Tecfluid SC-250 User Manual

Variable Area
Flow Meter
Series
SC-250
Instructions Manual
The following users manuals are included:
AMM Limit Switch Users Manual AMD Limit Switch Users Manual TKEX Transmitter Users Manual HALLTEC III TEH, TTEH Transmitters Users Manual HALLTEC III EEx Transmitters Users Manual TP-1200 Pneumatic Transmitter Users Manual.
C-MI-09 Rev.: 4 English Version
Technical Data
Accuracy: Based on VDE / VDI 3513 ± 2,5% of full scale value. On Order: ± 1,6% of full scale value.
Rangeability: 10:1
Scale length: ~100 mm.
Scales: Direct in l/h etc. or in %.
Mounting: Vertical.
Rising flow direction.
Pipe fittings: DIN flanges. Others on order.
Materials: EN 1.4404 (AISI-316L), PVC, PTFE, PP.
Working pressure :
- SC-250 EN 1.4404 PN 40 DN 15...DN 50 PN 16 DN 65...DN 150
- SC-250 PVC / PTFE / PP PN 16 DN 15...DN 50 PN 10 DN 65...DN 150
- SC-250 EN 1.4404+PVC / PTFE / PP PN 40 DN 15...DN 40 PN 16 DN 50...DN 125
PN 10 DN 150 Others on order.
Working temper ature:
Standard:
- EN 1.4404: -50ºC...+200ºC
- PVC: 0ºC...+ 50ºC
- PTFE: -20ºC...+150ºC
With thermal separator:
Indicator housing:
Mounting length:
Conforms with the Pressure Equipment
Directive 97/23/EC. This equipment is considered as being a pressure
accessory and NOT a safety accessory as defined
!
in the 97/23/EC directive, Article 1, paragraph
2.1.3.
Optional limit switches:
• Maximum current: 3A.
• Maximum voltage: 250 Vac.
- PP: -20ºC...+ 85ºC
- EN 1.4404: -180ºC...+400ºC
IP 65, Polyamide 11 covered aluminium
DN 15...DN 125: 250 mm. DN 150: 300 mm.
- SC-AMM Micro-switch mounted in the indicator housing.
Conforms with Directive 73 / 23 / EEC (Low Voltage)
2
- SC-AMD DIN 19234 (NAMUR) vane operated inductive detector, mounted in the indicator housing.
• Nominal voltage: 8,2 Vdc
Conforms with Directive 89/336/EEC (EMC)
Optional transmitters:
- TKEX Angular position converter, coupled to the indicating system of the flow meter, which gives a linear output 0...4-20 mA proportional to the measured flow rate.
• Power supply: 12,7...36 Vdc.
• Output signal: 0...4-20 mA.
• Electrical connection: 2, 3 ó 4 wire.
Certified by PTB to EEx ia IIC T6.
- TEH3 A position transducer with
analog output for 2 or 4 wire connection.
• Power supply: 10 to 50 Vdc (2 wire) 220 Vac, 240 Vac, 110 Vac, 24 Vac
50/60 Hz (4 wire)
• Output signal: 4-20 mA. Conforms with Directives 73 / 23 / EEC
(Low voltage) and 89/336/EEC (EMC)
- TTEH3 A position transducer with analog output and totalizer for 2 or 4 wire connection.
• Power supply: 10 to 50 Vdc (2 wire) 220 Vac, 240 Vac, 110 Vac, 24 Vac
50/60 Hz (4 wire)
• Output signal: 4-20 mA. Conforms with Directives 73 / 23 / EEC
(Low voltage) and 89/336/EEC (EMC)
- TEH3/EEX A position transducer with analog output for 2 wire connection.
• Power supply: 10 to 24 Vdc
• Output signal: 4-20 mA. Conforms with Directives 89/336/EEC
(EMC) and 94 / 9 / CE (ATEX) Certified by LOM to EEx ia IIC T4
- TTEH3/EEX A position transducer with analog output and totalizer for 2 wire connection.
• Power supply: 10 to 24 Vdc
• Output signal: 4-20 mA. Conforms with Directives 89/336/EEC
(EMC) and 94 / 9 / CE (ATEX) Certified by LOM to EEx ia IIC T4
- TP1200 Pneumatic transmitter that gives an
output of 3-15 psi or 0,2-1 bar proportional to the measured flow rate.
• Air supply: 1,4 bar ±0,1 bar
g
Flow Meter Dimensions with DIN 2501 Flanges
DN-15 to DN-80
ø
DN
ø l
L
145
C max.B
ø D ø k
Serie SC-2 50
DN PN
m.Pa.s.
kg/l
C
bar
item
A
= =
160
DN-100 to DN-150
DN D k g l x nº B Flange
A C L
PN 15 95 65 45 14 x 4 16 40 116 45 250 25 115 85 68 14 x 4 18 40 124 45 250 40 150 110 88 18 x 4 18 40 130 45 250 50 165 125 102 18 x 4 20 40 136 45 250 65 185 145 122 18 x 4 18 16 140 45 250 80 200 160 138 18 x 8 20 16 148 45 250
100 220 180 158 18 x 8 20 16 156 - 250 125 250 210 188 18 x 8 22 16 168 - 250 150 285 240 212 22 x 8 22 16 182 - 300
3
Flow Meter Dimensions with CLAMP ISO 2852 Pipe Fittings
Ø D Ø B
145
250
EN 1.4404 (AISI-316L)
160
A
Nominal DN 15 15 25 40 50 65 80 100 125 150
Nominal Pipe Ø
(exterior)
21,3 (33,7) 40 51 63,5 70 88,9 114.3 139,7 168,3
Ø B 19,3 31,3 37,6 48,6 60,3 66,8 84,9 110,3 135,7 163,1 Ø D 34 50,5 50,5 64 77,5 91 106 130 155 183
A 112 116 124 130 136 140 148 156 168 182
Flow Meter Dimensions with DIN 11851 Pipe Fittings
Ø D Ø B
145
Serie SC-250
DN PN
kg/l
m.Pa.s.
C
bar
item
160
250
A
EN 1.4404 (AISI-316L)
Nominal DN 15 15 25 40 50 65 80 100 125 150
NW Fitting 20 25 40 50 65 65 80 100 125 150
Ø B 20 26 38 50 66 66 81 100 125 150 Ø D
Rd 34 x 1/8”
Rd 52 x 1/6”
Rd 65 x 1/6”
Rd 78 x 1/6”
Rd 95 x 1/6”
Rd 95 x 1/6”
Rd 110
x 1/4”
Rd 130
x 1/4”
Rd 160
x 1/4”
A 112 116 122 126 138 138 146 155 168 180
4
Rd 190
x 1/4”