Honeywell HERCULINE 2000 User Manual

5 (1)

HercuLine® 2000 Series Actuator

Installation, Operation and

Maintenance Manual

Doc. No.:

62-86-25-10

Revision:

7

Date:

7/08

Honeywell Field Solutions

Notices and Trademarks

Copyright 2008 by Honeywell

Revision 7 July 2008

Warranty/Remedy

Honeywell warrants goods of its manufacture as being free of defective materials and faulty workmanship. Contact your local sales office for warranty information. If warranted goods are returned to Honeywell during the period of coverage, Honeywell will repair or replace without charge those items it finds defective. The foregoing is Buyer's sole remedy and is in lieu of all other warranties, expressed or implied, including those of merchantability and fitness for a particular purpose. Specifications may change without notice. The information we supply is believed to be accurate and reliable as of this printing. However, we assume no responsibility for its use.

While we provide application assistance personally, through our literature and the Honeywell web site, it is up to the customer to determine the suitability of the product in the application.

CE Conformity

This product conforms with the protection requirements of the following European Council Directive: 89/336/EEC, the EMC directive and 73/23/EEC, the Low Voltage Directive. Conformance of this product with any other “CE Mark” Directive(s) shall not be assumed.

Attention

The emission limits of EN 50081-2 are designed to provide reasonable protection against harmful interference when this equipment is operated in an industrial environment. Operation of this equipment in a residential area may cause harmful interference. This equipment generates, uses, and can radiate radio frequency energy and may cause interference to radio and television reception when the equipment is used closer than 30 m to the antenna(e). In special cases, when highly susceptible apparatus is used in close proximity, the user may have to employ additional mitigating measures to further reduce the electromagnetic emissions of this equipment.

Honeywell Process Solutions

512 Virginia Drive

Fort Washington, PA 19034

HercuLink® and HercuLine® are trademarks of Honeywell

Palm is a trademark of Palm Inc.

Other brand or product names are trademarks of their respective owners.

ii

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

 

 

7/08

About This Document

Abstract

This manual describes the installation, set up, operation, maintenance, and troubleshooting of the HercuLine 2000 series actuators.

References

The following list identifies all documents that may be sources of reference for material discussed in this publication.

 

Document Title

Doc ID

 

 

 

HercuLine 2000

Series Actuator Specification

61-86-03-14

HercuLine 2000

Series Actuator Model Selection Guide

62-86-16-21

Modbus® RTU Serial Communications User Manual

51-52-25-66

Modbus® RTU Serial Communications User Manual

51-52-25-103

Configuration/Remote Calibration Interfaces for HercuLine Actuators

 

HercuLink™ User Manual

62-86-25-11

HART Communications Installation and Operations Manual

62-86-25-12

 

 

 

Contacts

World Wide Web

The following lists Honeywell’s World Wide Web sites that will be of interest to our customers.

Honeywell Organization

WWW Address (URL)

Corporate

http://www.honeywell.com

Honeywell Process Solutions

http://www.honeywell.com/ps

 

 

Telephone

Contact us by telephone at the numbers listed below.

 

Organization

Phone Number

United States and Canada

Honeywell

1-800-423-9883

Tech. Support

 

 

1-800-525-7439

Service

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

iii

7/08

 

 

Symbol Definitions

The following table lists those symbols that may be used in this document to denote certain conditions.

Symbol

Definition

This DANGER symbol indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury.

This WARNING symbol indicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury.

This CAUTION symbol may be present on Control Product instrumentation and literature. If present on a product, the user must consult the appropriate part of the accompanying product literature for more information.

This CAUTION symbol indicates a potentially hazardous situation, which, if not avoided, may result in property damage.

WARNING

PERSONAL INJURY: Risk of electrical shock. This symbol warns the user of a potential shock hazard where HAZARDOUS LIVE voltages greater than 30 Vrms, 42.4 Vpeak, or 60 Vdc may be accessible. Failure to comply with these instructions could result in death or serious injury.

ATTENTION, Electrostatic Discharge (ESD) hazards. Observe precautions for handling electrostatic sensitive devices

Protective Earth (PE) terminal. Provided for connection of the protective earth (green or green/yellow) supply system conductor.

Functional earth terminal. Used for non-safety purposes such as noise immunity improvement. NOTE: This connection shall be bonded to protective earth at the source of supply in accordance with national local electrical code requirements.

Earth Ground. Functional earth connection. NOTE: This connection shall be bonded to Protective earth at the source of supply in accordance with national and local electrical code requirements.

Chassis Ground. Identifies a connection to the chassis or frame of the equipment shall be bonded to Protective Earth at the source of supply in accordance with national and local electrical code requirements.

iv

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

 

 

7/08

Contents

Contents

Introduction .............................................................................................

1

Product Description ......................................................................................................

1

Specifications ..........................................................................................

5

Technical and Operating Specifications.......................................................................

5

Model Selection Guide ...............................................................................................

10

Installation .............................................................................................

12

Installation Overview ..................................................................................................

12

Mechanical Stops .......................................................................................................

12

Before Starting............................................................................................................

13

Actuator Mounting ......................................................................................................

13

Mechanical Installation ...............................................................................................

15

Electrical Installation...................................................................................................

17

Burner Control/Flame Safety.................................................................

23

Series 90 Control – HercuLine® 2001 model only......................................................

24

Split Range .................................................................................................................

26

Master/Slave Arrangement.........................................................................................

26

Set Up and Calibration Procedures.......................................................

31

Overview.....................................................................................................................

31

Local Display and Keypad..........................................................................................

31

Set Up Tips.................................................................................................................

33

Set Up Groups............................................................................................................

34

Set Up Procedure.......................................................................................................

36

Configuration Prompt Hierarchy .................................................................................

38

Input Set Up Group.....................................................................................................

39

Relays Set Up Group..................................................................................................

44

Current Out Set Up Group..........................................................................................

49

Communications Set Up Group..................................................................................

50

Digital Input Set Up Group .........................................................................................

51

Display Set Up Group.................................................................................................

52

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

v

7/08

 

 

Contents

Lock Set Up Group.....................................................................................................

53

Read Status Set Up Group.........................................................................................

55

Drive Set Up Group ....................................................................................................

56

Maintenance Set Up Group........................................................................................

59

Regions of Motor Travel .............................................................................................

62

CAL POSOUT Group .................................................................................................

63

Auto - Manual Drive Switch ........................................................................................

64

Calibration ..................................................................................................................

65

Setting End-of-Travel Limit Switches .........................................................................

78

Setting Auxiliary Switches ..........................................................................................

81

Start-Up/Operation ................................................................................

83

Introduction.................................................................................................................

83

Power-up Diagnostics.................................................................................................

83

Operations Checklist ..................................................................................................

83

Operating Displays .....................................................................................................

84

Motor Stall ..................................................................................................................

84

Position Sensor Operation .........................................................................................

85

Remote Setpoint Operation........................................................................................

85

Maintenance..........................................................................................

87

Introduction.................................................................................................................

87

Basic Maintenance .....................................................................................................

87

Replacement Procedures...........................................................................................

89

Replacement/Upgrade/Accessory Kits..................................................

91

Replacement Kits .......................................................................................................

91

Upgrade Kits.............................................................................................................

102

Accessory Kits ..........................................................................................................

104

Troubleshooting ..................................................................................

105

Introduction...............................................................................................................

105

Troubleshooting Procedures ....................................................................................

106

Appendix A - HercuLine® 2001/2002 Configuration Record Sheet......

112

Index ...................................................................................................

116

vi

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

 

 

7/08

 

 

Contents

 

Tables

 

Table 1 Specifications - General.............................................................................................................................

5

Table 2 Recommended Minimum Wire Size........................................................................................................

17

Table 3 Terminal Connections: HercuLine® 2000...............................................................................................

18

Table 4 Terminal Connections: HercuLine® 2001/2002 with auto/manual.........................................................

19

Table 5 Split Range Set Up Procedure .................................................................................................................

26

Table 6 Keypad Description .................................................................................................................................

32

Table 7 Set Up Tips..............................................................................................................................................

33

Table 8 Set Up Groups .........................................................................................................................................

34

Table 9 Set Up Procedure Using Display and Keypad .........................................................................................

36

Table 10 Input Set Up Group Parameters.............................................................................................................

39

Table 11 Equal Percentage Valve Characteristics ................................................................................................

42

Table 12 Quick Opening Valve Characteristic .....................................................................................................

43

Table 13 Relay Set Up Group Parameters ............................................................................................................

44

Table 14 Relay Type Descriptions........................................................................................................................

45

Table 15 Current Out Set Up Group Parameters ..................................................................................................

49

Table 16 Communications Set Up Group Parameters ..........................................................................................

50

Table 17 Digital Input Set Up Group Parameters.................................................................................................

51

Table 18 Display Set Up Group Parameters.........................................................................................................

52

Table 19 Lock Set Up Group Parameters .............................................................................................................

53

Table 20 Read Status Set Up Group Parameters ..................................................................................................

55

Table 21 Drive Set Up Group Parameters ............................................................................................................

56

Table 22 Maintenance Set Up Group Parameters.................................................................................................

59

Table 23 CAL POSOUT Group Parameters.........................................................................................................

63

Table 24 Auto - Manual Switch Functions...........................................................................................................

64

Table 25 Input Calibration Procedure...................................................................................................................

69

Table 26 Motor Calibration Procedure .................................................................................................................

70

Table 27 Output Calibration Procedure................................................................................................................

71

Table 28 Slidewire Emulation Calibration Procedure ..........................................................................................

73

Table 29

NCS Position Sensor Calibration Procedure.........................................................................................

74

Table 30

Potentiometer Position Sensor Calibration Procedure..........................................................................

76

Table 31 Load Position Sensor Factory Calibration .............................................................................................

77

Table 32 End-of-Travel Limit Switch Setting Procedure .....................................................................................

79

Table 33 Auxiliary Switch Setting Procedure ......................................................................................................

82

Table 34 Typical Operating Displays ...................................................................................................................

84

Table 35 Spur Gear Lubrication Procedure ..........................................................................................................

87

Table 36 Motor Drive Fuse Replacment Procedure .............................................................................................

89

Table 37 Relay PWA Replacement Procedure .....................................................................................................

90

Table 38 Replacement kits....................................................................................................................................

96

Table 39 Observable Symptoms of Failure ........................................................................................................

105

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

vii

7/08

 

 

Contents

Figures

Figure 1 HercuLine® 2000 Series Actuator

2

Figure 2 HercuLine® 2002 Actuator Internal View

3

Figure 3 Outline and Dimensions of HercuLine® 2000 Series Actuators

14

Figure 4 Constant Torque Linkage

15

Figure 5 Variable Torque Linkage

16

Figure 6 Standard crank arm

16

Figure 7 Crank arm with optional ball joint and push rod

16

Figure 8 HercuLine® 2000 connections

18

Figure 9 HercuLine® 2001/2002 connections

19

Figure 10 HercuLine® 2003 connections

20

Figure 11 CE wiring part 1

21

Figure 12 CE Wiring part 2

22

Figure 13 Burner Control/Flame Safety Wiring

23

Figure 14 Series 90 connections

24

Figure 15 T775 Controller connections

25

Figure 16 Flow Diagram

27

Figure 17 Interconnection Diagram

27

Figure 18 Proportional Flow Using Multiple Actuators

28

Figure 19 Multiple Actuator Interconnection Diagrams

29

Figure 20 Interconnection Diagrams

30

Figure 21 HercuLine® 2000 Display and Keypad

31

Figure 22 Relay connectors

46

Figure 23 Regions of Motor Travel

62

Figure 24 Auto - Manual Switch

64

Figure 25 Calibration Wiring Connections (non-slidewire emulation)

66

Figure 26 Calibration Wiring Connections (slidewire emulation)

67

Figure 27 Jumper Location on CPU PWA

68

Figure 28 Location of NCS Assembly

75

Figure 29 Location of potentiometer position sensor

77

Figure 30 End of Travel Limit Switch Settings

78

Figure 31 Location of End-of-Travel Limit and Auxiliary Switches

80

Figure 32 Auxiliary Switch Settings

81

Figure 33 Terminal Block Connections for Modbus Communications

86

Figure 34 Spur Gear Location

88

Figure 35 Power Distribution PWA and Relay PWA Locations

89

Figure 36 Motor Drive Circuit Fuses

90

Figure 37 Replacement Kits 6, 7, 8, 11, 12, 14

91

Figure 38 Replacement Kit 10

92

Figure 39 Replacement Kits 1, 2, 3, 4, 5, 9, 15, 16, 19

93

Figure 40 Replacement Kit 13

94

Figure 41 Replacement Kits 17, 18

95

Figure 42 Test for Actuator Operation

107

Figure 43 Power Up Diagnostics

108

Figure 44 Test Power Distribution PWA

109

Figure 45 Test AUTO - MANUAL Switch

110

Figure 46 Test Relay Function

111

viii

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

 

 

7/08

Introduction

Product Description

Introduction

Product Description

Honeywell’s HercuLine® 2000 series actuators are available in four versions: HercuLine® 2000,

HercuLine® 2001, HercuLine® 2002, and HercuLine® 2003. All are low torque, precision electric rotary actuators incorporating all of the high quality and reliable features of the traditional HercuLine series actuators. These precision control and high reliability actuators ensure processes operate at maximum efficiency, with minimal downtime, and lowest lifetime cost.

Honeywell's HercuLine® 2000 series actuators are precision engineered for exceptional reliability, accurate positioning, and low maintenance (Figure 1). Designed for very precise positioning of dampers and quarter turn valves the HercuLine® 2000 series actuators perform especially well in extremely demanding environments requiring continuous-duty, high reliability, and low maintenance.

Model distinctions

HercuLine® 2000 series actuators are used in applications requiring on/off or power to open/close position proportional with 135 or 1000 ohm feedback.

HercuLine® 2001 and 2002 are smart actuators used in applications requiring current proportional control or digital control. They offer digital electronics providing for precision positioning control, easy set-up and configuration, on board health monitoring, and network communications. Programming access is provided through our HercuLink® Palm PDA software connected to the actuator via a 232/485 converter, via HART communications or through the optional local keypad and display.

HercuLine® 2002 smart actuators offer features and functions similar to the HercuLine® 2001 and are used for more severe service applications requiring features such as non-contact position sensing.

HercuLine® 2003 actuators are unidirectional/ 360 degree rotation, special purpose actuators.

The keypad and display are available on the HercuLine® 2001 and HercuLine® 2002 products at additional charge.

HercuLink® Software

HercuLink® Computer software enables access to programming and communication functions available as standard with the HercuLine® 2001 and 2002 actuators without the added expense of the keypad & display HMI. Using a PalmPDA, laptop PC or desktop computer, HercuLink® software, and a RS232/485 converter users may configure, calibrate, and access maintenance information locally or remotely to the actuator.

Using HercuLink® software, the computer may be used as a master device over a Modbus network to access information to/from the actuators and to control the device. Set-up configurations may also be stored on the computer for download to other HercuLine® devices. Information may be stored on the users PC in CSV format for use in preventative maintenance programs.

Certified on Palmm125, m130, and m505.

Compatible with Palm OS3.5 or higher.

Compatible with Windows 2000 or XP operating systems

Minimum system requirements:

Windows 2000 (w/service pack 2), Windows NT (w/service pack 5), Windows ME, Windows XP

200 MHz Pentium with 64 Megs Ram

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

1

7/08

 

 

Introduction

Product Description

Display and

keypad

Handwheel

Conduit entry

Shaft and position indicator

Auto/manual switch

Figure 1 HercuLine® 2000 Series Actuator

2

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

 

 

7/08

Introduction

Product Description

Display

Keypad

PWA

TB3 Connector for customer input and output connection on CPU PWA

Wiring

Label

Mechanical Stops

Cams and limit switches

TB1 customer power connection

 

Non-contact

External

 

auto-manual

Relay PWAs

sensor

switch

 

 

Figure 2 HercuLine® 2002 Actuator Internal View

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

3

7/08

 

 

Introduction

Product Description

4

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

 

 

7/08

Specifications

Technical and Operating Specifications

Specifications

This section provides you with the technical specifications and the model selection guide for the HercuLine® 2000 Series Actuators.

Technical and Operating Specifications

 

Table 1 Specifications - General

 

 

 

 

 

 

 

 

 

Physical

 

 

 

Weight

2000: 25 lb. (11.36 kg)

 

 

 

 

2001,2002: 27 lbs. (12.27 kg)

 

 

 

 

 

 

 

Enclosure

Precision-machined die cast aluminum housing, finished in light gray powder coat

 

epoxy.

 

 

 

 

 

 

 

Gear Train

Alloy steel, high efficiency steel spur gear primary train. Precision ground, self-

 

locking/self releasing worm gear final mesh.

 

 

 

 

 

 

 

 

Mechanical Stops

Factory set at 90° or 150° (+/-5°).

 

 

 

 

Attention: Do not adjust the mechanical Stops. Adjusting the stops will void

 

the warranty

 

 

 

 

 

 

 

 

 

Storage Temperature

–40 °C to +93 °C (–40 °C to +200 °F)

 

 

 

 

 

 

 

Relative Humidity

0 % to 99 % R.H. non-condensing over the full operating temperature range.

 

 

 

 

 

Scale

0 % to 100 % corresponding to full crank arm travel.

 

 

 

 

 

 

Crank Arm

Adjustable radii 1.0 in (25.4mm) to a maximum of 2.8 in (71.1mm). Position

 

adjustable through 360° rotation.

 

 

 

 

 

 

 

 

Output Shaft

0.625+/-.005 in (15.88 +/-.13mm) diameter

 

 

 

 

 

 

Rotation

90° or 150° degrees between 0 % and 100 % on scale, limited by mechanical stops.

Manual Handwheel

Provides a means of positioning the actuator in the event of a power failure or set-

 

up.

 

 

 

 

 

 

 

 

 

Lubrication

Texaco Starplex 2 EP Grease

 

 

 

 

 

 

 

 

Output Torque/Full

Torque lb-in (N

 

50 Hz (90°/150°)

60 Hz (90°/150°)

Travel Stroking Time

M)

 

4.5 / 7.5

4 / 6

 

 

50 / (6.0)

 

9 / 15

7 / 12

 

 

100 / (11.5)

 

18 / 30

15 / 25

 

 

200 / (22.5)

 

36 / 60

30 / 50

 

 

 

54 / 90

 

 

400 / (45.0)

 

45 / 75

 

 

 

 

 

 

400 / (45.0)

 

 

 

 

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

5

7/08

 

 

Specifications

Technical and Operating Specifications

 

Electrical

Mains Supply

100-130 Vac single phase, 50 Hz or 60 Hz

 

200-240 Vac single phase, 50 Hz or 60 Hz

 

 

Motor

Instant start/stop, non-coasting, non-burnout, continuous duty, permanent

 

magnet, synchronous induction motor. Can be stalled up to 100 hours without

 

damage.

 

 

Motor Current

= No load = full load = locked rotor = 0.4 amp for 120Vac, 0.2 amp for 240 Vac

Loss of Power

 

Stays in place on loss of power

 

 

Local Auto/Manual Switch

Optional – Allows local and automatic operation of the actuator.

 

 

End of travel Limit

Standard – adjustable to limit actuator travel to less than 90 or 150 degrees

Switches

respectively

 

 

Auxiliary Switches/Relays

Optional – Up to 4 additional SPDT switches rated at (10 A at 125 Vac, 5 A at 250

 

Vac).

 

 

 

Certifications

Approvals

CSA/UL (Standard)

 

CE Compliant (optional)

 

 

Enclosure Rating

Type 4 (NEMA 4), IP66 (standard)

 

 

 

Torque Settings of Crank Arm Bolts

Clamp Bolt

88 lb-in (10 N-m)

 

 

Electrical and Performance Specifications

 

HercuLine® 2002

HercuLine® 2001

HercuLine® 2000/2003

Input Signals

Analog:

Analog:

 

 

0/4 to 20 mA (With CPU

0/4 to 20 mA (With CPU

120 vac drive open/120 vac

 

PWA jumper in current

PWA jumper in current

drive close

 

position)

position)

240 vac drive open/240 vac

 

 

 

 

0/1 to 5 Vdc

0/1 to 5 Vdc

drive close

 

0 to 10 Vdc

0 to 10 Vdc

 

 

Digital:

Series 90 control

 

 

Modbus RTU (RS485)

Digital:

 

 

 

Modbus RTU (RS485)

 

 

 

 

 

Isolation

Input signal, output signal and power are isolated from each other.

NA

Load Requirement (4-20)

Current Out — 0 to 1000 ohms

 

NA

Input Impedance

0/4 to 20 mA

250 ohms

NA

 

0/1 to 5 Vdc

10 K ohms

 

 

0-10 vdc

 

 

Feedback

0 to 20 mA, 4 to 20 mA

 

Dual output 1000 ohms

 

0 to 5 Vdc & 1 to 5 Vdc with 250 ohm resistor, (0 to 16 Vdc with 800

over 90 degrees (135 ohms

 

with 158 resistor)

 

ohm resistor)

 

 

 

Dual output 1000 ohms

 

 

 

 

 

 

over 150 degrees (135

 

 

 

ohms with with 158 resistor)

6

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

 

 

7/08

Specifications

Technical and Operating Specifications

 

 

 

HercuLine® 2002

 

HercuLine® 2001

HercuLine® 2000/2003

 

Feedback

Slidewire emulation - Provides

 

 

 

 

 

 

output voltage ratiometric to

 

 

 

 

 

 

shaft position and

 

 

 

 

 

 

potentiometric to supply voltage

 

 

 

 

 

 

(1 Vdc to 18 Vdc) without a

 

 

 

 

 

 

slidewire. Emulates a 100 ohm

 

 

 

 

 

 

to 1000 ohm slidewire. 10 mA

 

 

 

 

 

 

output maximum.

 

 

 

 

Communications

Modbus RTU or optional HART™

NA

 

Operating Temperature

–40°C to +75 °C (–40°F to +170 °F)

 

-40°C to +85 °C (-40°F to

 

 

 

 

 

 

+185 °F)

 

Position sensing

Non-contact position sensor

 

1000 ohm film potentiometer

Dual 1000 ohm film

 

 

 

 

 

 

potentiometers

 

 

 

 

 

 

(not on 2003)

 

Sensitivity

0.2 % to 5 % of 90° span, proportional to deadband

NA

 

Hysteresis

Less than 0.4 % of full scale

 

 

NA

 

Deadband

0.2 % to 5 % of 90° span, programmable. Shipped at 0.5 %

NA

 

Repeatability

0.2 % of 90° span

 

NA

 

Repositions

 

 

 

 

 

(minimum @ 90 or 150

 

 

 

 

 

degree stroke)

 

 

 

 

 

Table 1 option –050-

160

 

120

500

 

Table 1 option –100-

290

 

250

 

 

Table 1 option –200-

450

 

400

 

 

Table 1 option –400-

700

 

400

 

 

Table 1 option –600-

 

900

 

400

 

 

 

 

 

 

 

Voltage/ Supply

0.25 % of span with +10/–15 % voltage change

NA

 

Stability

 

 

 

 

 

Temperature

Less than ±0.030 % of span per degree C for 0 °C to 50 °C

NA

 

Coefficient

Less than ±0.05 % of span per degree C for –40 °C to 75 °C

 

 

 

 

 

 

Zero Suppression

90 % of span.

 

NA

 

Input Filters

Selectable spike and low pass filters.

NA

 

Solid State Motor

Two triac switches for clockwise or anti-clockwise motor operation.

NA

 

Control

Transient voltage protection provided.

 

 

Failsafe operation

If input signal exceeds configured input range. Selectable and

NA

 

 

 

adjustable.

 

 

 

Direction of Rotation

Field programmable

 

Wire swap

 

Duty Cycle

Continuous

 

 

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

7

7/08

 

 

Specifications

Technical and Operating Specifications

 

 

 

 

HercuLine® 2002

 

HercuLine® 2001

 

HercuLine® 2000/2003

Programmable

Selectable and configurable operating parameters:

 

NA

Functions

 

 

 

 

 

 

 

 

 

 

Input range

 

 

 

 

 

 

Input filtering

 

 

 

 

 

 

Input characterization

 

 

 

 

 

 

Security

 

 

 

 

 

 

Digital Input action

 

 

 

 

 

 

Deadband

 

 

 

 

 

 

Failsafe on loss of input signal

 

 

 

 

 

 

Failsafe on loss of position sensor

 

 

 

 

 

 

Direction of rotation

 

 

 

 

 

 

Relay closure action

 

 

 

 

 

 

Communication parameters

 

 

 

 

 

 

Split range operation

 

 

 

 

 

 

Output range

 

 

 

 

 

 

Alarms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Specifications – Local Display and Keypad

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Display

 

 

 

 

 

Display Design

 

 

Multi-segment LED displays that provides up to ten alphanumeric characters. Display

 

 

 

 

 

arrangement consists of two rows:

 

 

 

 

 

 

 

 

1st row (Upper display) – four characters

 

 

 

 

 

 

2nd row (Lower display) – six characters.

 

 

 

LED indicators

 

 

Six single LEDs provide actuator status and alarm indications.

 

 

 

 

 

 

 

 

 

 

Display Operating

 

 

-30 °C to +50 °C (-20 °F to +122 °F)

 

 

 

Temperature

 

 

Automatically shuts off when operating temperature exceeds +50 °C

 

 

 

 

 

 

 

 

 

Storage Temperature

 

 

-40 °C to +93 °C (-40 °F to +200 °F)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Keypad

 

 

 

 

 

Keys

 

 

Six single pushbutton keys allow access to all status displays and set up group

 

 

 

 

 

parameters.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

See Set Up and Calibration Procedures (page 31) for detailed information on display and keypad functions.

8

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

 

 

7/08

 

 

Specifications

 

 

Technical and Operating Specifications

 

 

 

 

 

Specifications – Communications

 

 

 

 

 

Communications

 

Communications

RS 485 Serial Communication, Modbus RTU Protocol

 

Option

 

 

 

 

 

Connection

Twisted pair cable with shield

 

 

 

 

Maximum loop length

600 meters (2000 feet)

 

 

 

 

Communication Mode

Half duplex

 

 

 

 

Baud Rate

300, 600, 1200, 2400, 4800, 9600, 19.2K

 

 

 

 

 

Required Specifications – PDA (customer provided)

 

 

 

 

 

PDA

 

Operating System

Palm OS version 3.5 or greater

 

 

 

 

RAM

At least 8 MB

 

 

 

 

Communications

Serial port with RS232 compatible levels to drive external converter

 

 

Note: As of this writing only Palm devices have this feature. Honeywell has qualified

 

 

the M105, M125, M130, and M505 devices with the HercuLink application.

 

 

 

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

9

7/08

 

 

Specifications

Model Selection Guide

Model Selection Guide

Instructions

 

Select the desired key number. The arrow to the right marks the selection available.

 

 

 

 

 

Make the desired selections from Tables I thru VIII using the column below the arrow.

 

 

 

 

 

A dot ( ) denotes unrestricted availability.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Key Number

 

I

II

 

III

IV

V

 

VI

 

VII

VIII

 

IX

 

_ _ _ _

 

-

_ _ _

-

_ _ _

-

_ _ _

-

_ _ _

-

_ _

-

_ _ _ _ _ _

-

_

-

_

-

_ _

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

KEY NUMBER - Motor Selection

 

 

 

 

 

 

 

 

 

 

Selection

 

Availability

Basic Motor Unit (no electronics)

 

 

 

 

 

 

 

 

 

 

2000

 

 

 

 

Basic Motor Unit plus Digital Electronics

 

 

 

 

 

 

 

2001

 

 

 

 

Enhanced Performance Motor Unit with Non-contact Position Sensing

2002

 

 

 

 

Unidirectional Motor (M640D Replacement)

 

 

 

 

 

 

 

2003

 

 

 

 

TABLE I - TORQUE & SPEED SELECTION (speed per 150 degree rotation)

 

 

 

 

 

 

 

Torque, lb-in/(N-M)

 

50Hz

 

 

 

 

 

60Hz

 

 

 

 

 

 

 

50 / (6.0)

 

 

 

 

7.5 sec

 

 

 

 

 

6 sec

050

 

 

 

 

 

100 / (11.5)

 

 

 

15 sec

 

 

 

 

 

12 sec

100

 

 

 

 

 

200 / 22.5)

 

 

 

30 sec

 

 

 

 

 

25 sec

200

 

 

 

 

 

400 / (45.0)

 

 

 

60 sec

 

 

 

 

 

50 sec

400

 

 

 

 

 

400 / (45.0)

 

 

 

90 sec

 

 

 

 

 

75 sec

600

 

 

 

 

 

TABLE II - ROTATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Travel

 

 

 

90 degrees

 

 

 

 

 

 

 

090

 

 

 

 

 

 

 

 

 

 

 

150 degrees

 

 

 

 

 

 

 

150

 

 

 

 

 

 

 

 

 

 

 

360 degrees

 

 

 

 

 

 

 

360

 

 

 

 

 

TABLE III - POWER SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Single Phase

100 - 130 Vac, 60 Hz

 

 

 

 

 

 

 

126

 

 

 

 

 

 

 

 

 

 

 

100 - 130 Vac, 50 Hz

 

 

 

 

 

 

 

125

 

 

 

 

 

 

 

 

 

 

 

200 - 240 Vac, 60 Hz

 

 

 

 

 

 

 

246

 

 

 

 

 

 

 

 

 

 

 

200 - 240 Vac, 50 Hz

 

 

 

 

 

 

 

245

 

 

 

 

 

TABLE IV - ANALOG INPUT/OUTPUT SIGNALS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

 

 

 

3 Wire Drive up/down

 

 

 

 

 

 

 

0 _ _

 

 

 

 

 

 

 

 

 

 

0/4-20 mA, 0/1-5 Vdc, 0-10 Vdc

 

 

 

2 _ _

 

 

 

 

 

 

 

 

 

 

0/4-20 mA, 0/1-5 Vdc, 0-10 Vdc

 

 

 

3 _ _

 

 

 

 

 

 

 

 

 

 

0 to 135 ohm input (Series 90 control)

4 _ _

 

a

 

 

 

 

 

 

 

 

Contact Input for 2003

 

 

 

 

 

 

 

6 _ _

 

 

 

 

Output

 

 

 

None

 

 

 

 

 

 

 

 

 

 

_ 00

 

 

 

 

 

 

 

 

(Note 1)

Dual 1000 Ohm (1000 ohms over 150 degrees)

_ 15

b

 

 

 

 

 

 

 

(Note 1)

Dual 1000 Ohm (1000 ohms over 90 degrees)

_ 19

c

 

 

 

 

 

 

 

 

 

Slidewire Emulation

 

 

 

 

 

 

 

_ 60

 

 

 

 

 

 

 

 

 

 

Slidewire Emulation

 

 

 

 

 

 

 

_ 65

 

 

 

 

 

 

 

 

 

 

0/4-20mAdc (0/1-5 Vdc, 0-16 Vdc)

 

 

 

_ 80

 

 

 

 

 

 

 

 

 

 

0/4-20mAdc (0/1-5 Vdc, 0-16 Vdc)

 

 

 

_ 85

 

 

 

 

TABLE V - SWITCH AND RELAY OUTPUTS (2 end-of-travel switches are standard)

 

 

 

 

 

 

 

Auxiliary Outputs

No Auxiliary Switches

 

 

 

 

 

 

 

0 _

 

 

 

 

 

 

 

 

 

 

 

2 Auxilliary Switches

 

 

 

 

 

 

 

2 _

 

 

 

 

 

 

 

 

 

 

 

4 Auxilliary Switches

 

 

 

 

 

 

 

4 _

 

 

 

 

 

Relay Outputs

No Relays

 

 

 

 

 

 

 

_ 0

 

 

 

 

 

 

 

 

 

 

 

2 Programmable Relay Outputs

 

 

 

_ 2

 

 

 

 

 

 

 

 

 

 

 

2 Programmable Relay Outputs

 

 

 

_ 3

 

 

 

 

 

 

 

 

 

 

 

4 Programmable Relay Outputs

 

 

 

_ 4

 

 

 

 

 

continued

10

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

 

 

7/08

Specifications

Model Selection Guide

 

 

 

 

 

 

2000 2001 2002 2003

TABLE VI - OPTIONS

 

 

 

 

 

Selection

Local keypad/

No local display interface supplied

(Note 2)

 

0_ _ _ _ _

display

Integrally mounted local display/keypad interface

 

1_ _ _ _ _

Local Auto/

No auto/manual switch

 

 

 

_ 0_ _ _ _

manual switch

Auto/manual switch with "Out of Auto Contact"

 

_ 1_ _ _ _

 

Auto/manual switch with "Out of Auto Contact"

 

_ 2_ _ _ _

Handwheel

No Handwheel

 

 

 

 

_ _ 0_ _ _

Certificates

Handwheel

 

 

 

 

_ _ 1_ _ _

None

 

 

 

 

_ _ _ 0 _ _

 

Certificate of Conformance

 

 

 

_ _ _ 1_ _

Approvals

UL Type 4/IP66, CSA

 

(Note 4)

 

_ _ _ _ 0_

 

CE

 

 

 

 

_ _ _ _ 1_

Shipped Rotation

Counter clockwise shaft rotation on increasing signal

_ _ _ _ _0

 

Clockwise shaft rotation on increasing signal

 

_ _ _ _ _1

TABLE VII - COMMUNICATIONS/PROTOCOL

 

 

 

 

None

No communications option board or protocol

 

0

Modbus RTU RS485

RS-485 Modbus compliant - standard with EEU

 

1

HART 5

HART Communications Protocol

 

 

 

2

TABLE VIII - MANUALS

 

 

 

 

 

Standard

English

 

 

 

 

0

TABLE IX - FACTORY OPTIONS

 

 

 

 

 

Factory Options

None

 

 

 

 

00

Restrictions

 

 

 

 

 

 

Restriction

Available Only With

Not Available With

 

Letter

Table

Selection

Table

Selection

 

a

IV

_ 00

IV

_ 60, _ 80

 

b

II

150

II

 

090

 

c

II

090

II

 

150

 

ACCESSORIES

Mounting Hardware

Mounting plate adapter for Barber Colman Series MP495

 

51452354-501

 

Mounting plate adapter for Landis & Staefa SQM53/56

 

51452354-502

 

Direct Couple Valve Hardware

 

51452354-503

 

North American Valve Retrofit Kit

 

51452354-511

Linkage Assembly

Ball joint for 5/16" dia. Pushrod

 

51452354-504

 

Pushrod 12 in. (304,5 mm) long, 5/16 " dia.

 

51452354-505

 

Pushrod 18 in. (457,2 mm) long, 5/16 " dia.

 

51452354-506

 

Pushrod 24 in. 609,6 mm) long, 5/16 " dia.

 

51452354-507

 

Pushrod 48 in. (1219,2 mm) long, 5/16 " dia.

 

51452354-508

HART

Turk Cable for Handheld Connection

 

51452352-501

Handheld Config.

HercuLinkTM Palm Software

 

51452354-509

(Note 3)

Battery powered 232/485 converter with cable

 

51452354-510

Remote Mount

Remote 4-20 mA requires 135 ohm fdbk, 120V 50/60Hz

 

R7195A1031

Control

Remote 4-20 mA requires 1000 ohm fdbk, 120V 50/60Hz

 

R7195A1056

 

Remote 4-20 mA requires 135 ohm fdbk, 220V 50/60Hz

 

R7195A1064

 

Remote 135 ohm input requires 135 ohm fdbk, 120V 50/60Hz

R7195B1021

Notes: 1. 135 ohm available by parallelling 1K potentiometer with 158 Ohm resistor (supplied).

2.HercuLinkTM software (pn 51452354-509), RS232/485 converter (pn 51452354-510), customer supplied PalmTM PDA running OS3.5 or higher and Palm serial cable are required for the 2001 and 2002 actuators if no display is selected.

3.Requires PDA manufacturer's serial interface cable.

4.CSA approval is good for 75°C and a maximum relay load of 3.5 amps or 70°C with a relay load of 5 amps.

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

11

7/08

 

 

Installation

Installation Overview

Installation

Installation Overview

The procedures to install the HercuLine® 2000 Series actuator and place it in service require that you:

Select a suitable location for installation. (See Installation Considerations below.)

Mount the actuator securely.

Install mechanical connections or linkage between control arm and final control element. Use HAL software application to aid in mechanical installation.

Make all electrical connections for actuator according to local and national electrical codes.

Power up actuator.

Enter, verify and adjust set up parameters for proper operation.

Adjust control arm linkage for accurate operation of final control element.

This section provides you with mechanical and electrical installation information required to mount and connect the HercuLine® 2000 Series Actuator to your specific application. Unpacking instructions, installation consisderations, electrical and safety precautions also included in this section should be observed.

Mechanical Stops

Factory set at 90° or 150° (+/-5°).

See Figure 2 for location.

Attention: Do not adjust the mechanical stops. Adjusting the stops will void the warranty.

12

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

 

 

7/08

Installation

Before Starting

Before Starting

Unpacking

If there are visible signs of damage to the shipping container, notify the carrier and Honeywell immediately.

If there is no visible damage, compare the contents with the packing list. Notify the carrier and Honeywell immediately if there is equipment damage or shortage.

Please do not return goods without contacting Honeywell Applications Center in advance. The contact number is 1-800-423-9883.

Installation Considerations

Mount the actuator in a location where it will be easily accessible for maintenance and for manual operation by means of the handwheel. The exact location must be determined in accordance with the linkage used.

It is important that the actuator be mounted securely to a solid foundation commensurate with the maximum torque developed. Use studs or bolts that are as large as the foot mounting holes.

Allocate sufficient clearance around the actuator for the removal of all covers to permit inspection of internal parts and to provide access to the handwheel.

Actuator Mounting

Firmly bolt the actuator to a mounting surface that will not distort when subjected to the torque stresses generated by the actuator. The output shaft of the actuator should be parallel to the output shaft of the driven device. The output shaft crank arm is fully adjustable through 360°.

Mounting holes (bottom and side) and location of shaft/crank arm duplicate mounting for Honeywell Actionators M640A, 740A, 940A for drop-in replacement. Optional adaptor plates available for replacing Landis and Staefa SQM53/56 and Barber Coleman series MP495 models.

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

13

7/08

 

 

Installation

Actuator Mounting

 

CLEARANCE FOR TOP REMOVAL:

289

101,6

11.379

4.0

 

 

25.4

1.00

mm inches

Figure 3 Outline and Dimensions of HercuLine® 2000 Series Actuators

14

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

 

 

7/08

Installation

Mechanical Installation

Mechanical Installation

Linkage Set-up

Many applications require the use of a linkage assembly and often the final control element does not have a linear torque curve. The actuator linkage can be set up to achieve an optimal delivered torque distribution for specific applications. To assist with linkage design, Honeywell offers a linkage analysis software application (HAL). The software can be ordered as P/N 51197910-001.

Constant Torque Linkage (typical)

A constant torque linkage is employed when it is desired to provide a linear torque profile throughout the full range of final control element travel. In this situation, the actuator and driven crank arms will be set-up proportionally with respect to each other. Figure 4 shows a general linkage setup to achieve a linear torque profile.

 

Vertical

 

Vertical

 

Centerline

Centerline

45°

45°

45°

45°

 

 

Linkage

 

Start

Stop

Close

Open

Drive Unit

 

Horizontal Offset

Damper

Crank Arm

 

Crank Arm

 

 

 

 

 

a/n 23199

 

Figure 4 Constant Torque Linkage

Variable Torque Linkage

A variable torque linkage is employed when it is desired to provide a non-linear torque profile throughout the full range of final control element travel. In this general situation, the actuator and driven crank arms will be set up to provide a higher torque for seating or unseating the final control element. Figure 5 shows a general linkage setup to achieve a non-linear torque profile. Note that this linkage can be characterized in many different ways by varying start angles and rotation requirements of both the Actuator Crank Arm and the Driven Arm.

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

15

7/08

 

 

Installation

Mechanical Installation

Vertical

 

Vertical

 

Centerline

 

Centerline

 

 

45°

45°

Actuator

Linkage

 

 

Crank Arm

 

 

 

 

 

 

Close

 

Open

Horizontal Offset

 

Damper

 

 

a/n 23200

Crank Arm

 

Figure 5 Variable Torque Linkage

Actuator Crank Arms

The HercuLine® 2000 Series Actuator comes standard with a crank arm with adjustable radius of 1.0 in (25.4mm) to 2.80 in (71.12mm). See Figure 6.

Figure 6 Standard crank arm

Figure 7 Crank arm with optional ball joint and push rod

16

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

 

 

7/08

Installation

Electrical Installation

Electrical Installation

General Wiring Recommendations

Only qualified personnel should perform wiring.

Wiring must conform to national and local electrical codes.

In general, copper wire used. Unless locally applicable codes dictate otherwise, the recommended minimum wire sizes in Table 2 should be observed.

 

Table 2 Recommended Minimum Wire Size

 

 

AWG

Description

14

Earth ground wire to common power supply.

18Earth ground wire to single actuator. 120/240 V ac line leads. +24 V and common signal leads. Common signal leads, relays, and aux switches.

Safety Precautions

An external disconnect switch must be installed to break all current carrying conductors connected to the actuator. Turn off power before working on conductors. Failure to observe this precaution may result in serious personal injury.

Actuator Connections

ATTENTION

The ground terminal must be connected to a reliable earth ground.

While the unit is powered, a potentially lethal shock hazard exists inside the case. Do not open the case while the unit is powered. Do not access the terminals while the unit is powered.

The actuator terminal connections for the field wiring are located behind the cover on the actuator case as shown in Figure 2. Power and field wiring is brought into the actuator through two access holes located on the side of the actuator case.

Use both openings: one for low level wiring (control signal) and the other for high level wiring (120Vac).

Do not run both the High Level and Low Level wiring through the same opening.

The screw terminals, locations, and descriptions for all customer connections are identified in the tables and figures that follow.

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

17

7/08

 

 

Installation

Electrical Installation

HercuLine® 2000 Terminal Connections

Table 3 Terminal Connections: HercuLine® 2000

Connection

Terminal Numbers

Descriptions

 

and LABEL

 

 

See Figure 8

 

Hot

1

Hot wire for 120/240VAC mains supply. Use only if Auto/Manual

 

 

switch is present.

 

 

 

Neutral

2

Neutral wire for 120/240VAC mains supply

 

 

 

Auto/Manual Switch

3

Switch contact to indicate setting of actuator AUTO/MANUAL

Contact

4

switch.

 

 

Switch is closed when actuator is “NOT-IN-AUTO”

 

 

 

CW from Controller

5

CW motor drive

 

 

 

CCW from Controller

6

CCW motor drive

 

 

 

Potentiometer #1

7

Clockwise-End

 

8

Slider

 

9

Counterclockwise-End

 

 

 

Potentiometer #2

10

Clockwise-End

 

11

Slider

 

12

Counterclockwise-End

 

 

 

Protective Ground

 

Ground wire connection for mains supply

 

 

 

158 ohm 158 ohm

Install resistors to convert 1000 ohm

 

potentiometer to 135 ohms

 

1

1 REQUIRED ONLY IF AUTO/MANUAL SWITCH IS PRESENT

Figure 8 HercuLine® 2000 connections

18

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

 

 

7/08

Installation

Electrical Installation

HercuLine® 2001/2002 with Auto/Manual Terminal Connections

Table 4 Terminal Connections: HercuLine® 2001/2002 with auto/manual

Connection

 

 

Terminal Numbers

Descriptions

 

 

 

 

 

 

 

 

and LABEL

 

 

 

 

 

 

 

 

 

 

 

 

See Figure 9

 

 

 

 

 

 

 

 

 

 

 

TB1

 

 

 

 

 

 

 

Hot

 

1

 

 

Hot wire for 120/240VAC mains supply

 

 

 

Neutral

 

2

 

 

Neutral wire for 120/240VAC mains supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protective Ground

 

3

 

 

Ground wire connection for mains supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Auto/Manual Switch

 

4

 

 

Switch contact to indicate setting of actuator AUTO/MANUAL

Contact

 

5

 

 

switch.

 

 

 

 

 

 

 

 

 

 

Switch is closed when actuator is “NOT-IN-AUTO”

 

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

TB3

 

 

 

 

 

 

 

4 to 20mA Output*

 

1

(+)

Analog signal output

 

 

 

 

 

 

2

(-)

 

 

 

 

 

 

 

 

Feedback

 

3

 

 

Feedback signal used in conjunction with 4 to 20mA OUTPUT

 

 

 

 

 

 

 

voltage when using Slidewire Emulation

 

 

 

4 to 20mA Input

 

4

(+)

Analog signal input

 

 

 

 

 

 

5

(-)

 

 

 

 

 

 

 

 

Modbus

 

6

(+)

Connection for RS485 Modbus loop wires

 

 

 

Communication

 

7

(-)

 

 

 

 

 

 

 

 

 

 

 

8

Shield

 

 

 

 

 

 

 

HART Communications

 

4

(+)

HART Communication is 4-20 mA only.

 

 

 

 

 

 

5

(-)

 

 

 

 

 

 

 

 

Digital Input

 

9

Com

Customer’s contact closure

 

 

 

 

 

 

 

10 Input

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HART

 

 

 

 

 

 

 

 

 

Communications

 

 

 

 

 

 

 

 

 

 

Connection

 

 

 

 

 

 

 

 

 

+

 

_

 

 

HART connection using

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

external Turck connector

 

 

 

 

 

 

 

 

 

Auxiliary

 

 

 

 

 

 

 

 

Connector

 

 

 

 

 

 

 

 

_

 

 

 

+

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Brown

 

Blue

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Black

 

 

 

 

 

 

 

 

 

 

 

Black Wire Not Used

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 9 HercuLine® 2001/2002 connections

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

19

7/08

 

 

Installation

Electrical Installation

HercuLine® 2003 Wiring Connections and Operation (Actionator 640D Replacement)

Wiring

Figure 10 HercuLine® 2003 connections

Operation

The 2003 actuator is uni-directional (it does not reverse rotation with a reversal in control action). Figure 10 illustrates the internal wiring and the external connections.

The smaller insert of the figure describes the limit switch action for one complete cycle. When the two-position controller detects a sufficient fall in temperature in a heating application, the switch portion between the “4” and “5” terminals will close.

The motor then rotates for 180º or until the opening switch breaks (stops are adjustable, factory set at 180º), and stops in full open position.

A subsequent rise in temperature causes the controller to close the switch between the “4” and “6” terminals when the motor will start to rotate (in the same direction) for 180º or until the closing switch breaks.

The motor stops in the closed position and completes one cycle.

20

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

 

 

7/08

Installation

Electrical Installation

Power Connections

Depending on which power supply selection is ordered for your actuator, wire the power input (MAINS POWER) as described in the previous tables and figures. Wiring must conform to national and local electrical codes.

CE Wiring

When wiring the actuator power input for CE approved units, you must also install a MOV and ferrite beads supplied with the CE unit.

You need the following tools:

5mm hex key

small flat blade screwdriver

small needle nose pliers

While the unit is powered, a potentially lethal shock hazard exists inside the case. Do not open the case while the unit is powered. Do not access the terminals while the unit is powered.

Step

Action

 

 

 

 

1Remove AC power to actuator.

2Loosen the 6 captive screws (use 5mm hex key) and remove the cover.

3Locate the terminals TB1-1, TB1-2 and ground screw.

4Loosen the screws at terminals TB1-1 and TB1-2. Remove screw used for ground.

5Install the appropriate MOV assembly as shown in Figure 11.

6All ferrites require 1 loop of wire per ferrite. Connect as shown in following steps.

7Current input and output (slidewire emulation) connection

Communications and digital input connection

Ground

 

screw

Current input

 

and output

TB1-2

(slidewire

emulation)

 

TB1-1

 

 

Communications

 

and digital input

Figure 11 CE wiring part 1

Revision 7

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

21

7/08

 

 

Honeywell HERCULINE 2000 User Manual

Installation

Electrical Installation

Step

Action

 

 

 

 

8AC power connection

Auxiliary switches connection

Relay contact connection

Aux switches 1 and 2

(SW3 and SW4)

Aux switches 3 and 4

(SW5 and SW6)

Relays 1 and 2

Relays 3 and 4

AC power connection

Figure 12 CE Wiring part 2

9 Install new gasket and top cover. Secure top cover with 6 captive screws.

10Reapply AC power to the actuator.

11Actuator is ready for use.

Input Signal Connections

ATTENTION

Shielded and grounded cables are recommended.

0/4-20 mA Input Signals

For current signal input, ensure jumper W2 on the CPU PWA is in the “Current” position. See Figure 27 on page 68. Observing polarity, connect the signal input wires TB3–4(+) and TB3–5(-) on CPU terminal board.

0/1-5 Vdc and 0 to 10 Vdc Input Signals

For voltage signal input, ensure jumper W2 on the CPU PWA is in the “Voltage” position. See Figure 27 on page 68. Observing polarity, connect the signal input wires to terminals TB3–4(+) and TB3–5(-) of the terminal block.

22

HercuLine™ 2000 Series Actuator - Installation, Operation and Maintenance Manual

Revision 7

 

 

7/08

Loading...
+ 98 hidden pages