Emerson EXD-SH1, EXD-SH2 Operating instructions

0 (0)

Operating instructions

EXD-SH1/2 Controller with ModBus communication capability for electrical control valves

G e n e r a l i nf o r ma t i o n :

EXD-SH1/2 are stand-alone superheat and or temperature controllers. EXD-SH1 is intended for operation of one bipolar electrical control valve whereas EXD-SH2 is designed for operation of two independent bipolar electrical control valves.

A table of the available application possibilities is listed below:

Controller

Circuit 1: Main function

Circuit 2: Main function

EXD-SH1

Superheat or temperature control

 

EXD-SH2

Superheat or temperature control

Superheat Control

Notes:

It is possible to use only circuit 1 from EXD-SH2. In this case, the circuit 2 must be disabled (C2 parameter) and the sensors and the valve for the second circuit are not needed.

ModBus communication is described in a Technical Bulletin and it is not covered by this document.

T e c h ni c a l d a ta :

Power supply

24VAC/DC +10%/-10% 50/60HZ,

Power consumption

EXD-SH1: 25VA

EXD-SH2: 50VA

Plug-in connector

Removable screw terminals wire size 0.14...1.5 mm2

Protection class

IP00

 

 

 

ECN-N… / TP1… (temperature range down to -45°C)

Temperature sensors

ECN-Z… (temperature range down to -80°C ultra low

 

temperature)

 

 

Allowable

 

 

 

operating/surrounding

0…+55°C

 

 

temperature

 

 

 

Maximum cable distance

50 cm

 

 

between EXD-SH and

 

 

AWG 18 wire size (≥ 1mm2)

EXD-PM

 

 

 

Pressure sensors

PT5N, PT5N-FLR or ratiometric probes

Output alarm relay current

Resistive Load 24 V AC/DC, 1 A

rating

Inductive Load 24 V AC/DC, 0.5 A

Contact is closed:

During alarm condition

 

Contact is open:

During normal operation and supply power OFF

Stepper motor output

Valves:

EX4-8 (EX4-7-FLR)

 

CV4-7

 

 

 

 

Mounting

For standard DIN rail

 

Marking

,

 

 

 

 

 

 

Warning:

EXD-SH1/2 (EXD-PM, ECP-024) has a potential ignition source and does not comply with ATEX requirements. Installation only in non-explosive environment. For flammable refrigerants only use valves and accessories approved for it!

D i me n s i o n s ( m m ) :

S a f e ty i n s tr u c t i o n s :

Read operating instructions thoroughly. Failure to comply can result in device failure, system damage or personal injury.

It is intended for use by persons having the appropriate knowledge and skill.

Before installation or service disconnect all voltages from system and device.

Do not operate system before all cable connections are completed.

Do not apply voltage to the controller before completion of wiring.

Entire electrical connections have to comply with local regulations.

Inputs are not isolated, potential free contacts needed to be used.

.

Disposal: Electrical and electronic waste must NOT be disposed of with other commercial waste. Instead, it is the user responsibility to pass it to a designated collection point for the safe recycling of Waste Electrical and Electronic Equipment (WEEE directive 2012/19/EU). For further information, contact your local environmental recycling center.

T e mp e r a t u r e s e t t i ng i n n o r ma l s e n s e

(Controller function as temperature controller)

Valve opening %

1tbd

100%

Temperature

0%

 

 

1tAL

1tst

1tAH

T e mp e r a t u r e s e t t i ng i n r e v e r s e se n s e

(Controller function as temperature controller)

Valve opening %

1tbd

100%

Temperature

0%

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1tAL

1tst/

1tAH

E l e c t r i c a l c o n ne c t i o n a n d w i r i ng :

 

 

 

Refer to the electrical wiring diagram for electrical connections.

Note: Keep controller and sensor wiring well separated from supply power cables. Minimum recommended distance 30 mm.

When connecting the wires of the EXV-M… (electrical plug of valves) consider the color coding as follows:

EXV-M…: WH: White; BK: Black; BN: Brown; BL: Blue

The digital input DI1 (EXD-SH1/SH2) and DI2 (EXD-SH2) are the interfaces between EXD-SH1/2 and upper level system controller if the Modbus communication has not been used. The external digital inputs must be free of potential (dry contact) and shall be operated in function system’s compressor/demand.

Operating condition

Digital input status

Compressor starts/run

External contact to be closed (Start)

Compressor stops

External contact to be open (Stop)

Note: Connecting any EXD-SH1/2 inputs to the supply voltage will permanently damage the EXD-SH1/2

Emerson Climate Technologies GmbH

www.climate.emerson.com/en-gb

Date: 29.07.2020

Am Borsigturm 31 I 13507 Berlin I Germany

 

EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx

Emerson EXD-SH1, EXD-SH2 Operating instructions

Operating instructions

EXD-SH1/2 Controller with ModBus communication capability for electrical control valves

Wiring options: UPS (ECP-024) /Supercap (EXD-PM)

UPS for up to two controllers

24 V

One supercap for one EXD-SH1

24VAC/

VDC

See parameter 2uP *

24 V

24 V

 

Two supercaps for one EXD-SH2

 

 

 

 

 

 

 

 

 

 

 

 

24 V

 

 

 

 

 

 

 

 

 

24 V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Warning:

 

 

 

 

 

 

 

Use a class II category transformer for 24VAC power supply. Do not ground

 

 

 

 

 

the 24VAC lines. We recommend using individual transformers for EXD-

 

 

 

 

 

SH1/2 controller and for third party controllers to avoid possible interference

 

 

 

 

 

or grounding problems in the power supply.

 

 

 

 

If EXD-PM is connected, it is mandatory to have individual transformer for

 

 

 

 

 

EXD-SH… and EXD-PM.

 

 

 

 

 

 

 

 

 

 

*) Parameter 2uP with No. 8 = only pressure

Circuit 1 (EXD-SH1/SH2)

 

14-17

Electrical control valve circuit 1 (ECV1)

 

 

 

EXV-M… Electrical plug: wire colors

sensor circuit 1 is used

Circuit 2 (EXD-SH2)

 

 

WH-white BK-black BL-blue BN-brown

 

 

 

Download/upload key

 

19-22

Electrical control valve circuit 2 (ECV2)

 

 

 

 

 

 

EXV-M… Electrical plug: wire colors

 

 

 

1 and 7

Supply voltage 24 VAC/DC

 

 

 

 

 

 

WH-white BK-black BL-blue BN-brown

 

 

 

2 and 8

Temperature sensor circuit 1

 

23 and 24

RS485 (+/-terminal)

 

 

 

 

 

 

 

 

3 and 8

Temperature sensor circuit 2

 

25 and 26

Alarm relay circuit 1 (C, NO)

Suitable for

 

 

 

 

 

 

 

24 VAC/DC

 

 

 

 

 

 

 

 

 

4 and 5

PT5N… circuit 1 & circuit 2 (white wire: 4 – 20 mA

 

27 and 28

Alarm relay circuit 2 (C, NO) –

Suitable for

 

 

 

 

signal)

 

 

24 VAC/DC

 

 

 

 

 

 

 

 

 

9

+ 12VDC Voltage input for PT5N… (brown wire)

 

29 and 30

Digital input circuit1 (DI1)

Dry contact,

 

 

 

 

 

 

 

potential free

 

 

 

 

 

 

 

 

 

Alternative ratiometric third Party Pressure Transmitter:

 

Digital input circuit 2 (DI2)

Dry contact,

 

 

 

Warning: Read the note in the last page for limitation of

 

31 and 30

 

 

 

 

potential free

 

 

 

 

 

 

 

 

 

error condition

 

 

 

 

 

 

 

 

 

 

 

 

4 and 5

Pressure transmitter circuit 1 & circuit 2

 

35 and36

Battery/Super capacitor connection terminal

 

 

 

 

(0.5 - 4.5 V signal)

 

 

 

 

 

 

 

 

 

 

 

 

11

+ 5 VDC voltage input

 

Fuse: EXD-SH1 (1A), EXD-SH2 (2A)

 

 

 

10

GND Ground

 

6,12,13,

Not used (Terminals on EXD-SH12)

 

 

 

 

18,32-34

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Emerson Climate Technologies GmbH

www.climate.emerson.com/en-gb

 

 

 

 

 

Date: 29.07.2020

Am Borsigturm 31 I 13507 Berlin I Germany

 

 

 

 

EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx

Operating instructions

EXD-SH1/2 Controller with ModBus communication capability for electrical control valves

P r e pa r a t i o n f o r S ta r t - u p :

Vacuum the entire refrigeration circuit.

Note: EX/CV valves are delivered partially open position. Do not charge system with refrigerant before closure of valve.

Apply supply voltage 24V to EXD-SH1/2 while the digital input (DI1/DI2) is open. The valve will be driven to close position.

After closure of valve, start to charge the system with refrigerant.

S e t u p o f pa r a me t e r s :

(need to be checked/modified before system start-up)

Make sure that digital input (DI1/DI2) is open. Turn on the 24V power supply to EXD-SH1/2.

Parameters Password (H5), type of function (1Fct), refrigerant type (1u0/2u0), pressure sensor type (1uP/2uP) and valve scaling (1uF/2uF) need to be set according system requirement and only when digital input DI1/DI2 is open. This feature is for added safety to prevent accidental damage of compressors and other system components.

Once the main parameters have been selected and saved, the EXD-SH1/2 is ready for startup. All other parameters can be modified at any time during operation or in system standby, if it is necessary.

D i s p l a y / ke y p a d u n i t : ( L E D s a n d b u t t o n f u nc t i o n s )

 

 

 

 

 

 

 

 

 

 

 

 

Observing operating

 

 

 

 

 

 

Observing operating

 

Circuit 1 is ON

 

 

 

 

 

 

 

 

 

parameters of

 

 

 

 

 

 

parameters of

 

 

 

 

 

 

 

 

ON: alarm

 

 

 

 

 

 

 

 

circuit2

 

 

circuit1

 

 

 

Circuit 2 is ON

 

 

OFF: no alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Upper

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lower

 

Corresponding

 

 

 

 

 

 

 

 

 

 

 

 

 

 

valve of circuit

 

 

 

 

 

 

 

 

 

 

 

 

 

Display

 

1 and or 2 is in

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

regulation

 

 

 

 

 

 

 

 

 

 

 

 

Data Display

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Change 1/2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Blinking:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Valve is opening

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameters

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setting/saving

 

Blinking:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Next parameter/

Next parameter/

 

 

 

 

 

valve is closing

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

value (higher)

value (lower)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Activating/deactivating

 

Manual Instant values

 

 

 

 

 

 

 

instant values display mode

 

display mode active

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D i s p l a y de s c r i p t i o n :

 

 

Selected main function

 

 

Superheat control

 

Temperature

 

Compressor

 

Compressor

 

control

 

ON

 

OFF

 

 

 

 

 

Upper display

Superheat (K/F)

 

Superheat (K/F)

 

Controlled

 

 

temperature

shows

 

 

 

 

 

 

(°C/F)

 

 

 

 

 

Lower display

Valve opening

 

Suction pressure

 

Valve opening

shows

(%)

 

(bar/psig)

 

(%)

Note: when Superheat value is blinking, the controller is in MOP function.

I n s t a n t v a l ue d i s pl a y mo d e :

• The controller displays the values of one circuit at a time, to change from one

circuit to the other, press

button (Function only for EXD-SH2).

• By pressing the

key, the instant value display mode can be

activated/deactivated, which allows the user to check the measured/calculated values in real time in a sequence shown as below table:

Value on upper display

Code on lower display

Superheat (K/F)

SH

Valve opening (%)

OPEn

Suction temperature (°C/°F)

tASP

Suction pressure (bar/psig)

PEuA

Saturation temperature (°C/°F)

tEuA

Software version: (0A)

SH1 or SH2

Repeating display of values

P a r a me t e r c o nf i g u r a t i o n mo d e :

The configuration of parameters is protected by a numerical password. The default password is “12”. To enter the parameter configuration:

Press both the and buttons for more than 5 seconds.

A flashing “0” is displayed in upper and “PAS” at lower.

Press until “12” is displayed; (password).

Press to confirm password.

Press or to show the code of the parameter (see table of parameter codes) that has to be accessed/changed.

Press to choose and adjust parameter value.

Press or to increase or decrease the value.

Press to temporarily confirm the new value. The selected value blinks a few times and the display shows the next available parameter code.

Repeat the procedure for other parameters if needed.

To exit and save the new settings:

When all parameters where changed press to save all the new values and exit the parameters modification procedure.

To exit and not save the new settings:

Press and to cancel the parameter modification and delete any changes made.

Another way to exit without saving the changes made at the parameters is to not press any button for at least 120 seconds (TIME OUT).

Note: While in parameter modification mode, the controller will display the parameter code on the lower display and the parameter value on the upper display.

Special manual functions: (Rest, clear)

Press both the and buttons for more than 5 seconds.

A flashing “0” is displayed.

Press until “12” is displayed; (if default password has been changed, it must select the new password)

Press to confirm password

Select the special function as explained at the parameter configuration mode

The special functions are:

Displayed Value

Code

Factory Reset

-Fdt

Clear Alarms (only manual reset)

ALrr

The default value for each variable is 0, when it set to 1 it will trigger the corresponding function.

The factory reset of the controller (-Fdt) is possible when digital input DI1/DI2 is open.

M a n u a l Va l v e o p e r a t i o n ( se r v i c e / ma i n t e n a n c e ) :

• Press for more than 5 seconds

Select, modify and save the variables like explained at the parameter configuration mode

Code

Parameter description and choices

Min

Max

Factory

Field

 

 

 

 

 

 

setting

setting

1Ho

Manual mode operation; circuit 1

0

1

 

0

 

0 = disabled

1 = Enabled

 

 

 

 

 

 

 

 

 

 

 

1HP

Valve opening (%)

0

100

 

0

 

2Ho

Manual mode operation; circuit 2

0

1

 

0

 

0 = disabled

1 = Enabled

 

 

 

 

 

 

 

 

 

 

 

2HP

Valve opening (%)

0

100

 

0

 

Note: During manual operation, functional alarms such as low superheat are disabled. It is recommended to monitor the system operation when the controller is operated manually. Manual operation is intended for service or temporary operation of valve at a specific condition. After achieving the required operation, set the parameter 1Ho and 2Ho at 0 so the controller automatically operates the valve(s) according to its setpoint(s).

Emerson Climate Technologies GmbH

www.climate.emerson.com/en-gb

Date: 29.07.2020

Am Borsigturm 31 I 13507 Berlin I Germany

 

EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx

Operating instructions

EXD-SH1/2 Controller with ModBus communication capability for electrical control valves

L i s t o f pa r a me t e r s i n sc r o l l i ng s e q ue n c e b y p r e s si n g b u t t o n :

 

Code

 

Parameter description and choices

 

 

Min

 

Max

 

 

Factory

 

 

 

 

 

 

 

setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

H5

 

Password

 

 

 

 

 

1

1999

 

12

 

Adr

 

ModBus address

 

 

 

 

 

1

 

127

 

1

 

br

 

Modbus baudrate

 

 

 

 

 

0

 

1

 

0

 

PAr

 

Modbus parity

 

 

 

 

 

0

 

1

 

0

 

-C2

 

Circuit 2 of EXD-SH2 enabled

 

 

 

0

 

1

 

1

 

 

0 =Disabled

 

 

1 = Enabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-uC

 

Units conversion

 

 

 

 

 

0

 

1

 

0

 

 

0 = °C, K, bar

 

 

1 = F, psig

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit

1 Parameters

 

 

 

 

 

 

 

 

 

 

 

 

1Fct

 

Function

 

 

 

 

 

0

 

2

 

0

 

 

0 = Superheat control

1 = Temperature

control

 

normal sense

 

 

 

2 = temperature control reverse sense

 

 

 

 

 

 

 

 

 

 

1u4

 

Control Mode

 

 

 

 

 

0

 

3

 

0

 

 

0 = standard

 

 

1 = slow

 

 

 

 

 

 

 

 

 

 

 

2 = intermediate control

 

3 = adjustable fixed PID

 

 

 

 

 

 

Refrigerant type

 

 

 

 

 

0

 

19

 

1

 

 

 

0 = R22

1 = R134a

2 = R507

 

 

 

3 = R404A

 

 

 

1u0

 

4 = R407C

5 = R410A

6 = R124

 

 

7 = R744

 

 

8 = R407A

9 = R407F

10 = R23

 

 

 

11 = R32*

 

 

 

 

 

 

 

 

 

12 = R1234ze*

13 = R448A

14 = R449A

 

15 = R450A

 

 

 

16 = R513A

17 = R290*

18 = R1270*

 

19 = R454C*

 

 

 

Pressure sensor type

 

 

 

 

0

 

8

 

1

 

1uP

 

0 = PT5N-07x

1 = PT5N-18x

2 = PT5N-30x

 

 

 

 

 

3 = PT5N-50x

4 = PT5N-150D

5 = PT5N-10P-FLR

 

 

 

 

 

 

6 = Ratio metric (gauge)

7 = Ratio metric (absolute)

8 = Modbus

 

1Prr

 

Ratio metric range (bar)

 

 

 

 

3

 

60

 

30

 

 

 

Valve type

 

 

 

 

 

0

 

12

 

0

 

1ut

 

0 = EX4-6(FLR)

1 = EX7(FLR)

2 = EX8

 

3 = N/A

4

= N/A

 

 

5 = N/A

6 = N/A

7 = N/A

8 = N/A

9 = N/A

 

 

 

 

 

 

10 = CV4

11 = CV5-6

12 = CV7

 

 

 

 

 

 

 

1uF

 

Valve scaling (%)

 

 

 

 

 

5

 

100

 

100

 

1uu

 

Start opening (%)

 

 

 

 

 

0

 

100

 

10

 

1u9

 

Start opening duration (s)

 

 

 

 

0

 

120

 

5

 

1uL

 

Low superheat alarm

 

 

 

 

0

 

2

 

1

 

 

0 = disabled

1 = enabled auto reset

 

 

 

 

 

 

 

2 = enabled manual reset

 

 

 

Alarm at 0.5K (if it maintains 1 min.); Alarm clear immediately at 3K

 

1u5

 

Superheat set point (K)

 

 

 

 

0.5

 

30

 

6

 

 

Range = 3-30 K if parameter 1uL is set to 1 or 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1u2

 

MOP function

 

 

 

 

 

0

 

1

 

1

 

 

0 = disabled

 

 

1 = Enabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MOP saturation temp (°C)

 

 

 

 

 

 

 

 

 

(see

 

1u3

 

Factory setting according to selected refrigerant

 

-

 

-

 

 

MOP

 

 

 

(1u0). The default value can be changed

 

 

 

 

 

 

 

table)

 

1P9

 

Low pressure alarm mode

 

 

 

 

0

 

2

 

0

 

 

0 = disabled

1 = enabled auto-reset

2 = enabled manual reset

 

 

 

 

 

 

1PA

 

Low pressure alarm cut-out (bar)

 

 

 

-0.8

 

17.7

 

0

 

1Pb

 

Low pressure alarm delay (s)

 

 

 

5

 

199

 

5

 

1Pd

 

Low pressure alarm cut-in (bar)

 

 

 

-0.5

 

18

 

0.3

 

1P4

 

Freeze alarm delay mode

 

 

 

 

0

 

2

 

0

 

 

0 = disabled

1 = enabled auto-reset

2 = enabled manual reset

 

 

 

 

 

 

1P2

 

Freeze alarm cut-out (°C)

 

 

 

 

-5

 

5

 

0

 

1P5

 

Freeze alarm delay (s)

 

 

 

 

5

 

199

 

 

30

 

1P-

 

Superheat control circuit1 (Kp factor)

 

 

 

0.1

 

10

 

 

1.0

 

 

 

Display 1/10K

 

 

 

 

 

 

 

 

 

 

 

 

1i-

 

Superheat control circuit1 (Ti factor)

 

 

 

1

 

350

 

100

 

1d-

 

Superheat control circuit1 (Td factor)

 

 

 

0.1

 

30

 

 

3.0

 

 

 

Display 1/10K

 

 

 

 

 

 

 

 

 

 

 

 

1uH

 

High superheat alarm mode

 

 

 

 

0

 

1

 

0

 

 

0 = disabled

 

 

1 = enabled auto-reset;

 

 

 

 

 

 

 

 

 

 

 

 

1uA

 

High superheat alarm set point (K)

 

 

 

16

 

40

 

30

 

1ud

 

High superheat alarm delay (min)

 

 

 

1

 

15

 

3

 

1tSt

 

Temperature control set point (°C)

 

 

 

-80

 

50

 

4

 

1tbd

 

Temperature band (K)

 

 

 

 

1

 

10

 

 

2

 

1tAF

 

Temperature alarm mode

 

 

 

 

0

 

1

 

0

 

 

0 = disabled

 

1 = enabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1tAL

 

Min. temperature alarm set point (°C)

 

 

 

-50

 

50

 

0

 

1tdL

 

Min. temperature alarm delay (min)

 

 

 

1

 

10

 

3

 

1tAH

 

Max. temperature alarm set point (°C)

 

 

-50

 

50

 

15

 

1tdH

 

Max. temperature alarm delay (min)

 

 

 

1

 

10

 

3

 

1tt

 

Temperature sensor type

 

 

 

 

0

 

1

 

0

 

 

0 = ECN-Nxx (-45…+40°C) / TP1-…(-45…+150°C)

 

 

 

 

 

 

 

 

 

 

1 = ECN-Z... ( -80…-40°C) for R23

 

 

 

 

 

 

 

 

 

 

Code

 

Parameter description and choices

 

 

Min

 

Max

 

 

Factory

 

 

 

 

 

 

 

setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit

2 Parameters (only EXD-SH2)

 

 

 

 

 

 

 

 

 

 

 

2u4

 

Control Mode

 

 

 

 

 

0

3

 

0

 

 

0 = standard

 

 

1 = slow

 

 

 

 

 

 

 

 

 

 

 

2 = intermediate control

 

3 = adjustable fixed PID

 

 

 

 

 

 

Refrigerant type

 

 

 

 

 

0

19

 

1

 

 

 

0 = R22

1 = R134a

 

2 = R507

 

 

3 = R404A

 

 

 

2u0

 

4 = R407C

5 = R410A

 

6 = R124

 

7 = R744

 

 

8 = R407A

9 = R407F

 

10 = R23

 

 

 

11 = R32*

 

 

 

 

 

 

 

 

 

 

12 = R1234ze*

13 = R448A

 

14 = R449A

 

15 = R450A

 

 

 

16 = R513A

17 = R290*

 

18 = R1270*

 

19 = R454C*

 

 

 

Pressure sensor type

 

 

 

 

0

9

 

1

 

2uP

 

0 = PT5N-07x

1 = PT5N-18x

2 = PT5N-30x

 

 

 

 

 

3 = PT5N-50x

4 = PT5N-150D

5 = PT5N-10-FLR

 

 

 

 

 

6 = Ratio metric (gauge)

 

 

7 = Ratio metric (absolute)

 

 

 

8 = Modbus

9 = Pressure sensor circuit1 is used (1uP)

 

 

 

 

2Prr

 

Ratio metric range (bar)

 

 

 

 

3

 

60

 

 

30

 

 

 

Valve type

 

 

 

 

 

0

12

 

0

 

2ut

 

0 = EX4-6(FLR)

1 = EX7(FLR)

2 = EX8

 

3 = N/A

4

= N/A

 

 

5 = N/A

6 = N/A

 

7 = N/A

8 = N/A

9 = N/A

 

 

 

 

 

 

 

10 = CV4

11 = CV5-6

 

12 = CV7

 

 

 

 

 

 

 

2uF

 

Valve scaling (%)

 

 

 

 

 

5

100

 

100

 

2uu

 

Start opening (%)

 

 

 

 

 

0

100

 

10

 

2u9

 

Start opening duration (s)

 

 

 

 

0

120

 

5

 

2uL

 

Low superheat alarm

 

 

 

 

0

2

 

1

 

 

0 = disabled

1 = enabled auto reset

2 = enabled

manual

reset

 

 

 

Alarm at 0.5K (if it maintains 1 min.); Alarm clear immediately at 3K

 

2u5

 

Superheat set point (K)

 

 

 

 

0.5

30

 

6

 

 

Range = 3-30K if parameter 2uL is set to 1 or 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2u2

 

MOP function

 

 

 

 

 

0

1

 

1

 

 

0 = disabled

 

 

1 = Enabled

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MOP saturation temp (°C)

 

 

 

 

 

 

 

 

 

(see

 

2u3

 

Factory setting according to selected refrigerant

 

-

 

-

 

 

MOP

 

 

 

(2u0). The default value can be changed

 

 

 

 

 

 

 

table)

 

2P9

 

Low pressure alarm mode

 

 

 

 

0

2

 

0

 

 

0 = disabled

1 = enabled auto-reset

2 = enabled manual reset

 

 

 

 

2PA

 

Low pressure alarm cut-out (bar)

 

 

 

 

-0.8

17.7

 

0

 

2Pb

 

Low pressure alarm delay (s)

 

 

 

 

5

199

 

5

 

2Pd

 

Low pressure alarm cut-in (bar)

 

 

 

 

-0.5

18

 

0.3

 

2P4

 

Freeze alarm delay mode

 

 

 

 

0

2

 

0

 

 

0 = disabled

1 = enabled auto-reset

2 = enabled manual reset

 

 

 

 

2P2

 

Freeze alarm cut-out (°C)

 

 

 

 

-5

5

 

0

 

2P5

 

Freeze alarm delay (s)

 

 

 

 

5

 

199

 

 

30

 

2P-

 

Superheat control circuit2

 

 

 

 

0.1

10

 

1.0

 

 

 

(Kp factor), fixed PID

Display 1/10K

 

 

 

 

 

 

 

 

2i-

 

Superheat control circuit2 (Ti factor),

 

 

 

1

 

350

 

 

100

 

 

 

fixed PID

 

 

 

 

 

 

 

 

 

 

 

 

2d-

 

Superheat control circuit2

 

 

 

 

0.1

30

 

3.0

 

 

 

(Td factor), fixed PID

Display 1/10K

 

 

 

 

 

 

 

 

2uH

 

High superheat alarm mode

 

 

 

 

0

1

 

0

 

 

0 = disabled

 

 

1 = enabled auto-reset;

 

 

 

 

 

 

 

 

 

 

 

 

2uA

 

High superheat alarm set point (K)

 

 

 

16

40

 

30

 

2ud

 

High superheat alarm delay (min)

 

 

 

1

15

 

3

 

2tt

 

Temperature sensor type

 

 

 

 

0

1

 

0

 

 

0 = ECN-Nxx (-45…+40°C) / TP1-…(-45…+150°C)

 

 

 

 

 

 

 

 

 

 

1 = ECN-Z60 ( -80°C…-40°C) for R23

 

 

 

 

 

 

 

 

 

*)

Warning -Flammable refrigerants:

 

 

 

 

 

 

 

 

 

EXD-SH1/2 (EXD-PM, ECP-024) has a potential ignition source and does not comply with ATEX requirements. Installation only in non-explosive environment. For flammable refrigerants only use valves and accessories approved for it!

MOP default value table:

Refrigerant

Default (C°)

Refrigerant

Default (C°)

Refrigerant

Default (C°)

R22

+13

R744

-5

R449A

+12

R134a

+15

R407A

+10

R450A

+19

R507

+7

R407F

+10

R513A

+13

R404A

+7

R23

-40

R290

+15

R407C

+15

R32

+15

R1270

+15

R410A

+15

R1234ze

+24

R454C

+17

R124

+50

R448A

+12

 

 

Emerson Climate Technologies GmbH

www.climate.emerson.com/en-gb

Date: 29.07.2020

Am Borsigturm 31 I 13507 Berlin I Germany

 

EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx

Operating instructions

EXD-SH1/2 Controller with ModBus communication capability for electrical control valves

C o n t r o l ( v a l v e ) s t a r t - u p be h a v i o r f a c to r y se t t i n g s

(1uu + 1u9) / (2uu +2u9)

EX4/5/6 ≤ 5.3 Seconds

EX7 ≤ 5.6 Seconds

EX8 ≤ 5.9 Seconds

CV4 ≤ 5.3 Seconds

CV5/6 ≤ 5.3 Seconds

CV7 ≤ 6.6 Seconds

U p l o a d / do w nl o a d K e y : F un c t i o n

For serial production of systems/units, upload/download key allows the transmission of configured parameters among range of identical systems.

Uploading procedure (storing configured parameters in key):

Insert the key while the first (reference) controller is ON and press button; the “uPL” message appears followed by “End” message for 5 seconds.

Note: If the “Err” message is displayed for failed programming, repeat the

E r r o r / A l a r m h a n d l i ng :

above procedure.

Downloading procedure (configured parameters from key to other controllers):

Turn off power to new controller.

Insert a loaded Key (with stored data from reference controller) into new controller and turn on the power supply.

The stored parameters of the key will be downloaded automatically into the new controller memory; The “doL” message appears followed by a “End” message for 5 seconds.

The new controller with new loaded parameters setting will start to operate after “End” message disappears.

Remove the key.

Note: If the “Err” message is displayed for failed programming, repeat the above procedure.

Alarm

Description

Related

Alarm

Valve

 

Requires clear

What to do?

alarm after

code

parameter

relay

 

 

resolving alarm

 

 

 

 

 

 

1E0/2E0

Pressure sensor circuit 1/2 error

-

Triggered

Fully close

Check wiring connection and measure the signal.

No

1E1/2E1

errorTemperature sensor circuit 1/2

-

Triggered

Fully close

Check wiring connection and measure the resistance of sensor.

No

1Π/2Π

Valve Circuit 1/2 electrical

-

Triggered

-

Check wiring connection and measure the resistance of winding.

No

connection error

AFE 1/2

Freeze protection circuit 1/2

1P4/2P4:1

Triggered

Fully close

Check the system for cause of low pressure such as insufficient load on

No if it is ON

AFE 1/2

1P4/2P4:2

Triggered

Fully close

Yes if it is blinking

 

evaporator.

LSH 1/2

Low superheat

1uL/2uL:1

Triggered

Fully close

Check wiring connection and operation of valve.

No if it is ON

LSH 1/2

1uL/2uL:2

Triggered

Fully close

Yes if it is blinking

(<0,5K)

 

tAL1

Min. temperature alarm

1tAL

Triggered

Fully close

Check wiring connection, operation of valve, size of valve and load.

No

tAH1

Max. temperature alarm

1tAH

Triggered

Fully close

No

HSH 1/2

High superheat circuit 1/2

1uH/2uH:1

Triggered

Operating

Check the system.

No

LOP 1/2

Low pressure circuit 1/2

1P9/2P9 1

Triggered

Operating

Check the system for cause of low pressure such as refrigerant loss.

No if it is ON

LOP 1/2

1P9/2P9 2

Triggered

Operating

Yes if it is blinking

 

 

Err

Failed

-

-

-

Repeat again the procedure for uploading/downloading.

No

uploading/downloading

 

 

 

 

 

 

ACEr

 

 

 

 

Check Modbus communication. Note: Modbus alarm (ACEr) detection is

 

Modbus Timed Out

-

-

-

active only when the pressure sensor type is configured to be Modbus type

No

 

 

 

 

 

and the corresponding circuit is on demand.

 

PFA

Power failure alarm

-

Triggered

Fully close

When the controller is connected to the battery supply and power supply

No

interrupted, this alarm code will be displayed while the valve is closing.

ACF1 or ACF2: Alarm code (circuit1/2) for “not permitted configuration/ selection” Alarm will be displayed for the following cases:

If two circuits of the EXD-SH2 are connected to two different type of pressure transducers i.e. 4-20 mA and 0-5 V. It is mandatory that two circuits always are connected to the same type of pressure transmitter technology.

Temperature control function is possible only with EX4-8 series valves. If other valves are used, then the ACF alarm will be displayed.

Ratiometric pressure transmitters cannot be selected in conjunction with R744.

Notes:

S e r v i c e / T r o u bl e s ho o ti n g :

When several alarms are present, the alarms will be shown one after the other on the lower display.

Pressure sensor error for third party ratiometric pressure transmitters is based on detection of interruption of two wires (5 V and signal 0.5 - 4.5 V). If only third wire (ground) is open/ interrupted, no error can be detected and controller will receive a false signal between 50% and 100% higher. This false signal leads to improper operation of EXD-SH1/2 controller and can lead to system/compressor damage. EMERSON is not responsible in such cases.

Symptom

Cause

Action

Operating superheat is several degrees higher or

Incorrect signal from pressure or temperature

1- Check the sensors (see list of parameters)

lower than set-point

sensors

2- Make sure the sensor cables are not installed along with other high voltage

 

 

cables

Operating superheat is too low i.e. compressor wet

1- Incorrect wiring of ECVs

1- Check the wiring

running

2- Defective sensors

2- Check the sensor

Valve is not fully closed

1- The digital input is ON

1- Valve is shut off only when the digital input is turned off.

 

2- Wrong setting of parameter ut.

2- Check the setting of parameter ut.

Instable superheat (hunting)

Evaporator is designed to operate at higher

Increase the superheat set-point.

 

superheat

 

Valve opens when EXD commands to close and

Wrong wiring between EXD-SH... and valve

Correct the wiring.

vice versa

 

 

EX8 is not able to open at high differential

Wrong setting of parameter ut

Check the parameter ut. (Larger valve requires higher torque and higher

pressure

 

current)

Superheat set-point is shifting after several months

Stepper motor driven valves require

Do not jumper digital input permanently. Interrupt digital input once every

of uninterrupted operation or permanent jumper of

synchronization

week for 10 seconds if compressor never stops.

24 V digital input

 

 

Emerson Climate Technologies GmbH

www.climate.emerson.com/en-gb

Date: 29.07.2020

Am Borsigturm 31 I 13507 Berlin I Germany

 

EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx

Betriebsanleitung

EXD-SH1/2 Regler mit ModBus Kommunikation für elektrische Regelventile

B e s c h r e i b u n g :

EXD-SH1/2 eigenständige Überhitzungsund Temperaturregler. Der EXD-SH1 ist für ein bipolares elektrisches Regelventil aus den Serien EX/CV, der EXD-SH2 für zwei getrennt arbeitende Ventile.

Folgende Anwendungen sind möglich:

Regler

Regelkreis 1

Regelkreis 2

EXD-SH1

Überhitzungsoder Temperaturregelung

 

EXD-SH2

Überhitzungsoder Temperaturregelung

Überhitzungsregelung

Hinweis:

Es ist möglich nur den Kreislauf 1 vom EXD-SH2 zu verwenden. In diesem Falle muss der Kreislauf 2 über den Parameter C2 abgeschaltet werden; Ventil und Sensoren brauchen nicht angeschlossen werden.

Die ModBus Kommunikation ist im Technical Bulletin beschrieben und nicht Teil dieses Dokuments.

T e c h ni s c h e D a te n :

Versorgungsspannung

24VAC/DC +10%/-10% 50/60 Hz,

Leistungsaufnahme

EXD-SH1: 25 VA

EXD-SH2: 50 VA

Steckerverbindung

Abnehmbare Schraubklemmen für Kabelquerschnitte

von 0,14 bis 1,5 mm2

 

Schutzklasse

IP00

 

 

ECN-N… / TP1…

 

Temperaturfühler

(Temperaturbereich bis

-45°C)

ECN-Z… (Temperaturbereich bis -80°C,

 

 

Tieftemperatur)

 

Zulässige

 

 

Umgebungstemperatur bei

0…+55°C

 

Betrieb

 

 

Maximale Kabellänge

50 cm

 

zwischen EXD-SH und

 

AWG 18 adrig, Querschnitt (≥ 1 mm2)

EXD-PM

 

 

Drucktransmitter

PT5N, PT5N-FLR oder ratiometrische Sensoren

Belastbarkeit Alarm-Relais

Resistive Load 24 V AC/DC, 1 A

Inductive Load 24 V AC/DC, 0,5 A

 

Kontakt geschlossen:

Während Alarm

 

Kontakt offen:

Während Normalbetrieb und AUS

Versorgungsspannung

 

 

 

Schrittmotorausgang

Ventile: EX4-8 (EX4-7-FLR), CV4-7

Montage

Standard Schienenmontage

Kennzeichnung

,

 

 

 

 

 

 

Warnung:

EXD-SH1/2 (EXD-PM, ECP-024) hat eine potentielle Zündquelle und entspricht nicht den ATEX Bestimmungen. Installation nur in nicht explosionsgefährdeter Umgebung. Für brennbare Kältemittel nur Ventile und Zubehörteile, die dafür zugelassen sind verwenden!

A b me s s u n g e n ( m m ) :

S i c h e r h e i t s h i nw e i s e :

Lesen Sie die Betriebsanleitung gründlich. Nichtbeachtung kann zum Versagen oder zur Zerstörung des Gerätes und zu Verletzungen führen.

Der Einbau darf nur von Fachkräften vorgenommen werden.

Der Kältekreislauf darf nur in drucklosem Zustand geöffnet werden.

Die Anlage erst in Betrieb nehmen, wenn alle Kabelverbindungen vollständig sind.

• Die Anlage darf erst dann in Betrieb genommen werden, wenn alle Verbindungen hergestellt sind.

Für den gesamten elektrischen Anschluss sind die länderspezifischen Vorschriften einzuhalten.

Digitaleingänge sind spannungsbehaftet; nur potentialfreie Schaltkontakte verwenden.

Entsorgung: Elektround Elektronik-Altgeräte dürfen nicht mit anderen Gewerbemüll entsorgt werden. Stattdessen ist es in der Verantwortung Benutzer es zu einem Sammelpunkt für die sichere Entsorgung von Elektround ElektronikAltgeräte (WEEE-Richtlinie 2012/19/EU) zu übergeben. Für weitere Informationen kontaktieren Sie bitte Ihren örtlichen Recyclinghof.

T e mp e r a t u r e i n s t e l l u n g e n D i r e kt - P r o p o r t i o na l b e tr i e b

(Temperatur-Regelmodus)

Ventilöffnung %

1tbd

100%

Temperatur

0%

1tAL

1tst

 

 

1tAH

T e mp e r a t u r e i n s t e l l u n g e n In d i r e kt - P r o p o r t i o na l b e tr i e b

(Temperatur-Regelmodus)

Ventilöffnung %

1tbd

100%

Temperatur

0%

 

 

1tAL

1tst/

1tAH

E l e kt r i s c h e r A n s c h l u s s u n d V e r d r a h t u n g :

Den elektrischen Anschluss gemäß Verdrahtungsschema durchführen!

Hinweis: Signalleitungen und Leitungen mit Netzspannung in getrennten Kabelschächten verlegen, Mindestabstand 30mm.

Bei Anschluss von EXV-M… (Ventilstecker) muss die Farbe der Adern wie

folgt berücksichtigt werden:

EXV-M…: WH: Weiß; BK: Schwarz; BN: Braun; BL: Blau

Die Digitaleingänge DI1 (EXD-SH1/SH2) und DI2 (EXD-SH2) sind die Schnittstellen zwischen EXD-SH1/2 und dem übergeordnetem Systemregler, wenn keine Modbus Kommunikation eingesetzt wird. Die externen Schaltkontakte müssen potentialfrei sein (dry contact) und entsprechend der Systemanforderung angesteuert werden.

Betriebszustand

Status Digitaleingang

Verdichter startet/läuft

Externe Schaltkontakte schließen (Start)

Kompressor stoppt

Externe Schaltkontakte öffnen (Stopp)

Hinweis: Das Aufschalten von externer Spannung auf die Digitaleingänge führt zur dauerhaften Beschädigung des EXD-SH1/2.

Emerson Climate Technologies GmbH

www.climate.emerson.com/en-gb

Date: 29.07.2020

Am Borsigturm 31 I 13507 Berlin I Germany

 

EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx

Betriebsanleitung

EXD-SH1/2 Regler mit ModBus Kommunikation für elektrische Regelventile

EXV-M…

EXV-M…

Kabel &

Kabel &

Stecker

Stecker

EXD-M…

Kabel & Stecker

24VAC/

VDC

Temperaturfühler

ECN-N…/ Siehe Parameter 2uP

TP1-…/

ECN-Z…

Drucktransmitter PT5N-…

Möglichkeiten Verdrahtung: UPS (ECP-024) /Supercap (EXD-PM)

UPS für bis zu zwei Controller

Ein Supercap für ein EXD-SH1

Zwei Supercaps für ein EXD-SH2

Warnung:

Für die 24V Stromversorgung sind ausschließlich Transformatoren der Klasse II zu verwenden. Die 24V Leitungen dürfen nicht geerdet werden. Wir empfehlen die Verwendung jeweils separater EMERSON Transformatoren für EXD-SH1/2 Regler und die Regler anderer Hersteller, weil unter Umständen über die Erdleitungen Kurzschlüsse entstehen können.

Wenn EXD-PM angeschlossen ist, ist es notwendig, dass der EXD-SH-Regler und die EXD-PM-Kondensatoren eigene Transformatoren haben.

Kreislauf 1 (EXD-SH1/SH2)

 

14-17

Elektrisches Regelventil Kreislauf 1 (ECV1)

*) Parameter 2uP mit Nr. 8 = nur

 

 

 

EXV-M… elektr. Stecker: Adernfarben

Drucksensor von Kreislauf 1 genutzt

Kreislauf 2 (EXD-SH2)

 

 

 

WH-weiß BK-schwarz BL-blau BN-braun

 

Kopierschlüssel

 

19-22

Elektrisches Regelventil Kreislauf 2 (ECV2)

 

 

 

 

EXV-M… elektr. Stecker: Adernfarben

 

1 & 7

Versorgungsspannung 24 VAC/DC

 

 

 

 

WH-weiß BK-schwarz BL-blau BN-braun

 

2 & 8

Temperaturfühler Kreislauf 1

 

23 & 24

RS485 (+/-Klemmen)

 

 

 

3 & 8

Temperaturfühler Kreislauf 2

 

25 & 26

Alarmrelais Kreislauf 1 (C, NO)

geeignet für

 

 

24 VAC/DC

 

 

 

 

 

 

 

 

 

 

4 & 5

PT5N… Kreislauf 1 & Kreislauf 2

 

27 & 28

Alarmrelais Kreislauf 2 (C, NO) –

geeignet für

 

(weiße Ader: 4 – 20 mA Signal)

 

24 VAC/DC

 

 

 

 

 

 

 

 

 

9

+ 12 VDC Spannungseingang für PT5N… (braune

 

29 & 30

Digitaleingang Kreislauf (DI1) –

für potentialfreie

 

Ader)

 

Kontakte

 

 

 

 

 

 

 

 

 

Alternative ratiometrische Drucktransmitter v.

 

 

 

 

 

 

Drittanbietern:

 

31 & 30

Digitaleingang Kreislauf 2 (DI2)

für potentialfreie

 

Warnung: Beachten sie die Einschränkungen betreffend der

Kontakte

 

 

 

Fehlerzustände auf der letzten Seite

 

 

 

 

 

 

4 & 5

Drucktransmitter Kreislauf 1 & Kreislauf 2

 

35 & 36

Batterie/ Power Modul Anschluss

 

 

(0,5 - 4,5 V Signal)

 

 

 

 

 

 

 

 

 

 

11

+ 5 VDC Spannungseingang

 

Sicherung EXD-SH1 (1A), EXD-SH2 (2A)

 

10

GND Erdung

 

6,12,13,

Nicht verwendet (Terminals on EXD-SH12)

 

 

18,32-34

 

Emerson Climate Technologies GmbH

www.climate.emerson.com/en-gb

 

 

Date: 29.07.2020

Am Borsigturm 31 I 13507 Berlin I Germany

 

 

EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx

Betriebsanleitung

EXD-SH1/2 Regler mit ModBus Kommunikation für elektrische Regelventile

V o r b e r e i t u n g e n f ür d i e I nb e t r i e b na h me :

Gesamten Kältekreislauf evakuieren.

Hinweis: Die Elektrischen Regelventile EX/CV werden halb geöffnet ausgeliefert. Den Kältekreislauf nur bei geschlossenem Ventil mit Kältemittel füllen.

Die 24V Versorgungsspannung des EXD-SH1/2 einschalten, während die Digitaleingänge (DI1/DI2) offen sind. Das Ventil wird schließen.

Bei geschlossenem Ventil System mit Kältemittel füllen.

P a r a me t e r e i n s te l l u n g :

(müssen vor dem Starten geprüft und bei Bedarf angepasst werden)

Stellen sie sicher, dass die Digitaleingänge (DI1/DI2) offen sind. Schalten sie die 24V Spannungsversorgung des EXD-SH1/2 ein.

Wenn die Digitaleingänge DI1/DI2 offen sind, müssen die Parameter Passwort (H5), Funktion (1Fct), Kältemittel (1u0/2u0), Drucksensortyp (1uP/2uP) und Regelbereich (1uF/2uF) entsprechend den Systemanforderungen eingestellt werden. Dies ist eine Sicherheitsmaßnahme um zu verhindern, dass versehentlich am Verdichter und an anderen Komponenten Schäden entstehen.

Sobald die wichtigsten Parameter eingestellt und gespeichert sind, ist der Regler EXD-SH1/2 fertig für die Inbetriebnahme. Alle anderen Parameter könne auch während des Betriebes oder im Stand-By Modus verändert werden.

A n z e i g e / T a s t a t u r ( L E D s a n d T e s t e nf u n kt i o n e n )

 

 

 

 

 

 

 

 

 

 

 

Anzeige Parameter

 

 

 

 

 

 

 

Anzeige Parameter

 

Kreislauf 1 ist AN

 

 

 

 

 

 

 

 

 

Kreislauf 2 aktiv

 

 

 

 

 

 

 

Kreislauf 1 aktiv

 

 

 

 

 

 

 

AN: Alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Kreislauf 2 ist AN

 

 

 

 

AUS: kein Alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

oberes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Anzeigefeld

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Regelbetrieb

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

unteres

 

Ventil 1 bzw 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Anzeigefeld

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Anzeigen-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

wechsel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Kreislauf 1

 

Blinkt:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

bzw. 2

 

Ventil geöffnet

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Einstellung/

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Speicherung

 

 

Blinkt:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Nächster

 

 

Nächster

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Ventil schließt

 

 

 

 

Parameter/Istwert

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Parameter/Istwert

 

 

 

 

 

 

 

 

 

(Aufwärts)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Abwärts)

 

 

 

 

 

 

 

 

 

 

 

 

 

Istwertanzeigemodus

ist

 

 

 

 

 

 

Aktivierung/Deaktivierung

 

 

 

 

 

 

 

 

 

Istwertanzeigemodus

 

 

manuell aktiviert

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A n z e i g e B e sc h r e i b u n g :

 

 

Gewählte Hauptfunktion

 

 

Überhitzungsregelung

 

Temperatur-

 

Verdichter

 

Verdichter

 

regelung

 

AN

 

AUS

 

 

 

 

 

Oberes

Überhitzung

 

Überhitzung

 

Isttemperatur

Anzeigefeld

(K/F)

 

(K/F)

 

(°C/F)

Unteres

Ventilöffnung

 

Saugdruck

 

Ventilöffnung

Anzeigefeld

(%)

 

(bar/psig)

 

(%)

Hinweis: Wenn der Überhitzungswert blinkt ist der Regler im MOP Betrieb.

I s t w e r t a n z e i g e n mo d u s :

Es werden jeweils die Istwerte von einem Kreis angezeigt.

 

Um von einem Kreis zum anderen zu wechseln kann die Taste

betätigt

 

werden. (Funktion nur bei EXD-SH2).

 

Durch Drücken der Taste kann die Istwertanzeige aktiviert/deaktiviert werden. Damit können folgende gemessene oder berechnete Istwerte entsprechend der unteren Tabelle abgerufen werden.

Wert im oberen Anzeigefeld

Code im unteren Anzeigefeld

Überhitzung (K/F)

SH

Ventilöffnung (%)

OPEn

Saugtemperatur (°C/°F)

tASP

Saugdruck (bar/psig)

PEuA

Sättigungstemperatur (°C/°F)

tEuA

Softwareversion: (0A)

SH1 oder SH2

Die Werte können wiederholt angezeigt werden

P a r a me t e r e i n s te l l u n g s mo d u s :

Der Parametereinstellungsmodus ist durch ein numerisches Passwort geschützt. Die Werkseinstellung ist “12”.

Zum starten des Parametereinstellungsmodus:

Beide Tasten, und für mehr als 5 Sekunden gedrückt halten.

Im oberen Anzeigefeld wird eine blinkende “0” und im unteren Anzeigefeld “PAS” angezeigt

gedrückt halten bis “12” (das Passwort) angezeigt wird.

Mit das Passwort bestätigen.

Mit oder können die Parameter der Liste nacheinander angezeigt werden.

Mit kann der Parameter der eingestellt bzw. verändert werden soll ausgewählt werden.

Mit oder können die Werte vergrößert oder verkleinert werden.

Durch drücken von wird der Wert zwischengespeichert. Der Wert blinkt für kurze Zeit dann wechselt die Anzeige zum nächsten Parameter.

Diese Abfolge kann für alle einzustellenden Parameter wiederholt werden.

Um die neuen Werte dauerhaft zu speichern und den Einstellmodus zu verlassen:

• Taste drücken

Den Einstellmodus verlassen OHNE die neuen Einstellungen dauerhaft zu speichern:

Beide Tasten und drücken: die vorherigen Änderungen werden gelöscht und der Parametereinstellmodus wird geschlossen.

Eine andere Möglichkeit zum Beenden ohne Speicherung ist mehr als 120 Sekunden ohne eine Tasteneingabe zu warten (TIME OUT).

Hinweis: Im Parametereinstellungsmodus wird im unteren Anzeigefeld der Parameter und im oberen Anzeigefeld der Wert angezeigt.

Spezielle Funktionen (Reset, clear) und Handbetrieb

Beide Tasten und für mehr als 5 Sekunden gedrückt halten.

Eine blinkende “0” wird angezeigt.

drücken bis “12” angezeigt wird; (falls ein individuelles, numerisches Passwort eingestellt ist muss dieses eingegeben werden.)

Mit wird das Passwort bestätigt

Folgende Spezielle Funktionen können ausgewählt werden:

Anzeige

Code

Zurück zur Werkseinstellung

-Fdt

Alarme löschen (nur manuell)

ALrr

Die Voreinstellung ist 0, mit 1wird die jeweilige Funktion aktiviert

Zurück zur Werkseinstellung (-Fdt) kann nur aktiviert werden, wenn die Digitaleingänge DI1/DI2 offen sind.

H a n d b e t r i e b Ve n t i l e ( S e r v i c e / W a r t u ng ) :

länger als 5 Sekunden gedrückt halten

Die Auswahl, Änderung und Speicherung der Parameter ist wie beim obigen Parametereinstellungsmodus.

Code

 

 

 

 

Werk-

Individ-

Parameter und Optionen

Min

Max

einstell-

uelle

 

 

 

 

 

ung

Einstell.

1Ho

Handbetrieb Kreislauf 1

0

1

0

 

 

0 = inaktiv

1 = aktiv

 

 

 

 

1HP

Ventilöffnung (%)

 

0

100

0

 

2Ho

Handbetrieb Kreislauf 2

0

1

0

 

0 = inaktiv

1 = aktiv

 

 

 

 

2HP

Ventilöffnung (%)

 

0

100

0

 

Hinweis: Während des Handbetriebes sind Funktionsalarme, wie “Zu niedrige Überhitzung” unterdrückt. Deshalb muss die Anlage in diesem Falle sorgfältig mit anderen Mitteln überwacht werden. Der Handbetrieb ist nur für Test und Servicezwecke vorgesehen. Danach sind für den Automatik Betrieb die Parameter 1Ho und 2Ho auf “ 0” zu setzen so dass der Regler entsprechend den Sollwerteinstellungen arbeiten kann.

Emerson Climate Technologies GmbH

www.climate.emerson.com/en-gb

Date: 29.07.2020

Am Borsigturm 31 I 13507 Berlin I Germany

 

EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx

Betriebsanleitung

EXD-SH1/2 Regler mit ModBus Kommunikation für elektrische Regelventile

P a r a me t e r t a b e l l e ( h i n t e r l e g t e R e i h e nf o l g e mi t

T a s t e ) :

 

 

 

 

 

 

 

 

 

Code

Parameterbeschreibung und - auswahl

 

 

Min

 

Max

Werk

H5

Passwort

 

 

 

 

 

1

 

1999

 

12

Adr

ModBus Adresse

 

 

 

 

1

 

127

 

1

br

Modbus Baudrate

 

 

 

 

0

 

1

 

0

PAr

Modbus Parität

 

 

 

 

0

 

1

 

0

-C2

Regelkreis 2 von EXD-HP2 aktivieren

 

0

 

1

 

1

0

=eingeschaltet

1 = ausgeschaltet

 

 

 

 

 

 

 

 

 

 

 

-uC

Maßeinheitensystem umstellen

 

 

 

0

 

1

 

0

0

= °C, K, bar

 

1 = F, psig

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Kreislauf

1 Parameter

 

 

 

 

 

 

 

 

 

1Fct

Funktion

 

 

 

 

 

0

 

2

 

0

0

= Überhitzungsregelung

1 = Temperaturregelung direkt proportional

 

2

= Temperaturregelung indirekt proportional

 

 

 

 

 

1u4

Regelungsart Überhitzung

 

 

 

0

 

2

 

0

0

= Standard

 

 

1 = langsam

 

 

 

 

 

 

 

2

= Zwischeneinstellung

3 = PID fest einstellbar

 

 

 

 

Kältemittel

 

 

 

 

 

0

 

19

 

1

 

 

0 = R22

 

1 = R134a

 

2 = R507

 

 

3 = R404A

 

 

1u0

 

4 = R407C

 

5 = R410A

 

6 = R124

7 = R744

 

 

8 = R407A

 

9 = R407F

 

10 = R23

11 = R32*

 

 

 

 

 

 

 

12 = R1234ze*

13 = R448A

 

14 = R449A

15 = R450A

 

 

16 = R513A

 

17 = R290*

 

18 = R1270*

19 = R454C*

 

Drucksensor

 

 

 

 

 

0

 

8

 

1

1uP

0

= PT5N-07x

1 = PT5N-18x

2 = PT5N-30x

 

 

 

3

= PT5N-50x

4 = PT5N-150D 5 = PT5N-10P-FLR

 

 

 

 

6

= Ratiometrisch (Druck relativ)

7 = Ratiometrisch (Druck absolute)

 

8

= Modbus

 

 

 

 

 

 

 

 

 

 

1Prr

Ratiometrischer Bereich (bar)

 

 

 

3

 

60

 

30

 

Ventiltyp

 

 

 

 

 

0

 

12

 

0

1ut

 

0 = EX4-6

 

1 = EX7

 

2 = EX8

 

3 = N/A

4

 

= N/A

 

5 = N/A

 

6 = N/A

 

7 = N/A

8 = N/A

9 = N/A

 

 

 

 

 

10 = CV4

 

11 = CV5-6

 

12 = CV7

 

 

 

 

 

1uF

Ventil-Regelungsbereich (%)

 

 

 

5

 

100

 

100

1uu

Start Öffnung (%)

 

 

 

 

0

 

100

 

10

1u9

Dauer Ventilöffnung bei Start (s)

 

 

 

0

 

120

 

5

 

Alarm ein „zu geringe Überhitzung“

 

 

0

 

2

 

1

1uL

0

= aus

 

1 = ein – autom. Rückstellung

 

 

 

 

 

 

2

= ein – Handrückstellung

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm bei 0.5K (bei Dauer > 1 min.); autom. Rückstellung sofort bei 3K

1u5

Überhitzungssollwert (K)

 

 

 

0.5

 

30

 

6

Bereich = 3-30 K wenn Parameter 1uL auf 1 oder 2

 

 

 

 

 

 

 

 

 

 

 

1u2

MOP Funktion

 

 

 

 

0

 

1

 

1

0

= aus

 

1 = ein

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MOP Sättigungstemperatur (°C)

 

 

 

 

 

 

 

 

1u3

Werkseinstellung entsprechend dem gewählten

 

-

 

-

 

(lt. MOP

Kältemittel (1u0).

 

 

 

 

 

 

Tabelle)

 

 

 

 

 

 

 

 

 

 

Einstellung kann geändert werden

 

 

 

 

 

 

 

1P9

Niedrigdruckalarm Regelkreis 1

 

 

 

0

 

2

 

0

0

= aus

1 = ein - autom. Reset

2 = ein - Handrückstellung

 

 

 

1PA

Grenzwert für Niederdruckalarm (bar)

 

-0.8

 

17.7

 

0

1Pb

Niedrigdruckalarm Verzögerung (s)

 

 

5

 

199

 

5

1Pd

Rückstellung Niederdruckalarm (bar)

 

 

-0.5

 

18

 

0.3

1P4

Frostschutzalarm Regelkreis 1

 

 

 

0

 

2

 

0

0

= aus

1 = ein - autom. Rückstellung 2 = ein - Handrückstellung

 

1P2

Grenzwert Frostschutzalarm (°C)

 

 

-5

 

5

 

0

1P5

Alarmverzögerung Frostschutz (s)

 

 

5

 

199

 

30

1P-

Überhitzungsregelung Kreislauf 1

 

 

0.1

 

10

 

1.0

 

(Kp Faktor) Display 1/10K

 

 

 

 

 

 

 

 

1i-

Überhitzungsregelung Kreislauf 1 (Ti Faktor)

 

1

 

350

 

100

1d-

Überhitzungsregelung Kreislauf 1

 

 

0.1

 

30

 

3.0

 

(Td Faktor) Display 1/10K

 

 

 

 

 

 

 

 

1uH

Alarm „zu große Überhitzung“

 

 

 

0

 

1

 

0

 

0

= aus

1 = ein mit Auto Reset

 

 

 

 

 

 

 

1uA

Grenzwert “Zu große Überhitzung” (K)

 

16

 

40

 

30

1ud

Verzögerung “Zu große Überhitzung” (min)

 

1

 

15

 

3

1tSt

Temperaturregelung Sollwert (°C)

 

 

-80

 

50

 

4

1tbd

Temperatur-Regelbereich (K)

 

 

 

1

 

10

 

2

1tAF

Temperatur Alarm

 

 

 

 

0

 

1

 

0

 

0

= aus

1 = ein

 

 

 

 

 

 

 

 

1tAL

Alarm unterer Temperaturwert (°C)

 

 

-50

 

50

 

0

1tdL

Verzögerung Alarm unterer Temperaturwert

 

1

 

10

 

3

(min)

 

 

 

 

 

 

 

 

 

 

1tAH

Alarm oberer Temperaturwert (°C)

 

 

-50

 

50

 

15

1tdH

Verzögerung Alarm Oberer Temperaturwert

 

1

 

10

 

3

(min)

 

 

 

 

 

 

 

 

 

 

1tt

Temperatursensor

 

 

 

 

0

 

1

 

0

0

= ECN-Nxx (-45…+40°C) / TP1-…(-45…+150°C)

 

 

 

 

 

 

 

1

= ECN-Z60 ( -80…-40°C) für R23

 

 

 

 

 

 

 

Code

Parameterbeschreibung und -auswahl

 

 

Min

 

Max

 

Werk

 

 

 

 

 

 

 

 

 

 

Kreislauf

2 Parameter (nur EXD-SH2)

 

 

 

 

 

 

 

 

2u4

Regeloptionen

 

 

 

 

0

 

2

 

0

0 = Standard

 

 

1 = langsam

 

 

 

 

 

 

 

2 = Zwischeneinstellung

3 = PID fest einstellbar

 

 

 

 

Kältemittel

 

 

 

 

 

0

 

19

 

1

 

0 = R22

 

1 = R134a

 

2 = R507

 

 

3 = R404A

 

 

2u0

4 = R407C

 

5 = R410A

 

6 = R124

7 = R744

 

8 = R407A

 

9 = R407F

 

10 = R23

11 = R32*

 

 

 

 

 

 

12 = R1234ze*

13 = R448A

 

14 = R449A

15 = R450A

 

 

16 = R513A

 

17 = R290*

 

18 = R1270*

19 = R454C*

 

Drucksensor

 

 

 

 

 

0

 

9

 

1

2uP

0 = PT5N-07x

1 = PT5N-18x

2 = PT5N-30x

 

 

 

3 = PT5N-50x

4 = PT5N-150D

5 = PT5N-10P-FLR

 

 

 

 

6 = Ratiometrisch (Druck relativ)

7 = Ratiometrisch (Druck absolute)

 

8= Modbus

 

9 = Drucksensor von Kreislauf 1 genutzt (1uP)

 

2Prr

Ratiometrisch Bereich (bar)

 

 

 

3

 

60

 

30

 

Ventiltyp

 

 

 

 

 

0

 

12

 

0

2ut

0 = EX4-6

 

1 = EX7

 

2 = EX8

 

3 = N/A

4

= N/A

5 = N/A

 

6 = N/A

 

7 = N/A

8 = N/A

9 = N/A

 

 

 

 

10 = CV4

 

11 = CV5-6

 

12 = CV7

 

 

 

 

 

2uF

Ventil-Regelungsbereich (%)

 

 

 

5

 

100

 

100

2uu

Start Öffnung (%)

 

 

 

 

0

 

100

 

10

2u9

Dauer Ventilöffnung bei Start (s)

 

 

 

0

 

120

 

5

 

Alarm ein „ zu geringe Überhitzung“

 

 

0

 

2

 

1

2uL

0 = aus

 

1 = ein - autom. Rückstellung

 

 

 

 

 

 

2 = ein – Handrückstellung

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm bei 0.5 K (bei Dauer >1 min.); autom. Rückstellung sofort bei 3K

2u5

Überhitzungssollwert (K)

 

 

 

0.5

 

30

 

6

Bereich = 3-30 K wenn Parameter 2uL auf 1 oder 2

 

 

 

 

 

 

 

 

 

 

 

2u2

MOP Funktion

 

 

 

 

0

 

1

 

1

0 = aus

1 = ein

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MOP Sättigungstemperatur (°C)

 

 

 

 

 

 

 

 

2u3

Werkseinstellung entsprechend dem gewählten

 

-

 

-

 

(lt. MOP

Kältemittel (2u0). Einstellung kann geändert

 

 

 

Tabelle)

 

 

 

 

 

 

 

werden

 

 

 

 

 

 

 

 

 

 

2P9

Niederdruckalarm Regelkreis 2

 

 

 

0

 

2

 

0

0 = aus

1 = ein - autom. Rückstellung

2 = ein - Handrückstellung

 

2PA

Grenzwert für Niederdruckalarm (bar)

 

-0.8

 

17.7

 

0

2Pb

Niederdruckalarm Verzögerung (s)

 

 

5

 

199

 

5

2Pd

Rückstellung Niederdruckalarm (bar)

 

 

-0.5

 

18

 

0.3

2P4

Frostschutzalarm Regelkreis 2

 

 

 

0

 

2

 

0

 

0 = aus

1 = ein - autom. Rückstellung

 

2 = ein - Handrückstellung

2P2

Grenzwert Frostschutzalarm (°C)

 

 

-5

 

5

 

0

2P5

Alarmverzug Frostschutz (s)

 

 

 

5

 

199

 

30

2P-

Überhitzungsregelung Kreislauf 2

 

 

0.1

 

10

 

1.0

 

(Kp Faktor), feste PID

Display 1/10K

 

 

 

 

 

 

2i-

Überhitzungsregelung Kreislauf 2

 

 

1

 

350

 

100

 

(Ti Faktor), feste PID

 

 

 

 

 

 

 

 

2d-

Überhitzungsregelung Kreislauf 2

 

 

0.1

 

30

 

3.0

 

(Td Faktor), feste PID

Display 1/10K

 

 

 

 

 

 

2uH

Alarm “zu große Überhitzung“

 

 

 

0

 

1

 

0

 

0 = aus

1 = ein - autom.-Rückstellung

 

 

 

 

 

2uA

Grenzwert “Zu große Überhitzung” (K)

 

16

 

40

 

30

2ud

Verzögerung “Zu große Überhitzung” (min)

 

1

 

15

 

3

2tt

Temperatursensor

 

 

 

 

0

 

1

 

0

0 = ECN-Nxx (-45…+40°C) / TP1-…(-45…+150°C)

 

 

 

 

 

 

 

1 = ECN-Z60 ( -80…-40°C) für R23

 

 

 

 

 

 

 

*) Warnung – Brennbare Kältemittel

EXD-SH1/2 (EXD-PM, ECP-024) hat eine potentielle Zündquelle und entspricht nicht den ATEX Bestimmungen. Installation nur in nicht explosionsgefährdeter Umgebung. Für brennbare Kältemittel nur Ventile und Zubehörteile, die dafür zugelassen sind verwenden!

MOP Werkseinstellung:

Kältemittel

Eingestellter

Refrigerant

Eingestellter

Refrigerant

Eingestellter

 

Wert (C°)

 

Wert (C°))

 

Wert (C°)

R22

+13

R744

-5

R449A

+12

R134a

+15

R407A

+10

R450A

+19

R507

+7

R407F

+10

R513A

+13

R404A

+7

R23

-40

R290

+15

R407C

+15

R32

+15

R1270

+15

R410A

+15

R1234ze

+24

R454C

+17

R124

+50

R448A

+12

 

 

Emerson Climate Technologies GmbH

www.climate.emerson.com/en-gb

Date: 29.07.2020

Am Borsigturm 31 I 13507 Berlin I Germany

 

EXD-SH12_OI_EN_DE_FR_IT_PL_RU_0720_R04_865917.docx

Loading...
+ 21 hidden pages