Toshiba MMD-AP0186BHP1-E, MMD-AP0126BHP1-E, MMD-AP0246BHP1-E, MMD-AP0276BHP1-E, MMD-AP0306BHP1-E Service Manual

...
0 (0)
SERVICE MANUAL
AIR-CONDITIONER
MULTI TYPE
INDOOR UNIT
< Concealed Duct Standard Type >
FILE NO. SVM-16043
MMD-AP0076BHP1-E MMD-AP0096BHP1-E MMD-AP0126BHP1-E MMD-AP0156BHP1-E MMD-AP0186BHP1-E
MMD-AP0076BHP1-TR
MMD-AP0096BH
MMD-AP0126BHP1-TR MMD-AP0156BHP1-TR MMD-AP0186BHP1-TR
MMD-AP02 MMD-AP0276BHP1-TR MMD-AP0306BHP1-TR MMD-AP0366BHP1-TR MMD-AP0486BHP1-TR MMD-AP0566BHP1-TR
46BHP1-TR
P1-TR
R410A
April
201
6
CONTENTS
PRECAUTIONS FOR SAFETY ................................................................................ 6
1. SPECIFICATIONS .................................................................................................. 13
2. AIR DUCTING WORK............................................................................................. 15
3. CONSTRUCTION VIEWS (EXTERNAL VIEWS).................................................... 17
4. WIRING DIAGRAMS............................................................................................... 19
5. PARTS RATING...................................................................................................... 20
6. REFRIGERANT CYCLE DIAGRAM ....................................................................... 21
7. CONTROL OUTLINE.............................................................................................. 22
8. APPLIED CONTROL AND FUNCTIONS
(INCLUDING CIRCUIT CONFIGURATION) .......................................................... 28
8-1. Indoor controller block diagram ........................................................................................ 28
8-1-1. In Case of Connection of Wired (Simple) Remote Controller ............................. 28
8-1-2. In Case of Connection of Wireless Remote Controller ....................................... 29
8-1-3. Connection of Both Wired (Simple) Remote Controller and Wireless Remote
Controller ................................................................................................................ 30
8-2. Indoor Print Circuit Board MCC-1631 ...............
Optional connector specifications of indoor P.C. board................................................. 32
8-3.
8-4. Test operation of indoor unit .............................................................................................33
8-5. Method to set indoor unit function DN code .................................................................... 34
8-6. Applied control of indoor unit ........................................................................................... 37
9. TROUBLESHOOTING............................................................................................ 53
9-1. Overview .............................................................................................................................. 53
9-2. Troubleshooting method ....................................................................................................54
9-3. Troubleshooting based on information displayed on remote controller ....................... 60
9-4. Check codes displayed on remote controller and SMMS outdoor unit
(7-segment display on I/F board) and locations to be checked .................................... 65
9-5. Sensor characteristics ....................................................................................................... 84
10. P.C. BOARD EXCHANGE PROCEDURES.......................................................... 85
10-1. Replacement of indoor P.C. boards................................................................................. 85
11. DETACHMENTS................................................................................................... 91
12. EXPLODED VIEWS AND PARTS LIST ............................................................... 98
................................................................ 31
– 2 –
Original instruction
Please read carefully through these instructions that contain important information which complies with the “Machinery” Directive (Directive 2006/42/EC), and ensure that you understand them.
Generic Denomination: Air Conditioner
Definition of Qualified Installer or Qualified Service Person
The air conditioner must be installed, maintained, repaired and removed by a qualified installer or qualified service person. When any of these jobs is to be done, ask a qualified installer or qualified service person to do them for you. A qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the table below.
Agent Qualifications and knowledge which the agent must have
• The qualified installer is a person who installs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified installer who is allowed to do the electrical work involved in installation, relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he
Qualified installer
or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation, relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
Qualified service person
• The qualified service person is a person who installs, repairs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, repair, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified service person who is allowed to do the electrical work involved in installation, repair, relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to do the refrigerant handling and piping work involved in installation, repair, relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
– 3 –
Definition of Protective Gear
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing. In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below. Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns, electric shocks and other injuries.
Work undertaken
All types of work
Electrical-related work
Work done at heights (50 cm or more)
Transportation of heavy objects
Repair of outdoor unit
Protective gloves ‘Safety’ working clothing
Gloves to provide protection for electricians and from heat Insulating shoes Clothing to provide protection from electric shock
Helmets for use in industry
Shoes with additional protective toe cap
Gloves to provide protection for electricians and from heat
Protective gear worn
The important contents concerned to the safety are described on the product itself and on this Service Manual.
Please read this Service Manual after understanding the described items thoroughly in the following contents (Indications / Illustrated marks), and keep them.
[Explanation of indications]
Indication Explanation
DANGER
WARNING
CAUTION
Indicates contents assumed that an imminent danger causing a death or serious injury of the repair engineers and the third parties when an incorrect work has been executed.
Indicates possibilities assumed that a danger causing a death or serious injury of the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
Indicates contents assumed that an injury or property damage (*) may be caused on the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
* Property damage: Enlarged damage concerned to property, furniture, and domestic animal / pet
[Explanation of illustrated marks]
Indication Explanation
Indicates prohibited items (Forbidden items to do) The sentences near an illustrated mark describe the concrete prohibited contents.
Indicates mandatory items (Compulsory items to do) The sentences near an illustrated mark describe the concrete mandatory contents.
Indicates cautions (Including danger / warning) The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.
– 4 –
Warning Indications on the Air Conditioner Unit
[Confirmation of warning label on the main unit]
Confirm that labels are indicated on the specified positions If removing the label during parts replace, stick it as the original.
Warning indication Description
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing this panel.
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing this panel.
CAUTION
Do not touch the aluminium fins of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
CAUTION
Do not climb onto the fan guard.
Doing so may result in injury.
CAUTION
Do not touch the aluminium fins of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
CAUTION
Do not climb onto the fan guard.
Doing so may result in injury.
– 5 –
PRECAUTIONS FOR SAFETY
The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual.
DANGER
Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breaker for both the indoor and outdoor units to the OFF position. Otherwise, electric shocks may result.
Before opening the electrical box cover of the indoor unit or service panel of the outdoor unit, set the circuit breaker to the OFF position. Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with the interior parts. Only a qualified installer (*1) or qualified service person (*1) is allowed to remove the intake grille of the indoor unit or service panel of the outdoor unit and do the work required.
Before opening the suction board cover, set the circuit breaker to the OFF position. Failure to set the circuit breaker to the OFF position may result in injury through contact with the rotation parts. Only a qualified installer (*1) or qualified service person (*1) is allowed to remove the suction board
Tu r n o f f
braeaker
Electric
shock hazard
Prohibition
Stay on
protection
cover and do the work required.
Before starting to repair the outdoor unit fan or fan guard, be absolutely sure to set the circuit breaker to the OFF position, and place a “Work in progress” sign on the circuit breaker.
When cleaning the filter or other parts of the indoor unit, set the circuit breaker to OFF without fail, and place a “Work in progress” sign near the circuit breaker before proceeding with the work.
When you have noticed that some kind of trouble (such as when an error display has appeared, there is a smell of burning, abnormal sounds are heard, the air conditioner fails to cool or heat or water is leaking) has occurred in the air conditioner, do not touch the air conditioner yourself but set the circuit breaker to the OFF position, and contact a qualified service person. Take steps to ensure that the power will not be turned on (by marking “out of service” near the circuit breaker, for instance) until qualified service person arrives. Continuing to use the air conditioner in the trouble status may cause mechanical problems to escalate or result in electric shocks or other failure.
When you access inside of the service panel to repair electric parts, wait for about five minutes after turning off the breaker. Do not start repairing immediately.Otherwise you may get electric shock by touching terminals of high-voltage capacitors. Natural discharge of the capacitor takes about five minutes.
When checking the electric parts, removing the cover of the electric parts box of Indoor Unit and/or service panel of Outdoor Unit inevitably to determine the failure, use gloves to provide protection for electricians, insulating shoes, clothing to provide protection from electric shock and insulating tools. Be careful not to touch the live part. Electric shock may result. Only “Qualified service person” is allowed to do this work.
Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work is being carried out. There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
When checking the electric parts, removing the cover of the electric parts box of Indoor Unit and/or front panel of Outdoor Unit inevitably to determine the failure, put a sign “Do not enter” around the site before the work. Failure to do this may result in third person getting electric shock.
Before operating the air conditioner after having completed the work, check that the electrical parts box cover of the indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may receive an electric shock if the power is turned on without first conducting these checks.
If, in the course of carrying out repairs, it becomes absolutely necessary to check out the electrical parts with the electrical parts box cover of one or more of the indoor units and the service panel of the outdoor unit removed in order to find out exactly where the trouble lies, wear insulated heat-resistant gloves, insulated boots and insulated work overalls, and take care to avoid touching any live parts. You may receive an electric shock if you fail to heed this warning. Only qualified service person (*1) is allowed to do this kind of work.
– 6 –
WARNIG
General
Before starting to repair the air conditioner, read carefully through the Service Manual, and repair the air conditioner by following its instructions.
Only qualified service person (*1) is allowed to repair the air conditioner. Repair of the air conditioner by unqualified person may give rise to a fire, electric shocks, injury, water leaks and / or other problems.
Do not use any refrigerant different from the one specified for complement or replacement. Otherwise, abnormally high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product or an injury to your body.
Only a qualified installer (*1) or qualified service person (*1) is allowed to carry out the electrical work of the air conditioner. Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and / or electrical leaks.
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing.
To connect the electrical wires, repair the electrical parts or undertake other electrical jobs, wear gloves to provide protection for electricians, insulating shoes and clothing to provide protection from electric shocks. Failure to wear this protective gear may result in electric shocks.
Electrical wiring work shall be conducted according to law and regulation in the community and installation manual. Failure to do so may result in electrocution or short circuit.
Use wiring that meets the specifications in the Installation Manual and the stipulations in the local regulations and laws. Use of wiring which does not meet the specifications may give rise to electric shocks, electrical leakage, smoking and/or a fire.
Only a qualified installer (*1) or qualified service person (*1) is allowed to undertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work.
When working at heights, use a ladder which complies with the ISO 14122 standard, and follow the procedure in the ladder’s instructions. Also wear a helmet for use in industry as protective gear to undertake the work.
Before working at heights, put a sign in place so that no-one will approach the work location, before proceeding with the work. Parts and other objects may fall from above, possibly injuring a person below. While carrying out the work, wear a helmet for protection from falling objects.
When executing address setting, test run, or troubleshooting through the checking window on the electric parts box, put on insulated gloves to provide protection from electric shock. Otherwise you may receive an electric shock.
When the first filter comes out without connected to the other one, insert it once more to connectthe two filters together and pull out them as connected. Do not insert hands to take out the second filter. You may injure Yourself.
Do not touch the aluminum fin of the outdoor unit. You may injure yourself if you do so. If the fin must be touched for some reason, first put on protective gloves and safety work clothing, and then proceed.
Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects may fall off of the outdoor unit and result in injury.
Use forklift to carry in the air conditioner units and use winch or hoist at installation of them.
When transporting the air conditioner, wear shoes with protective toe caps, protective gloves and other protective clothing.
When transporting the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if the bands should break.
Be sure that a heavy unit (10 kg or heavier) such as a compressor is carried by two persons.
This air conditioner has passed the pressure test as specified in IEC 60335-2-40 Annex EE.
Check earth
wires.
Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the main unit, otherwise an electric shock is caused when a leak occurs.If the earth wire is not correctly connected, contact an electric engineer for rework.
After completing the repair or relocation work, check that the ground wires are connected properly.
Be sure to connect earth wire. (Grounding work) Incomplete grounding causes an electric shock. Do not connect ground wires to gas pipes, water pipes, and lightning rods or ground wires for telephone wires.
– 7 –
Prohibition of
modification.
Use specified
parts.
Do not bring
a child close
to the
equipment.
Insulating measures
No fire
Refrigerant
Do not modify the products.Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury.
When any of the electrical parts are to be replaced, ensure that the replacement parts satisfy the specifications given in the Service Manual (or use the parts contained on the parts list in the Service Manual). Use of any parts which do not satisfy the required specifications may give rise to electric shocks, smoking and / or a fire.
If, in the course of carrying out repairs, it becomes absolutely necessary to check out the electrical parts with the electrical parts box cover of one or more of the indoor units and the service panel of the outdoor unit removed in order to find out exactly where the trouble lies, put a sign in place so that no­one will approach the work location before proceeding with the work. Third-party individuals may enter the work site and receive electric shocks if this warning is not heeded.
Connect the cut-off lead wires with crimp contact, etc., put the closed end side upward and then apply a watercut method, otherwise a leak or production of fire is caused at the users’ side.
When performing repairs using a gas burner, replace the refrigerant with nitrogen gas because the oil that coats the pipes may otherwise burn. When repairing the refrigerating cycle, take the following measures.
1) Be attentive to fire around the cycle. When using a gas stove, etc., be sure to put out fire before work; otherwise the oil mixed with refrigerant gas may catch fire.
2) Do not use a welder in the closed room. When using it without ventilation, carbon monoxide poisoning may be caused.
3) Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may catch the inflammables.
The refrigerant used by this air conditioner is the R410A.
Check the used refrigerant name and use tools and materials of the parts which match with it. For the products which use R410A refrigerant, the refrigerant name is indicated at a position on the outdoor unit where is easy to see. To prevent miss-charging, the route of the service port is changed from one of the former R22.
Do not use any refrigerant different from the one specified for complement or replacement. Otherwise, abnormally high pressure may be generated in the refrigeration cycle, which may result in a failure or explosion of the product or an injury to your body.
For an air conditioner which uses R410A, never use other refrigerant than R410A. For an air conditioner which uses other refrigerant (R22, etc.), never use R410A. If different types of refrigerant are mixed, abnormal high pressure generates in the refrigerating cycle and an injury due to breakage may be caused.
When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge the air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge the air completely may cause the air conditioner to malfunction.
Do not charge refrigerant additionally. If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating cycle resulted in cause of breakage or injury. Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute vacuuming, and then newly recharge the specified amount of liquid refrigerant. In this time, never charge the refrigerant over the specified amount.
When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant or air other than R410A into the specified refrigerant. If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating cycle resulted in cause of injury due to breakage.
After installation work, check the refrigerant gas does not leak. If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
Never recover the refrigerant into the outdoor unit. When the equipment is moved or repaired, be sure to recover the refrigerant with recovering device. The refrigerant cannot be recovered in the outdoor unit; otherwise a serious accident such as breakage or injury is caused.
– 8 –
Assembly /
Wiring
Insulator
check
Ventilation
Compulsion
Check after
repair
After repair work, surely assemble the disassembled parts, and connect and lead the removed wires as before. Perform the work so that the cabinet or panel does not catch the inner wires. If incorrect assembly or incorrect wire connection was done, a disaster such as a leak or fire is caused at user’s side.
After the work has finished, be sure to use an insulation tester set (500 V Megger) to check the resistance is 1 MΩ or more between the charge section and the non-charge metal section (Earth position). If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.
When the refrigerant gas leaks during work, execute ventilation. If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the refrigerant and the closed room full with gas is dangerous because a shortage of oxygen occurs. Be sure to execute ventilation.
If refrigerant gas has leaked during the installation work, ventilate the room immediately. If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.
After installation work, check the refrigerant gas does not leak. If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
When the refrigerant gas leaks, find up the leaked position and repair it surely. If the leaked position cannot be found up and the repair work is interrupted, pump-down and tighten the service valve, otherwise the refrigerant gas may leak into the room. The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous. When installing equipment which includes a large amount of charged refrigerant such as a multi air conditioner in a sub-room, it is necessary that the density does not the limit even if the refrigerant leaks. If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused.
Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may cause a crack in the flare nut after a long period, which may result in refrigerant leakage.
Nitrogen gas must be used for the airtight test.
The charge hose must be connected in such a way that it is not slack.
For the installation / moving / reinstallation work, follow to the Installation Manual. If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shock or fire is caused.
Once the repair work has been completed, check for refrigerant leaks, and check the insulation resistance and water drainage. Then perform a trial run to check that the air conditioner is running properly.
After repair work has finished, check there is no trouble. If check is not executed, a fire, electric shock or injury may be caused. For a check, turn off the power breaker.
After repair work (installation of front panel and cabinet) has finished, execute a test run to check there is no generation of smoke or abnormal sound. If check is not executed, a fire or an electric shock is caused. Before test run, install the front panel and cabinet.
Be sure to fix the screws back which have been removed for installation or other purposes.
Do not
operate the
unit with the
valve closed.
Check after
reinstallation
Check the following matters before a test run after repairing piping.
• Connect the pipes surely and there is no leak of refrigerant.
• The valve is opened.
Running the compressor under condition that the valve closes causes an abnormal high pressure resulted in damage of the parts of the compressor and etc. and moreover if there is leak of refrigerant at connecting section of pipes, the air is sucked and causes further abnormal high pressure resulted in burst or injury.
Only a qualified installer (*1) or qualified service person (*1) is allowed to relocate the air conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and / or vibration may result.
Check the following items after reinstallation.
1) The earth wire is correctly connected.
2) The power cord is not caught in the product.
3) There is no inclination or unsteadiness and the installation is stable.
If check is not executed, a fire, an electric shock or an injury is caused.
When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in reputing, injury, etc.
– 9 –
Cooling check
Installation
When the service panel of the outdoor unit is to be opened in order for the compressor or the area around this part to be repaired immediately after the air conditioner has been shut down, set the circuit breaker to the OFF position, and then wait at least 10 minutes before opening the service panel. If you fail to heed this warning, you will run the risk of burning yourself because the compressor pipes and other parts will be very hot to the touch. In addition, before proceeding with the repair work, wear the kind of insulated heat-resistant gloves designed to protect electricians.
Take care not to get burned by compressor pipes or other parts when checking the cooling cycle while running the unit as they get heated while running. Be sure to put on gloves providing protection for heat.
When the service panel of the outdoor unit is to be opened in order for the fan motor, reactor, inverter or the areas around these parts to be repaired immediately after the air conditioner has been shut down, set the circuit breaker to the OFF position, and then wait at least 10 minutes before opening the service panel. If you fail to heed this warning, you will run the risk of burning yourself because the fan motor, reactor, inverter heat sink and other parts will be very hot to the touch. In addition, before proceeding with the repair work, wear the kind of insulated heat-resistant gloves designed to protect electricians.
Only a qualified installer or service person is allowed to do installation work. Inappropriate installation may result in water leakage, electric shock or fire.
Before starting to install the air conditioner, read carefully through the Installation Manual, and follow its instructions to install the air conditioner.
Be sure to use the company-specified products for the separately purchased parts. Use of non­specified products may result in fire, electric shock, water leakage or other failure. Have the installation performed by a qualified installer.
Do not supply power from the power terminal block equipped on the outdoor unit to another outdoor unit. Capacity overflow may occur on the terminal block and may result in fire.
Do not install the air conditioner in a location that may be subject to a risk of expire to a combustible gas. If a combustible gas leaks and becomes concentrated around the unit, a fire may occur.
Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure themselves or receive electric shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running.
Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations and laws.
Install the circuit breaker where it can be easily accessed by the qualified service person (*1).
If you install the unit in a small room, take appropriate measures to prevent the refrigerant from exceeding the limit concentration even if it leaks. Consult the dealer from whom you purchased the air conditioner when you implement the measures. Accumulation of highly concentrated refrigerant may cause an oxygen deficiency accident.
Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise it may cause imperfect combustion.
When mounting the rails, push them until the 3 latches click. (Concealed duct type only)
Insert the filters into the direction which the arrows, carved on the filters, show. (2 filters are identical)
Explanations given to user
If you have discovered that the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF position, and contact a qualified service person to have the repairs done. Do not set the circuit breaker to the ON position until the repairs are completed.
Relocation
• Only a qualified installer (*1) or qualified service person (*1) is allowed to relocate the air conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and / or vibration may result.
• When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in reputing, injury, etc.
(*1) Refer to the “Definition of Qualified Installer or Qualified Service Person”
– 10 –
Declaration of Conformity
Manufacturer:
TOSHIBA CARRIER (THAILAND) CO., LTD.
144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road,
Tambon Bangkadi, Amphur Muang, Pathumthani 12000, Thailand
Authorized Representative / Nick Ball
TCF holder: Toshiba EMEA Engineering Director
Toshiba Carrier UK Ltd. Porsham Close, Belliver Industrial Estate, PLYMOUTH, Devon, PL6 7DB. United Kingdom
Hereby declares that the machinery described below:
Generic Denomination: Air Conditioner
Model / type: Indoor unit
<Concealed Duct Standard Type> MM
D-AP0076BHP1-E(TR) MMD-AP0126BHP1-E(TR) MMD-AP0186BHP1-E(TR) MMD-AP0276BHP1-E(TR) MMD-AP0366BHP1-E(TR) MMD-AP0566BHP1-E(TR)
MMD-AP0096BHP1-E(TR), MMD-AP0156BHP1-E(TR), MMD-AP0246BHP1-E(TR), MMD-AP0306BHP1-E(TR), MMD-AP0486BHP1-E(TR),
Commercial name: Super Modular Multi System Air Conditioner
Super Heat Recovery Multi System Air Conditioner MiNi-Super Modular Multi System Air Conditioner (MiNi-SMMS series)
Complies with the provisions of the “Machinery” Directive (Directive 2006/42/EC) and the regulations transposing into national law
“Declaration of incorporation of partly completed machinery”
Must not be put into service until the final machinery into which it is to be incorporated has been declared in conformity with the provisions of this Directive, where appropriate.
Complies with the provisions of the following harmonized standard:
EN 378-2: 2008+A2:2012
NOTE
This declaration becomes invalid if technical or operational modifications are introduced without the manufacturer’s consent.
– 11 –
Specifications
Model
MMD-AP0076BHP1-E
MMD-AP0096BHP1-E
MMD-AP0126BHP1-E
MMD-AP0156BHP1-E
MMD-AP0186BHP1-E
MMD-AP0246BHP1-E
MMD-AP0276BHP1-E
MMD-AP0306BHP1-E
MMD-AP0366BHP1-E
MMD-AP0486BHP1-E
MMD-AP0566BHP1-E
MMD-AP0076BHP1-TR
MMD-AP0096BHP1-TR
MMD-AP0126BHP1-TR
MMD-AP0156BHP1-TR
MMD-AP0186BHP1-TR
MMD-AP0246BHP1-TR
MMD-AP0276BHP1-TR
MMD-AP0306BHP1-TR
MMD-AP0366BHP1-TR
MMD-AP0486BHP1-TR
MMD-AP0566BHP1-TR
Sound Pressure level (dBA)
Cooling Heating
∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗
∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗ ∗
Weight (kg) Main unit
23
23
23
23
23
30
30
30
40
40
40
23
23
23
23
23
30
30
30
40
40
40
: Under 70 dBA
– 12 –
1. SPECIFICATIONS
Model name
(50Hz)
MMD-AP
0076 0096 0126 0156 0186 0246 0276 0306 0366 0486 0566
∗∗∗∗
BHP1-E(TR)
Cooling/Heating capacity
Electrical
Power supply
(Note 1) (kW)
characteristics
Running current (A)
Power consumption (kW)
Starting current (A)
Appearance
Dimension Height (mm)
Width (mm)
Depth (mm)
Total weight (kg)
Heat exchanger
Soundproof / Heat-insulating meterial
Fan unit
Fan
Standard air flow (m³/h) (Med./Low)
Motor output (W)
External static pressure
(Pa)
(factory setting)
2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3 7.1/8.0 8.0/9.0 9.0/10.0 11.2/12.5 14.0/16.0 16.0/18.0
1phase 50Hz 230V(220V-240V)
0.26 0.29 0.42 0.52
0.038 0.043 0.062 0.077
0.45 0.50 0.73 0.90
0.61 1.07 1.23
0.094 0.172 0.198
1.06 1.85 2.13
Zinc hot dipping steel plate
275
700 1000 1400
750
23 30 40
Finned tube
Polyethlene foam
Centrifugal fan
540
(450/360)
570
(480/390)
800
(660/540)
150
1,200
(990/870)
1,260
(1110/930)
1,920
(1620/1380)
2,100
(1740/1500)
250
30 40 50
30-40-50-65-80-100-120 (7steps)
Remote controller
Standard filter (Long life filter)
Controller
Air filter
Connecting
External static pressure (Pa)
Gas side (mm)
9.5 12.7 15.9
pipe
Liquid side (mm)
Drain port (mm)
Sound pressure level (Note 2)
(High/Med./Low)
(dB(A))
29/26/23
25(Polyvinyl chloride tube)
30/26/23 33/29/25 36/31/27 40/36/33
9.56.4
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by
JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 m height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated valves due to the effects of external sound.
Note : Rated conditions Cooling: Indoor air temperature 27˚C DB/19˚C WB, Outdoor air temperature 35˚C DB
Heating: Indoor air temperature 20˚C DB, Outdoor air temperature 7˚C DB/6˚C WB
– 13 –
Model name
(60Hz)
MMD-AP∗∗∗∗BHP1-E(TR)
0076 0096 0126 0156 0186 0246 0276 0306 0366 0486 0566
Cooling/Heating capacity
Electrical
Power supply
(Note 1) (kW)
characteristics
Running current (A)
Power consumption (kW)
Starting current (A)
Appearance
Dimension Height (mm)
Width (mm)
Depth (mm)
Total weight (kg)
Heat exchanger
Soundproof / Heat-insulating meterial
Fan unit
Fan
Standard air flow (m³/h) (Med./Low)
Motor output (W)
External static pressure
(Pa)
(factory setting)
2.2/2.5 2.8/3.2 3.6/4.0 4.5/5.0 5.6/6.3 7.1/8.0 8.0/9.0 9.0/10.0 11.2/12.5 14.0/16.0 16.0/18.0
1phase 60Hz 220V
0.27 0.31 0.44 0.55
0.038 0.043 0.062 0.077
0.47 0.54 0.76 0.95
0.64 1.12 1.29
0.094 0.172 0.198
1.11 1.94 2.23
Zinc hot dipping steel plate
275
700 1000 1400
750
23 30 40
Finned tube
Polyethlene foam
Centrifugal fan
540
(450/360)
570
(480/390)
800
(660/540)
150
1,200
(990/870)
1,260
(1110/930)
1,920
(1620/1380)
2,100
(1740/1500)
250
30 40 50
30-40-50-65-80-100-120 (7steps)
Remote controller
Standard filter (Long life filter)
Controller
Air filter
Connecting
External static pressure (Pa)
Gas side (mm)
9.5 12.7 15.9
pipe
Liquid side (mm)
Drain port (mm)
Sound pressure level (Note 2)
(High/Med./Low)
(dB(A))
29/26/23
25(Polyvinyl chloride tube)
30/26/23 33/29/25 36/31/27 40/36/33
9.56.4
Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by
JIS B 8615 based on the reference piping. The reference piping consists of 5 m of main piping and 2.5 m of branch piping connected with 0 m height.
Note 2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616.
Normally, the values measured in the actual operating environment become larger than the indicated valves due to the effects of external sound.
Note : Rated conditions Cooling: Indoor air temperature 27˚C DB/19˚C WB, Outdoor air temperature 35˚C DB
Heating: Indoor air temperature 20˚C DB, Outdoor air temperature 7˚C DB/6˚C WB
– 14 –
2. AIR DUCTING WORK
AP0076 type AP0096, AP0126 type
Standard air volume: 540 m3/h
External static pressure(Pa)
External static pressure (Pa)
140
120
100
80
60
40
20
Upper limit of
Upper limit of
external static
external static pessure(120Pa)
pressure (120 Pa)
Low (120 Pa)
Low tap(120Pa)
Standard air volume : 540m3/h
Lower limit of
Lower limit of external static
external static
pressure (120 Pa)
pessure(120Pa)
High tap(120Pa)
High tap(100Pa)
High tap (100 Pa)
High tap (80 Pa)
High tap(80Pa)
High tap (65 Pa)
High tap(65Pa)
High tap (50 Pa)
High tap(50Pa)
High tap(40Pa)
High tap (40 Pa)
High tap (30 Pa)
High tap(30Pa)
Standard filter pressure
Standard filter pressure loss
loss
High tap (120 Pa)
140
120
100
Low (120 Pa)
Low tap(120Pa)
80
60
External static pressure(Pa)
40
External static pressure (Pa)
20
Upper limit of
Upper limit of
external static
external static pessure(120Pa)
pressure (120 Pa)
Standard air volume: 570 m3/h
Standard air volume : 570m3/h
Lower limit of
Lower limit of external static
external static
pressure (120 Pa)
pessure(120Pa)
High tap (120 Pa)
High tap(120Pa)
High tap (100 Pa)
High tap(100Pa)
High tap (80 Pa)
High tap(80Pa)
High tap (65 Pa)
High tap(65Pa)
High tap(50Pa)
High tap (50 Pa)
High tap(40Pa)
High tap (40 Pa)
High tap (30 Pa)
High tap(30Pa)
Standard filter
Standard filter
pressure loss
pressure loss
0
200 300 400 500 600 700 800
Air volume(m3/h)
Air Volume (m3/h)
0
200 300 400 500 600 700 800
AP0156, AP0186 type AP0246, AP0276 type
Standard air volume : 800m3/h
140
Upper limit of
Upper limit of external
external static
static pressure (120 Pa)
pessure(120Pa)
120
100
Low (120 Pa)
Low tap(120Pa)
80
60
External static pressure(Pa)
40
External static pressure (Pa)
20
0
380480580680780880980
Air Volume (m3/h)
Standard air volume: 800 m3/h
Lower limit of
Lower limit of external
external static
static pressure (120 Pa)
pessure(120Pa)
Air volume(m3/h)
High tap (120 Pa)
High tap(120Pa)
High tap (100 Pa)
High tap(100Pa)
High tap (80 Pa)
High tap(80Pa)
High tap
High tap(65Pa)
(65 Pa)
High tap (50 Pa)
High tap(50Pa)
High tap
High tap
(40 Pa)
a)
(40P
High tap
High tap
(30 Pa)
(30Pa)
Standard filter
Standard filter pressure loss
pressure loss
140
Upper limit of external
Upper limit of
static pressure
external static
(120 Pa)
pessure(120Pa)
120
100
80
Low tap(120Pa)
Low (120 Pa)
60
40
External static pressure (Pa)
20
0
570 770 970 1170 1370
Air volume(m3/h)
Air Volume (m3/h)
Standard air volume: 1200 m3/h
Air Volume (m3/h)
Lower limit of
Lower limit of external
external static
static pressure
pessure(120Pa)
(120 Pa)
High tap (120 Pa)
High tap(120Pa)
High tap
High tap(100Pa)
(100 Pa)
High tap
High tap(80Pa)
(80 Pa)
High tap
High tap(65Pa)
(65 Pa)
High tap (50 Pa)
H
igh tap(50Pa)
High tap(40Pa)
High tap (40 Pa)
High tap
High tap(30Pa)
(30 Pa)
Standard filter
Standard filter
pressure loss
pressure loss
– 15
AP0306 type AP0366 type
Standard air volume: 1260 m3/h
140
120
Upper limit of
Upper limit of
external static
external static
pressure (120 Pa)
pessure(120Pa)
Standard air volume : 1260m3/h
Lower limit of
Lower limit of
external static
external static
pressure (120 Pa)
pessure(120Pa)
100
80
Low (120 Pa)
Low tap(120Pa)
60
External static pressure(Pa)
40
External static pressure (Pa)
20
0
630 830 1030 1230 143 0
High tap (120 Pa)
High tap(120Pa)
High tap
High tap
(100 Pa)
(100Pa)
High tap (80 Pa)
High tap(80Pa)
High tap
High tap
(65Pa)
(65 Pa)
High tap (50 Pa)
High tap(50Pa)
High tap
High tap
(40 Pa)
(40Pa)
High tap
High tap(30Pa)
(30 Pa)
Standard filter
Standard filter pressure loss
pressure loss
140
Upper limit of
Upper limit of
external static
external static
pessure(120Pa)
pressure (120 Pa)
120
100
Low tap(120Pa)
Low (120 Pa)
80
60
External static pressure(Pa)
40
External static pressure (Pa)
20
0
900 1100 1300 1 500 1700 1900 2100 2300 2500
Air volume(m3/h)
Air Volume (m3/h)
AP0486, AP0566 type
Standard air volume: 2100 m3/h
140
120
Upper limit of
Upper limit of
external static
external static
pressure (120 Pa)
pessure(120Pa)
Standard air volume : 2100m3/h
Lower limit of
Lower limit of
external static
external static
pessure(120Pa)
pressure (120 Pa)
High tap (120 Pa)
High tap(120Pa)
Standard air volume: 1920 m3/h
Standard air volume : 1920m3/h
Lower limit of
Lower limit of external static
external static
pressure (120 Pa)
pessure(120Pa)
High tap (120 Pa)
High tap(120Pa)
High tap (100 Pa)
High tap(100Pa)
High tap (80 Pa)
High tap(80Pa)
High tap (65 Pa)
High tap(65Pa)
High tap (50 Pa)
High tap(50Pa)
High tap (40 Pa)
High tap(40Pa)
High tap (30 Pa)
High tap(30Pa)
Standard filter
Standard filter
pressure loss
pressure loss
Air volume(m3/h)
Air Volume (m3/h)
100
Low tap(120Pa)
Low (120 Pa)
80
60
External static pressure(Pa)
40
External static pressure (Pa)
Standard filter
Standard filter
20
pressure loss
pressure loss
0
1000 1200 1400 1600 1800 2000 2200 2400 2600
Air volume(m3/h)
Air Volume (m3/h)
High tap(100Pa)
High tap (100 Pa)
High tap (80 Pa)
High tap(80Pa)
High tap (65 Pa)
High tap(65Pa)
High tap(50Pa)
High tap(40Pa)
High tap (50 Pa)
High tap (40 Pa)
High tap
High tap
(30Pa)
(30 Pa)
– 16
3. CONSTRUCTION VIEWS (EXTERNAL VIEWS)
MMD-AP0076BHP1*, AP0096BHP1*, AP0126BHP1*, AP0156BHP1*, AP0186BHP1*
AP0246BHP1*, AP0276BHP1*, AP0306BHP1*, AP0366BHP1*, AP0486BHP1*, AP0566BHP1*
C
L
Hanging bolt pitch
650
750
345
187.5
355
415
570
275
180
Hanging bolt pitch B
Main unit dimension A
External dimensions of flange C
D
70 or more
345 or more
Drain pan / Drain pump check cover
750
650 5050
50 50
22
43
113.5
131
236
25
Electrical control box
Dimension
AP007 ~ 018 type
AP024 ~ 030 type
AP036 ~ 056 type
ABCD
700 765 640 750
1000 1065 940 1050 500
1400 1465 1340 1450 700
Air discharge
100 or more
Check port
450
120
E
Service space (E for maintenance of air filter)
E
700
17
AP007 ~ AP018 type
AP024 ~ AP030 type
<Under air intake>
235.4
37.5
<Back air intake>
235.2
659.4
660
<Under air intake>
959.4
37.5
27
254
100 100
27
27
254
100 100
27
37.5
100
100
100100100100
235.4
37.5
100100
100100
100100100100100
<Back air intake>
960
27
100100
254
235.2
2727
100100
254
87.5
100
100100
675
27
100100
87.5
AP036 ~ AP056 type
<Under air intake>
235.4
37.5
100
<Back air intake>
100100100
975
100
100100
254
100 100
27 27
37.5
37.5
1359.4
100
100
100100100
100
100100
100
100100100100
100100
37.5
235.2
37.5
100
100
100
1360
100100100
100
1375
18
2727
100100
254
100
100100100100100
37.5
4. WIRING DIAGRAMS
Models : MMD-AP0076BHP1*, AP0096BHP1*, AP0126BHP1*, AP0156BHP1*,
AP0186BHP1*, AP0246BHP1*, AP0276BHP1*, AP0306BHP1*, AP0366BHP1*, AP0486BHP1*, AP0566BHP1*
19
5. PARTS RATING
Model
Fan motor
Drain pump motor
Float switch
Pulse motor
Pulse motor valve
TA sensor
TC1 sensor
TC2 sensor
TCJ sensor
Model
Fan motor
Drain pump motor
Float switch
Pulse motor
Pulse motor valve
TA sensor
TC1 sensor
TC2 sensor
TCJ sensor
MMD-AP
MMD-AP
0076BHP1 0096BHP1 0126BHP1 0156BHP1 0186BHP1
ICF-340W150-2
MDP-1401
FS-1A-31-3
EFM-MD12TF-1
EFM-25YGTCTH-2 EFM-40YGTF-1
Lead wire length: 218 mm
Ø4 size lead wire length: 1000 mm Vinyl tube (Blue)
Ø6 size lead wire length: 1000 mm Vinyl tube (Black)
Ø6 size lead wire length: 1000 mm Vinyl tube (Red)
0246BHP1
0276BHP1 0306BHP1 0366BHP1 0486BHP1
340W150-1 340W250-1
EFM-40YGTF-1 EFM-60YGTCTH-1
Ø4 size lead wire length: 1000 mm Vinyl tube (Blue)
Ø6 size lead wire length: 1000 mm Vinyl tube (Black)
Ø6 size lead wire length: 1000 mm Vinyl tube (Red)
MDP-1401
FS-1A-31-3
EFM-MD12TF-1
Lead wire length: 218 mm
0566BHP1
– 20
6. REFRIGERANT CYCLE DIAGRAM
Indoor unit
Gas sideLiquid side
Strainer
Pulse Motor
Valve (PMV)
Sensor
(TC2)
Capillary tube
Strainer
Sensor
(TCJ)
Explanation of functional parts in indoor unit
Functional part name
Pulse Motor Valve
PMV
Temp. Sensor (Connector CN104 (2P): Yellow)
1.TA
2.TC1
3.TC2
4.TCJ
(Connector CN082 (6P): Blue)
1) Controls super heat in cooling operation
2) Controls under cool in heating operation
3) Recovers refrigerant oil in cooling operation
4) Recovers refrigerant oil in heating operation
1) Detects indoor suction temperature
(Connector CN100 (3P):
1) Controls PMV super heat in cooling operation
(Connector CN101 (2P): Black)
1) Controls PMV under cool in heating operation
(Connector CN102 (2P): Red)
1) Controls PMV super heat in cooling operation
Brown)
Heat exchanger
at indoor side
Fan
Sensor
(TA)
Functional outline
M
Sensor
(TC1)
Fan motor
– 21
7. CONTROL OUTLINE
Indoor unit
Control specifications
NO.
1
2
3
Item Specification outline Remarks
Upon power supply reset
1. Identification of outdoor unit When the power supply is reset, the outdoor unit is identified, and control is redirected according to the identification result.
2. Indoor fan speed and air flow direction control availability settings Settings such as indoor fan speed and air flow direction control availability are replaced on the basis of EEPROM data.
3. If power supply reset is performed in the wake of a fault, the check code is cleared. If the abnormality persists after the Start / Stop button on the remote controller is pressed to resume operation, the check code is redisplayed on the remote controller.
Operation selection
Room temp. control
1. The operation mode changes in response to an operation selection command issued via the remote controller.
Remote controller command Control outline
STOP Air conditioner shutdown
FAN Fan operation
COOL Cooling operation
DRY Drying operation
HEAT Heating operation
1. Adjustment range - remote controller temperature setting (°C)
COOL / DRY HEAT
Wired type 18~29 18~29
Wireless type 18~30 16~30
2. In heating operation, the temperature setting may be fine-tuned via the
Ts: Temperature
Ta: Room
Shift in heating suction temperature (not applicable to remote controller thermo operation)
DN code “06”.
SET DATA 0 2 4 6
Temperature setting adjustment +0 ˚C +2 ˚C +4 ˚C +6 ˚C
setting
temperature
Automatic capacity control
4
Factory default
Model type SET DATA
Floor standing (standard, concealed, cabinet) 0
Other model 2
1. The outdoor unit determines the operational capacities of indoor units according to the difference between Ta and Ts.
Cooling Heating
Ta
(˚C)
+2
+1
Ts
–1
SD
SB
S9
S7
S5
S3
S0
Ta
(˚C)
+1
Ts
–1
–2
S3
S5
S7
S9
SB
SD
SF
S0
Ts: Temperature
setting
Ta: Room
temperature
– 22
NO. Item Specification outline Remarks
Fan speed control
1. The fan operates in one of the four speed modes of “HIGH (HH)”, “MED
(H)”, “LOW (L)” and “AUTO” on the basis of a command issued via the remote controller. (Concealed duct high static pressure type: HH only)
2. In AUTO fan speed mode, the air speed changes according to the
difference between Ta and Ts.
<Cooling>
Ta (˚C)
+3.0
+2.5
+2.0
+1.5
+1.0
+0.5
Tsc
–0.5
HH <HH>
H+ <HH>
H <HH>
L+ <H+>
L <H>
L <H> L <L+>
A B C
D
E
F G
HH > H+ > H > L+ > L > UL or LL
• Control is identical in remote controller thermo and body thermo operation. Speed modes shown in < > apply to cooling operation under AUTO air conditioner operation mode.
• In AUTO fan speed mode, the fan speed remains the same for 3 minutes each time a speed change occurs.
5
However, a speed change command issued via the remote controller can override this, and the fan speed changes accordingly.
• At the beginning of cooling operation, a higher speed (steeper downward temperature gradient) is chosen.
• As long as the temperature difference remains on a boundary line, the fan speed stays the same.
<Heating>
Ta (˚C)
(–0.5) –1.0
(0) Tsh
(+0.5) +1.0
(+1.0) +2.0
(+1.5) +3.0
(+2.0) +4.0
Figures inside ( ) applies to remote controller thermo operation. Figures outside ( ) applies to body thermo operation. Speed modes shown in < > apply to heating operation under AUTO air conditioner operation mode.
• In AUTO fan speed mode, the fan speed remains the same for 1 minute each time a speed change occurs. However, a speed change command issued via the remote controller can override this, and the fan speed changes accordingly.
• At the beginning of heating operation, a higher speed (steeper upward temperature gradient) is chosen.
• As long as the temperature difference remains on a boundary line, the fan speed stays the same.
• When TC2 60 °C, the fan speed is raised by one step.
3. If the air conditioner goes thermo OFF during heating operation, the fan speed drops down to LL (breeze).
L <L+>
L+ <H>
H <H+>
H+ <HH>
HH <HH>
E
D
C
B
A
DN code “32” “0000”: Body thermo “0001”: Remote controller thermo
TC2: Indoor heat exchanger sensor temperature
“HEATING STANDBY
displayed
– 23
NO. Item Specification outline Remarks
Cold air discharge prevention control
1. In heating operation, the upper limit of the fan tap is set according to the lower of whichever is the higher between TC2 sensor and TCJ sensor temperatures, on the one hand, and TC1 sensor temperature, on the other.
• If the fan continuously operates in zone B for 6 minutes, it automatically moves into zone C.
• During defrosting, the control point is shifted by +6 °C.
TCJ: Indoor heat exchanger sensor temperature
• In zones D and E, priority is given to the remote controller fan
6
32
30
28
D
C
E
26
20
16
˚C
A zone: OFF B zone: 26˚C or above and
C zone: 28˚C or above and
D zone: 30˚C or above and
B
E zone: High
A
below 28˚C breeze
below 30˚C Low
below 32˚C Medium
speed setting.
•In zone A, “HEATING STANDBY is displayed.
Freeze prevention control (low temp. release)
7
1. During cooling, the air conditioner is operated in the manner described below according to the temperature readings of the TC1, TC2 and TCJ sensors.
• If zone J operation is detected for 5 minutes, the air conditioner is forced into thermo OFF.
• In zone K, the timer is put on pause, with the current timer count retained.
• If zone I operation is detected, the timer count is cleared, and the air conditioner returns to normal operation.
• If continuous zone J operation forces the air conditioner into thermo OFF, the indoor fan is operated in breeze mode until it moves into zone I. The control is terminated under the following conditions:
Termination conditions
1) TC1 12 °C, TC2 12 °C, and TCJ 12 °C
(˚C)
P1 Q1
P1
I
K
J
a
Q1
TC1
10˚C (5˚C)
0˚C
TC2, TCJ
–10˚C –14˚C
2) Passage of 20 minutes after stoppage
2. During cooling, the air conditioner is operated in the manner described below according to the temperature readings of the TC2 and TCJ sensors.
• If zone M operation is detected for 45 minutes, the air conditioner is forced into thermo OFF.
• In zone N, the timer is put on pause, with the current timer count retained.
• When the air conditioner goes back into zone M, timer count is resumed from the retained value.
TC1: Indoor heat exchanger sensor temperature
(˚C)
P2
Q2
L
N
M
P2 Q2
TC2, TCJ
5
–2.0
• If zone L operation is detected, the timer count is cleared, and the air conditioner returns to normal operation.
Reset conditions
1) TC1 12 °C, TC2 12 °C and TCJ 12 °C
2) Passage of 20 minutes after stoppage
– 24
* With models
without TC2, TC2 is not part of the control parameters.
NO. Item Specification outline Remarks
Cooling oil (refrigerant) recovery control
8
Heating refrigerant (oil) recovery control
9
While the outdoor unit is recovering cooling oil (refrigerant), the indoor units perform the following control tasks: [common for operational (cooling thermo ON / thermo OFF / FAN), as well as nonoperational indoor units]
1) Open the indoor PMV to a certain degree.
2) Engage in recovery control for a specified period of time and return to normal cooling operation at the end of this period upon terminating the control.
3) Operate the drain pump throughout the recovery control period and for about 1 minute after it.
While the outdoor unit is recovering heating refrigerant (oil), the indoor units perform the following control tasks:
1) Open the indoor PMV to a certain degree.
2) Control the indoor fan according to the operation mode.
[Indoor units operating in heating thermo ON / OFF state]
Let the indoor fan continue operating, but turn it off if the temperature of the indoor heat exchanger drops.
[Indoor units operating in FAN mode]
Turn off the indoor fan and display “HEATING STANDBY
remote controller. [Non-operational indoor units]
Keep the indoor fan turned off.
3) Terminate the recovery operation depending on the TC2 temperature reading. The timing of termination is determined by each indoor unit.
4) Operate the indoor fan and drain pump for about 1 minute after the termination of the recovery operation. (Applicable to compact 4-way cassette type and 1- way cassette type)
” on the
• Recovery operation normally takes place roughly every 2 hours.
• The opening position of the indoor PMV depending on the type and capacity of the indoor unit.
• Recovery operation normally takes place roughly every hour.
• The opening position of the indoor PMV depending on the type and capacity of the indoor unit.
Defrosting control
10
Short intermittent operation
11
compensation control
Drain pump control
12
While the outdoor unit is engaged in defrosting control, the indoor units perform the following control tasks:
1) Open the indoor PMV to a certain degree.
2) Control the indoor fan according to the operation mode.
[Indoor units operating in heating thermo ON / OFF state]
Let the indoor fan continue operating for a while, but turn it off as the temperature of the indoor heat exchanger drops.
[Indoor units operating in FAN mode]
Let the indoor fan continue operating.
[Non-operational indoor units]
Keep the indoor fan turned off.
3) As defrosting control comes to an end, it gives way to heating refrigerant (oil) recovery control. (For control details, see “9. Heating refrigerant (oil) recovery control” above.)
1. For 5 minutes after startup, the system is forced to continue operating even if it reaches the thermo OFF region.
2. However, priority is given to cooling / heating selection, operation standby, and protective control, so that there is no overriding of thermo OFF in these cases.
1. During cooling (including DRY operation), the drain pump is operated at all times.
2. If the float switch is activated while the drain pump is in operation, the drain pump continues operating, with the relevant check code displayed.
3. If the float switch is activated while the drain pump is turned off, thermo OFF is forced on the air conditioner, with the drain pump put into operation. If the float switch continues to be activated for about 5 minutes, the drain pump is turned off, with the relevant check code displayed.
• For defrosting commencement conditions, see 5 Control Outline “10. Defrosting control (reverse defrosting method)” in SMMS-i Outdoor Unit Service Manual A10-005 above.
• The opening position of the indoor PMV depending on the type and capacity of the indoor unit.
Check code [P10]
Elimination of
13
residual heat
1. When the air conditioner is turned off after engaging in heating operation, the indoor fan is operated for about 30 seconds in “breeze” mode.
25
NO. Item Specification outline Remarks
Filter sign display (not applicable to wireless type)
*Provided in
14
the separately mounted type, TCB-AX21E.
Operation standby Heating standby
15
1. The indoor fan’s cumulative hours of operation are counted, and when these exceed the prescribed value (2500H), a filter replacement signal is sent to the remote controller to display a filter sign on it.
2. When a filter reset signal is received from the remote controller, the timer measuring cumulative hours is cleared. If the prescribed hours have been exceeded, the hours count is reset, with the sign on the remote controller display erased.
2500HFilter service life
<Operation standby> .......... Displayed on remote controller
1. When any of the DN codes listed below is displayed
• “P05” - Detection of an open phase in the power supply wiring
• “P10” - Detection of indoor flooding in at least one indoor unit
• “L30” - Detection of an interlock alarm in at least one indoor unit
2. Forced thermo OFF
• “COOL / DRY” operation is unavailable because at least one indoor unit is operating in “HEAT” mode.
• “HEAT” operation is unavailable because at least one indoor unit is operating in “COOL / DRY” mode under priority cooling setting (bit 1 of SW11 on outdoor I/ F P.C. board ON).
3. All indoor units not able to engage in any of the above operations stand by in thermo OFF state.
4. The indoor fan has been turned off because the system is engaged in a heat refrigerant (oil) recovery operation.
<Heating standby> .......... Displayed on remote controller
1. Normal thermo OFF
• During heating, the indoor unit goes thermo OFF as the heating temperature setting is reached.
2. During heating, the fan rotates at a breeze speed (UL or lower) or remains stationary to prevent cold air from being discharged (including defrosting operation).
3.Forced thermo OFF
• “HEAT” operation is unavailable because at least one indoor unit is operating in “COOL / DRY” mode under priority cooling setting (bit 1 of SW11 on outdoor I/ F P.C. board ON).
“FILTER
” displayed
• “OPERATION STANDBY displayed No display provided on wireless remote controller
• “HEATING STANDBY displayed
Selection of central control mode
16
1. The range of operations that can be performed via an indoor unit remote controller can be determined through the setting of the central controller.
2. Setting details
TCC-Link central control
Operation
via TCCLink
Individual
Central 1
Central 2
Central 3
Central 4
(
{
Start / stop
central control
selection
{
× ×
{
: Accessible × : Inaccessible)
{
Operation on RBC-AMT32E
Operation
mode
selection
Timer
setting
{
{
× × ×
{
× ×
{
{
Temperature
setting
{
{
× ×
{
Fan speed
setting
{
{
{
{
{
Air flow
direction
setting
{
{
{
{
{
RBC-
AMT32E
display
CENTRAL
CONTROL
PROGRESS
• In the case of a wired remote controller, “CENTRAL CONTROL IN PROGRESS
” is displayed (lit up) while in central control mode.
• The display blinks when a control function
IN
inaccessible to a remote controller is chosen.
• A wireless remote controller has the same set of control functions, although there is no display. When a control operation is performed via a wireless remote controller while in central control mode, a peep sound alert (5 times) is provided.
26
NO. Item Specification outline Remarks
DC motor 1) When the fan operation has started, positioning of the stator and the
rotor are performed. (Moves slightly with tap sound)
2) The motor operates according to the command from the indoor controller.
17
Notes)
• When the fan rotates while the air conditioner stops due to entering of
outside air, etc, the air conditioner may operate while the fan motor stops.
• When a fan lock is found, the air conditioner stops, and an error is
displayed.
• If static pressure of the used duct does not match with the setup value of
static pressure, which was decided in the static pressure setting code No. [5D], the air conditioner may stop or an error code may be displayed.
SAVE
Power saving mode
1. Push the
2. The “
button on the remote controller
“ segment lights up on the wired remote controller display.
3. The requirement capacity ratio is limited to approximately 75 %.
18
4. If the power saving operation is enabled, the settings are retained
when the operation is stopped, when the mode is changed, or when the power is reset. The power saving operation will be enabled the next time the operation starts.
Frequency fixed operation (Test run)
<In case of wired remote controller>
1) When pushing [CHK] button for 4 seconds or more, [TEST] is displayed on the display screen and the mode enters in Test run mode.
2) Push [ON/OFF] button.
3) Using [MODE] button, set the mode to [COOL] or [HEAT].
• Do not use other mode than [COOL]/[HEAT] mode.
• During test run operation, the temperature cannot be adjusted.
• An error is detected as usual.
• A frequency fixed operation is performed.
4) After the test run, push [ON/OFF] button to stop the operation. (Display in the display part is same as the procedure in Item 1.)
5) Push [CHK] button to clear the test run mode. ([TEST] display in the display part disappears and the status returns to the normal stop status.)
Check code “P12”
The power saving operation cannot be set by the wireless remote controller or wired remote controller of AMT31E or older.
Command frequency is approximately [S7]
19
<In case of wireless remote controller>
1) When TEMPORARY button is pushed for 10 seconds or more, “Pi!” sound is heard and the operation changes to test run. After approx. 3 minutes, a cooling operation starts forcedly. Check cool air starts blowing. If the operation does not start, check wiring again.
2) To stop a test operation, push TEMPORARY button once again (Approx. 1 second). Check wiring / piping of the indoor and outdoor units in test run.
TEMPORARY button
27
8. APPLIED CONTROL AND FUNCTIONS
Wired (Simple) heder remote controller (Max. 2 units) Schedule remote controller
Outdoor unit
Outdoor unit
NU1U2
U1 U2
L
321
Up to 8 units are connectable.
1 It is unavailable to connect the Schedule remote controller to the simple wired remote controller.
Same as left
#3
(Follower)
A B
AB
Same as left
#2
(Follower)
A B
DC5V
DC5V
Indoor unit #1 (Heder)
Indoor control P.C. board (MCC-1631)
Drain pump
PMV
Indoor
fan motor
CPU
H8/36109
Driver
DC12V
DC5V
DC20V
External output
Remote controller
communication circuit
Display LCD Function setup
Key switch
CN2
CN1
1
CPU
Display LED
Display LCD LCD driver
CPU
Remote controller
communication circuit
Function setup
Key switch
Power circuit
Power circuit
DC280V
Fan motor
control circuit
CPU
TMP88CH47FG
(TMP88PH47FG)
EEPROM1
EEPROM2
TA sensor
TC1 sensor
TC2 sensor
TCJ sensor
Float input
HA
Run
Alarm
Defrost
Thermo. ON
COOL HEAT
FAN
BUS
comunication circuit
AC
synchronous
signal input circuit
Power supply
1
, 220-240V, 50Hz
1
, 220V, 60Hz
Powe r
circuit
Secondary
battery
Outdoor unit
321
(INCLUDING CIRCUIT CONFIGURATION)
8-1. Indoor controller block diagram
8-1-1. In Case of Connection of Wired (Simple) Remote Controller
<Concealed Duct Standard type>
28
8-1-2. In Case of Connection of Wireless Remote Controller
<Concealed Duct Standard type>
Indoor unit #1 (Heder)
Wireless remote controller
Receiver P.C. board
Display LED
Drain
pump
PMV
Indoor
fan motor
DC280V
Receive circuit
Buzzer
DC5V
Powe r circuit
Indoor control P.C. board (MCC-1631)
DC20V
DC5V
DC12V
TMP88CH47FG
(TVP88PH47FG)
Fan motor
Power circuit
control circuit
Remote controller
communication circuit
Remote controller
communication circuit
CPU
CPU
AB
Driver
External output
Run
Alarm
Defrost
Thermo. ON
COOL HEAT
FAN
Function setup SW
Temporary
operation SW
CPU
H8/36109
AC
synchronous
signal input circuit
EEPROM2
EEPROM1
TA sensor
TC1 sensor
TC2 sensor
TCJ sensor
Float input
HA
BUS
comunication circuit
#2
(Follower)
A B
Same as left
#3
(Follower)
A B
Same as left
321
321
L
Power supply
, 220-240V, 50Hz
1
, 220V, 60Hz
1
29
NU1U2
U1 U2
Outdoor unit
Outdoor unit
Up to 8 units are connectable.
Outdoor unit
8-1-3. Connection of Both Wired (Simple) Remote Controller and Wireless Remote Controller
<Concealed Duct Standard type>
Indoor unit #1 (Heder)
Receive
circuit
Buzzer
DC5V
Powe r
circuit
Display LED
CPU
Remote controller
communication circuit
Receiver P.C. board
Function setup SW
Temporary
operation SW
Wired (Simple) heder remote controller
communication circuit
(Max. 2 units)
Display
LCD
Display
LED
Remote controller
ABAB
CPU
Function
setup
Key
switch
DC5V
Powe r
circuit
CN2
CN1
1
Schedule remote controllerWireless remote controller
Display
LCD
DC5V
Powe r circuit
LCD
driver
CPU
Function
setup
Key
switch
Secondary
battery
Drain pump
PMV
Indoor
fan motor
DC280V
Indoor control P.C. board (MCC-1631)
Power circuit
DC20V
DC5V
DC12V
TVP88CH47FG
(TMP88PH47FG)
control circuit
Remote controller
communication circuit
CPU
Fan motor
AB
Driver
External output
Run
Alarm
Defrost
Thermo. ON
COOL HEAT
FAN
CPU
H8/36109
comunication circuit
AC
synchronous
signal input circuit
NU1U2
L
Outdoor unit
#2
(Follower)
A B
EEPROM2
EEPROM1
TA sensor
TC1 sensor
TC2 sensor
TCJ sensor
Float input
HA
BUS
Up to 8 units are connectable.
1 It is unavailable to connect the Schedule remote
U1 U2
controller to the simple wired remote controller.
Same as left
Outdoor unit
(Follower)
321
#3
A B
Same as left
321
Outdoor unit
Power supply
1
, 220-240V, 50Hz
1
30
, 220V, 60Hz
Loading...
+ 75 hidden pages