Toshiba MMY-MAP1606FT8P-UK, MMY-MAP0806FT8P-UK, MMY-MAP0806FT8JPUK, MMY-MAP2006FT8P-UK, MMY-MAP1806FT8P-UK Installation Manual

...
0 (0)
AIR CONDITIONER (MULTI TYPE)
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Installation Manual
Outdoor Unit
Model name:
MMY-MAP0806FT8P-UK MMY-MAP1006FT8P-UK MMY-MAP1206FT8P-UK MMY-MAP1406FT8P-UK MMY-MAP1606FT8P-UK MMY-MAP1806FT8P-UK MMY-MAP2006FT8P-UK
MMY-MAP0806FT8JPUK MMY-MAP1006FT8JPUK MMY-MAP1206FT8JPUK MMY-MAP1406FT8JPUK MMY-MAP1606FT8JPUK MMY-MAP1806FT8JPUK MMY-MAP2006FT8JPUK
For commercial use
English
– 1 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Original instruction
ADOPTION OF NEW REFRIGERANT
This Air Conditioner uses R410A an environmentally friendly refrigerant.
Contents
1 Precautions for safety ......................................................... 3
2 Accessory parts. .......................................................... .....
3 Installation of new refrigerant air conditioner . ............................ .....
4 Selection of installation place. ..................................................
5 Carrying in the outdoor unit . .................................................
6 Installation of the outdoor unit. ...............................................
7 Refrigerant piping
. ..........................................................
8 Electric wiring. ................................................................
9 Address setting . .............................................................
10 How to set up the cooling only indoor unit . ...................................
11 Test run 12 Troubleshooting
. ............................ .................... ............ .........
................ .............................................
.
13 Machine card and logbook. ...................................................
..
11 12 14
24 28
37
38
40
41
Thank you for purchasing this Toshiba air conditioner. This Installation Manual describes the installation method of the outdoor unit. For installation of indoor units, follow the Installation Manual supplied with the indoor unit. Moreover, as this installation manual includes the important articles concerning the “Machinery Directive” (Directive 2006/42/EC), please read through the manual and make sure you understand it. After installation, give this Installation Manual with the Owner’s Manual, the Owner’s Manual and the Installation Manual supplied with the indoor unit to the customer and tell the customer to keep them safe. Prepare an exclusive power source for indoor units, independent to that for outdoor units. Y-shaped branching joints or a branching header (separately purchased) are required for connecting pipes between indoor and outdoor units. Choose either of them considering the system capacity concerning piping. For installing branching pipes, refer to the installation manual of the Y-shaped branching unit or branching header (separately purchased). Outdoor connecting branching joints are required for connecting between outdoor units.
Generic Denomination: Air Conditioner
8 9 9
Denition of Qualied Installer or Qualied Service Person
The air conditioner must be installed, maintained, repaired and removed by a qualied installer or qualied service person. When any of these jobs is to be done, ask a qualied installer or qualied service person to do them for you. A qualied installer or qualied service person is an agent who has the qualications and knowledge described in the table below.
Agent Qualications and knowledge which the agent must have
• The qualied installer is a person who installs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified installer who is allowed to do the electrical work involved in installation, relocation and removal has the qualications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have
Qualied installer
Qualied service person
been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation, relocation and removal has the qualications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person is a person who installs, repairs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, repair, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified service person who is allowed to do the electrical work involved in installation, repair, relocation and removal has the qualications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to do the refrigerant handling and piping work involved in installation, repair, relocation and removal has the qualications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
2-EN1-EN
Denition of Protective Gear
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing. In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below. Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns, electric shocks and other injuries.
Work undertaken Protective gear to wear
All types of work
Electrical-related work
Work at heights (50 cm or more)
Transportation of heavy objects
Repair of outdoor unit Gloves to provide protection for electricians and from heat
Protective gloves ‘Safety’ working clothing
Gloves to provide protection for electricians and from heat Insulating shoes Clothing to provide protection from electric shock
Helmets for use in industry
Shoes with additional protective toe cap
Warning indications on the air conditioner unit
Warning indication Description
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing this panel.
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing this panel.
CAUTION
Do not touch the aluminum fins of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
CAUTION
Do not climb onto the fan guard.
Doing so may result in injury.
CAUTION
Do not touch the aluminium ns of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
CAUTION
Do not climb onto the fan guard.
Doing so may result in injury.
– 2 –
4-EN3-EN
– 3 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
1 Precautions for safety
The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual.
WARNING
General
• Before starting to install the air conditioner, read through the Installation Manual carefully, and follow its instructions to install the air conditioner. Otherwise, falling down of the unit may occur, or the unit may cause noise, vibration or water leakage.
• Only a qualied installer(*1) or qualied service person(*1) is allowed to do installation work. If installation is carried out by an unqualied individual, a re, electric shocks, injury, water leakage, noise and/or vibration may result.
• If using separately sold products, make sure to use Toshiba specied products only. Using unspecied products may cause re, electric shock, water leak or other failure.
• Do not use any refrigerant different from the one specied for complement or replacement.
Otherwise, abnormally high pressure may be generated in the
refrigeration cycle, which may result in a failure or explosion of the product or an injury to your body.
• Before opening the service panel of the outdoor unit, set the circuit breaker to the OFF position. Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with the interior parts. Only a qualied installer(*1) or qualied service person(*1) is allowed to remove the service panel of the outdoor unit and do the work required.
• Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breakers for both the indoor and outdoor units to the OFF position. Otherwise, electric shock may result.
• Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work is being carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
• Only a qualied installer(*1) or qualied service person(*1) is allowed to undertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work.
• Wear protective gloves and safety work clothing during installation, servicing and removal.
• Do not touch the aluminium n of the outdoor unit. You may injure yourself if you do so. If the n must be touched for some reason, rst put on protective gloves and safety work clothing, and then proceed.
• Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects may fall off of the outdoor unit and result in injury.
• When working at height, put a sign in place so that no-one will approach the work location before proceeding with the work. Parts or other objects may fall from above, possibly injuring a person below. Also, be sure that workers put on helmets.
• When cleaning the lter or other parts of the outdoor unit, set the circuit breaker to OFF without fail, and place a “Work in progress” sign near the circuit breaker before proceeding with the work.
• The refrigerant used by this air conditioner is the R410A.
• You shall ensure that the air conditioner is transported in stable condition. If you nd any part of the product broken, contact your dealer.
• Do not disassemble, modify or move the product yourself. Doing so may cause re, electric shock, injury or water leaks.
6-EN5-EN
• This appliance is intended to be used by expert or trained users
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
in shops, in light industry, or for commercial use by lay persons.
• We do not take any responsibility on the local design.
Selection of installation location
• If you install the unit in a small room, take appropriate measures to prevent the refrigerant from exceeding the limit concentration even if it leaks. Consult the dealer from whom you purchased the air conditioner when you implement the measures. Accumulation of highly concentrated refrigerant may cause an oxygen deciency accident.
• Do not install in a location where ammable gas may leaks are possible. If the gas should leak and accumulate around the unit, it may ignite and cause a re.
• When transporting the air conditioner, wear shoes with protective toe caps, protective gloves and other protective clothing.
• When transporting the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if the bands should break.
• Other than floor standing and console types, install the indoor unit at least 2.5 m above the oor level since otherwise the users may injure themselves or receive electric shocks if they poke their ngers or other objects into the indoor unit while the air conditioner is running.
• Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise it may cause imperfect combustion.
• Do not install outdoor units where the operation sound may cause a disturbance. (Especially at the boundary line with a neighbour, install the air conditioner while considering the noise.)
Installation
• Follow the instructions in the Installation Manual to install the air conditioner. Failure to follow these instructions may cause the product to fall down or topple over or give rise to noise, vibration, water leakage or other failure.
• The designated bolts (M12) and nuts (M12) for securing the outdoor unit must be used when installing the unit.
• Install the outdoor unit property in a location that is durable enough to support the weight of the outdoor unit. Insufcient durability may cause the outdoor unit to fall, which may result in injury.
• Install the unit in the prescribed manner for protection against strong wind and earthquake. Incorrect installation may result in the unit falling down, or other accidents.
• Be sure to x the screws back which have been removed for installation or other purposes.
Refrigerant piping
• Install the refrigerant pipe securely during the installation work before operating the air conditioner. If the compressor is operated with the valve open and without refrigerant pipe, the compressor sucks air and the refrigeration cycles is over pressurized, which may cause a injury.
• Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the are nut may cause a crack in the are nut after a long period, which may result in refrigerant leakage.
• Ventilate the air if the refrigerant gas leaks during installation. If the leaked refrigerant gas comes into contact with re, toxic gas may be produced.
– 4 –
8-EN7-EN
– 5 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
• After the installation work, conrm that refrigerant gas does not leak. If refrigerant gas leaks into the room and ows near a re source, such as a cooking range, noxious gas may be generated.
• When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge the air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge the air completely may cause the air conditioner to malfunction.
• Nitrogen gas must be used for the airtight test.
• The charge hose must be connected in such a way that it is not slack.
• If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes in contact with re, noxious gas may be generated.
Electrical wiring
• Only a qualied installer(*1) or qualied service person(*1) is allowed to carry out the electrical work of the air conditioner.
Under no circumstances must this work be done by an
unqualied individual since failure to carry out the work properly may result in electric shocks and/or electrical leaks.
• When connecting the electrical wires, repairing the electrical parts or undertaking other electrical jobs, wear gloves to provide protection for electricians and from heat, insulating shoes and clothing to provide protection from electric shocks. Failure to wear this protective gear may result in electric shocks.
• When executing address setting, test run, or troubleshooting through the checking window on the electrical control box, put on insulated heat-proof gloves, insulated shoes and other clothing to provide protection from electric shock. Otherwise you may receive an electric shock.
• Use wiring that meets the specications in the Installation Manual and the stipulations in the local regulations and laws. Use of wiring which does not meet the specications may give rise to electric shocks, electrical leakage, smoking and/or a re.
• Check that the product is properly earthed. (grounding work)
Incomplete earthing may cause electric shock.
• Do not connect the earth line to a gas pipe, water pipe, lightning conductor, or a telephone earth line.
• After completing the repair or relocation work, check that the ground wires are connected properly.
• Install a circuit breaker that meets the specications in the installation manual and the stipulations in the local regulations and laws.
• Install the circuit breaker where it can be easily accessed by the agent.
• When installing the circuit breaker outdoors, install one which is designed to be used outdoors.
• Under no circumstances must the power cable be extended. Connection trouble in the places where the cable is extended may give rise to smoking and/or a re.
• Electrical wiring work shall be conducted according to law and regulation in the community and installation manual.
Failure to do so may result in electrocution or short circuit.
• Do not supply power from the power terminal block equipped on the outdoor unit to another outdoor unit. Capacity overow may occur on the terminal block and may result in re.
• When carrying out electric connection, use the wire specied in the Installation Manual and connect and x the wires securely to prevent them applying external force to the terminals. Improper connection or xing may result in re.
10-EN9-EN
Test run
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
• Before operating the air conditioner after having completed the work, check that the electrical parts box cover of the indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may receive an electric shock if the power is turned on without rst conducting these checks.
• When you have noticed that some kind of trouble (such as when an error display has appeared, there is a smell of burning, abnormal sounds are heard, the air conditioner fails to cool or heat or water is leaking) has occurred in the air conditioner, do not touch the air conditioner yourself but set the circuit breaker to the OFF position, and contact a qualied service person. Take steps to ensure that the power will not be turned on (by marking “out of service” near the circuit breaker, for instance) until qualied service person arrives. Continuing to use the air conditioner in the trouble status may cause mechanical problems to escalate or result in electric shocks or other failure.
• After the work has nished, be sure to use an insulation tester set (500V Megger) to check the resistance is 1 MΩ or more between the charge section and the non-charge metal section (Earth section). If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.
• Upon completion of the installation work, check for refrigerant leaks and check the insulation resistance and water drainage.
Then conduct a test run to check that the air conditioner is
operating properly.
• If you have discovered that the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF position, and contact a qualied service person(*1) to have the repairs done. Do not set the circuit breaker to the ON position until the repairs are completed.
• After the installation work, follow the Owner’s Manual to explain to the customer how to use and maintain the unit.
Relocation
• Only a qualied installer(*1) or qualied service person(*1) is allowed to relocate the air conditioner. It is dangerous for the air conditioner to be relocated by an unqualied individual since a re, electric shocks, injury, water leakage, noise and/or vibration may result.
• When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air or other gas to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in rupture, injury or other trouble.
• Never recover the refrigerant into the outdoor unit. Be sure to use a refrigerant recovery machine to recover the refrigerant when moving or repairing. It is impossible to recover the refrigerant into the outdoor unit. Refrigerant recovery into the outdoor unit may result in serious accidents such as explosion of the unit, injury or other accidents.
Explanations given to user
• Upon completion of the installation work, tell the user where the circuit breaker is located. If the user does not know where the circuit breaker is, he or she will not be able to turn it off in the event that trouble has occurred in the air conditioner.
– 6 –
(*1) Refer to the “Denition of Qualied Installer or Qualied Service Person.”
12-EN11-EN
CAUTION
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
New refrigerant air conditioner installation
This air conditioner adopts the new HFC refrigerant (R410A) which does not destroy ozone layer.
• The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed.
Therefore, during installation work, be sure that water, dust,
former refrigerant, or refrigerating oil does not enter the refrigerating cycle.
• To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the main unit and installation tools are changed from those for the conventional refrigerant.
• Accordingly the exclusive tools are required for the new refrigerant (R410A).
• For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not enter.
– 7 –
To Disconnect the Appliance from Main Power Supply.
• This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm.
The installation fuse (all type can be used) must be used for the power supply line of this conditioner.
Do not wash air conditioners with pressure washers.
• Electric leaks may cause electric shocks or res.
13-EN 14-EN
2 Accessory parts
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Q’ty
Part name
Owner’s Manual 1111
Installation Manual 1111 – This manual for installer.
F-GAS label 1111
Attached clamp lter –––1
Attached binding band –––1 Attached pipe
(Ø22.2 both forward and downward)
Attached pipe (Ø28.6 both forward and downward)
Attached pipe (Ø19.1 both forward and downward)
Attached pipe (Ø19.1 both forward and downward)
Attached pipe (Ø22.2 both forward and downward)
MAP080 MAP100
MAP120 MAP140
1–––
–111
1–––
–1––
––11
MAP160 MAP180 MAP200
Shape Usage
(Be sure to hand it to the customers.)
Fill the items on the label after adding refrigerant.
For earth line.
Suction-side gas pipe Ø25.4Ø22.2 pipe tting
Suction-side gas pipe Ø25.4Ø28.6 pipe tting
Discharge-side gas pipe Ø15.9Ø19.1 pipe tting * Flare the connector on the
outdoor unit for installation.
Discharge-side gas pipe * Flare the connector on the
outdoor unit for installation.
Discharge-side gas pipe Ø19.1Ø22.2 pipe tting * Flare the connector on the
outdoor unit for installation.
Part name
Attached pipe (Ø12.7 for draw-out forward)
Attached pipe (Ø12.7 for draw-out downward)
Attached pipe (Ø15.9 for draw-out forward)
Attached pipe (Ø15.9 for draw-out downward)
Attached pipe (Ø19.1 for draw-out forward)
Attached pipe (Ø19.1 for draw-out downward)
Q’ty
MAP080 MAP100
MAP120 MAP140
–1––
–1––
––1–
––1–
–––1
–––1
MAP160 MAP180 MAP200
Shape Usage
Liquid pipe Ø15.9Ø12.7 pipe tting * Flare the connector on the
outdoor unit for installation.
Liquid pipe * Flare the connector on the
outdoor unit for installation.
Liquid pipe Ø15.9Ø19.1 pipe tting * Flare the connector on the
outdoor unit for installation.
Attached pipe (Ø12.7 for draw-out forward)
Attached pipe (Ø12.7 for draw-out downward)
1 5 -EN 16 -EN
1–––
1–––
Liquid pipe * Flare the connector on the
outdoor unit for installation.
– 8 –
– 9 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
3 Installation of new refrigerant air conditioner
This air conditioner adopts the new HFC refrigerant (R410A) which does not deplete the ozone layer.
• R410A refrigerant is vulnerable to impurities such as water, oxidizing membranes, or oils because the pressure
of R410A refrigerant is higher than that of the former refrigerant by approximately 1.6 times.
As well as the adoption of the new refrigerant, the refrigerating oil has been also changed. Therefore, pay
attention so that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle of the new refrigerant air conditioner during installation.
• To prevent mixing of refrigerant or refrigerating oil, the size of the charge port of the main unit or connecting
section of the installation tool differs to that of an air conditioner for the former refrigerant.
Accordingly, exclusive tools are required for the new refrigerant (R410A) as shown below.
• For connecting pipes, use new and clean piping materials so that water or dust does not enter.
Required tools and cautions on handling
It is necessary to prepare the tools and parts for installation as described below. The tools and parts which will be newly prepared in the following items should be restricted to exclusive use.
Explanation of symbols
: Newly prepared (It is necessary to use it exclusively with R410A, separately from those for R22 or R407C.)
: Former tool is available.
Used tools Usage Proper use of tools/parts
Gauge manifold Charging hose
Charging cylinder Charging refrigerant Unusable (Use the Refrigerant charging balance.) Gas leak detector Checking gas leak
Vacuum pump Vacuum drying Vacuum pump with counterow Vacuum drying
Flare tool Flare processing of pipes Usable by adjusting size Bender Bending processing of pipes Refrigerant recovery device Recovering refrigerant Torque wrench Tightening are nut Pipe cutter Cutting pipes
Refrigerant canister Charging refrigerant Brazing machine/Nitrogen gas
cylinder Refrigerant charging balance Charging refrigerant
Vacuuming, charging refrigerant and operation check
Brazing of pipes
Exclusive to R410A Exclusive to R410A
Exclusive to R410A
Usable if a counter-ow preventive adapter is attached
R22 (Existing article)
R22 (Existing article) Exclusive to R410A Exclusive to Ø12.7mm and Ø15.9mm R22 (Existing article)
Exclusive to R410A Enter the refrigerate name for identication
R22 (Existing article) R22 (Existing article)
4 Selection of installation place
Upon customer’s approval, install the air conditioner in a place which satises the following conditions:
• Place where it can be installed horizontally.
• Place which can reserve a sufcient service space for safe maintenance or checks.
• Place where there is no problem even if the drained water overows.
Avoid the following places:
• Salty places (seaside area) or places with much gas sulde (hot spring area) (If selecting such a place, special maintenance is required.)
• Places where oil (including machine oil), steam, oil smoke or corrosive gas is generated.
• Places where iron or other metal dust is present. If iron or other metal dust adheres to or collects on the interior of the air conditioner, it may spontaneously combust and start a re.
• Places where an organic solvent is used.
• Chemical plants with a cooling system using liquid carbon dioxide.
• Places where a device generating high frequency (inverter, non-utility generator, medical apparatus, or communication equipment) is set. (Malfunction or abnormal control of the air conditioner, or interference to devices listed above may occur.)
• Places where discharged air from the outdoor unit blows against the windows of a neighbour’s house.
• Places unable to bear the weight of the unit.
• Places with poor ventilation.
• The cooling performance may decline considerably when total operating capacity of cooling indoor units is less than 4HP while ambient temperature is below 0°C.
1 7 -EN
18-EN
Installation space
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
Leave space necessary for running, installation and servicing.
Air discharge
Air intake
Air intake
Air intake
500mm or more
(Rear side)
10mm or more
500mm or more
(Front side)
Installation/servicing
surface
Square hole for handling
Outdoor unit top view
20mm or more20mm or more
NOTE
• If there is an obstacle above the outdoor unit, leave a space of 2000mm or more to the top end of the outdoor unit.
• If there is a wall around the outdoor unit, make sure that its height does not exceed 800mm.
Air intake
10mm or more
q Combination of outdoor units (* : FT8P-UK , FT8JPUK )
Model name Unit 1 Unit 2 Unit 3
MMY-MAP0806* MMY-MAP0806* - ­MMY-MAP1006* MMY-MAP1006* - ­MMY-MAP1206* MMY-MAP1206* - ­MMY-MAP1406* MMY-MAP1406* - ­MMY-MAP1606* MMY-MAP1606* - ­MMY-MAP1806* MMY-MAP1806* - ­MMY-MAP2006* MMY-MAP2006* - ­MMY-AP2216* MMY-MAP1206* MMY-MAP1006* ­MMY-AP2416* MMY-MAP1406* MMY-MAP1006* ­MMY-AP2616* MMY-MAP1406* MMY-MAP1206* ­MMY-AP2816* MMY-MAP1406* MMY-MAP1406* ­MMY-AP3016* MMY-MAP1606* MMY-MAP1406* ­MMY-AP3216* MMY-MAP1806* MMY-MAP1406* ­MMY-AP3416* MMY-MAP1806* MMY-MAP1606* ­MMY-AP3616* MMY-MAP1806* MMY-MAP1806* ­MMY-AP3816* MMY-MAP2006* MMY-MAP1806* ­MMY-AP4016* MMY-MAP2006* MMY-MAP2006* ­MMY-AP4216* MMY-MAP1406* MMY-MAP1406* MMY-MAP1406*
– 0 1 –
20-EN19-EN
– 1 1 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
5 Carrying in the outdoor unit
CAUTION
Handle the outdoor unit carefully, observing the following items.
When using a forklift or other machinery for loading/unloading in transportation, insert the fork of the forklift into
the rectangular holes for handling as shown below.
When lifting up the unit, insert a rope able to bear the unit’s weight into the rectangular holes for handling, and
tie the unit from 4 sides.
(Apply padding in positions where the rope comes into contact with the outdoor unit so that no damage is
caused to the outer surface of the outdoor unit.)
(There are reinforcing plates on the side surfaces, so the rope cannot be passed through.)
INCORRECT INCORRECTCORRECT
Plaster board
Rope
Rectangular
holes for handling
Front/Back
CORRECT
Fork of the forklift
Side
INCORRECT
Plaster board
Rectangular holes for lifting
Reinforcing plate
Weight centre and weight
¿ Weight centre of an outdoor unit
Anchor bolt positionA. B. C.Anchor bolt position Anchor bolt position
700
755
Y
Anchor bolt position
X
Z
No. Model type X (mm) Y (mm) Z (mm) Weight (kg)
MMY-MAP080*
A
MMY-MAP100* MMY-MAP120*
B
MMY-MAP140* MMY-MAP160*
C
MMY-MAP200*
755
Anchor bolt position
500 385 635 263
605 370 630 316
780 365 650 377MMY-MAP180*
920
755
Y
Anchor bolt position
Z
1310
Y
XX
Z
(Unit : mm)
22-EN21-EN
6 Installation of the outdoor unit
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
WARNING
Be sure to install the outdoor unit in a place able to bear its weight. If strength is insufcient, the unit may fall down resulting in human injury.
Perform specied installation work to protect against strong wind and earthquakes. If the outdoor unit is imperfectly installed, an accident by falling or dropping may be caused.
CAUTION
• Drain water is discharged from the outdoor unit. (Especially while heating) Install the outdoor unit in a place with good drainage.
• For installation, be careful of the strength and level of the foundation so that abnormal sounds (vibration or
noise) are not generated.
REQUIREMENT
Installation in a snowfall area
1. Install the outdoor unit on a higher foundation than the snowfall or set up a stand to install the unit so that
snowfall will not affect the unit.
• Set up a stand higher than the snowfall.
• Apply an angled structure to the stand so that drainage will not be prevented. (Avoid using a stand with a at
surface.)
2. Mount a snowfall-hood onto the air intake and the air discharge.
• Leave enough space for the snowfall-hood so that it will not be an obstacle for the air intake and the air
discharge.
Snowfall-hood for air discharge (locally procured)
Snowfall-hood for air intake (4 faces) (locally procured)
• Anchor bolt positions are as shown below:
Continuous hole (15 x 20 long hole)
Model type A B C
MAP080*, MAP100* 700 990 – MAP120*, MAP140* 920 1210 – MAP160*, MAP180*, MAP200* 1310 1600 1500
310 or more
A A A
2. When drawing out the refrigerant pipe from the underside, set the height of the stand to 500mm or more.
500mm or more
310 or more
755
790
B
C* A
B
*Only MAP160, MAP180, MAP200 type has holes for additional strength.
3. Do not use 4 stands on the corner to support the outdoor unit.
Incorrect Correct
(Unit : mm)
4. Mount the vibration-proof rubber (including vibration-proof blocks) so that it ts under the whole clamping leg.
Correct Correct
1. To install multiple outdoor units, arrange them with 20mm or more spaces in between. Fix each outdoor unit with M12 anchor bolts at 4 positions. 20mm projection is appropriate for an anchor bolt.
20
20mm or more 20mm or more
M12 anchor bolt 4 positions/unit
Stand (locally procured)
Vibration-proof rubber
2 1 –
Anchor bolt
Install the vibration-proof rubber so that the bent part of the xing leg is grounded.
The bent part of the xing leg is not grounded.
IncorrectIncorrect Incorrect
24-EN23-EN
– 13 –
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk
5. Be careful of the connecting arrangement of the header unit and follower units. Set the outdoor units in order of capacity from the one with the largest capacity. (A (Header unit) B C)
• Be sure to use a header unit for the leading outdoor unit to be connected to the main pipe. (Figure 1, 3 and 6)
• Be sure to use a T-shaped branch joint (RBM-BT14FE/RBM-BT24FE: separately purchased) to connect each
outdoor unit.
• Be careful of the direction of the Outdoor unit connection piping kit for the liquid side. (As shown in Figure 2, a
Outdoor unit connection piping kit cannot be attached so that the refrigerant of the main pipe ows directly into the header unit.)
• When attaching a Y-shaped branch unit for the outdoor unit connection piping kit, attach it level with the
ground (Be sure not to exceed ±15 degrees.). Regarding a T-shape branch joints for the liquid side, there is no restriction for its angle.
At a level position
(Horizontal line) (Horizontal line)
A
(A arrow view) (B arrow view)
B
Within ±15 degrees
Within ±15 degrees
Do not connect a branch unit vertically.
• In case of using the Y-shaped branching joint for connecting between
outdoor units (Discharge gas joint and Suction gas joint), please keep the straight part of at least 500mm at the inlet.
500 mm
or more
Discharge side gas piping / Liquid piping
q Figure 1 q Figure 2
Correct Incorrect
Header unit A
Follower unit B
Follower unit C
Header unit A
Follower unit B
Follower unit C
<Upright connection of suction gas joint>
q Figure 5
Incorrect
Header unit A Follower unit B
Main pipe To indoor unit
Suction gas joint
Suction gas joint
A
Vertical line
A view
Unit
<When drawing pipes downward>
[Vertical connection of branch units]
q Figure 6 q Figure 7
Correct Incorrect
Header unitAFollower unitBFollower unit
C
Main pipe
To indoor unit
Liquid joint
Discharge gas joint
Suction side gas piping
q Figure 3 q Figure 4
Correct Incorrect
Header unit A
Main pipe To the indoor unit
Follower unit B
Suction gas joint
Follower unit C
Liquid joint
To indoor unit
Main pipe
Discharge gas joint
[Inverse connection of suction gas joint]
Header unit A
Main pipe To the indoor unit
Follower unit B
Suction gas joint
Follower unit C
Main pipe
L-shaped
pipe
To the indoor unit
Suction gas joint
Suction gas joint
Suction gas joint
26-EN25-EN
Loading...
+ 30 hidden pages