The Mixing Control 360 is designed to control the supply water temperature to a hydronic system in order to provide outdoor reset or
setpoint operation. The control uses a floating action mixing valve to regulate the supply water temperature, while protecting the boiler
against flue gas condensation. The control has a Liquid Crystal Display (LCD) to view system status and operating information.
Additional Functions Include:
• Quick Setup for easy installation and programming of control
• User comfort adjustment to increase or decrease building space
temperature
• Advanced settings to fine-tune building requirements
• Boiler Control for improved energy savings
• Optional indoor sensor for room air temperature control
• Test sequence to ensure proper component operation
• Setback input for energy savings
• 120 V (ac) power supply
• CSA C US certified (approved to applicable UL standards)
• Powered mixing system pump output
To increase or decrease the
building temperature:
• Press the Item, , buttons
simultaneously for 1 sec. to
enter the ADJUST menu
Motor
Terminal
Speed
Unit
Item
Mixing Control 360
Floating Action
1 2
359 10 11
Mixing PowerBoiler
Demand
L NNOpn ClsSw
Open Close
4
Sys
Pmp
• Use the, , buttons to
Mixing
Demand
6
adjust the ROOM setting
Display defaults back to VIEW
menu after 20 sec.
Powered Output
7 8
R R CUnO Com Boil Mix Com Out Indr
Test
Made in Canada by
tekmar Control Systems Ltd.
tektra 912-02
Power: 120 V 50/60 Hz 1300 VA
Floating Output: 24 V (ac) 0.34 A 8 VA
Relays: 240 V (ac) 10 A 1/3 hp
Demand: 20 to 260 V (ac) 2 VA
Do not apply power
121314 151617 18
Installer Instructions
ROOM - Set to desired room temp.
OUTDR DSGN - Set to coldest (design)
outdoor temp.
Terminal Unit Set to
High Mass Radiant ------- 1
Low Mass Radiant ------- 2
Fan Coil ------------------ 3
Convector ---------------- 4
Radiator ------------------ 5
Baseboard --------------- 6
Refer to brochure for more information
Meets Class B:
Canadian ICES
FCC Part 15
Signal wiring must be
rated at least 300 V.
Date Code
H1170E
Note:
Mixing demand must
be powered with 20 to
260 V (ac) before the
boiler is able to fire.
This brochure is organized into four main sections. They are: 1) Sequence of Operation, 2) Installation, 3) Control Settings, and 4)
Tro ub l e s h ooting. The Sequence of Operation section has three sub-sections. We recommend reading Section A: General Operation of the Sequence of Operation, as this contains important information on the overall operation of the control. Then read the sub-sections that apply to your installation. For quick installation and setup of the control, refer to the Installation section, DIP Switch
Settings section, followed by the Quick Setup section.
The Control Settings section (starting at DIP Switch Settings) of this brochure describes the various items that are adjusted and
displayed by the control. The control functions of each adjustable item are described in the Sequence of Operation.
Table Of Contents
User Interface pg. 2
Description of Display Elements pg. 3
Sequence of Operation pg. 4
Section A: General Operation pg. 4
Section B: Mixing pg. 5
Section C: Boiler Operation pg. 8
Installation pg. 10
DIP Switch Settings pg. 14
Reference Material: Essay E 003 “Characterized Heating Curve and Reset Ratio”
Essay E 021 “Mixing Methods and Sizing of Variable Speed Injection Pumps”
Quick Setup pg. 14
Control Settings pg. 15
View Menu pg. 15
Adjust Menu pg. 16
Testing and Troubleshooting pg. 17
Error Messages pg. 19
Technical Data pg. 20
Limited Warranty pg. 20
User Interface
The 360 uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to set up and monitor the operation of your system. The 360 has three push buttons (Item, , ) for selecting, viewing, and adjusting settings. As you
program your control, record your settings in the ADJUST menu table which is found in the second half of this brochure.
Item
The abbreviated name of the selected item will be displayed in the item field of the display. To view the next available item, press and release the Item button. Once you have
reached the last available item, pressing and releasing the Item button will return the
display to the first item.
Item
Adjust
To make an adjustment to a setting in the control, press and hold simultaneously for 1
second all 3 buttons. The display will then show the word ADJUST in the top right corner.
Then select the desired item using the Item button. Finally use the and/or button to
make the adjustment.
To exit the ADJUST menu, either select the ESC item and press the
onds.
When the Item button is pressed and held in the VIEW menu, the display scrolls through all the adjust items in both access levels.
Additional information can be gained by observing the status field and pointers of the LCD. The status field will indicate which of
the control’s outputs are currently active. Most symbols in the status field are only visible when the VIEW menu is selected.
When the Mixing Control 360 is powered up, the control displays the control type number in the LCD for 2 seconds. Next, the
software version is displayed for 2 seconds. Finally, the control enters into the normal operating mode.
OPERATION
The 360 uses a floating action mixing valve to vary the supply water temperature to a hydronic system. The supply water temperature is based on either the current outdoor temperature, or a fixed setpoint.
Outdoor Reset
When the outdoor design (OUTDR DSGN) setting is not set to OFF,
the 360 calculates a mixing supply water temperature based on the
outdoor air temperature. The 360 uses a Characterized Heating Curve and optionally indoor temperature feedback from an indoor
sensor in this calculation.
When the outdoor design (OUTDR DSGN) setting is set to OFF, the
360 supplies a fixed mixing supply temperature equal to the MIX
TARGET setting. An outdoor sensor is not required during this mode
of operation.
Decreasing Outdoor Temperature
Increasing Water Temperature
FLOATING ACTION
A 24 V (ac) floating action actuator motor is connected directly to the 360 on the R Opn, R Cls, and C terminals (9,10 and 11). The
360 pulses the actuator motor open or close to maintain the correct mixed supply water temperature at the mix sensor when there
is a mixing demand. The mixing valve that the actuator is connected to can be either a 2-way, 3-way, or 4-way valve. A visual
indication as to whether the control is currently opening or closing the mixing valve is displayed in the LCD.
BOILER PROTECTION (BOIL MIN)
The 360 is capable of providing boiler protection from cold mixing
system return water temperatures. If the boiler sensor temperature
is cooler than the BOIL MIN setting while the boiler is firing, the 360
reduces the output to the mixing valve. This limits the amount of cool
return water to the boiler and allows the boiler temperature to recover.
This feature can only be used if a boiler sensor is installed.
The 360 has a built-in exercising function. If the system pump or valve has not been operated at least once every 3 days, the control
turns on the output for a minimum of 10 seconds. This minimizes the possibility of a pump or valve seizing during a long period
of inactivity. The 360 ensures that the mixing valve operates over its entire range at least once each exercising period. While the
control is exercising the Te st LED flashes.
Note: The exercising function does not work if power to the control, pump, or valve is disconnected.
SETBACK (UNOCCUPIED)
To provide greater energy savings, the 360 has a setback capability. With setback, the
supply water temperature in the system is reduced when the building is unoccupied. By
reducing the supply water temperature, air temperature in the space may be reduced
even when thermostat(s)are not turned down. Any time the UnO Sw (12)a nd th e Com
(13) terminals are shorted together, the control operates in the unoccupied (Night) mode.
When in the unoccupied (Night) mode, the UNOCC segment is displayed in the LCD. The
360 adjusts the supply water temperature based on the UNOCC settings made in the
control. This feature has no effect when the control is used as a setpoint control.
13
12
Com
UnO
Sw
Timer Switch
FACTORY DEFAULTS
The control comes preset with several factory defaults. These defaults are based on the terminal unit selection (see section B2).
To fine-tune building requirements, these defaults may be changed. If a factory default value for a terminal unit is changed, the
terminal unit number will flash when selected in the ADJUST menu.
To reload the factory defaults listed in section B2, power down the control and wait for 10 seconds. Power up the control while
simultaneously holding the Item and buttons. The terminal unit number should now be displayed constantly in the LCD rather
than flashing.
Section B: Mixing
Section B1
General
Section B2
Installer
Section B3
Advanced
Section B1: General
2
MIXING DEMAND
A mixing demand is required in order for the 360 to provide heat. A mixing demand is
generated by applying a voltage between 24 and 240 V (ac)across the Mixing Demand
terminals (1 and 2).Once voltage is applied, the Mixing Demand pointer is displayed in the
LCD. If the 360 is not in WWSD, the 360 closes the Sys Pmp contact. The 360 calculates
a MIX TARGET supply temperature based on the outdoor air temperature and settings. If
required, the 360 operates the boiler in order to provide heat to the mixing valve.
24 to 240 V (ac)
SYSTEM PUMP OPERATION (SYS PMP)
The system pump contact (Sys Pmp, terminal 5) closes whenever there is a mixing demand and the 360 is not in WWSD. The
system pump segment is displayed in the LCD. After the mixing demand has been satisfied, the 360 continues to operate the
system pump for 20 seconds. This allows some residual heat to be purged out to the heating system. During WWSD, the system
pump is operated based on the exercise function.
An indoor sensor may be used in order to provide indoor temperature feedback. The indoor sensor is connected to the Com and
Indr terminals (16 and 18). In addition, power must be applied to the Mixing Demand terminals (1 and 2) as described in the MIXING
DEMAND section. With the indoor sensor connected, the 360 is able to sense the actual room temperature. Indoor temperature
feedback fine-tunes the supply water temperature in the mixing system to maintain room temperature. To adjust the room temperature, use the ROOM OCC or ROOM UNOCC setting in the ADJUST menu at the control.
If a multiple zone system is used with an indoor sensor, proper placement of the indoor sensor is essential. The indoor sensor
should be located in an area which best represents the average air temperature of the zones.
CHARACTERIZED HEATING CURVE
When used as a mixing reset control, the 360 varies the supply water temperature based on the outdoor air temperature. The
control takes into account the type of terminal unit that the system is using. Since different types of terminal units transfer heat to a
space using different proportions of radiation, convection and conduction, the supply water temperature must be controlled differently. Once the control is told what type of terminal unit is used, the control varies the supply water temperature according to the
type of terminal unit. This improves the control of the air temperature in the building.
MIXING TARGET TEMPERATURE (MIX TARGET)
When used as a mixing reset control, the MIX TARGET temperature is calculated from the Characterized Heating Curve settings,
outdoor air temperature and optionally, indoor air temperature. When used as a setpoint control, the installer sets the MIX TARGET
temperature. The control displays the temperature that it is currently trying to maintain as the mixing supply temperature. If the
control does not have a mixing demand,”- - -” is displayed as the MIX TARGET.
Section B2: Installer
OUTDOOR DESIGN (OUTDR DSGN)
The OUTDR DSGN is the outdoor air temperature that is the typical
coldest temperature of the year where the building is located. This temperature is used when doing the heat loss calculations for the building.
If a cold outdoor design temperature is selected, the mixing supply temperature rises gradually as the outdoor temperature drops. If a warm
outdoor design temperature is selected, the mixing supply temperature
rises rapidly as the outdoor temperature drops.
SETPOINT OPERATION (MIX TARGET)
For setpoint control, set the OUTDR DSGN to OFF. The MIX TARGET
becomes the setpoint supply temperature that the control is to maintain.
The MIX TARGET temperature is set by the installer in the ADJUST
menu. An outdoor sensor is not required during this mode of operation.
ROOM OCC & UNOCC (ROOM)
The ROOM is the desired room temperature for the mixing zones, and it
provides a parallel shift of the Characterized Heating Curve. The room
temperature desired by the occupants is often different from the design
indoor temperature (MIX INDR). If the room temperature is not correct,
adjusting the ROOM setting increases or decreases the amount of heat
available to the building. A ROOM setting is available for both the occupied (Day) and unoccupied (Night) modes.