The Mixing Control 362 is a microprocessor based control with two distinct operating modes.
MODE —1— allows the control to provide a reset mixed supply water temperature to a heating system based on outdoor air temperature.
Multiple zone temperature controls can be achieved by using either a conventional thermostat system or by using tekmar Zone Controls
attached to the 362. For single zone heating applications, a single Room Temperature Unit (RTU) can be connected directly to the 362
for zone temperature control.
MODE —2— allows the control to provide a single zone of snow melting. With the addition of a Snow Melting Kit 092, the 362 can
provide slab temperature control and slab ΔT protection. The melting mode is initiated manually either with a demand signal or from the
Snow Melting Kit enabling device.
The 362 incorporates a large Liquid Crystal Display (LCD) in order to provide system status and operating information. The same LCD
is used when setting up and installing the control. Standard features for both modes of operation include boiler return protection,
intelligent boiler operation, Warm Weather Shut Down (WWSD), and pump exercising. As well, with the addition of a new Monitor
feature, it is now possible to track pump and boiler running hours, boiler cycles and high and low sensor temperatures. The 362 also has
a unique feature that allows the control to supply heat to the mixed system from either the boiler or a thermal storage tank.
1 Heating
2 Snow melting
Do not apply power
13
14
tN1/
Com1510K16UnO
tN2
Reset Ratio
Characterized
Heating Curve
17
Com
Sw
Te s t
off
off
red
red
For maximum heat,
press and hold
button for 3 seconds.
18
Mix19Boil20Out
not testing
not testing
testing
testing
testing pausedred
Tes t
Meets Class B:
Canadian ICES
FCC Part 15
Date Code
H1176D
Note:
Mixing demand must be
powered with 20 to 260
V (ac) before the mixing
valve is able to open and
the boiler is able to fire.
View
Open
%
1
Item
Menu
Mixing Control 362
Floating Action / Variable Speed
5
4
3
2
1
Mix
Demand
Power
N L
Pmp
Mix
°
UnOcc
Mix Demand
F
WWSD
Minimum
Maximum
Melting
Idling
7
9
6810
Pwr
Opn Cls
Boiler
Mix
Var
C US
Setback
None
Operating Modes
See product literature
INSTALLATION CATEGORY II
Made in Canada by
tekmar Control Systems Ltd.
tektra 929-04
Power115 V ±10% 60 Hz 900 VA
R
Relays230 V (ac) 7.5 A 1/3 hp, pilot duty 240 VA
Var. Pump 230 V (ac) 2.4 A 1/6 hp, fuse T2.5 A 250V
Demands 20 to 260 V (ac) 2 VA
Signal wiring must be rated at least 300 V.
Wiring must be rated 194°F (90°C) minimum
Reference Material: Essay E 003: Characterized Heating Curve and Reset Ratio
E 021: Mixing Methods and Sizing of Variable Speed Injection Pumps
User Interface
The 362 uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to setup and monitor
the operation of your system. The 362 has four push buttons (Menu, Item, , ) for selecting and adjusting settings. As you program
your control, record your settings in the Adjust Menu table which is found in the second half of this brochure.
Menu
All of the items displayed by the control are organized into various menus. These menus are
listed on the left hand side of the display (Menu Field). To select a menu, use the
button. By pressing and releasing the
available menu. Once a menu is selected, there will be a group of items that can be viewed
within that menu.
Item
The abbreviated name of the selected item will be displayed in the item field of the display.
To view the next available item, press and release the
the last available item in a menu, pressing and releasing the
display to the first item in the selected menu.
Adjust
To make an adjustment to a setting in the control, begin by selecting the appropriate menu
Menu
using the
and / or button to make the adjustment.
button. Then select the desired item using the
Menu
button, the display will advance to the next
Item
button. Once you have reached
Item
button will return the
Item
button. Finally, use the
Menu
Menu
Menu
Menu
Item
Item
Item
Additional information can be gained by observing the Status and Pointers fields of the LCD. The status field will indicate which of
the control’s outputs are currently active. Most symbols in the status field are only visible when the View Menu is selected.
When the Mixing Control 362 is powered up, the control displays the control type number in the LCD for 2 seconds. Next, the software
version is displayed for 2 seconds. Finally, the control enters into the normal operating mode and the LCD defaults to displaying the
current outdoor air temperature.
MODES OF OPERATION
The Mixing Control 362 has two distinct operating modes. The mode of
operation for the control is selected in the Adjust Menu.
MODE 1 (Heating)
Mode 1 is the Heating mode of operation. In this mode, the 362 is an
Outdoor Reset control for a building heating system. The 362 uses a
mixing device to vary the supply water temperature to the building
heating system according to the outdoor conditions.
MODE 2 (Snow Melting)
Mode 2 is the Snow Melting mode of operation. In this mode, the 362 is
a Slab Outdoor Reset control for a single zone of snow melting. The 362
uses a mixing device to vary the supply water temperature to a single
zone snow melting system. In the Snow Melting mode, the 362 uses a
slab sensor and mixing return sensor in order to provide slab temperature
control and slab protection. It is recommended to purchase a Snow Melt
Enable Kit 092 when using this mode of operation.
MIXING DEVICE SELECTION (MIXING)
The 362 can supply a lower water temperature to part of the heating system by varying the speed of an injection pump or modulating
a mixing valve. This selection is made under the MIXING item in the
VARIABLE SPEED INJECTION (VAR)
A standard wet rotor circulator is connected to the 362 on the
Cls / Var
output to the circulator when there is a
varies to maintain the correct mixed supply water temperature at the mix
sensor. For correct sizing and piping of the variable speed injection driven
circulator, refer to essay E 021. A visual indication of the current variable
speed output is displayed in the LCD in the form of a segmented bar graph.
Two small indicators at the top of the graph indicate whether the output is
increasing or decreasing.
FLOATING ACTION (FLOT)
A floating action actuator motor is connected to the 362 on the
Opn
motor open or close to maintain the correct supply water temperature at the
mix sensor when there is a
is connected to can be either a 2-way, 3-way or 4-way valve. A visual
indication as to whether the control is currently opening or closing the
mixing valve is displayed in the LCD with the words Open and Close. Also,
a visual indication of the current position of the valve is displayed in the LCD
in the form of a segmented bar graph.
terminals (8 and 10). The 362 increases or decreases the power
terminals (8, 9 and 10). The 362 pulses the actuator
Mix Demand
Adjust Menu
Pwr Mix
Mix Demand
. The mixing valve that the actuator
. The circulator speed
and
Pwr Mix
4 of 36
.
,
MIXING TARGET TEMPERATURE (MIX TRG)
(
RESET RATIO
When in Mode 1, the MIX TRG temperature is determined from either the
the outdoor air temperature. When in Mode 2, the MIX TRG temperature is determined from either the outdoor air temperature and the
desired slab temperature or the Melting and Idling settings. The control displays the temperature that it is currently trying to maintain
as the mixing supply temperature. If the control does not presently have a requirement for heat, it displays “- - -” in the LCD.
&
CHARACTERIZED HEATING CURVE
)
Characterized Heating Curve
or the
Reset Ratio
settings and
MIXING MAXIMUM (MIX MAX)
The MIX MAX sets the highest water temperature that the control is allowed
to calculate as the MIX TRG temperature. If the control does target the MIX
MAX setting, and the MIX SUP temperature is within 5˚F (3˚C) of the MIX
MAX, the
Maximum
pointer is displayed in the LCD while either the MIX
x
i
e
M
d
S
u
p
p
l
y W
a
t
e
r
T
e
r
u
t
a
r
e
p
m
e
MIX MAX
TRG temperature or the MIX SUP temperature is being viewed.
Pointer On
Pointer On
BOILER PROTECTION (BoiL MIN )
The 362 is capable of providing boiler protection from cold mixing system
return water temperatures. If the boiler sensor temperature is cooler than
the Boil MIN setting while the boiler is firing, the 362 reduces the output
from the mixing device. This limits the amount of cool return water to the
boiler and allows the boiler temperature to recover. This feature can only
be used if the Boil SENS item is not set to NONE.
EXERCISING (EXERCISE)
The 362 has a built-in pump and valve exercising function. The exercising period is adjustable and comes factory set at 70 hours. If a
pump or valve output on the control has not been operated at least once during every exercising period, the control turns on the output
for 10 seconds. This minimizes the possibility of a pump or valve seizing during a long period of inactivity. In the case where a mixing
valve is being used as the mixing device, the 362 ensures that the valve operates over its entire range at least once each exercising
period.
Note: The exercising function does not work if power to the control or pumps is disconnected.
Section B: Mixing Reset (Mode —1—)
Section B1
General Mixing
Operation
Section B2
Alternate Mixing
Demands
Section B1: General Mixing Operation (Mode —1—)
MIXING DEMAND
A mixing demand is generated by applying a voltage between 24 and 240 V (ac) across the
Mix Demand
in the LCD. If the 362 is not in WWSD, the 362 closes the
segment is displayed in the LCD. The 362 calculates a MIX TRG supply temperature based
on the outdoor air temperature and settings. If required, the 362 operates the boiler in order
to provide heat to the mixing device.
CHARACTERIZED HEATING CURVE OR RESET RATIO
When used as a mixing reset control (MODE 1), the 362 has two methods of varying the supply water temperature based on the outdoor
air temperature. The installer can select either a
Characterized Heating Curve
The
Characterized Heating Curve
indoor temperature is the most accurate. The control takes into account the type of terminal unit that the system is using. Since different
types of terminal units transfer heat to a space using different proportions of radiation, convection and conduction, the supply water
temperature must be controlled differently. Once the control is told what type of terminal unit is used, the control varies the supply
water temperature according to the type of terminal unit. This improves the control of the air temperature in the building.
terminals (1 and 2). Once voltage is applied, the
Mix Pmp
Characterized Heating Curve
method of controlling the supply water temperature based on outdoor air temperature and optionally
Mix Demand
pointer is displayed
contact. The Mixing Pump
or a
24 to 240 V (ac)
Reset Ratio
2
1
Mix
Demand
.
Reset Ratio
The
Reset Ratio
method of controlling the supply water temperature is based solely on the outdoor air temperature. This method does
not take into account the type of terminal unit that the heating system is using and therefore is not as accurate as a
The MIX STRT temperature is the mixing supply water temperature that the
heating system requires when the outdoor air temperature equals the OUT
STRT air temperature.
OUTDOOR START (OUT STRT)
(
RESET RATIO
)
Mixing Reset
Ratio
MIX MAX
MIX DSGN
The OUT STRT temperature is the outdoor air temperature at which the
control provides the MIX STRT supply water temperature to the system.
OUTDOOR DESIGN (OUT DSGN)
(
RESET RATIO
&
CHARACTERIZED HEATING CURVE
)
The OUT DSGN is the outdoor air temperature that is typically the coldest
o
N
l
a
m
r
MIX SETB
k
c
a
b
t
e
S
temperature of the year where the building is located. This temperature is
used when doing heat loss calculations for the building.
MIX DESIGN (MIX DSGN)
Sequence, Section B
(
RESET RATIO
&
CHARACTERIZED HEATING CURVE
)
The MIX DSGN temperature is the supply water temperature required to
heat the mixing zones when the outdoor air is as cold as the Outdoor Design
temperature.
MIX STRT
OUT STRT
80
(27)
WWSD Occ
WWSD Unocc
60
(16)
40
(5)
Outdoor Air Temperature
OUT DSGN
20
(-7)
0
(-18)
MIXING MAXIMUM (MIX MAX)
(
RESET RATIO
The MIX MAX sets the highest water temperature that the control is allowed to calculate as the MIX TRG temperature. If the control does
target the MIX MAX setting, and the MIX SUP temperature is within 5˚F (3˚C) of the MIX MAX, the
LCD while either the MIX TRG temperature or the MIX SUP temperature is being viewed.
&
CHARACTERIZED HEATING CURVE
)
Maximum
pointer is displayed in the
-20
(-29)
210
(99)
190
(88)
170
(77)
150
(66)
130
(54)
110
(43)
90
(32
70
(21)
Supply Water Temperature
WARM WEATHER SHUT DOWN (WWSD) OCC & UNOCC
(
RESET RATIO
When the outdoor air temperature rises above the WWSD setting, the 362 turns on the
is in Warm Weather Shut Down, the
heating system to satisfy this demand.
SETBACK (SETBACK)
(
RESET RATIO
The SETBACK is the amount that the mixing supply water temperature is reduced when the 362 is placed into an
using an internal or an external setback as described later in this section. This setting is only available if the
selected and
MIXING INDOOR (MIX INDR)
(
CHARACTERIZED HEATING CURVE
The MIX INDR is the room temperature used in the original heat loss
calculations for the building. This setting establishes the beginning of the
Characterized Heating Curve
replaces the MIX STRT water temperature and OUT STRT air temperature
settings used by the
MIXING MINIMUM (MIX MIN)
(
CHARACTERIZED HEATING CURVE
The MIX MIN is the lowest temperature that the control is allowed to use as
a MIX TRG temperature. During mild conditions, if the 362 calculates a
MIX TRG temperature that is below the MIX MIN setting, the MIX TRG
temperature is adjusted to match the MIX MIN setting. During this condition,
the
Minimum
temperature or the MIX SUP temperature is being viewed.
If either an Indoor Sensor or a Room Temperature Unit (RTU) is used and
the 362 is operating at the MIX MIN temperature, the Mixing Pump is cycled using Pulse Width Modulation (PWM) with a 15 minute cycle
length. By cycling the Mixing Pump and controlling the flow of supply water, the control provides an average supply water temperature
to the mixing system. This average temperature is equal to the original MIX TRG. This minimizes overheating of the zone while the control
is operating at the MIX MIN temperature.
pointer is displayed if there is a demand. However, the control does not operate the
)
Setback / None
DIP switch is set to
Setback
.
)
for the mixing zones. This single setting
Reset Ratio
pointer turns on in the LCD when either the MIX TRG
)
.
6 of 36
WWSD
pointer in the display. When the control
UnOccupied
Reset Ratio
mode,
DIP switch is
ROOM OCC & UNOCC (ROOM)
(
CHARACTERIZED HEATING CURVE
The ROOM is the desired room temperature for the mixing zones and it provides a parallel shift of the
The room temperature desired by the occupants is often different from the design indoor temperature (MIX INDR). If the room
temperature is not correct, adjusting the ROOM
Setback / None
DIP switch is set to
)
Characterized Heating Curve
setting increases or decreases the amount of heat available to the building. If the
Setback
, a ROOM setting must be made for both the
Occupied
and
UnOccupied
modes.
.
MIXING TARGET TEMPERATURE (MIX TRG)
(
RESET RATIO
The MIX TRG temperature is determined from either the
temperature. The control displays the temperature that it is currently trying to maintain as the mixing supply temperature. If the control
does not presently have a requirement for heat, it displays “- - -” in the LCD.
TERMINAL UNITS (TERMINAL)
When using a
unit. The terminal unit determines the shape of the
to how the terminal unit delivers heat into the building space. The 362 provides for selection
between six different terminal unit types: two types of radiant floor heat, fancoil, fin-tube
convector, radiator and baseboard.
Hydronic Radiant Floor
HRF1 is a heavy, or high mass, hydronic radiant floor system. This type of a hydronic radiant
floor is embedded in either a thick concrete or gypsum pour. This heating system has a large
thermal mass and is slow acting.
Hydronic Radiant Floor
HRF2 is a light, or low mass, hydronic radiant floor system. Most commonly, this type of
radiant heating system is either attached to the bottom of a wood sub floor, suspended in
the joist space, or sandwiched between the subfloor and the surface. This type of radiant
system has a relatively low thermal mass and responds faster than a high mass system.
Fancoil
A fancoil terminal unit or air handling unit (AHU) consists of an hydronic heating coil and
either a fan or blower. Air is forced across the coil at a constant velocity by the fan or blower
and is then delivered into the building space.
&
CHARACTERIZED HEATING CURVE
Characterized Heating Curve
(HRF 1)
(HRF 2)
(COIL)
)
Characterized Heating Curve
, the control requires the selection of a terminal
Characterized Heating Curve
or the
according
Reset Ratio
settings and the outdoor air
HRF 1
HRF 2
COIL
Sequence, Section B
Fin–tube Convector
A convector terminal unit is made up of a heating element with fins on it. This type of terminal
unit relies on the natural convection of air across the heating element to deliver heated air
into the space. The amount of natural convection to the space is dependant on the supply
water temperature to the heating element and the room air temperature.
Radiator
A radiator terminal unit has a large heated surface that is exposed to the room. A radiator
provides heat to the room through radiant heat transfer and natural convection.
Baseboard
A baseboard terminal unit is similar to a radiator, but has a low profile and is installed at the
base of the wall. The proportion of heat transferred by radiation from a baseboard is greater
than that from a fin-tube convector.
(RAD)
(BASE)
(CONV)
MIXING PUMP OPERATION (Mix Pmp)
The Mixing Pump contact (
the mixing pump is operated based on the EXERCISE setting in the
PURGE (PURGE)
After the
that the Mixing Pump continues to run is an adjustable time setting. This setting allows any excess heat to be purged out to the heating
system. The Mixing Pump continues to run until the Purging time has elapsed or the mixing supply temperature drops below the MIXMIN setting. This setting should not be used if the mixing system is zoned using either zone pumps or fast acting zone valves.
Mixing Demand
CONV
RAD
BASE
Mix Pmp
has been satisfied, the 362 can continue to operate the Mixing Pump for a period of time. The length of time
To provide greater energy savings, the 362 has a setback capability. With setback, the supply
water temperature in the system is reduced when the building is not used (AWAY) or when
the building is UnOccupied. By reducing the supply water temperature, air temperature in the
space may be reduced even when thermostat(s) are not turned down. This feature is enabled
by setting the
Setback / None DIP
switch to the
Setback
position, and providing either an
external signal or an internal override.
Note: AWAY does not require the DIP switch =
Setback
17
16
UnO
Com
Sw
Timer Switch
External UnOccupied
An external signal can place the 362 into an UnOccupied mode. Any time the
and the
Com
(17) terminals are shorted together, the control operates in the UnOccupied
mode. When in the UnOccupied mode, the
362 adjusts the supply water temperature(s) based on the
the control.
Sequence, Section B
Internal Overrides
The 362 has a number of setback overrides that are selected through the
UnOcc
UnO Sw
segment is displayed in the LCD. The
UnOcc
settings made in
(16)
Schd
UnOcc
Schd
Menu. These
setback overrides have priority over any external setback signal. Any time an override is in
Ovr
effect, the
segment is displayed in the LCD.
Temporary (TMPY)
If a temporary override is selected, the 362 operates in the selected override mode for 3 hours. Once completed, the control reverts
to the previous operation.
Permanent (PERM)
If a permanent override is selected, the 362 operates in the selected override mode until a new override is selected.
Away (AWAY)
If the AWAY override is selected, the 362 operates with a fixed WWSD of 62˚F (17˚C) and a fixed room temperature of 62˚F (17˚C).
BOOSTING (BOOST)
When the control changes from the
enters into a
to the system are raised above their normal values for a period of time to
provide a faster recovery from the building’s setback temperature. The
maximum length of the boost is selected in the user interface. This setting
is only available if a
available for a
Control is used.
Typical settings for the
hours for a building that has a fast responding heating system. For a
building that has a slow responding heating system, a setting between four
hours and eight hours is typical. After a
timer must be adjusted to come out of setback some time in advance of the
desired
BOOST setting. If the building is not up to temperature at the correct time, the BOOST setting should be lengthened and the setback
timer should be adjusted accordingly. If the building is up to temperature before the required time, the BOOST setting should be shortened
and the setback timer should be adjusted accordingly. If the system is operating near its design conditions or if the supply water
temperatures are being limited by settings made in the control, the time required to bring the building up to temperature may be longer
than expected.
Boosting
Occupied
UnOccupied
mode. In this mode, the supply water temperatures
Characterized Heating Curve
Reset Ratio,
and not needed or available if a tekmar Zone
Boost
function vary between 30 minutes and two
Boost
time. This time in advance is normally the same as the
to the
Occupied
mode, it
is selected; It is not
time is selected, the setback
Water Temperature
UnOcc to Occ
Boost
Mix TRG
(Occupied)
Mix
TRG (UnOccupied)
Boost setting - 20 minutes to 8 hours
Time
Self Adjusting
Water Temperature
Ovr
SOFT START (SOF STRT)
The SOF STRT function allows the 362 to slowly ramp the water temperature up to the required supply temperature. By allowing the
temperature in the system to be adjusted slowly, the control reduces any thermal expansion noises and stresses that may be caused
by a quick change in supply water temperature.
In addition to using conventional thermostats to provide a mixing demand as described in Section B1, the 362 can use a number of other
methods to provide a mixing demand.
10K INDOOR SENSOR (10K = INDR)
Set the 10K item to INDR to add an indoor sensor for temperature control of a single zone
mixing system. The indoor sensor is connected to the
In addition, power must be applied to the
section B1. With the indoor sensor connected, the 362 is able to sense the actual room
temperature. With this information, the 362 provides a more constant water flow through the
mixing system. At the same time, indoor temperature feedback fine tunes the supply water
temperature in the mixing system to prevent over heating or under heating. To adjust the room
temperature for the mixing zone, use the ROOM
menu at the control.
10K ZONE CONTROL (10K = ZoIn)
Set the 10K item to ZoIn to add indoor temperature feedback control of multiple mixing zones.
Control of mixing zones is provided by connecting a tekmar zone control to the 362. The zone
control provides its own internal
provide an external
Mix Demand
capable of automatically adjusting the MIX TRG temperature to improve building occupant
comfort and system performance.
10K SLAB SENSOR (10K = SLAB)
Set the 10K item to SLAB to add a slab sensor for temperature control of a single zone mixing
system. The 362 can use a slab sensor to control the actual slab temperature. A slab sensor
is placed in the slab and connected to the
be applied to the
Mix Demand
terminals (1 and 2) as described in Section B1. With the slab
sensor connected, the 362 will limit the mixing supply temperature in order to maintain the slab
sensor between the SLAB MIN and SLAB MAX settings.
Slab Minimum
(SLAB MIN)
The SLAB MIN sets the minimum allowed core temperature of the slab as long as the control is not in a WWSD. Caution should be
used when adjusting the SLAB MIN setting as this may lead to overheating of the zone during mild conditions. If the AWAY setting
is selected in the Schedule menu, the 362 ignores the SLAB MIN setting.
Slab Maximum
(SLAB MAX)
The SLAB MAX sets the maximum allowed core temperature of the slab. If the slab is to be maintained at a fixed core temperature,
set SLAB MAX and SLAB MIN items to the same setting.
ROOM TEMPERATURE UNIT (RTU) 062, 063
If the mixing system consists of a single zone, temperature control of that zone can be provided
by using an RTU. The RTU is connected to the
(11 and 13). In addition, power must be applied to the
described in Section B1. With the RTU connected, the 362 measures the actual room
temperature. With this information, the 362 provides a constant water flow through the mixing
system. At the same time, indoor temperature feedback fine tunes the supply water
temperature in the mixing system to prevent over heating or under heating. The RTU allows
the user to adjust the desired room temperature at the RTU. Remote sensor capability is also
available through an RTU as described in the RTU data brochure.
Com
and
10K
terminals (14 and 15).
Mix Demand
Occupied
terminals (1 and 2) as described in
or
UnOccupied
setting in the Adjust
mixing demand
as described earlier in Section B1. The zone control is
to the 362. In this case, there is no need to
Com
and the
10K
terminals (14 and 15). Power must
Com
and tekmar Net
Mix Demand
TM
tN1/tN2
terminals
terminals (1 and 2) as
tekmar
Indoor Sensor
tekmar
Zone Control
Power
Occupied
UnOccupied
Heat Required
Optimum Start / Stop
24 hr. Timer
System Pump
Timer Active
70°F
(21°C)
12 hrs.
Zone 1 Lo stage
1
• Dial the desired duration
618
of the UnOccupied period.
• Press start button at the time of day
Zone 2 Hi stage
2
you want the UnOcc. period to begin.
Timer Active light turns on.
Zone 3 Lo stage
3
0
24
40
100
(4)
(38)
UnOccupied
Zone 4 Hi stage
4
UnOccupied
Duration
Start
0 = always Occupied
24 = always UnOccupied
Zone Control 368
One & Two Stage
tekmar
Slab Sensor
tekmar
RTU
View
°
F
UnOcc 1
ItemMenu
tekmar
362 Control
Mix Demand
View
Boiler Demand
°
F
DHW Demand
Setpoint Demand
Minimum
1
2
%
Maximum
1
DHW
Item
Menu
R
Universal Reset Control 363
NRTL/C
Mixing, Boiler & DHW
LR 58223
LR 58233
E150539
tekmar 362
Control
Mix Demand
View
Boiler Demand
°
F
DHW Demand
Setpoint Demand
Minimum
2
1
%
Maximum
1
DHW
Item
Menu
R
Universal Reset Control 363
NRTL/C
Mixing, Boiler & DHW
LR 58223
LR 58233
E150539
tekmar
362 Control
Mix Demand
View
Boiler Demand
°
F
DHW Demand
Setpoint Demand
Minimum
2
1
%
Maximum
1
DHW
Item
Menu
R
Universal Reset Control 363
NRTL/C
Mixing, Boiler & DHW
LR 58223
LR 58233
E150539
tekmar
362 Control
Mix Demand
View
Boiler Demand
°
F
DHW Demand
Setpoint Demand
Minimum
2
1
%
Maximum
1
DHW
Item
Menu
Heat
Universal Reset Control 363
Mixing, Boiler & DHW
R
NRTL/C
LR 58223
LR 58233
E150539
Section C: Snow Melting (Mode —2—)
Section C1
General Snow
Melting
Section C2
Snow Melting
Enable / Disable
Section C3
With Slab Sensor
Section C4
Without Slab
Sensor
Section C1: General Snow Melting
The Mixing Control 362 is capable of controlling a single zone snow melting system. In order to provide the best control of the snow
melting system, the 362 should be equipped with an optional tekmar Slab Sensor 072 or 073 and an optional Universal Sensor 071 that
measures the slab return temperature. These can be purchased separately or as part of the Snow Melt Enable Kit 092. The Kit also
includes alternate Start / Stop module 039. With these installed, the 362 is capable of providing the features listed in the following section.
Also described in this section are several different methods of starting and stopping the snow melting system.
NOTE: When operating in the Snow Melting mode, the
operation of the contro
SLAB PROTECTION (∆T MAX)
Boiler Sensor on the Return or No Boiler Sensor
(
NON-DEDICATED HEAT SOURCE
If the snow melting system is one of several loads on a boiler or boiler plant, the amount of
heat available to the system can potentially damage the snow melting slab. The 362 controls
a mixing device that is installed between the snow melting slab and the boiler(s). The control
limits the rate at which heat can be applied to the slab through the
is the temperature difference between the slab supply temperature and the slab return
temperature. By limiting this temperature difference, the rate at which heat is applied to the
slab can be controlled and thermal stresses in the slab can be minimized. When the control
is operating at the ∆T MAX, the
in the View menu. This mode of operation only works when the Boil SENS item is set to RET
or NONE.
Boiler Sensor on the Supply
(
DEDICATED HEAT SOURCE
If the snow melting system consists of a snow melting slab and a dedicated boiler, a mixing
device is installed between the snow melting slab and the boiler to protect the boiler from
low operating temperatures. In a dedicated snow melting system with a properly sized
boiler, it is not necessary for the control to provide ∆T protection of the snow melting slab;
Since the boiler output is matched to the slab requirements, it is not possible to heat the slab
too rapidly and cause thermal stresses that will result in damage to the slab. Therefore, the
∆T MAX item in the
When operating a dedicated snow melting system, the 362 is designed to operate the boiler
as efficiently as possible. This mode of operation only works when the Boil SENS item is
set to SUP.
Adjust
)
Maximum
pointer can be seen when viewing the MIX ∆T item
)
menu and the MIX ∆T item in the
Reset Ratio / Characterized Heating Curve DIP switch
∆T MAX setting. The ∆T
View
menu are not available.
has no effect on the
tensile stress
VISCOSITY COMPENSATION (EXCEEDING ∆T MAX)
At low temperatures, the glycol solutions used in snow melting systems become very viscous and difficult to pump. In order to overcome
this condition during a cold start of a snow melting system, the 362 is allowed to exceed the ∆T MAX setting for a period of time in order
to warm the glycol solution. This allows the control to compensate for the high viscosity of the glycol solution and is used when the supply
temperature is below 30˚F (-1˚C). When the control exceeds the
item in the
RAMPING OF THE ∆T
When the control starts applying heat to the slab, the supply temperature to the snow melting system is ramped up over a period of time
until it reaches the maximum allowed ∆T. This function does not occur when the boiler sensor is on the supply.
OPERATING STATUS (SNOWMELT)
While in the Snow Melting mode (Mode 2), an additional item is available in the
current operating status of the snow melting system.
• STRT The word STRT is displayed after the snow melting system has been enabled. It is
• STOP The word STOP is displayed for five seconds after the snow melting system has
• IDLE The word IDLE is displayed as long as the control is operating the slab at the idling temperature.
• EXT The word EXT is displayed when the RUN TIME has reached 0:00 and the control still has an external demand for melting. In
• 0:00 to 17:00 hr While the slab is up to temperature, and the control is melting, the remaining RUN TIME is displayed.
• INF If an infinite RUN TIME is selected and the control is melting, INF is displayed.
• WWSD When the control is in a Warm Weather Shut Down, WWSD is displayed.
• CWCO When the control is in a Cold Weather Cut Off, CWCO is displayed
View
menu.
displayed until the slab reaches the melting temperature. If the slab is at the melting
temperature, STRT is displayed for five seconds after the snow melting system has
started operation. This is to verify that the control has entered into the
snow melting mode.
stopped operation. The word STOP is also displayed if either a Remote Start/Stop
Module 039 or Remote Display Module 040 stops the snow melting system and an
external demand is still present.
this situation, the control continues melting until the snow melting demand is removed or the control is stopped.
The running time is the length of time that the snow melting system operates once the slab has reached the melting temperature. During
the time that the slab is approaching the melting temperature, the RUN TIME does not decrease. Once the slab has reached the melting
temperature, the RUN TIME begins counting down. When the RUN TIME reaches 0:00 as displayed by the SNOWMELT item in the
menu, the 362 has finished Melting.
View
WARM WEATHER SHUT DOWN (WWSD)
When both the slab temperature and the outdoor temperature exceed the
Melting temperature by more than 1.5˚F (1˚C), the control enters into a
WWSD. In a WWSD, the snow melting system is shut down in order to
conserve energy.
COLD WEATHER CUT OUT (CWCO)
Maintaining the slab at either the Melting or Idling temperature during extremely cold temperatures can be expensive or impossible. The
control shuts off the snow melting system once the outdoor air temperature drops below the Cold Weather Cut Out (CWCO) temperature.
While the control is in a CWCO, the word CWCO is displayed in the SNOWMELT item in the View menu. If the control had been started
prior to the CWCO, it resumes the melting mode once the outdoor air temperature rises above the CWCO temperature.
BOILER OPERATION
Refer to section D for a description of the boiler operation.
BOILER PROTECTION (Boil MIN)
The 362 ensures that the boiler supply water temperature remains above
the Boil MIN setting. If the boiler supply water temperature begins to drop
due to the slab return temperature, the mixing device is throttled back to
allow the boiler to recover. This minimizes the time that the boiler operates
below its condensing temperature and prolongs the life of the boiler. The
362 can only provide boiler protection if the Boil SENS item is set to SUP
or RET. The 362 cannot provide boiler protection if the Boil SENS item is
set to NONE.
SNOW MELTING OVERRIDE
Sequence, Section C2
Internal Override
If the AWAY setting is selected in the Schedule menu, the system is shut down. Both the
as long as the control remains in the AWAY mode. The
External Override
While in Mode 2, any signal received on the UnO Sw and COM terminal (16 and 17) is ignored and does not affect the operation of
the control.
MIXING PUMP OPERATION (Mix Pmp)
The Mixing Pump (Mix Pmp) contact closes and remains closed as long as the control is either in the Melting or Idling mode. The Mixing
Pump contact shuts off if the control is in WWSD, CWCO, or if there is no call for Melting or Idling.
PURGE (PURGE)
The Mixing Pump (Mix Pmp) continues to operate for the set PURGE time after the control finishes operation.
Melting
and
Idling
temperatures are ignored
Setback / N one
DIP does not matter for internal overrides.
Section C2: Snow Melting Enable (Mode —2—)
There are three methods in which the snow melting system can be enabled on the Mixing Control 362. Either an
Remote Start / Stop Module 039
EXTERNAL DEMAND
An external snow melting demand is generated when a voltage between
24 and 240 V (ac) is applied across
external demand must be present for at least 4 seconds in order to start the
snow melting system. Once started, the slab temperature is increased to
the MELTING setting and maintained at the melting temperature until the
Run Time reaches 0:00. If the Run Time reaches 0:00 and the external
demand is still present, the control continues at the melting temperature
until the external demand is removed or the system is otherwise stopped.