is used to measure
•
the DHW tank temperature.
The DHW storage tank’s temperature during the UnOccupied
period.This item can only be adjusted if a tekmar sensor is used to
measure the DHW tank temperature.
Adjust
Menu
Range
35 to 100˚F
(2 to 38˚C)
35 to 100˚F
(2 to 38˚C)
OFF, 35 to 120˚F
(2 to 49˚C)
0 to 50˚F
(0 to 28˚C)
35 to 100˚F
(2 to 38˚C)
35 to 100˚F
(2 to 38˚C)
0 to 50˚F
(0 to 28˚C)
OFF, 70 to 190˚F
(OFF, 21 to 88˚C)
OFF, 70 to 190˚F
(21 to 88˚C)
The system’s warm weather shut down during the Occupied period.
Occ
UnOcc
Copyright © 1999 U 363 -06/99 2 of 4
•
The system’s warm weather shut down during the UnOccupied period.
•
35 to 100˚F, OFF
(2 to 38˚C)
35 to 100˚F, OFF
(2 to 38˚C)