Toshiba MM-A0224HT, MM-A0280HT, MM-A0280HX SERVICE MANUAL

0 (0)
Toshiba MM-A0224HT, MM-A0280HT, MM-A0280HX SERVICE MANUAL

Modular Multi VRF System

Applications Manual

MMS-04AE-07-03

 

Contents

Page

Chapter

 

 

 

 

 

 

General Information

5

 

1

 

 

 

 

 

 

 

 

 

 

 

Indoor Units – General

15

 

2

 

 

 

 

 

 

 

 

 

 

 

4-Way Cassette

19

 

3

 

 

 

 

 

 

 

 

 

 

 

2-Way Cassette

29

 

4

 

 

 

 

 

 

 

 

 

 

 

Duct

33

 

5

 

 

 

 

 

 

 

 

 

 

 

Slim Duct

37

 

6

 

 

 

 

 

 

 

 

 

 

 

Ceiling

41

 

7

 

 

 

 

 

 

 

 

 

 

 

High Wall

45

 

8

 

 

 

 

 

 

 

 

 

 

 

Chassis

49

 

9

 

 

 

 

 

 

 

 

 

 

 

Low Wall

53

 

10

 

 

 

 

 

 

 

 

 

 

 

Capacity Correction

57

 

11

 

 

 

 

 

 

 

 

 

 

 

Outdoor Units

71

 

12

 

 

 

 

 

 

 

 

 

 

 

Piping Design

85

 

13

 

 

 

 

 

 

 

 

 

 

 

Controls

98

 

14

 

 

 

 

 

 

 

 

 

 

 

Electrical Wiring

113

 

15

 

 

 

 

 

 

 

 

 

 

 

Selection Example

120

 

16

 

 

 

 

 

 

 

 

 

 

 

Commissioning Procedure

132

 

17

 

 

 

 

 

4

General Information

Introduction

1

 

With the new Modular Multi System (MMS), Toshiba once again demonstrate that we are in touch with tomorrow. The design team looked to the future to develop a highly efficient, environmentally friendly system, with state of the art controls.

Linking the precision performance of their leading inverter technology with the functionality of fixed speed units,Toshiba have created a range of systems from 22.4 to 128.8 kW (8 to 46 hp). The inverter unit adjusts performance to match the desired output as each fixed speed unit operates as needed.

Modular Multi 2 pipe, heat pump and cooling only systems provide an economical solution to many of your heating and cooling needs and when combined with the Super Multi 3 pipe system, Toshiba covers the full spectrum of VRF applications.

5

General Information

Benefits of VRF

The Variable Refrigerant Flow (VRF) product segment is one of the fastest growing areas of the air conditioning industry due to the inherent flexibility of the system.

Specifiers are selecting this type of air conditioning product because it provides the economy and stability of a network system with the versatility of an independent system.

The system is ideal for variable load situations such as hotels, offices and shops.

VRF systems are compact and discreet which makes them ideal for applications when the air conditioning system is being retro-fitted to the existing building.

Since the air is conditioned locally there is no need for large ductwork throughout the building for the flow of heated/cooled air. Only small pipes are necessary to carry the refrigerant to the desired location. Because the air is cooled to the desired temperature at the point of use, the end user gets rapid, precise temperature control.

When integrated with control systems the performance can be optimised to achieve ultra low energy consumption, particularly when there is high diversity in the capacity demand.

Qualifies for enhanced

Capital Allowance

As a variable-speed drive system this product is on DEFRA’s Energy Technology Product list and entities the purchaser in the UK to a tax benefit under the ECA scheme, Further details are on the following website: www.eca.gov.uk

6

General Information

 

 

 

 

 

 

 

 

 

 

 

 

 

Benefits of the Modular Multi System

 

 

1

 

 

 

 

Environmentally Compatible

 

 

 

 

 

 

 

 

 

 

 

 

 

HFC Refrigerant

Toshiba is committed to designing and manufacturing products that will not harm our environment. All of our European air conditioning products use HFC refrigerants that have zero ozone depletion potential.

THE INVENTOR OF INVERTER-DRIVE AIRCON TECHNOLOGY

Refrigerant Detection and Containment System (RDC)TM

As an additional precaution an optional refrigerant detection system is available. This senses the air quality within a room and if refrigerant levels exceed preset limits, it will emit an audible alarm and transmit a signal that can activate auxiliary valves, isolating the indoor unit from the system and preventing further leakage to the environment.

Energy Efficiency

The inverter system reduces the energy consumption by adjusting output to match capacity demands.Toshiba’s research team has led the way in the development of inverter technology and continues to deliver products that are best in class.

7

General Information

Benefits of the Modular Multi System

Intelligent

Refrigerant Distribution System

Internal controls within each indoor unit monitor and manage the refrigerant flow through the system to optimise the distribution of refrigerant across the running units.This ensures consistent performance from all indoor units regardless of the number of units in service or the resistance of the piping network.

Pressure and Temperature Sensor Control

Checks pressure and refrigerant temperature of each indoor unit for optimal capacity control.

8

General Information

 

Benefits of the Modular Multi System

1

 

Interactive Controls

The system is available with Interactive Intelligence, Toshiba’s range of sophisticated controls.The userfriendly software with a Windows® based platform allows management of up to 1,024 indoor units (up to 64 zones with 16 units per zone).The entire air conditioning network can be programmed to meet the end user’s needs.These controls are interactive; two-way communication enables your system to send you regular updates through the internet via your PC or mobile telephone. Service engineers can be notified of system status and any necessary action can be taken before it becomes evident to the user.

Up to 64 zones (allowing up to 16 units per zone)

Energy Monitoring

The power consumption of each individual indoor unit can be monitored allowing energy bills for shared systems to be sub-divided across multiple occupants.

Building managers can identify high-use systems and investigate potential opportunities for energy savings.

Up to 16 gateway interfaces

An energy meter connected to each outdoor system measures its usage (kW/h) and the energy consumption is proportioned to the indoor units based on their capacity demand.

A billing package is already included with the software, which allows billing on a multiple-tariff basis.

Internet Access

This feature is ideal for building management services with more than one site.

Remote monitoring and control is possible for multiple users at any one time using Microsoft Internet Explorer®

Various levels of access are permitted for security

Immediate access to operating conditions and historical performance. Allows rapid response to user enquiries.

Diagnostics

The network can also be linked to DD III,Toshiba’s system interrogation software allows the service engineers to gain access to critical system parameters to monitor the functions of the unit.

9

General Information

Benefits of the Modular Multi System

Reliable

Toshiba Quality

Toshiba’s reputation for quality has been established over 125 years of delivering reliable products.We maintain the highest standards in every aspect of our business, to ensure total customer satisfaction and continuously search for new ways in which to improve our customer offering.Toshiba believe in listening to customers, and working with them to make our products and services the very best they can be.

Reliability by Design

Toshiba uses the latest techniques and analysis tools to build reliability into the products and the processes from the very outset. Our products are built to last and serve you well beyond the minimum specification requirements.

Oil Management System

The MMS has an oil-balancing network to ensure the oil is evenly distributed across the outdoor units; thereby extending the life of the product.This system is outlined in greater detail in chapter 12.

Diagnostics

Our advances in control and monitoring equipment have produced state of the art system maintenance, designed to minimise downtime. Interactive Intelligence and DD III allow the end user to monitor trends in performance data that might signal that action should be taken.

10

General Information

Benefits of the Modular Multi System

1

 

Versatile

lengthMaximum

branchfirstafter

lengthpipingMaximum

8F

differenceheightMaximum

unitsindoorbetween

7F

 

 

 

 

 

 

 

 

6F

 

 

 

 

 

5F

 

 

 

 

 

4F

 

 

 

 

 

3F

 

30m

 

 

 

2F

 

 

50m

100m

 

 

 

 

 

 

 

 

 

1F

 

 

Maximum height difference b/w

outdoor and indoor units

50m

Design Flexibility

The unique refrigerant distribution control allows for a wide variety of piping options:

Up to 40 indoor units per system

Allowable height difference between indoor and outdoor units 50 m (outdoor unit above) or 30 m (outdoor unit below)

Up to 30 m height difference between indoor units

Equivalent length of 125 m (100 m actual) between outdoor unit and furthest indoor unit

Vertical distance of up to 4m permitted between outdoor units

Total pipework network of up to 250 m

Piping Possibilities

The indoor unit network can be designed with Y-joints after headers and headers after headers. The possibilities are endless thanks to the refrigerant distribution system that compensates for the variation in pipe resistance and balances the flow across the entire network.

Y joint branch after header branch

Header branch after Y joint

(Toshiba unique technology)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Header branch after header branch (Toshiba unique technology)

Expandability

The system is modular so it can be expanded as needed. Installations can also be staged to allow sequential installation. This is ideal for refurbishment situations when disruption of business operation must be minimised. It also allows for flexibility should the floor layout be modified at a later date.

11

General Information

Benefits of the Modular Multi System

Economical

Installation Savings

There are potential installation savings with the MMS, due to the additional network piping possibilities and the reduction in the number of pipes connecting the outdoor units to the indoor network.

Capacity Range

The variation of outdoor unit combinations allows MMS to meet system capacity demands from 22.4 to 128.8 kW (8 to 46 hp) in nineteen increments. This allows the system capacity to match your exact needs, reducing product costs.

Overview of the 19 Modular Multi System Configurations

OUTDOOR SYSTEM

 

INVERTER

 

FIXED

 

 

Total connected code

CAPACITY

 

 

28 kW (10 hp)

22.4 kW (8 hp)

28 kW (10 hp)

22.4 kW (8 hp)

16 kW (6 hp)

Maximum No.

 

 

Cooling only (no heating)

Code

MM-A0280CT

MM-A0224CT

MM-A0280CX

MM-A0224CX

MM-A0160CX

of indoor

 

 

 

 

Cooling

Heating*

hp

MM-A0280HT

MM-A0224HT

MM-A0280HX

MM-A0224HX

MM-A0160HX

units

Min

Max

22.4

25.0

8

 

1

 

 

 

13

4

10.8

 

 

 

 

 

 

 

 

 

 

 

28.0

31.5

10

1

 

 

 

 

16

5

13.5

 

 

 

 

 

 

 

 

 

 

 

38.4

43.0

14

 

1

 

 

1

16

7

18.9

 

 

 

 

 

 

 

 

 

 

 

44.8

50.0

16

 

1

 

1

 

18

8

21.6

 

 

 

 

 

 

 

 

 

 

 

50.4

56.5

18

1

 

 

1

 

18

9

24.3

 

 

 

 

 

 

 

 

 

 

 

56.0

63.0

20

1

 

1

 

 

20

10

27.0

 

 

 

 

 

 

 

 

 

 

 

60.8

68.0

22

 

1

 

1

1

22

11

29.7

 

 

 

 

 

 

 

 

 

 

 

67.2

75.0

24

 

1

 

2

 

24

12

32.4

 

 

 

 

 

 

 

 

 

 

 

72.8

81.5

26

1

 

 

2

 

26

13

35.1

 

 

 

 

 

 

 

 

 

 

 

78.4

88.0

28

1

 

1

1

 

28

14

37.8

 

 

 

 

 

 

 

 

 

 

 

84.0

94.5

30

1

 

2

 

 

30

15

40.5

 

 

 

 

 

 

 

 

 

 

 

89.6

100.0

32

 

1

 

3

 

32

16

43.2

 

 

 

 

 

 

 

 

 

 

 

95.2

106.5

34

1

 

 

3

 

34

17

45.9

 

 

 

 

 

 

 

 

 

 

 

100.8

113.0

36

1

 

1

2

 

36

18

48.6

 

 

 

 

 

 

 

 

 

 

 

106.4

119.5

38

1

 

2

1

 

38

19

51.3

 

 

 

 

 

 

 

 

 

 

 

112.0

126.0

40

1

 

3

 

 

40

20

54.0

 

 

 

 

 

 

 

 

 

 

 

117.6

131.5

42

1

 

 

4

 

40

21

56.7

 

 

 

 

 

 

 

 

 

 

 

123.2

138.0

44

1

 

1

3

 

40

22

59.4

 

 

 

 

 

 

 

 

 

 

 

128.8

144.5

46

1

 

2

2

 

40

23

62.1

 

 

 

 

 

 

 

 

 

 

 

* Heating capacities only apply to heat pump systems

Conditions

The capacities are based on Eurovent conditions: Cooling: Indoor air entering temperature 27°C db, 19°C wb, outdoor air temperature 35°C db Heating: Indoor air entering temperature 20°C db, outdoor air temperature 7°C db, 6°C wb

Unit operating range

Indoor

Outdoor

Cooling

Cooling

 

 

Maximum: 32°C db, 22.5°C wb

Maximum: 43°C db

Minimum: 18°C db, 15.5°C wb

Minimum: -5°C db

 

 

Relative humidity:

 

 

 

Maximum: 80%

 

Heating:

 

 

 

Maximum: 29°C

 

Minimum: 15°C

 

990 mm

1700 mm

750 mm

12

General Information

Benefits of the Modular Multi System

1

 

Small Riser Space

Example for a 84 kW (30 hp) system

50% Reduction in Riser Space

Space Saving, Compact Design

The compact Modular Multi outdoor units have a small footprint so they can fit into tight working spaces, thus freeing premium floor space for other usage. A single set of pipes connects the outdoor series to the indoor unit network, minimising the riser space required.

Example for a 84kW (30HP) system

300mm

Smaller

than

1.55m

competitors

10mm

20mm

20mm

10mm

500mm

3.03m

Units will fit in 90% of the world's lifts

13

General Information

Benefits of the Modular Multi System

Applying the Modular Multi System is easy. The following flowchart outlines the basic steps of the process, which are typical for almost all air conditioning applications.This manual is structured with separate chapters focusing on each of the steps along with a separate chapter on each type of indoor unit.We have also included a chapter which outlines an example of an MMS application.

Zoning

Indoor unit selection

Capacity correction

As with all air conditioning applications, proper zoning is important. Indoor units connected to a common system should have similar loading characteristics, thus minimising the potential for conflicting demand.

Indoor units are selected based on the predicted heat load as well as the style and layout of the space to be air conditioned. Air distribution and sound level characteristics may also be factors for consideration.

Indoor unit capacity will be adjusted based on the expected length and height of pipe runs and environmental conditions.

Outdoor unit selection

Piping design

Controls selection

Wiring design

The outdoor unit capacity is then determined, based on the expected demand.This is calculated by summing the capacity of the indoor network and predicting the peak load.

The piping network for the indoor units will be based on the zoning requirements and building layout. Numerous options are available due to the flexibility of the system.

The controls selection is dependent on the specification. Toshiba has a wide range of control systems available and has collaborated with customers on the development of unique systems to meet specific application requirements.

Each of the indoor and outdoor units will have its own power supply. Control wiring requirements will be determined by the controls selection.

14

Indoor units

Intelligent Indoor Units

The Modular Multi System indoor units are compatible with both the Cooling Only and Heat Pump outdoor

2

units. The MMS dedicated indoor range has precise capacity control.

Each MMS indoor unit has the following additional components:

Pressure and temperature sensors to determine the superheat conditions of the refrigerant

A pulsed modulating valve (PMV) to optimise refrigerant flow

A printed circuit board to communicate system parameters and demand to the outdoor system

 

Pulsed modulating valve

Temperature sensors

 

Pressure sensor capillary

The added intelligence of the indoor units provides precise capacity control without a multi controller unit. Localised sensing of the refrigerant conditions and internal controls provide excellent performance in all conditions.The units compensate for the piping resistances allowing greater flexibility in piping design. Communication between the indoor and outdoor network means greater performance and efficiency as system output closely matches the demand of the indoor network.

Modular Multi System

Very good capacity control because of the indoor unit knows the exact superheat value through constant monitoring of the coil temperature sensors and the pressure sensor. This allows the PMVs to adjust and account for all resistance in the circuit and achieve the desired capacity.

Localised

Pressure measurement

Temperature measurement

Refrigerant flow adjustment

System compensates for high pipe resistance

15

Indoor Units

 

Model Type

 

Model

 

Capacity

 

Cooling

 

Heating

 

Height

 

Width

 

Depth

 

Weight

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Name

 

Code

 

Capacity

 

Capacity

 

mm

 

mm

 

mm

 

kg

 

 

 

 

 

 

 

 

 

 

kW

 

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4-way Cassette*

 

MM-U056

 

1.0

 

2.8

 

3.2

259

 

820

 

820

 

25

 

 

 

 

 

 

 

 

1.25

 

3.5

 

4.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

 

4.2

 

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.7

 

4.8

 

5.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.0

 

5.6

 

6.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MM-U080

 

2.5

 

6.7

 

8.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.0

 

8.0

 

9.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MM-U112

 

3.2

 

9.0

 

10.2

309

 

1230

 

820

 

43

 

 

 

 

 

 

 

 

4.0

 

11.2

 

12.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MM-U140

 

5.0

 

14.0

 

15.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Concealed Duct

 

MM-B056

 

1.0

 

2.8

 

3.2

345

 

770

 

875

 

39

 

 

 

 

 

 

 

 

1.25

 

3.5

 

4.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

 

4.2

 

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.7

 

4.8

 

5.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.0

 

5.6

 

6.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MM-B080

 

2.5

 

6.7

 

8.0

345

 

1070

 

875

 

53

 

 

 

 

 

 

 

 

3.0

 

8.0

 

9.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MM-B112

 

3.2

 

9.0

 

10.2

345

 

1420

 

875

 

58

 

 

 

 

 

 

 

 

4.0

 

11.2

 

12.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MM-B140

 

5.0

 

14.0

 

15.8

345

 

1420

 

875

 

62

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-way Cassette

 

MM-TU028

 

0.8

 

2.2

 

2.6

190

 

910

 

480

 

23

 

 

 

 

 

 

 

 

1.0

 

2.8

 

3.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MM-TU042

 

1.25

 

3.5

 

4.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

 

4.2

 

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MM-TU056

 

1.7

 

4.8

 

5.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.0

 

5.6

 

6.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High Wall*

 

MM-K/KR042

 

0.8

 

2.2

 

2.6

372

 

1150

 

226

 

20

 

 

 

 

 

 

 

 

1.0

 

2.8

 

3.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.25

 

3.5

 

4.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

 

4.2

 

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MM-K/KR056

 

1.7

 

4.8

 

5.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.0

 

5.6

 

6.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MM-K/KR080

 

2.5

 

6.7

 

8.0

372

 

1478

 

226

 

26

 

 

 

 

 

 

 

 

3.0

 

8.0

 

9.6

 

 

 

 

 

 

 

 

 

 

Ceiling*

 

MM-C/CR042

 

0.8

 

2.2

 

2.6

188

 

1030

 

640

 

24

 

 

 

 

 

 

 

 

1.0

 

2.8

 

3.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.25

 

3.5

 

4.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

 

4.2

 

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MM-C/CR056

 

1.7

 

4.8

 

5.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.0

 

5.6

 

6.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MM-C/CR080

 

2.5

 

6.7

 

8.0

188

 

1230

 

640

 

28

 

 

 

 

 

 

 

 

3.0

 

8.0

 

9.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MM-C/CR 112

 

4.0

 

11.2

 

12.8

240

 

1430

 

640

 

39

 

 

 

 

 

 

MM-C/CR140

 

5.0

 

14.0

 

15.8

240

 

1630

 

640

 

44

 

 

Floor Low Wall*

 

MM-S/SR056

 

1.0

 

2.8

 

3.2

640

 

1030

 

188

 

24

 

 

 

 

 

 

 

 

1.25

 

3.5

 

4.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

 

4.2

 

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.7

 

4.8

 

5.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.0

 

5.6

 

6.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MM-S/SR080

 

2.5

 

6.7

 

8.0

640

 

1230

 

188

 

28

 

 

 

 

 

 

 

 

3.0

 

8.0

 

9.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Chassis

 

MM-N028

 

0.8

 

2.2

 

2.6

600

 

750

 

230

 

21

 

 

 

 

 

 

 

 

1.0

 

2.8

 

3.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MM-N042

 

1.25

 

3.5

 

4.0

600

 

1050

 

230

 

25

 

 

 

 

 

 

 

 

1.5

 

4.2

 

4.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MM-N056

 

1.7

 

4.8

 

5.4

600

 

1050

 

230

 

29

 

 

 

 

 

 

 

 

2.0

 

5.6

 

6.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MM-N080

 

2.5

 

6.7

 

8.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.0

 

8.0

 

9.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Slim Duct

 

MM-SB028

 

0.8

 

2.2

 

2.6

220

 

800

 

500

 

22

 

 

 

 

 

 

 

 

1.0

 

2.8

 

3.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

* These units are available with infrared remote control. For the four-way cassette unit a separate infrared panel is required.

16

Indoor Units

De-rating

1.The Modular Multi indoor units have a de-rating option that can be implemented to match actual load

requirements.The full output range including the de-rated units is outlined in the table shown.

2

2.When an indoor unit is derated the initial opening pulse of the indoor unit PMV is adjusted according to the capacity rating.

3a. In cooling code, the PMV pulse is then adjusted along with the inverter compressor frequency to ensure optimum superheat conditions at each indoor unit.

3b. In heating mode, the PMV pulse is then adjusted along with the outdoor unit PMV & inverter frequency to ensure the optimum subcooling condition at each indoor unit.

Total Cooling kW

2.2

 

2.8

3.5

4.2

4.8

5.6

6.7

8.0

9.0

11.2

14.0

 

Sensible Cooling kW

1.7

 

2.1

2.6

3.2

3.6

4.2

5.0

6.0

6.8

8.4

10.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4-way Cassette

 

 

 

 

 

 

 

 

 

 

 

 

 

2-way Cassette

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Duct/Slim Duct*

 

 

 

 

 

 

 

 

 

 

 

 

 

High Wall

 

 

 

 

 

 

 

 

 

 

 

 

 

Ceiling

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Chassis

 

 

 

 

 

 

 

 

 

 

 

 

 

Floor/Low Wall

 

 

 

 

 

 

 

 

 

 

 

 

 

Heating kW

2.6

 

3.2

4.0

4.8

5.4

6.4

8.0

9.6

10.2

12.8

15.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Capacity Code Setting

0.8

 

1.0

1.25

1.5

1.7

2.0

2.5

3.0

3.2

4.0

5.0

 

STANDARD CAPACITY SETTING

 

OUTPUT ACHIEVED BY DE-RATING

 

 

 

 

 

* Slim Duct indoor unit available in 2.8 kW standard and 2.2 kW de-rated capacities

 

 

 

 

 

 

Note: Indoor unit system capacity may be between 50 and 135% of the connected outdoor units.

 

 

 

 

17

Indoor Units

Part Numbering

The indoor unit part numbering system is defined as follows:

 

 

 

MM

-

U

 

 

056

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Product Designation

 

 

Unit Type

 

 

 

Cooling Capacity (STD)

MM Modular Multi

 

 

B

Duct

 

 

 

028

2.8 kW

 

 

 

 

C

Ceiling

 

 

 

042

4.2 kW

 

 

 

 

 

 

 

F

Floor

 

 

 

056

5.6 kW

 

 

 

 

K

High Wall

 

 

 

080

8.0 kW

 

 

 

 

N

Chassis

 

 

 

112

11.2 kW

 

 

 

 

S

Low Wall

 

 

 

140

14.0 kW

 

 

 

 

SB

Slim Duct

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TU

2-way Cassette

 

 

 

 

 

 

 

 

 

 

U

4-way Cassette

 

 

 

 

 

 

 

 

 

 

An R next to the unit

 

 

 

 

 

 

 

 

 

 

designation indicates a unit

 

 

 

 

 

 

 

 

with an infrared controls

 

 

 

 

 

 

 

 

 

 

option

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Location Precautions

Avoid installing the indoor unit in the following locations:

Where there is danger of flammable gas leakages.

Where there are high concentrations of oil.

Where the atmosphere contains an excess of salt.

Where high concentrations of organic solvent are present.

Where a machine that generates high frequencies is operated.

Where the unit will not be horizontal.

Where the floor/wall/ceiling structure is unable to support the weight of the unit.

Where it is not possible to fix the unit hangers, e.g. window glass.

Locate the unit to ensure uniform circulation of conditioned air.

18

Four-Way Cassette

• Slim design

• Highly efficient drain pump

• 2-, 3- and 4-way air distribution

3

Ultra quiet

Slim one-piece easy-to-clean panel

Threaded drain connection as standard

Long-life washable air filter

Synchronised motor-driven louvres

Fresh air intake facility

Branch duct option

Easy access to components

Infrared controls option via panel RBC-UxxxPGR

Modular Multi dedicated indoor unit. Monitors pressure and temperature and adjusts refrigerant flow to optimise performance locally.

MODEL

 

MM-U056

 

 

 

MM-U080

MM-U112

MM-U140

Cooling Capacity

kW

2.8

3.5

4.2

4.8

5.6

6.7

8.0

9.0

11.2

14.0

 

 

 

 

 

 

 

 

 

 

 

 

Heating Capacity

kW

3.2

4.0

4.8

5.4

6.4

8.0

9.6

10.2

12.8

15.8

 

 

 

 

 

 

 

 

 

 

 

 

Capacity Code

 

1.0*

1.25*

1.5*

1.7*

2.0

2.5*

3.0

3.2*

4.0

5.0

 

 

 

 

 

 

 

 

 

 

 

 

Sensible Cooling

kW

2.1

2.6

3.2

3.6

4.2

5.0

6.0

6.8

8.4

10.5

 

 

 

 

 

 

 

 

 

 

 

 

Airflow Rate H

m3/h

1020

1020

1020

1020

1020

1260

1260

1750

1750

1860

Airflow Rate M

m3/h

890

890

890

890

890

1140

1140

1520

1520

1620

Airflow Rate L

m3/h

830

830

830

830

830

1020

1020

1360

1360

1510

Unit Weight

kg

25

25

25

25

25

25

25

43

43

43

 

 

 

 

 

 

 

 

 

 

 

 

Height

mm

259

259

259

159

259

259

259

309

309

309

 

 

 

 

 

 

 

 

 

 

 

 

Width

mm

820

820

820

820

820

820

820

1230

1230

1230

Depth

mm

820

820

820

820

820

820

820

820

820

820

Air Filter

 

Washable, 500 µm

 

 

 

 

 

 

 

Gas Connection

mm

ø12.7 (1/2”)

 

 

 

ø15.9 (5/8”)

ø19.0 (3/4”)

ø19.0 (3/4”)

Liquid Connection

mm

ø 6.4 (1/4”)

 

 

 

ø 9.5 (3/8”)

ø 9.5 (3/8”)

ø 9.5 (3/8”)

Drain Connection

mm

Male 25.4 (1” BSP)

 

 

 

 

 

 

 

PANEL TYPE

 

RBC-U264PG/PGR**(W)-E

 

 

 

RBC-U464PG/PGR**(W)-E

 

 

 

 

 

 

 

 

 

 

 

Air Filter

 

Washable - 500 µm

 

 

 

 

 

Washable - 500 µm

 

Panel Weight

kg

6

6

6

6

6

6

6

8

8

8

8

 

 

 

 

 

 

 

 

 

 

 

 

 

Panel Height

mm

20

20

20

20

20

20

20

20

20

20

20

 

 

 

 

 

 

 

 

 

 

 

 

 

Panel Width

mm

940

940

940

940

940

940

940

1350

1350

1350

1350

Panel Depth

mm

940

940

940

940

940

940

940

940

940

940

940

*Setting shown is de-rated and adjustment must be made during installation/commissioning.

**Panel with R designation has infrared controls

19

Four-Way Cassette

Acoustic Data

 

 

 

 

 

 

 

 

 

Sound

 

MM-U056

Sound Power Level (SWL) - dB

 

 

 

 

 

Pressure Level

 

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

SWL

SPL (dBA)

NC*

Low

38.3

36.5

27.7

24.8

21.9

16.1

16.5

37.5

32

22

Med

39.5

38.8

30.2

28.7

23.3

16.4

16.6

39.7

35

24

High

41.1

41.2

33.6

32.6

26.4

18.7

17.8

42.7

38

29

 

 

 

 

 

 

 

 

 

 

 

MM-U080

 

 

 

 

 

 

 

 

 

 

 

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

SWL

SPL (dBA)

NC*

 

 

 

 

 

 

 

 

 

 

 

Low

40.5

40.8

33.1

35.7

28.4

20.0

21.5

42.9

35

32

Med

43.1

45.4

38.1

36.9

30.4

22.5

21.9

46.4

39

33

High

44.0

48.1

40.7

39.4

32.6

25.0

21.3

48.9

43

36

 

 

 

 

 

 

 

 

 

 

 

MM-U112

 

 

 

 

 

 

 

 

 

 

 

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

SWL

SPL (dBA)

NC*

Low

45.4

41.6

37.7

33.1

26.0

18.9

20.1

44.4

37

29

Med

50.4

44.1

40.6

37.1

30.0

21.8

20.2

47.4

40

34

High

52.6

44.9

41.5

38.5

31.5

23.8

20.5

48.6

42

35

MM-U140

 

 

 

 

 

 

 

 

 

 

 

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

SWL

SPL (dBA)

NC*

 

 

 

 

 

 

 

 

 

 

 

Low

47.8

45.7

42.9

36.5

29.6

25.1

19.1

47.7

40

33

Med

51.8

46.8

45.7

40.0

32.0

26.0

19.8

50.0

43

36

High

52.8

47.4

45.6

40.5

32.9

26.8

19.9

50.6

45

37

* For all practical purposes NR and NC curves may be regarded as mutually interchangeable. (Ref: CIBSE Guide Vol. B, page12-4. )

dB(A)

50

MM-U056

 

 

 

dB(A)

50

 

 

 

 

 

 

40

 

 

 

 

 

 

40

Level

 

 

 

 

NC-40

 

Level

30

 

 

 

 

 

 

30

Pressure

 

 

 

 

NC-30

H

Pressure

 

 

 

 

 

 

M

 

20

 

 

 

 

 

L

20

 

 

 

 

NC-20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sound

10

 

 

 

 

NC-10

 

Sound

10

 

 

 

 

 

 

 

0

 

 

 

 

 

 

0

 

125

250

500

1000

2000 4000 8000

 

 

Frequency (Hz)

dB(A)

50

MM-U112

 

 

 

dB(A)

50

 

 

 

 

 

 

40

 

 

 

 

 

 

40

Level

 

 

 

 

NC-40

 

Level

30

 

 

 

 

 

H

30

 

 

 

 

 

M

Pressure

 

 

 

 

NC-30

Pressure

 

 

 

 

 

 

L

 

20

 

 

 

 

NC-20

 

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sound

10

 

 

 

 

NC-10

 

Sound

10

 

 

 

 

 

 

 

0

 

 

 

 

 

 

0

 

125

250

500

1000

2000 4000 8000

 

 

MM-U080

 

 

 

 

 

 

 

NC-40

H

 

 

 

 

 

 

 

 

 

 

M

 

 

 

 

NC-30

L

 

 

 

 

 

1.5m

 

 

 

 

NC-20

Microphone

 

 

 

 

 

 

 

 

 

NC-10

 

125

250

500

1000

2000 4000 8000

 

Frequency (Hz)

MM-U140

 

 

 

 

 

 

 

NC-40

H

 

 

 

 

M

 

 

 

 

 

 

 

 

 

 

L

 

 

 

 

NC-30

 

 

 

 

 

NC-20

 

 

 

 

 

NC-10

 

125

250

500

1000

2000 4000 8000

 

Frequency (Hz)

Frequency (Hz)

20

Four-Way Cassette

Air Distribution Control

Conditioned air can be distributed through 2, 3 or 4 sides of the unit to optimise the flow distribution in a room. Insulation blocks are included with the unit to close off the airflow to certain sides of the unit.The diagram below defines which sides of the unit may be closed for each of the capacities.

Choose the number of airflows that are required, depending on the shape of the room and the location of

3

the indoor unit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MM-U056/U080

 

 

 

MM-U112/U140

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3-way

3-way

3-way

3-way

3-way

2-way

3-way

2-way

2-way

It is not possible to block the airflow from the longer sides of the unit (U112/U140).

• Insert insulation blocks, which are supplied as

accessories, at each side where the airflow is Insulation Block not required as shown in the diagram

opposite.

In addition, a motorised louvre facility allows the air to be directed in either a pre-set or a sweep pattern. Cassettes also have a branch duct facility for better air distribution in irregular shaped rooms.The combination of these two features gives the occupants total control over air movement within the room, via an easy-to-use remote controller.

21

Four-Way Cassette

Air Distribution

Note: Air velocity data collected at high fan speed.

MM-U056

Air velocity (m/s)

2.7m

(m)

2

 

 

 

 

 

Height

 

1.0

 

1

0.5

 

 

 

 

 

 

 

 

0.3

0.1

 

 

 

MM-U080

Air velocity (m/s)

2.7m

(m)

2

 

 

 

 

 

Height

 

1.0

 

1

0.5

0.1

 

 

 

 

 

 

 

0.3

 

0

1

2

3

4

5

0

1

2

3

4

5

 

Distance (m)

 

 

 

Distance (m)

 

 

MM-U112

 

 

 

 

MM-U140

 

 

 

 

 

Air velocity (m/s)

 

 

 

Air velocity (m/s)

 

2.7m

(m)

2

Height

1

 

0

 

 

 

 

 

2.7m

 

 

 

 

 

 

1.0

 

 

 

(m)

2

 

 

 

 

 

 

 

 

 

 

Height

1

1.0

 

 

 

 

 

0.5

 

 

 

 

 

 

 

 

0.1

 

 

 

 

 

 

 

0.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.3

 

0.1

 

 

 

 

0.3

 

 

1

2

3

4

5

 

0

1

2

3

4

5

Distance (m)

Distance (m)

Design Features

Flexible Air Distribution

Conditioned air can be distributed through 2, 3 or 4 sides of the unit. In addition, a motorised louvre facility allows the air to be directed in either a pre-set or a sweep pattern. Cassettes also have a branch duct facility for better air distribution in irregular shaped rooms.The combination of these two features gives the occupants total control over air movement within the room via an easy-to-use remote controller.

Fresh Air Facility

An additional advantage of Toshiba’s 4-way cassettes is that outdoor air, as well as conditioned air, can be introduced into the room. (Tempering to 15°C minimum is recommended.)

Quiet Operation

Noise levels have been reduced dramatically, thanks to the specially designed fan inlet that smoothes the airstream as it flows into an aerofoil fan and aerodynamic louvres.

Performance Tuning

Units are preset to a standard setting, however capacity code adjustments can be made to optimise cooling or heating.

Precise Capacity Control

Each indoor unit has pressure and temperature sensors for localised monitoring of refrigerant condition. A pulsed modulating valve (PMV) controls the refrigerant flow and the capacity demand is communicated to the outdoor system. This ensures excellent performance at all conditions. A 3-speed fan controls the cooled airflow volume automatically or manually (4-speed heating mode). Even at the highest fan speed, the unit is quiet in operation.

Easy to Install and Maintain

The 4-way cassette can be concealed within most ceiling voids, with an ultra-thin 20 mm grille. This onepiece panel is easy to install. Its surface is easy to wipe clean, a feature it shares with the synchronised louvre blades.The long-life washable filter also minimises maintenance.

22

Four-Way Cassette

Dimensional Drawings

MM-U056, MM-U080

 

connection

 

connection

 

200

 

 

 

Refrigerantflare

 

Refrigerantflare

 

 

 

 

A)ø(Gas

ø(LiquidB)

140

 

 

 

73

 

 

 

 

 

 

 

 

 

185

170

100

 

 

 

holes)

 

 

 

 

 

 

 

connection plate3xø20

 

 

 

 

 

 

 

Wiring (Gland

(25.4mmBSPthreadedconnection)

 

 

80

 

 

138

pipeDrainconnection

 

 

 

 

 

 

 

 

 

 

 

 

240

 

 

 

246.5

Ceiling

 

 

195

 

 

 

 

4-M10

 

 

 

Hangingbolts

 

 

 

106

 

 

sides)

106

 

(both150ø

 

 

 

30

 

forsideducts

259

 

20

kout

 

39

Knoc

160

138

 

 

 

 

 

298

 

 

80

10

 

4-ø6

32 ø 100

Note: All dimensions are in mm.

 

940

940 (P anel dimension)

880 (Ceiling opening)

820 (External cassette dimension)

800 (Hanger bolt pitch)

195

268

405

400

536

 

40

 

 

 

 

 

30

 

 

 

 

ø 144

 

 

ø 200

 

 

 

6

 

 

ø 30

 

 

 

 

 

 

 

 

 

2

80

10

30

 

 

30

 

 

ø 150

 

 

 

ø6

 

 

 

ø 97

 

°

 

 

6-

 

 

 

 

 

 

 

 

 

 

45

 

 

size

 

 

180

size

 

 

 

ø

 

ductinletairFresh

 

180ø

ductoutletSide

 

 

45°

130

 

 

 

 

 

ø

 

 

 

 

ø

144

 

 

 

 

 

 

 

 

 

 

130

 

 

 

 

 

 

 

°

45°

 

130

 

45

 

 

940

Condensate pipe 1 ″ BSP threaded connection

536

620(Hangerboltpitch)

(Externalcassettedimension)

880(Ceilingopening)

940(Paneldimension)

 

 

820

 

 

inlet

130

30

reshair

 

 

F

 

 

 

 

 

MM-U080

15.9(5/8”)

6.4(1/4”)

U056 U080

12.7(1/2) 15.9(5/8)

6.4(1/4) 6.4(1/4)

MM-U056

12.7(1/2”)

6.4(1/4”)

Model(MM-)

øA

øB Dimensions mm

øA

øB

3

23

Four-Way Cassette

Dimensional Drawings

MM-U112, MM-U140

 

Refrigerantflareconnection

(Gasside19(3/4))

185

170

100

80

Hanging bolts 4-M10

941

106

Knock out for side ducts ø 150 (both sides)

flareconnection

9.5(3/8))

140

Refrigerant

side(Liquid

200

73

 

 

138

240

246.5 202 30

106

 

30

210

138

309

 

348

 

 

 

 

 

 

 

 

80

10

 

 

 

 

 

 

 

6-ø6

 

connection plate3xø20holes)

 

 

1350

 

 

 

 

 

Wiring (Gland

 

 

 

 

 

 

 

 

connection)

 

 

 

 

 

 

 

 

connectionpipeDrain BSP.4mm(25″threaded

940

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BSP

 

 

 

 

 

Ceiling

940 (P anel dimension)

Condensatepipe1″ threadedconnection

 

 

 

 

 

 

880 (Ceiling opening)

 

 

 

 

 

 

 

 

820 (External cassette dimension)

 

 

 

 

 

 

 

 

800 (Hanger bolt pitch)

 

 

 

 

 

 

 

Ceilingpanel

 

 

 

 

 

 

80

10

 

610 605

 

940

1030(Hangerboltpitch)

(Externalcassettedimension)

1290(Ceilingopening)

1350(Panelopening)

4-ø6

 

 

 

 

 

1230

 

100

 

 

 

 

 

 

 

 

ø

 

 

 

 

 

 

 

 

32

 

 

30

 

 

 

 

 

 

 

 

40

 

130

 

 

 

 

 

20

inlet

30

 

 

 

 

 

air

 

 

 

 

 

 

 

39

 

 

 

 

 

 

 

 

Fresh

 

 

 

 

 

 

 

ø 180

45 °

ø 200

 

6

 

30

 

ø 150

 

45°

size

ø180

outletduct

45°

 

Side

45 °

 

ø 144

 

 

ø 30

 

 

 

2

 

 

30

 

ø 97

 

130

ductsize

inlet

 

ø

ø

144

air

 

 

 

Fresh

 

 

130

130

 

15mmormore

 

Ceiling

1000 mm or more

 

 

1000 mm

1000 mm

Obstacle

or more

or more

Note: All dimensions are in mm.

24

Four-Way Cassette

Drain Piping

Precautions

Ensure that the entire indoor drain piping is correctly heat-insulated otherwise condensation may result. Also, insulate the section which connects it to the indoor unit.

If nylon cable ties are used to secure the insulation, take precautions not to over-tighten them because

3

deformation of the heat insulation will reduce its effectiveness.

 

Take care not to apply excessive force or pressure at the unit side where the drain piping exits the indoor

 

unit.

 

 

 

 

 

The drain piping must be placed on a downward gradient (1/100 or greater) and there should be no

 

upward or downward curves in the pipe which obstruct the drainage, unless a drain pump is employed.

 

The drain pipe should be sufficiently supported to prevent warpage.

 

When one drainage system is used for a multiple of indoor units, install the piping as shown below:

 

 

15-20 m

Upward curve

Make this distance as long as possible – approx. 100 mm

 

 

Support clamp X

 

 

 

 

 

Insulator

 

 

 

 

 

Downward curve

 

Downward gradient 1/100 or greater

 

Downward gradient 1/100 or greater

 

 

 

 

 

Piping Material and Heat Insulator

 

 

 

 

Heat Insulator*

Hard PVC pipe**

*

Heat Insulator:

 

 

 

 

 

Polyethylene foam (thickness 6 mm)

 

 

 

 

**

Piping Material:

 

 

 

 

 

Hard PVC pipe nominal diameter inside Ø20 mm

 

Drain pan

Drain hose

Hard PVC adhesive

 

 

 

Connection to the unit is via a 1” BSP male connection – to ensure a waterproof seal, PTFE thread tape should be used.The maximum lift of the condensate pump from the drain outlet is 360 mm and the maximum overall lift from the underside of the ceiling to the centre of the drain piping is 600 mm.These values must not be exceeded, otherwise unit flooding will occur when the drain pump is switched off.

360 mm (max.) 600 mm (max.)

100 mm (max.)

Cassette

Ceiling

25

Four-Way Cassette

Fresh Air Inlet

These models have a cut out hole in the cabinet to enable outdoor air to enter the indoor unit at a maximum rate of 10% of selected air by volume. Before installing the unit, remove the cut out hole and insulation block and fit a spigot to connect the duct before hanging the unit. (Tempering incoming air to 15°C minimum is recommended.)

Details of Cut-Out Hole

The cut out hole is a ‘D’ shape half-cut hole on the side of the indoor unit, located on the side opposite the pipework.

Drain Pan

Insulation Block

Fresh Air Inlet

Add a spigot to the side of the indoor unit and attach using the 4 screw holes as shown below:

32 ø100

130

ø144

130

4-ø6

80

 

 

 

 

10

 

ø130

ø130

ø144

ø97

 

30

 

 

2

 

Note: All dimensions are in mm.

26

Four-Way Cassette

Air Outlet Duct

A portion of airflow can be redirected via the air outlet duct. Before installing the unit, remove the cut out hole and fit a spigot to connect the duct before hanging the unit.

Details of Cut-Out Hole

The cut out hole is a rectangular shape half-cut hole located on two sides if the unit.

3

Air outlet duct

Add a spigot to the side of the indoor unit and attach using the 6 screw holes as shown:

45°

ø 180

45°

45°

6-ø6

80

 

 

10

ø180

ø150

ø200

45°

30

 

6

Air Outlet Spigot (ø150)

Note: All dimensions are in mm.

27

28

Two-Way Cassette

Designed and developed for use with the nonozone depleting refrigerant, R407C

Quiet in operation

Adjustable air distribution

Compact – 190 mm void space required

4

Motorised louvres

Ideal for refurbishment and new build

Easy to install and maintain

Slim-line grille (25 mm)

Modular Multi dedicated indoor unit. Monitors pressure and temperature and adjusts refrigerant flow to optimise performance locally.

MODEL

 

MM-TU028

 

MM-TU042

 

MM-TU056

 

Cooling Capacity

kW

2.2

2.8

3.5

4.2

4.8

5.6

 

 

 

 

 

 

 

 

Heating Capacity

kW

2.6

3.2

4.0

4.8

5.4

6.4

Capacity Code

 

0.8*

1.0

1.25*

1.5

1.7*

2.0

 

 

 

 

 

 

 

 

Sensible Cooling

kW

1.7

2.1

2.6

3.2

3.6

4.2

Airflow Rate H

m3/h

550

550

700

700

750

750

Airflow Rate M

m3/h

500

500

635

635

681

681

Airflow Rate L

m3/h

445

445

567

567

607

607

Weight

kg

23

23

23

23

23

23

 

 

 

 

 

 

 

 

Height

mm

190

190

190

190

190

190

Width

mm

910

910

910

910

910

910

 

 

 

 

 

 

 

 

Depth

mm

480

480

480

480

480

480

 

 

 

 

 

Air Filter

 

Washable - 500 µm

Washable - 500 µm

Washable - 500 µm

Gas Connection

mm

ø12.7 (1/2")

 

ø12.7 (1/2")

 

ø12.7 (1/2")

 

 

 

 

 

 

 

 

 

Liquid Connection

mm

ø6.4 (1/4")

 

ø6.4 (1/4")

 

ø6.4 (1/4")

 

Drain Connection

mm

ø25.5 OD

 

ø25.5 OD

 

ø25.5 OD

 

PANEL TYPE

 

RBC-U134PG(W)-E

RBC-U134PG(W)-E

RBC-U134PG(W)-E

Panel Dimensions

 

 

 

 

 

 

 

Height

mm

25

25

25

25

25

25

Width

mm

1050

1050

1050

1050

1050

1050

Depth

mm

550

550

550

550

550

550

Unit Weight

kg

23

23

23

23

23

23

 

 

 

 

 

 

 

 

Panel Weight

kg

4.5

4.5

4.5

4.5

4.5

4.5

 

 

 

 

 

 

 

 

Panel Depth

 

 

 

 

 

 

 

Below Ceiling

mm

25

25

25

25

25

25

 

 

 

 

 

 

Panel Colour

 

Silky White (Munsell 2.9Y8.9/0.8)

 

 

 

 

 

 

 

 

 

 

 

Air Filter

 

Washable

 

 

 

 

 

29

Two-Way Cassette

Acoustic Data

 

 

 

 

 

 

 

 

 

Sound

 

MM-TU028

Sound Power Level (SWL) - dB

 

 

 

 

 

Pressure Level

 

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

SWL

SPL (dBA)

NC*

Low

31.0

35.3

30.5

24.6

20.0

19.8

21.3

37.1

34

25

Med

31.5

36.9

35.2

27.5

21.3

19.2

21.4

39.0

36

25

High

38.0

41.1

38.5

35.7

26.6

20.6

22.0

45.0

40

32

MM-TU042

 

 

 

 

 

 

 

 

 

 

 

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

SWL

SPL (dBA)

NC*

Low

25.5

36.8

33.2

29.6

23.6

21.4

21.7

39.8

34

25

Med

29.7

39.7

35.5

33.1

26.1

21.9

21.7

42.6

36

29

High

35.5

43.1

39.4

39.0

32.0

23.9

20.8

47.3

40

35

 

 

 

 

 

 

 

 

 

 

 

MM-TU056

 

 

 

 

 

 

 

 

 

 

 

125 Hz

250 Hz

500 Hz

1000 Hz

2000 Hz

4000 Hz

8000 Hz

SWL

SPL (dBA)

NC*

 

 

 

 

 

 

 

 

 

 

 

Low

27.0

36.7

33.9

34.2

24.6

20.6

21.1

41.6

35

31

Med

29.8

38.8

35.0

35.8

25.6

19.0

17.8

43.1

37

32

High

36.0

42.5

38.9

40.4

31.1

23.2

18.8

47.7

41

36

 

 

 

 

 

 

 

 

 

 

 

* For all practical purposes NR and NC curves may be regarded as mutually interchangeable. (Ref: CIBSE Guide Vol. B page B12-4.)

dB(A)

50

MM-TU028

 

 

 

dB(A)

50

 

 

 

 

 

 

40

 

 

 

 

 

 

40

Level

 

 

 

 

NC-40

H

Level

 

 

 

 

 

 

 

30

 

 

 

 

 

M

30

Pressure

 

 

 

 

NC-30

Pressure

20

 

 

 

 

 

L

20

 

 

 

 

NC-20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sound

10

 

 

 

 

NC-10

 

Sound

10

 

 

 

 

 

 

 

0

 

 

 

 

 

 

0

 

125

250

500

1000

2000 4000 8000

 

 

MM-TU042

 

 

 

 

 

 

 

NC-40

H

 

 

 

 

 

M

 

 

 

 

NC-30

L

 

 

 

 

 

 

 

 

 

NC-20

 

 

 

 

 

NC-10

 

125

250

500

1000

2000 4000 8000

 

Frequency (Hz)

Frequency (Hz)

dB(A)

50

MM-TU056

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Level

40

 

 

 

 

NC-40

M

 

 

 

 

 

 

 

H

Pressure

30

 

 

 

 

NC-30

L

20

 

 

 

 

NC-20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Sound

10

 

 

 

 

 

1.5m

 

 

 

 

NC-10

Microphone

 

 

 

 

 

 

 

 

 

 

 

 

0

125

250

500

1000

2000 4000 8000

 

Frequency (Hz)

30

Two-Way Cassette

Dimensional Drawings

MM-TU028, MM-TU042, MM-TU056

Refrigerantflareconnection

 

Refrigerantflareconnection

12.7(1/2))ø(Gas

Wiringconnection

131

 

anelouterdimension1050

20

40

110

66

73

 

 

 

(Liquidø6.4(1/4))

267

186

96

 

Ceilingopening1010

Hangboltpitch930

Unitdimension840

90

200

600

Minimum

 

pipejoint

ø25.5

170

 

 

 

 

P

 

 

70

40

 

 

 

installation

Drain

 

 

 

 

156

 

 

20

40

Hang bolt pitch 410

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit dimension 480

 

 

 

 

 

 

 

 

190

25

 

 

 

 

Ceiling opening 510

 

 

and

 

 

 

 

 

 

 

 

 

Panel outer dimension 550

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hangerbolt

(4-M10)

 

 

 

131

 

 

 

 

 

 

 

600

Minimum

requiredforservice

 

 

 

 

 

 

 

 

 

 

 

 

ViewA

 

 

Space

 

 

840

 

 

 

 

A

 

 

1050

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

TOSHIBA

 

 

 

 

 

 

70

 

 

 

 

 

 

 

 

 

 

 

 

 

190

550

600 Minimum

 

110

480

290

 

80

Note: All dimensions are in mm.

4

31

Loading...
+ 105 hidden pages