tekmar 362 Installation

- Data Brochure
D 362
Mixing Control 362
12/08
The Mixing Control 362 is a microprocessor based control with two distinct operating modes.
MODE —1— allows the control to provide a reset mixed supply water temperature to a heating system based on outdoor air temperature. Multiple zone temperature controls can be achieved by using either a conventional thermostat system or by using tekmar Zone Controls attached to the 362. For single zone heating applications, a single Room Temperature Unit (RTU) can be connected directly to the 362 for zone temperature control.
MODE —2— allows the control to provide a single zone of snow melting. With the addition of a Snow Melting Kit 092, the 362 can provide slab temperature control and slab ΔT protection. The melting mode is initiated manually either with a demand signal or from the Snow Melting Kit enabling device.
The 362 incorporates a large Liquid Crystal Display (LCD) in order to provide system status and operating information. The same LCD is used when setting up and installing the control. Standard features for both modes of operation include boiler return protection, intelligent boiler operation, Warm Weather Shut Down (WWSD), and pump exercising. As well, with the addition of a new Monitor feature, it is now possible to track pump and boiler running hours, boiler cycles and high and low sensor temperatures. The 362 also has a unique feature that allows the control to supply heat to the mixed system from either the boiler or a thermal storage tank.
1 Heating 2 Snow melting
Do not apply power
13
14
tN1/
Com1510K16UnO
tN2
Reset Ratio
Characterized Heating Curve
17
Com
Sw
Te s t
off
off
red
red
For maximum heat, press and hold button for 3 seconds.
18
Mix19Boil20Out
not testing
not testing testing
testing testing pausedred
Tes t
Meets Class B: Canadian ICES FCC Part 15
Date Code
H1176D
Note:
Mixing demand must be powered with 20 to 260 V (ac) before the mixing valve is able to open and the boiler is able to fire.
View
Open
%
1
Item
Menu
Mixing Control 362
Floating Action / Variable Speed
5
4
3
2
1
Mix
Demand
Power N L
Pmp
Mix
°
UnOcc
Mix Demand
F
WWSD
Minimum Maximum Melting Idling
7
9
6810
Pwr
Opn Cls
Boiler
Mix
Var
C US
Setback
None
Operating Modes
See product literature INSTALLATION CATEGORY II
Made in Canada by tekmar Control Systems Ltd. tektra 929-04
Power 115 V ±10% 60 Hz 900 VA
R
Relays 230 V (ac) 7.5 A 1/3 hp, pilot duty 240 VA Var. Pump 230 V (ac) 2.4 A 1/6 hp, fuse T2.5 A 250V Demands 20 to 260 V (ac) 2 VA
Signal wiring must be rated at least 300 V. Wiring must be rated 194°F (90°C) minimum
11 12
Com Mix
Ret
Input
Mix Demand
Signal
120 V (ac) Power
Input
Supply
Output
Mixing System
Pump
Output
M
OR
Output
Mixing Valve & Actuating
Motor OR Var. Speed
Driven Pump
Input
Universal
View
F
°
WWSD
1%%2
!
ItemMenu
Input
Room
Temperature
Unit (RTU)
1 of 36
View
F
°
WWSD
1%%2
!
ItemMenu
OR OR
Input
Remote
Display
Module (RDM)
79
8
Input
Snowmelt
Kit
(SMK)
Input
Outdoor
Input
Universal
Input
Universal Sensor
Input
tekmar
Timer
LR 58233
OR OR
70
tekmar Slab Sensor or Indoor Sensor or
Input
Zone Control
E150539
Copyright © D 362 -12/08
Included
How To Use The Data Brochure
This brochure is organized into four main sections. They are: 1) Sequence
Troubleshooting Sequence of Operation
apply to your installation.
Control Settings
The by the control. The control functions of each adjustable item are described in the
. The
Sequence of Operation
, as this contains important information on the overall operation of the control. Then read to the sub sections that
section (starting at DIP Switch Settings) of this brochure describes the various items that are adjusted and displayed
section has four sub sections. We recommend reading
of Operation

Table of Contents

User Interface ........................................... pg 2
Description of Display Elements ............ pg 3
Sequence of Operation ........................... pg 4
Section A: General
Section B: Mixing Reset
Section C: Snow Melting
Section D: Boiler Operation
Installation ................................................ pg 15
Electrical Connections.................. pg 16
Testing The Wiring......................... pg 18
DIP Switch Settings ................................. pg 20
........................ pg 4
............... pg 5
.............. pg 9
......... pg 13
Access Levels ........................................... pg 20
Control Settings ........................................ pg 21
View Menu
Adjust Menu
Schedule Menu
Miscellaneous Menu
RTU Menu
Testing and Troubleshooting .................. pg 28
Monitor Menu
Error Messages
Technical Data .......................................... pg 36
, 2)
Installation
Sequence of Operation
...................................... pg 21
................................... pg 22
.............................. pg 25
...................... pg 25
....................................... pg 26
................................. pg 30
.............................. pg 32
, 3)
Control Settings
Section A: General
.
, and 4)
of the
Limited Warranty ....................................... pg 36
Reference Material: Essay E 003: Characterized Heating Curve and Reset Ratio
E 021: Mixing Methods and Sizing of Variable Speed Injection Pumps

User Interface

The 362 uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to setup and monitor the operation of your system. The 362 has four push buttons (Menu, Item, , ) for selecting and adjusting settings. As you program your control, record your settings in the Adjust Menu table which is found in the second half of this brochure.
Menu
All of the items displayed by the control are organized into various menus. These menus are listed on the left hand side of the display (Menu Field). To select a menu, use the button. By pressing and releasing the available menu. Once a menu is selected, there will be a group of items that can be viewed within that menu.
Item
The abbreviated name of the selected item will be displayed in the item field of the display. To view the next available item, press and release the the last available item in a menu, pressing and releasing the display to the first item in the selected menu.
Adjust
To make an adjustment to a setting in the control, begin by selecting the appropriate menu
Menu
using the
and / or button to make the adjustment.
button. Then select the desired item using the
Menu
button, the display will advance to the next
Item
button. Once you have reached
Item
button will return the
Item
button. Finally, use the
Menu
Menu
Menu
Menu
Item
Item
Item
Additional information can be gained by observing the Status and Pointers fields of the LCD. The status field will indicate which of the controls outputs are currently active. Most symbols in the status field are only visible when the View Menu is selected.
Copyright © D 362 -12/08
2 of 36

Display

Item Field
Displays an abbreviated name of the selected item
Menu Field
Displays the current menu
Status Field
Displays the current status of the control’s inputs, outputs and operation
View Adjust
Monitor
Schd
Misc
Open Close
Menu
%
1
Item
Aux
1
2
UnOcc
DHW
°F°
sec
Number Field
Displays the current value of the selected item
Mix Demand WWSD
C
min
hr
Ovr
Minimum Maximum Melting
Idling
!
Buttons
Selects Menus, Items and
{
adjusts settings

Symbol Description

Mixing Device Output Scale
%
1
!
°
F, °C, sec,
min, hr
Open Close
Shows output of injection pump or mixing valve. Arrows show whether the output is increasing or decreasing.
Pump
Displays when mixing pump is in operation.
Burner
Displays when the boiler relay is turned on.
Warning
Displays when an error exists or a specific limit has been reached.
°F, °C, sec, min, hr
Units of measurement.
Open / Close
Displays when floating actuator is opening or closing.
Occ
UnOcc
Ovr
Lock - Unlock
Displays whether control is locked or unlocked.
Boost
Displays when control is in morning boost after setback.
Occupied Schedule
Displays when the control is in occupied mode.
UnOccupied Schedule
Displays when the control is in unoccupied mode.
Override
Displays when the control is in override mode.
Pointer
Displays the control operation as indicated by the text.
3 of 36
Copyright © D 362 -12/08
P1
OR
Mixing
P1
OR
Mixing

Sequence of Operation

Section A
General
Page 4 - 5
Section B
Mode 1:
Heating
Page 5 - 9
Section C
Mode 2:
Snow Melting
Page 9 - 13
Section D
Boiler Operation
Page 13 - 15
Section A —General Operation
POWERING UP THE CONTROL
When the Mixing Control 362 is powered up, the control displays the control type number in the LCD for 2 seconds. Next, the software version is displayed for 2 seconds. Finally, the control enters into the normal operating mode and the LCD defaults to displaying the current outdoor air temperature.
MODES OF OPERATION
The Mixing Control 362 has two distinct operating modes. The mode of operation for the control is selected in the Adjust Menu.
MODE 1 (Heating)
Mode 1 is the Heating mode of operation. In this mode, the 362 is an Outdoor Reset control for a building heating system. The 362 uses a mixing device to vary the supply water temperature to the building heating system according to the outdoor conditions.
MODE 2 (Snow Melting)
Mode 2 is the Snow Melting mode of operation. In this mode, the 362 is a Slab Outdoor Reset control for a single zone of snow melting. The 362 uses a mixing device to vary the supply water temperature to a single zone snow melting system. In the Snow Melting mode, the 362 uses a slab sensor and mixing return sensor in order to provide slab temperature control and slab protection. It is recommended to purchase a Snow Melt Enable Kit 092 when using this mode of operation.
MIXING DEVICE SELECTION (MIXING)
The 362 can supply a lower water temperature to part of the heating system by varying the speed of an injection pump or modulating a mixing valve. This selection is made under the MIXING item in the
VARIABLE SPEED INJECTION (VAR)
A standard wet rotor circulator is connected to the 362 on the
Cls / Var
output to the circulator when there is a varies to maintain the correct mixed supply water temperature at the mix sensor. For correct sizing and piping of the variable speed injection driven circulator, refer to essay E 021. A visual indication of the current variable speed output is displayed in the LCD in the form of a segmented bar graph. Two small indicators at the top of the graph indicate whether the output is increasing or decreasing.
FLOATING ACTION (FLOT)
A floating action actuator motor is connected to the 362 on the
Opn
motor open or close to maintain the correct supply water temperature at the mix sensor when there is a is connected to can be either a 2-way, 3-way or 4-way valve. A visual indication as to whether the control is currently opening or closing the mixing valve is displayed in the LCD with the words Open and Close. Also, a visual indication of the current position of the valve is displayed in the LCD in the form of a segmented bar graph.
terminals (8 and 10). The 362 increases or decreases the power
, and
Cls / Var
Copyright © D 362 -12/08
terminals (8, 9 and 10). The 362 pulses the actuator
Mix Demand
Adjust Menu
Pwr Mix
Mix Demand
. The mixing valve that the actuator
. The circulator speed
and
Pwr Mix
4 of 36
.
,
MIXING TARGET TEMPERATURE (MIX TRG)
(
RESET RATIO
When in Mode 1, the MIX TRG temperature is determined from either the the outdoor air temperature. When in Mode 2, the MIX TRG temperature is determined from either the outdoor air temperature and the desired slab temperature or the Melting and Idling settings. The control displays the temperature that it is currently trying to maintain as the mixing supply temperature. If the control does not presently have a requirement for heat, it displays - - - in the LCD.
&
CHARACTERIZED HEATING CURVE
)
Characterized Heating Curve
or the
Reset Ratio
settings and
MIXING MAXIMUM (MIX MAX)
The MIX MAX sets the highest water temperature that the control is allowed to calculate as the MIX TRG temperature. If the control does target the MIX
MAX setting, and the MIX SUP temperature is within 5˚F (3˚C) of the MIX MAX, the
Maximum
pointer is displayed in the LCD while either the MIX
x
i
e
M
d
S
u
p
p
l
y W
a
t
e
r
T
e
r
u
t
a
r
e
p
m
e
MIX MAX
TRG temperature or the MIX SUP temperature is being viewed.
Pointer On
Pointer On
BOILER PROTECTION (BoiL MIN )
The 362 is capable of providing boiler protection from cold mixing system return water temperatures. If the boiler sensor temperature is cooler than the Boil MIN setting while the boiler is firing, the 362 reduces the output from the mixing device. This limits the amount of cool return water to the boiler and allows the boiler temperature to recover. This feature can only be used if the Boil SENS item is not set to NONE.
EXERCISING (EXERCISE)
The 362 has a built-in pump and valve exercising function. The exercising period is adjustable and comes factory set at 70 hours. If a pump or valve output on the control has not been operated at least once during every exercising period, the control turns on the output for 10 seconds. This minimizes the possibility of a pump or valve seizing during a long period of inactivity. In the case where a mixing valve is being used as the mixing device, the 362 ensures that the valve operates over its entire range at least once each exercising period.
Note: The exercising function does not work if power to the control or pumps is disconnected.
Section B: Mixing Reset (Mode —1—)
Section B1
General Mixing
Operation
Section B2
Alternate Mixing
Demands
Section B1: General Mixing Operation (Mode —1—)
MIXING DEMAND
A mixing demand is generated by applying a voltage between 24 and 240 V (ac) across the
Mix Demand
in the LCD. If the 362 is not in WWSD, the 362 closes the segment is displayed in the LCD. The 362 calculates a MIX TRG supply temperature based on the outdoor air temperature and settings. If required, the 362 operates the boiler in order to provide heat to the mixing device.
CHARACTERIZED HEATING CURVE OR RESET RATIO
When used as a mixing reset control (MODE 1), the 362 has two methods of varying the supply water temperature based on the outdoor air temperature. The installer can select either a
Characterized Heating Curve
The
Characterized Heating Curve
indoor temperature is the most accurate. The control takes into account the type of terminal unit that the system is using. Since different types of terminal units transfer heat to a space using different proportions of radiation, convection and conduction, the supply water temperature must be controlled differently. Once the control is told what type of terminal unit is used, the control varies the supply water temperature according to the type of terminal unit. This improves the control of the air temperature in the building.
terminals (1 and 2). Once voltage is applied, the
Mix Pmp
Characterized Heating Curve
method of controlling the supply water temperature based on outdoor air temperature and optionally
Mix Demand
pointer is displayed
contact. The Mixing Pump
or a
24 to 240 V (ac)
Reset Ratio
2
1
Mix
Demand
.
Reset Ratio
The
Reset Ratio
method of controlling the supply water temperature is based solely on the outdoor air temperature. This method does
not take into account the type of terminal unit that the heating system is using and therefore is not as accurate as a
Characterized Heating Curve
.
5 of 36
Copyright © D 362 -12/08
70
(21)
90
(32)
110
(43)
130
(54)
150 (66)
170
(77)
190
(88)
Outdoor Air Temperature
Supply Water Temperature
210
(99)
-20
(-29)
0
(-18)
20
(-7)
40
(5)
60
(16)
80
(27)
MIX DSGN
MIX MAX
MIX MIN
WWSD Unocc
MIX INDOOR
OUT DSGN
Mixing Characterized
Heating Curve
WWSD Occ
50
(10)
MIX ROOM Occ
MIX ROOM Unocc
MIXING START (MIX STRT)
(
RESET RATIO
)
The MIX STRT temperature is the mixing supply water temperature that the heating system requires when the outdoor air temperature equals the OUT
STRT air temperature.
OUTDOOR START (OUT STRT)
(
RESET RATIO
)
Mixing Reset
Ratio
MIX MAX
MIX DSGN
The OUT STRT temperature is the outdoor air temperature at which the control provides the MIX STRT supply water temperature to the system.
OUTDOOR DESIGN (OUT DSGN) (
RESET RATIO
&
CHARACTERIZED HEATING CURVE
)
The OUT DSGN is the outdoor air temperature that is typically the coldest
o
N
l
a
m
r
MIX SETB
k
c
a
b
t
e
S
temperature of the year where the building is located. This temperature is used when doing heat loss calculations for the building.
MIX DESIGN (MIX DSGN)
Sequence, Section B
(
RESET RATIO
&
CHARACTERIZED HEATING CURVE
)
The MIX DSGN temperature is the supply water temperature required to heat the mixing zones when the outdoor air is as cold as the Outdoor Design temperature.
MIX STRT
OUT STRT
80
(27)
WWSD Occ
WWSD Unocc
60
(16)
40 (5)
Outdoor Air Temperature
OUT DSGN
20
(-7)
0
(-18)
MIXING MAXIMUM (MIX MAX)
(
RESET RATIO
The MIX MAX sets the highest water temperature that the control is allowed to calculate as the MIX TRG temperature. If the control does target the MIX MAX setting, and the MIX SUP temperature is within 5˚F (3˚C) of the MIX MAX, the LCD while either the MIX TRG temperature or the MIX SUP temperature is being viewed.
&
CHARACTERIZED HEATING CURVE
)
Maximum
pointer is displayed in the
-20
(-29)
210
(99)
190
(88)
170
(77)
150 (66)
130
(54)
110
(43)
90 (32
70
(21)
Supply Water Temperature
WARM WEATHER SHUT DOWN (WWSD) OCC & UNOCC (
RESET RATIO
When the outdoor air temperature rises above the WWSD setting, the 362 turns on the is in Warm Weather Shut Down, the heating system to satisfy this demand.
SETBACK (SETBACK)
(
RESET RATIO
The SETBACK is the amount that the mixing supply water temperature is reduced when the 362 is placed into an using an internal or an external setback as described later in this section. This setting is only available if the selected and
MIXING INDOOR (MIX INDR)
(
CHARACTERIZED HEATING CURVE
The MIX INDR is the room temperature used in the original heat loss calculations for the building. This setting establishes the beginning of the
Characterized Heating Curve
replaces the MIX STRT water temperature and OUT STRT air temperature settings used by the
MIXING MINIMUM (MIX MIN)
(
CHARACTERIZED HEATING CURVE
The MIX MIN is the lowest temperature that the control is allowed to use as a MIX TRG temperature. During mild conditions, if the 362 calculates a MIX TRG temperature that is below the MIX MIN setting, the MIX TRG temperature is adjusted to match the MIX MIN setting. During this condition, the
Minimum
temperature or the MIX SUP temperature is being viewed.
If either an Indoor Sensor or a Room Temperature Unit (RTU) is used and the 362 is operating at the MIX MIN temperature, the Mixing Pump is cycled using Pulse Width Modulation (PWM) with a 15 minute cycle length. By cycling the Mixing Pump and controlling the flow of supply water, the control provides an average supply water temperature to the mixing system. This average temperature is equal to the original MIX TRG. This minimizes overheating of the zone while the control is operating at the MIX MIN temperature.
Copyright © D 362 -12/08
&
CHARACTERIZED HEATING CURVE
Mix Demand
)
pointer is displayed if there is a demand. However, the control does not operate the
)
Setback / None
DIP switch is set to
Setback
.
)
for the mixing zones. This single setting
Reset Ratio
pointer turns on in the LCD when either the MIX TRG
)
.
6 of 36
WWSD
pointer in the display. When the control
UnOccupied
Reset Ratio
mode,
DIP switch is
ROOM OCC & UNOCC (ROOM)
(
CHARACTERIZED HEATING CURVE
The ROOM is the desired room temperature for the mixing zones and it provides a parallel shift of the The room temperature desired by the occupants is often different from the design indoor temperature (MIX INDR). If the room temperature is not correct, adjusting the ROOM
Setback / None
DIP switch is set to
)
Characterized Heating Curve
setting increases or decreases the amount of heat available to the building. If the
Setback
, a ROOM setting must be made for both the
Occupied
and
UnOccupied
modes.
.
MIXING TARGET TEMPERATURE (MIX TRG) (
RESET RATIO
The MIX TRG temperature is determined from either the temperature. The control displays the temperature that it is currently trying to maintain as the mixing supply temperature. If the control does not presently have a requirement for heat, it displays - - - in the LCD.
TERMINAL UNITS (TERMINAL)
When using a unit. The terminal unit determines the shape of the to how the terminal unit delivers heat into the building space. The 362 provides for selection between six different terminal unit types: two types of radiant floor heat, fancoil, fin-tube convector, radiator and baseboard.
Hydronic Radiant Floor
HRF1 is a heavy, or high mass, hydronic radiant floor system. This type of a hydronic radiant floor is embedded in either a thick concrete or gypsum pour. This heating system has a large thermal mass and is slow acting.
Hydronic Radiant Floor
HRF2 is a light, or low mass, hydronic radiant floor system. Most commonly, this type of radiant heating system is either attached to the bottom of a wood sub floor, suspended in the joist space, or sandwiched between the subfloor and the surface. This type of radiant system has a relatively low thermal mass and responds faster than a high mass system.
Fancoil
A fancoil terminal unit or air handling unit (AHU) consists of an hydronic heating coil and either a fan or blower. Air is forced across the coil at a constant velocity by the fan or blower and is then delivered into the building space.
&
CHARACTERIZED HEATING CURVE
Characterized Heating Curve
(HRF 1)
(HRF 2)
(COIL)
)
Characterized Heating Curve
, the control requires the selection of a terminal
Characterized Heating Curve
or the
according
Reset Ratio
settings and the outdoor air
HRF 1
HRF 2
COIL
Sequence, Section B
Fin–tube Convector
A convector terminal unit is made up of a heating element with fins on it. This type of terminal unit relies on the natural convection of air across the heating element to deliver heated air into the space. The amount of natural convection to the space is dependant on the supply water temperature to the heating element and the room air temperature.
Radiator
A radiator terminal unit has a large heated surface that is exposed to the room. A radiator provides heat to the room through radiant heat transfer and natural convection.
Baseboard
A baseboard terminal unit is similar to a radiator, but has a low profile and is installed at the base of the wall. The proportion of heat transferred by radiation from a baseboard is greater than that from a fin-tube convector.
(RAD)
(BASE)
(CONV)
MIXING PUMP OPERATION (Mix Pmp)
The Mixing Pump contact ( the mixing pump is operated based on the EXERCISE setting in the
PURGE (PURGE)
After the that the Mixing Pump continues to run is an adjustable time setting. This setting allows any excess heat to be purged out to the heating system. The Mixing Pump continues to run until the Purging time has elapsed or the mixing supply temperature drops below the MIX MIN setting. This setting should not be used if the mixing system is zoned using either zone pumps or fast acting zone valves.
Mixing Demand
CONV
RAD
BASE
Mix Pmp
has been satisfied, the 362 can continue to operate the Mixing Pump for a period of time. The length of time
, terminal 5) closes whenever there is a
Adjust
Mixing Demand
Menu.
and the 362 is not in WWSD. During WWSD,
7 of 36
Copyright © D 362 -12/08
SETBACK (UnOccupied)
To provide greater energy savings, the 362 has a setback capability. With setback, the supply water temperature in the system is reduced when the building is not used (AWAY) or when the building is UnOccupied. By reducing the supply water temperature, air temperature in the space may be reduced even when thermostat(s) are not turned down. This feature is enabled by setting the
Setback / None DIP
switch to the
Setback
position, and providing either an
external signal or an internal override. Note: AWAY does not require the DIP switch =
Setback
17
16
UnO
Com
Sw
Timer Switch
External UnOccupied
An external signal can place the 362 into an UnOccupied mode. Any time the and the
Com
(17) terminals are shorted together, the control operates in the UnOccupied mode. When in the UnOccupied mode, the 362 adjusts the supply water temperature(s) based on the the control.
Sequence, Section B
Internal Overrides
The 362 has a number of setback overrides that are selected through the
UnOcc
UnO Sw
segment is displayed in the LCD. The
UnOcc
settings made in
(16)
Schd
UnOcc
Schd
Menu. These
setback overrides have priority over any external setback signal. Any time an override is in
Ovr
effect, the
segment is displayed in the LCD.
Temporary (TMPY)
If a temporary override is selected, the 362 operates in the selected override mode for 3 hours. Once completed, the control reverts to the previous operation.
Permanent (PERM)
If a permanent override is selected, the 362 operates in the selected override mode until a new override is selected.
Away (AWAY)
If the AWAY override is selected, the 362 operates with a fixed WWSD of 62˚F (17˚C) and a fixed room temperature of 62˚F (17˚C).
BOOSTING (BOOST)
When the control changes from the enters into a to the system are raised above their normal values for a period of time to provide a faster recovery from the buildings setback temperature. The maximum length of the boost is selected in the user interface. This setting is only available if a available for a Control is used.
Typical settings for the hours for a building that has a fast responding heating system. For a building that has a slow responding heating system, a setting between four hours and eight hours is typical. After a timer must be adjusted to come out of setback some time in advance of the desired BOOST setting. If the building is not up to temperature at the correct time, the BOOST setting should be lengthened and the setback timer should be adjusted accordingly. If the building is up to temperature before the required time, the BOOST setting should be shortened and the setback timer should be adjusted accordingly. If the system is operating near its design conditions or if the supply water temperatures are being limited by settings made in the control, the time required to bring the building up to temperature may be longer than expected.
Boosting
Occupied
UnOccupied
mode. In this mode, the supply water temperatures
Characterized Heating Curve
Reset Ratio,
and not needed or available if a tekmar Zone
Boost
function vary between 30 minutes and two
Boost
time. This time in advance is normally the same as the
to the
Occupied
mode, it
is selected; It is not
time is selected, the setback
Water Temperature
UnOcc to Occ
Boost
Mix TRG
(Occupied)
Mix
TRG (UnOccupied)
Boost setting - 20 minutes to 8 hours
Time
Self Adjusting
Water Temperature
Ovr
SOFT START (SOF STRT)
The SOF STRT function allows the 362 to slowly ramp the water temperature up to the required supply temperature. By allowing the temperature in the system to be adjusted slowly, the control reduces any thermal expansion noises and stresses that may be caused by a quick change in supply water temperature.
Copyright © D 362 -12/08
8 of 36
Section B2: Alternate Mixing Demands (Mode —1—)
In addition to using conventional thermostats to provide a mixing demand as described in Section B1, the 362 can use a number of other methods to provide a mixing demand.
10K INDOOR SENSOR (10K = INDR)
Set the 10K item to INDR to add an indoor sensor for temperature control of a single zone mixing system. The indoor sensor is connected to the In addition, power must be applied to the section B1. With the indoor sensor connected, the 362 is able to sense the actual room temperature. With this information, the 362 provides a more constant water flow through the mixing system. At the same time, indoor temperature feedback fine tunes the supply water temperature in the mixing system to prevent over heating or under heating. To adjust the room temperature for the mixing zone, use the ROOM menu at the control.
10K ZONE CONTROL (10K = ZoIn)
Set the 10K item to ZoIn to add indoor temperature feedback control of multiple mixing zones. Control of mixing zones is provided by connecting a tekmar zone control to the 362. The zone control provides its own internal provide an external
Mix Demand
capable of automatically adjusting the MIX TRG temperature to improve building occupant comfort and system performance.
10K SLAB SENSOR (10K = SLAB)
Set the 10K item to SLAB to add a slab sensor for temperature control of a single zone mixing system. The 362 can use a slab sensor to control the actual slab temperature. A slab sensor is placed in the slab and connected to the be applied to the
Mix Demand
terminals (1 and 2) as described in Section B1. With the slab
sensor connected, the 362 will limit the mixing supply temperature in order to maintain the slab sensor between the SLAB MIN and SLAB MAX settings.
Slab Minimum
(SLAB MIN)
The SLAB MIN sets the minimum allowed core temperature of the slab as long as the control is not in a WWSD. Caution should be used when adjusting the SLAB MIN setting as this may lead to overheating of the zone during mild conditions. If the AWAY setting is selected in the Schedule menu, the 362 ignores the SLAB MIN setting.
Slab Maximum
(SLAB MAX)
The SLAB MAX sets the maximum allowed core temperature of the slab. If the slab is to be maintained at a fixed core temperature, set SLAB MAX and SLAB MIN items to the same setting.
ROOM TEMPERATURE UNIT (RTU) 062, 063
If the mixing system consists of a single zone, temperature control of that zone can be provided by using an RTU. The RTU is connected to the (11 and 13). In addition, power must be applied to the described in Section B1. With the RTU connected, the 362 measures the actual room temperature. With this information, the 362 provides a constant water flow through the mixing system. At the same time, indoor temperature feedback fine tunes the supply water temperature in the mixing system to prevent over heating or under heating. The RTU allows the user to adjust the desired room temperature at the RTU. Remote sensor capability is also available through an RTU as described in the RTU data brochure.
Com
and
10K
terminals (14 and 15).
Mix Demand
Occupied
terminals (1 and 2) as described in
or
UnOccupied
setting in the Adjust
mixing demand
as described earlier in Section B1. The zone control is
to the 362. In this case, there is no need to
Com
and the
10K
terminals (14 and 15). Power must
Com
and tekmar Net
Mix Demand
TM
tN1/tN2
terminals
terminals (1 and 2) as
tekmar
Indoor Sensor
tekmar
Zone Control
Power
Occupied
UnOccupied
Heat Required
Optimum Start / Stop
24 hr. Timer
System Pump
Timer Active
70°F (21°C)
12 hrs.
Zone 1 Lo stage
1
Dial the desired duration
618
of the UnOccupied period.
Press start button at the time of day
Zone 2 Hi stage
2
you want the UnOcc. period to begin. Timer Active light turns on.
Zone 3 Lo stage
3
0
24
40
100
(4)
(38)
UnOccupied
Zone 4 Hi stage
4
UnOccupied
Duration
Start
0 = always Occupied 24 = always UnOccupied
Zone Control 368
One & Two Stage
tekmar
Slab Sensor
tekmar
RTU
View
°
F
UnOcc 1
ItemMenu
tekmar
362 Control
Mix Demand
View
Boiler Demand
°
F
DHW Demand Setpoint Demand
Minimum
1
2
%
Maximum
1
DHW
Item
Menu
R
Universal Reset Control 363
NRTL/C
Mixing, Boiler & DHW
LR 58223
LR 58233
E150539
tekmar 362
Control
Mix Demand
View
Boiler Demand
°
F
DHW Demand Setpoint Demand
Minimum
2
1
%
Maximum
1
DHW
Item
Menu
R
Universal Reset Control 363
NRTL/C
Mixing, Boiler & DHW
LR 58223
LR 58233
E150539
tekmar
362 Control
Mix Demand
View
Boiler Demand
°
F
DHW Demand Setpoint Demand
Minimum
2
1
%
Maximum
1
DHW
Item
Menu
R
Universal Reset Control 363
NRTL/C
Mixing, Boiler & DHW
LR 58223
LR 58233
E150539
tekmar
362 Control
Mix Demand
View
Boiler Demand
°
F
DHW Demand Setpoint Demand
Minimum
2
1
%
Maximum
1
DHW
Item
Menu
Heat
Universal Reset Control 363
Mixing, Boiler & DHW
R
NRTL/C
LR 58223
LR 58233
E150539
Section C: Snow Melting (Mode —2—)
Section C1
General Snow
Melting
Section C2

Snow Melting

Enable / Disable
Section C3
With Slab Sensor
Section C4
Without Slab
Sensor
Section C1: General Snow Melting
The Mixing Control 362 is capable of controlling a single zone snow melting system. In order to provide the best control of the snow melting system, the 362 should be equipped with an optional tekmar Slab Sensor 072 or 073 and an optional Universal Sensor 071 that measures the slab return temperature. These can be purchased separately or as part of the Snow Melt Enable Kit 092. The Kit also includes alternate Start / Stop module 039. With these installed, the 362 is capable of providing the features listed in the following section. Also described in this section are several different methods of starting and stopping the snow melting system.
9 of 36
Copyright © D 362 -12/08
NOTE: When operating in the Snow Melting mode, the operation of the contro
SLAB PROTECTION (T MAX)
Boiler Sensor on the Return or No Boiler Sensor (
NON-DEDICATED HEAT SOURCE
If the snow melting system is one of several loads on a boiler or boiler plant, the amount of heat available to the system can potentially damage the snow melting slab. The 362 controls a mixing device that is installed between the snow melting slab and the boiler(s). The control limits the rate at which heat can be applied to the slab through the is the temperature difference between the slab supply temperature and the slab return temperature. By limiting this temperature difference, the rate at which heat is applied to the slab can be controlled and thermal stresses in the slab can be minimized. When the control is operating at the T MAX, the in the View menu. This mode of operation only works when the Boil SENS item is set to RET or NONE.
Boiler Sensor on the Supply (
DEDICATED HEAT SOURCE
If the snow melting system consists of a snow melting slab and a dedicated boiler, a mixing device is installed between the snow melting slab and the boiler to protect the boiler from low operating temperatures. In a dedicated snow melting system with a properly sized boiler, it is not necessary for the control to provide T protection of the snow melting slab; Since the boiler output is matched to the slab requirements, it is not possible to heat the slab too rapidly and cause thermal stresses that will result in damage to the slab. Therefore, the T MAX item in the When operating a dedicated snow melting system, the 362 is designed to operate the boiler as efficiently as possible. This mode of operation only works when the Boil SENS item is set to SUP.
Adjust
)
Maximum
pointer can be seen when viewing the MIX T item
)
menu and the MIX T item in the
Reset Ratio / Characterized Heating Curve DIP switch
T MAX setting. The ∆T
View
menu are not available.
has no effect on the
tensile stress
VISCOSITY COMPENSATION (EXCEEDING T MAX)
At low temperatures, the glycol solutions used in snow melting systems become very viscous and difficult to pump. In order to overcome this condition during a cold start of a snow melting system, the 362 is allowed to exceed the T MAX setting for a period of time in order to warm the glycol solution. This allows the control to compensate for the high viscosity of the glycol solution and is used when the supply temperature is below 30˚F (-1˚C). When the control exceeds the item in the
RAMPING OF THE T
When the control starts applying heat to the slab, the supply temperature to the snow melting system is ramped up over a period of time until it reaches the maximum allowed T. This function does not occur when the boiler sensor is on the supply.
OPERATING STATUS (SNOWMELT)
While in the Snow Melting mode (Mode 2), an additional item is available in the current operating status of the snow melting system.
STRT The word STRT is displayed after the snow melting system has been enabled. It is
STOP The word STOP is displayed for five seconds after the snow melting system has
IDLE The word IDLE is displayed as long as the control is operating the slab at the idling temperature.
EXT The word EXT is displayed when the RUN TIME has reached 0:00 and the control still has an external demand for melting. In
0:00 to 17:00 hr While the slab is up to temperature, and the control is melting, the remaining RUN TIME is displayed.
INF If an infinite RUN TIME is selected and the control is melting, INF is displayed.
WWSD When the control is in a Warm Weather Shut Down, WWSD is displayed.
CWCO When the control is in a Cold Weather Cut Off, CWCO is displayed
View
menu.
displayed until the slab reaches the melting temperature. If the slab is at the melting temperature, STRT is displayed for five seconds after the snow melting system has started operation. This is to verify that the control has entered into the snow melting mode.
stopped operation. The word STOP is also displayed if either a Remote Start/Stop Module 039 or Remote Display Module 040 stops the snow melting system and an external demand is still present.
this situation, the control continues melting until the snow melting demand is removed or the control is stopped.
T MAX setting, the
Maximum
View
menu called SNOWMELT. This item displays the
pointer will flash when viewing the MIX T
View
%
1
hr
Copyright © D 362 -12/08
10 of 36
RUNNING TIME (RUN TIME)
The running time is the length of time that the snow melting system operates once the slab has reached the melting temperature. During the time that the slab is approaching the melting temperature, the RUN TIME does not decrease. Once the slab has reached the melting temperature, the RUN TIME begins counting down. When the RUN TIME reaches 0:00 as displayed by the SNOWMELT item in the menu, the 362 has finished Melting.
View
WARM WEATHER SHUT DOWN (WWSD)
When both the slab temperature and the outdoor temperature exceed the Melting temperature by more than 1.5˚F (1˚C), the control enters into a WWSD. In a WWSD, the snow melting system is shut down in order to conserve energy.
COLD WEATHER CUT OUT (CWCO)
Maintaining the slab at either the Melting or Idling temperature during extremely cold temperatures can be expensive or impossible. The control shuts off the snow melting system once the outdoor air temperature drops below the Cold Weather Cut Out (CWCO) temperature. While the control is in a CWCO, the word CWCO is displayed in the SNOWMELT item in the View menu. If the control had been started prior to the CWCO, it resumes the melting mode once the outdoor air temperature rises above the CWCO temperature.
BOILER OPERATION
Refer to section D for a description of the boiler operation.
BOILER PROTECTION (Boil MIN)
The 362 ensures that the boiler supply water temperature remains above the Boil MIN setting. If the boiler supply water temperature begins to drop due to the slab return temperature, the mixing device is throttled back to allow the boiler to recover. This minimizes the time that the boiler operates below its condensing temperature and prolongs the life of the boiler. The 362 can only provide boiler protection if the Boil SENS item is set to SUP or RET. The 362 cannot provide boiler protection if the Boil SENS item is set to NONE.
SNOW MELTING OVERRIDE
Sequence, Section C2
Internal Override
If the AWAY setting is selected in the Schedule menu, the system is shut down. Both the as long as the control remains in the AWAY mode. The
External Override
While in Mode 2, any signal received on the UnO Sw and COM terminal (16 and 17) is ignored and does not affect the operation of the control.
MIXING PUMP OPERATION (Mix Pmp)
The Mixing Pump (Mix Pmp) contact closes and remains closed as long as the control is either in the Melting or Idling mode. The Mixing Pump contact shuts off if the control is in WWSD, CWCO, or if there is no call for Melting or Idling.
PURGE (PURGE)
The Mixing Pump (Mix Pmp) continues to operate for the set PURGE time after the control finishes operation.
Melting
and
Idling
temperatures are ignored
Setback / N one
DIP does not matter for internal overrides.
Section C2: Snow Melting Enable (Mode —2—)
There are three methods in which the snow melting system can be enabled on the Mixing Control 362. Either an
Remote Start / Stop Module 039
EXTERNAL DEMAND
An external snow melting demand is generated when a voltage between 24 and 240 V (ac) is applied across external demand must be present for at least 4 seconds in order to start the snow melting system. Once started, the slab temperature is increased to the MELTING setting and maintained at the melting temperature until the Run Time reaches 0:00. If the Run Time reaches 0:00 and the external demand is still present, the control continues at the melting temperature until the external demand is removed or the system is otherwise stopped.
or a
Remote Display Module 040
Mix Demand
(1 and 2) terminals. An
can be used to start the snow melting system.
24 to 240 V (ac)
11 of 36
External Demand
2
1
Mix
Demand
Copyright © D 362 -12/08
, a
Loading...
+ 25 hidden pages