Toshiba MMY-MAP1404T8-E,MMY-MAP1604T8-E,MMY-MAP0804T8,MMY-MAP1004T8,MMY-MAP1204T8,MMY-MAP1404T8,MMY-MAP1604T8,MMY-MAP0804T8-SG,MMY-MAP1004T8-SG,MMY-MAP1204T8-SG,MMY-MAP1404T8-SG,MMY-MAP1604T8-SG,MMY-MAP0804HT8Z-E,MMY-MAP1004HT8Z-E,MMY-MAP1204HT8Z-E,MMY-MAP1404HT8Z-E,MMY-MAP1604HT8Z-E,MMY-MAP0804HT8Z-TR,MMY-MAP1004HT8Z-TR,MMY-MAP1204HT8Z-TR,MMY-MAP1404HT8Z-TR,MMY-MAP1604HT8Z-TR,MMY-MAP0804HT8Z,MMY-MAP1004HT8Z,MMY-MAP1204HT8Z,MMY-MAP1404HT8Z,MMY-MAP1604HT8Z,MMY-MAP0804HT7Z,MMY-MAP1004HT7Z,MMY-MAP1204HT7Z,MMY-MAP1404HT7Z,MMY-MAP1604HT7Z,MMY-MAP0804T8Z-E,MMY-MAP1004T8Z-E,MMY-MAP1204T8Z-E,MMY-MAP1404T8Z-E,MMY-MAP1604T8Z-E,MMY-MAP0804T8Z,MMY-MAP1004T8Z,MMY-MAP1204T8Z, MMY-MAP0804HT8-E,MMY-MAP1004HT8-E,MMY-MAP1204HT8-E,MMY-MAP1404HT8-E,MMY-MAP1604HT8-E,MMY-MAP0804HT8-TR,MMY-MAP1004HT8-TR,MMY-MAP1204HT8-TR,MMY-MAP1404HT8-TR,MMY-MAP1604HT8-TR,MMY-MAP0804HT8,MMY-MAP1004HT8,MMY-MAP1204HT8,MMY-MAP1404HT8,MMY-MAP1604HT8,MMY-MAP0804HT7,MMY-MAP1004HT7,MMY-MAP1204HT7,MMY-MAP1404HT7,MMY-MAP1604HT7,MMY-MAP0804T8-E,MMY-MAP1004T8-E,MMY-MAP1204T8-E, MMY-MAP1404T8Z,MMY-MAP1604T8Z,MMY-MAP0804T8-SG,MMY-MAP1004T8-SG,MMY-MAP1204T8-SG,MMY-MAP1404T8-SG,MMY-MAP1604T8-SG,MMY-MAP0804HT8ZG-E,MMY-MAP1004HT8ZG-E,MMY-MAP1204HT8ZG-E,MMY-MAP1404HT8ZG-E,MMY-MAP1604HT8ZG-E,MMY-MAP0804HT8ZG-TR,MMY-MAP1004HT8ZG-TR,MMY-MAP1204HT8ZG-TR,MMY-MAP1404HT8ZG-TR,MMY-MAP1604HT8ZG-TR,MMY-MAP0804HT8ZG,MMY-MAP1004HT8ZG,MMY-MAP1204HT8ZG,MMY-MAP1404HT8ZG,MMY-MAP1604HT8ZG,MMY-MAP0804HT7ZG,MMY-MAP1004HT7ZG,MMY-MAP1204HT7ZG,MMY-MAP1404HT7ZG,MMY-MAP1604HT7ZG,MMY-MAP0804T8ZG-E,MMY-MAP1004T8ZG-E,MMY-MAP1204T8ZG-E,MMY-MAP1404T8ZG-E,MMY-MAP1604T8ZG-E,MMY-MAP0804T8ZG,MMY-MAP1004T8ZG,MMY-MAP1204T8ZG,MMY-MAP1404T8ZG,MMY-MAP1604T8ZG,MMY-MAP0804T8-SG,MMY-MAP1004T8-SG,MMY-MAP1204T8-SG,MMY-MAP1404T8-SG,MMY-MAP1604T8-SG, Service Manual

0 (0)
AIR CONDITIONER (MULTI TYPE)
SERVICE MANUAL
FILE No. A10-005
This service manual provides relevant explanations about new outdoor unit (SMMS-i). Please refer to the following service manuals for each indoor units.
Outdoor Unit
<SUPER MODULAR MULTI SYSTEM-i>
<Heat Pump Model>
<Cooling Only Model>
4-way Air Discharge Cassette Type (MMU-AP 2H)
A08-004
Compact 4-way Cassette (600 × 600) Type (MMU-AP 1MH)
A06-002
1-way Air Discharge Cassette Type SH (2 series) (MMU-AP 2SH)
A05-007
2-way Air Discharge Cassette Type (2 series) (MMU-AP 2WH)
A10-007
Slim Duct Type (MMD-AP 1SPH)
A05-007
Fresh Air Intake Indoor Unit Type (MMD-AP 1HFE)
A06-016
High-wall Type (2 series) (MMK-AP 2H)
A05-005
High-wall Type (3 series) (MMK-AP 3H)
SVM-09059
Other indoor units SMMS (1 series) A03-009, A03-010
MMY-MAP0804HT8(Z)(ZG)-E MMY-MAP1004HT8(Z)(ZG)-E MMY-MAP1204HT8(Z)(ZG)-E MMY-MAP1404HT8(Z)(ZG)-E MMY-MAP1604HT8(Z)(ZG)-E
MMY-MAP0804HT8(Z)(ZG)-TR MMY-MAP1004HT8(Z)(ZG)-TR MMY-MAP1204HT8(Z)(ZG)-TR MMY-MAP1404HT8(Z)(ZG)-TR MMY-MAP1604HT8(Z)(ZG)-TR
MMY-MAP0804HT8(Z)(ZG) MMY-MAP1004HT8(Z)(ZG) MMY-MAP1204HT8(Z)(ZG) MMY-MAP1404HT8(Z)(ZG) MMY-MAP1604HT8(Z)(ZG)
MMY-MAP0804HT7(Z)(ZG) MMY-MAP1004HT7(Z)(ZG) MMY-MAP1204HT7(Z)(ZG) MMY-MAP1404HT7(Z)(ZG) MMY-MAP1604HT7(Z)(ZG)
MMY-MAP0804T8(Z)(ZG)-E MMY-MAP1004T8(Z)(ZG)-E MMY-MAP1204T8(Z)(ZG)-E MMY-MAP1404T8(Z)(ZG)-E MMY-MAP1604T8(Z)(ZG)-E
MMY-MAP0804T8(Z)(ZG) MMY-MAP1004T8(Z)(ZG) MMY-MAP1204T8(Z)(ZG) MMY-MAP1404T8(Z)(ZG) MMY-MAP1604T8(Z)(ZG)
MMY-MAP0804T8-SG MMY-MAP1004T8-SG MMY-MAP1204T8-SG MMY-MAP1404T8-SG MMY-MAP1604T8-SG
1
Contents
Original instruction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
New Refrigerant (R410A). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
1 Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
1-1. Outdoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
1-2. Indoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
1-2-1. 4-way Air Discharge Cassette Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
1-2-2. Compact 4-way Cassette Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
1-2-3. 1-way Air Discharge Cassette Type (Compact type) . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
1-2-4. 1-way Air Discharge Cassette Type SH 2 series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
1-2-5. 2-way Air Discharge Cassette Type 1 series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
1-2-6. 2-way Air Discharge Cassette Type 2 series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
1-2-7. Concealed Duct Standard Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
1-2-8. Concealed Duct High Static Pressure Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
1-2-9. Slim Duct Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
1-2-10. Under Ceiling Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
1-2-11. High Wall Type 2 series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
1-2-12. High Wall Type 3 series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
1-2-13. Floor Standing Cabinet Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
1-2-14. Floor Standing Concealed Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
1-2-15. Floor Standing Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
1-2-16. Fresh Air Intake Indoor Unit for S-MMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
2 Parts Rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
2-1. Outdoor Unit (50Hz model: MMY-MAP 4HT8-E, MAP 4HT8-TR, MAP 4HT8, MAP 4T8-
SG) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
2-2. Outdoor Unit (60Hz model: MMY-MAP 4HT7) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
2-3. Outdoor Inverter (50Hz model: MMY-MAP 4HT8-E, MAP 4HT8-TR, MAP 4HT8,
MAP 4T8-SG) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
2-4. Outdoor Inverter (60Hz model: MMY-MAP 4HT7) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
2-5. Indoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
2-6. Parts Layout in Outdoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
2-7. Parts Layout in Inverter Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
2-8. Outdoor (Inverter) Print Circuit Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
2-8-1. Interface P.C. board (MCC-1606) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
2-8-2. Inverter P.C. board for compressor (MCC-1596) A3-IPDU . . . . . . . . . . . . . . . . . . . . . . 58
2-8-3. Inverter P.C. board for fan (MCC-1610) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
3 Refrigerant Piping Systematic Drawing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
4 Combined Refrigerant Piping System Schematic Diagrams. . . . . . . . . . . . . . . . . . 64
2
4-1. Normal Operation (COOL Mode / DEFROST Mode) - High Outside Air Temperature (Roughly 20
°C or Above) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
4-2. Normal Operation (COOL Mode) - Low Outside Air Temperature (Roughly Below 20 °C) . . . . . 65
4-3. Normal Operation (HEAT Mode) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
4-4. Emergency Operation (Cooling Operation under Header Outdoor Unit Backup Scenario). . . . . 67
4-5. Emergency Operation (Heating Operation under Header Outdoor Unit Backup Scenario). . . . . 68
4-6. Refrigerant Recovery from Failed Outdoor Unit (Pump-Down Operation under Follower Outdoor
Unit Backup Scenario) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69
5 Control Outline. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
6 Applied Control and Functions (including Circuit Configuration) . . . . . . . . . . . . . 85
6-1. Indoor Controller Block Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
6-1-1. When Main (Sub) Remote Controller Connected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
6-1-2. When Wireless Remote Controller Kit Connected . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
6-1-3. When Both Main (Sub) Remote Controller and Wireless Remote Controller Kit Connected .91
6-2. Indoor Printed Circuit Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
6-3. Optional Connector Specifications of Indoor P.C. Board. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
6-4. Test Operation of Indoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
6-5. Method to Set Indoor Unit Function DN Code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
6-6. Applied Control of Indoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
6-7. Applied control for Outdoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
6-7-1. Outdoor Fan High Static Pressure Shift . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
6-7-2. Priority Operation Mode Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
6-8. Applied Control of Outdoor Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
6-8-1. Power peak-cut Control (Standard) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
6-8-2. Power peak-cut Control (Extended) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
6-8-3. Snowfall Fan Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
6-8-4. External master ON/OFF Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112
6-8-5. Night operation (sound reduction) Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
6-8-6. Operation Mode Selection Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
6-8-7. Error/Operation Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
6-8-8. Compressor Operation Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 116
6-8-9. Operating Rate Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
7 TEST OPERATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
7-1. Procedure and Summary of Test Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
7-2. Check Items before Test Operation (before powering-on) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
7-3. Check at Main Power-on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
7-4. Address Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
7-4-1. Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
7-4-2. Address Setup and Check Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
7-4-3. Address Setup Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
7-4-4. Check after Address Setup when Central Control System Is Connected . . . . . . . . . . 138
3
7-5. Troubleshooting in Test Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
7-5-1. A Check Code Is Displayed on the Remote Controller . . . . . . . . . . . . . . . . . . . . . . . . 139
7-5-2. Operation from the indoor remote controller is not accepted, and a check code is displayed
on the 7-segment display of the interface PC board of the header unit. . . . . . . . . . . . 140
7-5-3. There is no display of a check code on the 7-segment display on the interface PC board of
the header unit, although there is indoor unit that is not accepting operation from the indoor
remote controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
7-5-4. In checking the number of connected outdoor units and connected indoor units after ad-
dress setup, a lower number of connected units is displayed. (There are outdoor/indoor
units that do not operate in a test operation.) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
7-6. Test Operation Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
7-6-1. Fan Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
7-6-2. Cooling/Heating Test Operation Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
7-7. Service Support Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
7-7-1. Check Function for Connecting of Refrigerant and Control Lines . . . . . . . . . . . . . . . . 148
7-7-2. Function to Start/Stop (ON/OFF) Indoor Unit from Outdoor Unit . . . . . . . . . . . . . . . . . 150
7-7-3. Error Clearing Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 155
7-7-4. Remote Controller Distinction Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
7-7-5. Pulse Motor Valve (PMV) Forced Open/Close Function in Indoor Unit . . . . . . . . . . . . 158
7-7-6. Pulse Motor Valve (PMV) Forced Open Fully/Close fully Function in Outdoor Unit . . . 158
7-7-7. Solenoid Valve Forced Open/Close Function in Outdoor Unit . . . . . . . . . . . . . . . . . . . 159
7-7-8. Fan Operation Check in Outdoor Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160
7-7-9. Abnormal Outdoor Unit Discrimination Method By Fan Operating Function . . . . . . . . 161
7-7-10. Manual Adjustment Function of Outside Temperature (TO) Sensor . . . . . . . . . . . . . . 162
7-7-11. Monitor Function of Remote Controller Switch. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
8 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
8-1. Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
8-2. Troubleshooting Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 167
8-3. Troubleshooting Based on Information Displayed on Remote Controller . . . . . . . . . . . . . . . . . 173
8-4. Check Codes Displayed on Remote Controller and SMMS-i Outdoor Unit (7-Segment Display on I/
F Board) and Locations to Be Checked. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 178
8-5. Diagnosis procedure for each check code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
8-6. 7-Segment Display Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
8-7. Oil Level Judgment Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
8-8. Leakage/Clogging of Refrigerating Cycle Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
8-9. Sensor Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
8-10. Pressure Sensor Output Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
9 BACKUP OPERATION (EMERGENCY OPERATION) . . . . . . . . . . . . . . . . . . . . . . . 241
9-1. Note for Backup Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
9-2. Compressor Backup Operation Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
9-3. Outdoor Unit Backup Operation Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
9-3-1. Follower outdoor unit backup operation setting (failure of follower outdoor unit) . . . . . 243
9-3-2. Header outdoor unit backup operation setting (failure of header outdoor unit) . . . . . . 245
4
9-4. Cooling-Season Outdoor Unit Backup Operation Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
10 OUTDOOR UNIT REFRIGERANT RECOVERY METHOD . . . . . . . . . . . . . . . . . . . . 248
10-1. Refrigerant Recovery from Failed Outdoor Unit (Pump-Down) . . . . . . . . . . . . . . . . . . . . . . . . . 248
10-1-1. Note for refrigerant recovery operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
10-1-2. Refrigerant recovery procedure A (Case of no outdoor unit backup operation setting) 248
10-1-3. Refrigerant recovery procedure B (Case of outdoor unit backup operation setting) . . 251
10-2. How to Operate System While Failed Outdoor Unit Being Repaired. . . . . . . . . . . . . . . . . . . . . 253
10-3. Work procedure after Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 254
11 REPLACING COMPRESSORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
11-1. Compressor Replacement Procedure (Outline). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
11-2. Replacement of Compressors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
11-3. Check Procedure to Search Cause of Compressor Oil Shortage . . . . . . . . . . . . . . . . . . . . . . . 260
12 OUTDOOR UNIT PARTS REPLACEMENT METHODS . . . . . . . . . . . . . . . . . . . . . . 263
13 P.C. BOARD EXCHANGE PROCEDURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276
13-1. Replacement of Indoor P.C. Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276
13-2. Replacement of Outdoor P.C. Boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
13-2-1. List of service P.C. boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
13-2-2. Configuration of inverter assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
13-2-3. Interface board (MCC-1606) replacement method. . . . . . . . . . . . . . . . . . . . . . . . . . . . 284
13-2-4. Comp-IPDU P.C. Board (MCC-1596) Replacement Procedure . . . . . . . . . . . . . . . . . . 285
13-2-5. Fan IPDU P.C. Board (MCC-1610) Replacement Procedure . . . . . . . . . . . . . . . . . . . 287
13-2-6. Noise Filter P.C. Board (MCC-1608 A, B) Replacement Procedure . . . . . . . . . . . . . . 288
14 EXPLODED DIAGRAM/PARTS PRICE LIST. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 291
5
Original instruction
Please read carefully through these instructions that contain important information which complies with the “Machinery” Directive (Directive 2006/42/EC), and ensure that you understand them. Some of the details provided in these instructions differ from the service manual, and the instructions provided here take precedence.
Generic Denomination: Air Conditioner
Definition of Qualified Installer or Qualified Service Person
The air conditioner must be installed, maintained, repaired and removed by a qualified installer or qualified service person. When any of these jobs is to be done, ask a qualified installer or qualified service person to do them for you. A qualified installer or qualified service person is an agent who has the qualifications and knowledge described in the table below.
Agent Qualifications and knowledge which the agent must have
Qualified installer
• The qualified installer is a person who installs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified installer who is allowed to do the electrical work involved in installation, relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to do the refrigerant handling and piping work involved in installation, relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified installer who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
Qualified service person
• The qualified service person is a person who installs, repairs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, repair, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to these operations.
• The qualified service person who is allowed to do the electrical work involved in installation, repair, relocation and removal has the qualifications pertaining to this electrical work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to do the refrigerant handling and piping work involved in installation, repair, relocation and removal has the qualifications pertaining to this refrigerant handling and piping work as stipulated by the local laws and regulations, and he or she is a person who has been trained in matters relating to refrigerant handling and piping work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
• The qualified service person who is allowed to work at heights has been trained in matters relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
6
Definition of Protective Gear
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing. In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below. Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns, electric shocks and other injuries.
The important contents concerned to the safety are described on the product itself and on this Service Manual. Please read this Service Manual after understanding the described items thoroughly in the following contents (Indications/Illustrated marks), and keep them.
[Explanation of indications]
* Property damage: Enlarged damage concerned to property, furniture, and domestic animal/pet
[Explanation of illustrated marks]
Work undertaken Protective gear worn
All types of work
Protective gloves ‘Safety’ working clothing
Electrical-related work
Gloves to provide protection for electricians and from heat Insulating shoes Clothing to provide protection from electric shock
Work done at heights (50 cm or more)
Helmets for use in industry
Transportation of heavy objects Shoes with additional protective toe cap
Repair of outdoor unit Gloves to provide protection for electricians and from heat
Indication Explanation
DANGER
Indicates contents assumed that an imminent danger causing a death or serious injury of the repair engineers and the third parties when an incorrect work has been executed.
WARNING
Indicates possibilities assumed that a danger causing a death or serious injury of the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
CAUTION
Indicates contents assumed that an injury or property damage (*) may be caused on the repair engineers, the third parties, and the users due to troubles of the product after work when an incorrect work has been executed.
Mark Explanation
Indicates prohibited items (Forbidden items to do) The sentences near an illustrated mark describe the concrete prohibited contents.
Indicates mandatory items (Compulsory items to do) The sentences near an illustrated mark describe the concrete mandatory contents.
Indicates cautions (Including danger/warning) The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.
7
Warning Indications on the Air Conditioner Unit
[Confirmation of warning label on the main unit]
Confirm that labels are indicated on the specified positions If removing the label during parts replace, stick it as the original.
Warning indication Description
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing this panel.
CAUTION
Do not touch the aluminium fins of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
CAUTION
Do not climb onto the fan guard.
Doing so may result in injury.
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect all remote electric power supplies before servicing.
WARNING
Moving parts. Do not operate unit with grille removed. Stop the unit before the servicing.
CAUTION
High temperature parts. You might get burned when removing this panel.
CAUTION
Do not touch the aluminum fins of the unit. Doing so may result in injury.
CAUTION
BURST HAZARD
Open the service valves before the operation, otherwise there might be the burst.
CAUTION
Do not climb onto the fan guard.
Doing so may result in injury.
8
Precautions for Safety
The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual.
DANGER
Turn off breaker.
Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breaker for both the indoor and outdoor units to the OFF position. Otherwise, electric shocks may result.
Before opening the intake grille of the indoor unit or service panel of the outdoor unit, set the circuit breaker to the OFF position.
Failure to set the circuit breaker to the OFF position may result in electric shocks through contact with the interior parts.
Only a qualified installer (*1) or qualified service person (*1) is allowed to remove the intake grille of the indoor unit or service panel of the outdoor unit and do the work required.
Before starting to repair the outdoor unit fan or fan guard, be absolutely sure to set the circuit breaker to the OFF position, and place a “Work in progress” sign on the circuit breaker.
When cleaning the filter or other parts of the indoor unit, set the circuit breaker to OFF without fail, and place a “Work in progress” sign near the circuit breaker before proceeding with the work.
When you have noticed that some kind of trouble (such as when an error display has appeared, there is a smell of burning, abnormal sounds are heard, the air conditioner fails to cool or heat or water is leaking) has occurred in the air conditioner, do not touch the air conditioner yourself but set the circuit breaker to the OFF position, and contact a qualified service person. Take steps to ensure that the power will not be turned on (by marking “out of service” near the circuit breaker, for instance) until qualified service person arrives. Continuing to use the air conditioner in the trouble status may cause mechanical problems to escalate or result in electric shocks or other failure.
Electric shock
hazard
When you access inside of the service panel to repair electric parts, wait for about five minutes after turning off the breaker. Do not start repairing immediately.Otherwise you may get electric shock by touching terminals of high-voltage capacitors. Natural discharge of the capacitor takes about five minutes.
Prohibition
Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair or removal work is being carried out.
There is a danger of electric shocks if the circuit breaker is set to ON by mistake.
Before operating the air conditioner after having completed the work, check that the electrical parts box cover of the indoor unit and service panel of the outdoor unit are closed, and set the circuit breaker to the ON position. You may receive an electric shock if the power is turned on without first conducting these checks.
Stay on
protection
If, in the course of carrying out repairs, it becomes absolutely necessary to check out the electrical parts with the electrical parts box cover of one or more of the indoor units and the service panel of the outdoor unit removed in order to find out exactly where the trouble lies, wear insulated heat-resistant gloves, insulated boots and insulated work overalls, and take care to avoid touching any live parts.
You may receive an electric shock if you fail to heed this warning. Only qualified service person (*1) is allowed to do this kind of work.
9
WARNING
General
Before starting to repair the air conditioner, read carefully through the Service Manual, and repair the air conditioner by following its instructions.
Only qualified service person (*1) is allowed to repair the air conditioner. Repair of the air conditioner by unqualified person may give rise to a fire, electric shocks, injury, water leaks
and/or other problems.
Do not use any refrigerant different from the one specified for complement or replacement. Otherwise, abnormally high pressure may be generated in the refrigeration cycle, which may result in a failure
or explosion of the product or an injury to your body.
Only a qualified installer (*1) or qualified service person (*1) is allowed to carry out the electrical work of the air conditioner.
Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and/or electrical leaks.
When transporting the air conditioner, wear shoes with protective toe caps, protective gloves and other protective clothing.
When connecting the electrical wires, repairing the electrical parts or undertaking other electrical jobs, wear gloves to provide protection for electricians and from heat, insulating shoes and clothing to provide protection from electric shocks.
Failure to wear this protective gear may result in electric shocks.
Electrical wiring work shall be conducted according to law and regulation in the community and installation manual. Failure to do so may result in electrocution or short circuit.
Only a qualified installer (*1) or qualified service person (*1) is allowed to undertake work at heights using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work.
When working at heights, use a ladder which complies with the ISO 14122 standard, and follow the procedure in the ladder’s instructions.
Also wear a helmet for use in industry as protective gear to undertake the work.
When working at heights, put a sign in place so that no-one will approach the work location, before proceeding with the work.
Parts and other objects may fall from above, possibly injuring a person below.
When executing address setting, test run, or troubleshooting through the checking window on the electric parts box, put on insulated gloves to provide protection from electric shock. Otherwise you may receive an electric shock.
Do not touch the aluminum fin of the outdoor unit. You may injure yourself if you do so. If the fin must be touched for some reason, first put on protective gloves
and safety work clothing, and then proceed.
Do not climb onto or place objects on top of the outdoor unit. You may fall or the objects may fall off of the outdoor unit and result in injury.
When transporting the air conditioner, wear shoes with additional protective toe caps.
When transporting the air conditioner, do not take hold of the bands around the packing carton. You may injure yourself if the bands should break.
Be sure that a heavy unit (10kg or heavier) such as a compressor is carried by two persons.
This air conditioner has passed the pressure test as specified in IEC 60335-2-40 Annex EE.
Check earth
wires.
Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of the main unit, otherwise an electric shock is caused when a leak occurs.If the earth wire is not correctly connected, contact an electric engineer for rework.
After completing the repair or relocation work, check that the ground wires are connected properly.
Be sure to connect earth wire. (Grounding work) Incomplete grounding causes an electric shock. Do not connect ground wires to gas pipes, water pipes, and lightning rods or ground wires for telephone wires.
Prohibition of
modification.
Do not modify the products.Do not also disassemble or modify the parts. It may cause a fire, electric shock or injury.
10
Use specified
parts.
When any of the electrical parts are to be replaced, ensure that the replacement parts satisfy the specifications given in the Service Manual (or use the parts contained on the parts list in the Service Manual).
Use of any parts which do not satisfy the required specifications may give rise to electric shocks, smoking and/ or a fire.
Do not bring a
child close to
the
equipment.
If, in the course of carrying out repairs, it becomes absolutely necessary to check out the electrical parts with the electrical parts box cover of one or more of the indoor units and the service panel of the outdoor unit removed in order to find out exactly where the trouble lies, put a sign in place so that no-one will approach the work location before proceeding with the work. Third-party individuals may enter the work site and receive electric shocks if this warning is not heeded.
Insulating measures
Connect the cut-off lead wires with crimp contact, etc., put the closed end side upward and then apply a water­cut method, otherwise a leak or production of fire is caused at the users’ side.
No fire
When performing repairs using a gas burner, replace the refrigerant with nitrogen gas because the oil that coats the pipes may otherwise burn.
When repairing the refrigerating cycle, take the following measures.
1) Be attentive to fire around the cycle. When using a gas stove, etc., be sure to put out fire before work; otherwise the oil mixed with refrigerant gas may catch fire.
2) Do not use a welder in the closed room. When using it without ventilation, carbon monoxide poisoning may be caused.
3) Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may catch the inflammables.
Refrigerant
The refrigerant used by this air conditioner is the R410A.
Check the used refrigerant name and use tools and materials of the parts which match with it. For the products which use R410A refrigerant, the refrigerant name is indicated at a position on the outdoor unit
where is easy to see. To prevent miss-charging, the route of the service port is changed from one of the former R22.
For an air conditioner which uses R410A, never use other refrigerant than R410A. For an air conditioner which uses other refrigerant (R22, etc.), never use R410A.
If different types of refrigerant are mixed, abnormal high pressure generates in the refrigerating cycle and an injury due to breakage may be caused.
When the air conditioner has been installed or relocated, follow the instructions in the Installation Manual and purge the air completely so that no gases other than the refrigerant will be mixed in the refrigerating cycle. Failure to purge the air completely may cause the air conditioner to malfunction.
Do not charge refrigerant additionally. If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over the specified standard amount is charged and an abnormal high pressure is applied to the inside of the refrigerating cycle resulted in cause of breakage or injury. Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute vacuuming, and then newly recharge the specified amount of liquid refrigerant.
In this time, never charge the refrigerant over the specified amount.
When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant or air other than R410A into the specified refrigerant. If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating cycle resulted in cause of injury due to breakage.
After installation work, check the refrigerant gas does not leak. If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
Never recover the refrigerant into the outdoor unit. When the equipment is moved or repaired, be sure to recover the refrigerant with recovering device.
The refrigerant cannot be recovered in the outdoor unit; otherwise a serious accident such as breakage or injury is caused.
Assembly/
Wiring
After repair work, surely assemble the disassembled parts, and connect and lead the removed wires as before. Perform the work so that the cabinet or panel does not catch the inner wires. If incorrect assembly or incorrect wire connection was done, a disaster such as a leak or fire is caused at user’s
side.
Insulator
check
After the work has finished, be sure to use an insulation tester set (500V Megger) to check the resistance is 1M! or more between the charge section and the non-charge metal section (Earth position).
If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.
11
Ventilation
When the refrigerant gas leaks during work, execute ventilation. If the refrigerant gas touches to a fire, poisonous gas generates. A case of leakage of the refrigerant and the
closed room full with gas is dangerous because a shortage of oxygen occurs. Be sure to execute ventilation.
Compulsion
When the refrigerant gas leaks, find up the leaked position and repair it surely. If the leaked position cannot be found up and the repair work is interrupted, pump-down and tighten the service
valve, otherwise the refrigerant gas may leak into the room. The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the
refrigerant gas itself is innocuous. When installing equipment which includes a large amount of charged refrigerant such as a multi air conditioner
in a sub-room, it is necessary that the density does not the limit even if the refrigerant leaks. If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused.
Tighten the flare nut with a torque wrench in the specified manner. Excessive tighten of the flare nut may cause a crack in the flare nut after a long period, which may result in
refrigerant leakage.
Nitrogen gas must be used for the airtight test.
The charge hose must be connected in such a way that it is not slack.
For the installation/moving/reinstallation work, follow to the Installation Manual. If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shock or fire is caused.
Check after
repair
Once the repair work has been completed, check for refrigerant leaks, and check the insulation resistance and water drainage.
Then perform a trial run to check that the air conditioner is running properly.
After repair work has finished, check there is no trouble. If check is not executed, a fire, electric shock or injury may be caused. For a check, turn off the power breaker.
After repair work (installation of front panel and cabinet) has finished, execute a test run to check there is no generation of smoke or abnormal sound.
If check is not executed, a fire or an electric shock is caused. Before test run, install the front panel and cabinet.
Be sure to fix the screws back which have been removed for installation or other purposes.
Do not
operate the
unit with the
valve closed.
Check the following matters before a test run after repairing piping.
• Connect the pipes surely and there is no leak of refrigerant.
• The valve is opened.
Running the compressor under condition that the valve closes causes an abnormal high pressure resulted in damage of the parts of the compressor and etc. and moreover if there is leak of refrigerant at connecting section of pipes, the air is sucked and causes further abnormal high pressure resulted in burst or injury.
Check after
reinstallation
Only a qualified installer (*1) or qualified service person (*1) is allowed to relocate the air conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
Check the following items after reinstallation.
1) The earth wire is correctly connected.
2) The power cord is not caught in the product.
3) There is no inclination or unsteadiness and the installation is stable.
If check is not executed, a fire, an electric shock or an injury is caused.
When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause
air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in reputing, injury, etc.
Cooling check
When the service panel of the outdoor unit is to be opened in order for the compressor or the area around this part to be repaired immediately after the air conditioner has been shut down, set the circuit breaker to the OFF position, and then wait at least 10 minutes before opening the service panel.
If you fail to heed this warning, you will run the risk of burning yourself because the compressor pipes and other parts will be very hot to the touch. In addition, before proceeding with the repair work, wear the kind of insulated heat-resistant gloves designed to protect electricians.
Take care not to get burned by compressor pipes or other parts when checking the cooling cycle while running the unit as they get heated while running. Be sure to put on gloves providing protection for electric shock and heat.
When the service panel of the outdoor unit is to be opened in order for the fan motor, reactor, inverter or the areas around these parts to be repaired immediately after the air conditioner has been shut down, set the circuit breaker to the OFF position, and then wait at least 10 minutes before opening the service panel.
If you fail to heed this warning, you will run the risk of burning yourself because the fan motor, reactor, inverter heat sink and other parts will be very hot to the touch.
In addition, before proceeding with the repair work, wear the kind of insulated heat-resistant gloves designed to protect electricians.
12
Explanations given to user
• If you have discovered that the fan grille is damaged, do not approach the outdoor unit but set the circuit breaker to the OFF position, and contact a qualified service person to have the repairs done. Do not set the circuit breaker to the ON position until the repairs are completed.
Relocation
• Only a qualified installer (*1) or qualified service person (*1) is allowed to relocate the air conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
• When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will cause air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in reputing, injury, etc.
(*1) Refer to the “Definition of Qualified Installer or Qualified Service Person.”
Installation
Only a qualified installer (*1) or qualified service person (*1) is allowed to install the air conditioner. If the air conditioner is installed by an unqualified individual, a fire, electric shocks, injury, water leakage, noise and/or vibration may result.
Before starting to install the air conditioner, read carefully through the Installation Manual, and follow its instructions to install the air conditioner.
Be sure to use the company-specified products for the separately purchased parts. Use of non-specified products may result in fire, electric shock, water leakage or other failure. Have the installation performed by a qualified installer.
Do not supply power from the power terminal block equipped on the outdoor unit to another outdoor unit. Capacity overflow may occur on the terminal block and may result in fire.
Do not install the air conditioner in a location that may be subject to a risk of expire to a combustible gas. If a combustible gas leaks and becomes concentrated around the unit, a fire may occur.
Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure themselves or receive electric shocks if they poke their fingers or other objects into the indoor unit while the air conditioner is running.
Install a circuit breaker that meets the specifications in the installation manual and the stipulations in the local regulations and laws.
Install the circuit breaker where it can be easily accessed by the qualified service person (*1).
If you install the unit in a small room, take appropriate measures to prevent the refrigerant from exceeding the limit concentration even if it leaks. Consult the dealer from whom you purchased the air conditioner when you implement the measures. Accumulation of highly concentrated refrigerant may cause an oxygen deficiency accident.
Do not place any combustion appliance in a place where it is directly exposed to the wind of air conditioner, otherwise it may cause imperfect combustion.
13
Declaration of Conformity
NOTE
This declaration becomes invalid if technical or operational modifications are introduced without the manufacturer’s consent.
Manufacturer: Toshiba Carrier Corporation
336 Tadehara, Fuji-shi, Shizuoka-ken 416-8521 JAPAN
Authorized Representative/ TCF holder:
Nick Ball Toshiba EMEA Engineering Director Toshiba Carrier UK Ltd. Porsham Close, Belliver Industrial Estate, PLYMOUTH, Devon, PL6 7DB. United Kingdom
Hereby declares that the machinery described below:
Generic Denomination: Air Conditioner
Model/type: Outdoor unit
<Heat Pump Model> MMY-MAP0804HT8(Z)(ZG)-E, MMY-MAP1004HT8(Z)(ZG)-E, MMY-MAP1204HT8(Z)(ZG)-E, MMY-MAP1404HT8(Z)(ZG)-E, MMY-MAP1604HT8(Z)(ZG)-E
MMY-MAP0804HT8(Z)(ZG)-TR, MMY-MAP1004HT8(Z)(ZG)-TR, MMY-MAP1204HT8(Z)(ZG)-TR, MMY-MAP1404HT8(Z)(ZG)-TR, MMY-MAP1604HT8(Z)(ZG)-TR
<Cooling Only Model> MMY-MAP0804T8(Z)(ZG)-E, MMY-MAP1004T8(Z)(ZG)-E, MMY-MAP1204T8(Z)(ZG)-E, MMY-MAP1404T8(Z)(ZG)-E, MMY-MAP1604T8(Z)(ZG)-E
Commercial name: Super Modular Multi System Air Conditioner
Complies with the provisions of the “Machinery” Directive (Directive 2006/42/EC) and the regulations transposing into national law
Complies with the provisions of the following harmonized standard:
EN 378-2: 2008+A1:2009
14
Specifications
Model
Sound power level (dBA)
Weight (kg)
Cooling Heating
MMY-MAP0804HT8-E, MMY-MAP0804HT8Z-E, MMY-MAP0804HT8ZG-E
77 78 242
MMY-MAP1004HT8-E, MMY-MAP1004HT8Z-E, MMY-MAP1004HT8ZG-E
78 79 242
MMY-MAP1204HT8-E, MMY-MAP1204HT8Z-E, MMY-MAP1204HT8ZG-E
82 83 242
MMY-MAP1404HT8-E, MMY-MAP1404HT8Z-E, MMY-MAP1404HT8ZG-E
82 83 330
MMY-MAP1604HT8-E, MMY-MAP1604HT8Z-E, MMY-MAP1604HT8ZG-E
83 84 330
MMY-MAP0804HT8-TR, MMY-MAP0804HT8Z-TR, MMY-MAP0804HT8ZGTR
77 78 242
MMY-MAP1004HT8-TR, MMY-MAP1004HT8Z-TR, MMY-MAP1004HT8ZGTR
78 79 242
MMY-MAP1204HT8-TR, MMY-MAP1204HT8Z-TR, MMY-MAP1204HT8ZGTR
82 83 242
MMY-MAP1404HT8-TR, MMY-MAP1404HT8Z-TR, MMY-MAP1404HT8ZGTR
82 83 330
MMY-MAP1604HT8-TR, MMY-MAP1604HT8Z-TR, MMY-MAP1604HT8ZGTR
83 84 330
MMY-MAP0804HT8, MMY-MAP0804HT8Z, MMY-MAP0804HT8ZG
77 78 242
MMY-MAP1004HT8, MMY-MAP1004HT8Z, MMY-MAP1004HT8ZG
78 79 242
MMY-MAP1204HT8, MMY-MAP1204HT8Z, MMY-MAP1204HT8ZG
82 83 242
MMY-MAP1404HT8, MMY-MAP1404HT8Z, MMY-MAP1404HT8ZG
82 83 330
MMY-MAP1604HT8, MMY-MAP1604HT8Z, MMY-MAP1604HT8ZG
83 84 330
MMY-MAP0804HT7, MMY-MAP0804HT7Z, MMY-MAP0804HT7ZG
77 78 242
MMY-MAP1004HT7, MMY-MAP1004HT7Z, MMY-MAP1004HT7ZG
78 79 242
MMY-MAP1204HT7, MMY-MAP1204HT7Z, MMY-MAP1204HT7ZG
82 83 242
MMY-MAP1404HT7, MMY-MAP1404HT7Z, MMY-MAP1404HT7ZG
82 83 330
MMY-MAP1604HT7, MMY-MAP1604HT7Z, MMY-MAP1604HT7ZG
83 84 330
MMY-MAP0804T8-E, MMY-MAP0804T8Z-E, MMY-MAP0804T8ZG-E
77 241
MMY-MAP1004T8-E, MMY-MAP1004T8Z-E, MMY-MAP1004T8ZG-E
78 241
MMY-MAP1204T8-E, MMY-MAP1204T8Z-E, MMY-MAP1204T8ZG-E
82 241
MMY-MAP1404T8-E, MMY-MAP1404T8Z-E, MMY-MAP1404T8ZG-E
82 330
MMY-MAP1604T8-E, MMY-MAP1604T8Z-E, MMY-MAP1604T8ZG-E
83 330
15
* Under 70 dBA
MMY-MAP0804T8, MMY-MAP0804T8Z, MMY-MAP0804T8ZG
77 241
MMY-MAP1004T8, MMY-MAP1004T8Z, MMY-MAP1004T8ZG
78 241
MMY-MAP1204T8, MMY-MAP1204T8Z, MMY-MAP1204T8ZG
82 241
MMY-MAP1404T8, MMY-MAP1404T8Z, MMY-MAP1404T8ZG
82 330
MMY-MAP1604T8, MMY-MAP1604T8Z, MMY-MAP1604T8ZG
83 330
MMY-MAP0804T8-SG 77 241
MMY-MAP1004T8-SG 78 241
MMY-MAP1204T8-SG 82 241
MMY-MAP1404T8-SG 82 330
MMY-MAP1604T8-SG 83 330
Model
Sound power level (dBA)
Weight (kg)
Cooling Heating
16
Carrying in the Outdoor Unit
CAUTION
Handle the outdoor unit carefully, observing the following items.
• When using a forklift or other machinery for loading/unloading in transportation, insert the prongs of the forklift into the rectangular holes for handling as shown below.
• When lifting up the unit, insert a rope able to bear the unit’s weight into the rectangular holes for handling, and tie the unit from 4 sides. (Apply padding in positions where the rope comes into contact with the outdoor unit so that no damage is caused to the outer surface of the outdoor unit.) (There are reinforcing plates on the side surfaces, so the rope cannot be passed through.)
Front /Back
GOOD NO GOOD NO GOOD
Plaster
Rope
Plaster
Rectangular holes for lifting
Reinforcing plate
Prongs of the forklift
Rectangular
holes for handling
GOOD
NO GOOD
Side
17
Weight centre and weight
Weight centre of an outdoor unit
No. Model type X (mm) Y (mm) Z (mm)
Weight (kg)
Heat pump model Cooling only model
(A)
MAP080
500 390 645 242 241MAP100
MAP120
(B)
MAP140
605 350 700 330 330
MAP160
Z
X
Z
X
Y
Y
(A)
(B)
Anchor bolt position
700
Anchor bolt position
920
Anchor bolt position
755
Anchor bolt position
755
18
Selection of Pipe Size
Coupling size of brazed pipe
(Unit: mm)
Screw size and tightening torque
Connected section
External size Internal size
Standard outer dia.
of connected
copper pipe
Connected section
Min. thickness
of coupling
External size Internal size
Min. depth of
insertion
Oval value
Standard outer dia.
(Allowable difference)
C F K G
6.35 6.35 (±0.03) 6.45 ( ) 7 6 0.06 or less 0.50
9.52 9.52 (±0.03) 9.62 ( ) 8 7 0.08 or less 0.60
12.70 12.70 (±0.03) 12.81 ( ) 9 8 0.10 or less 0.70
15.88 15.88 (±0.03) 16.00 ( ) 9 8 0.13 or less 0.80
19.05 19.05 (±0.03) 19.19 ( ) 11 10 0.15 or less 0.80
22.22 22.22 (±0.03) 22.36 ( ) 11 10 0.16 or less 0.82
28.58 28.58 (±0.04) 28.75 ( ) 13 12 0.20 or less 1.00
34.92 34.90 (±0.04) 35.11 ( ) 14 13 0.25 or less 1.20
38.10 38.10 (±0.05) 38.31 ( ) 15 14 0.27 or less 1.26
41.28 41.28 (±0.05) 41.50 ( ) 15 14 0.28 or less 1.35
Screw size
Tightening torque
(N•m)
Power supply terminal M6 2.5 to 3.0
Earth screw M8 5.5 to 6.6
Communication wire terminal M3.5 0.80 to 0.96
K
ØC
G
ØF
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.04
-0.02
+0.03
-0.03
+0.03
-0.03
+0.06
-0.02
+0.04
-0.04
+0.08
-0.02
+0.08
-0.02
19
Adding refrigerant
After finishing vacuuming, exchange the vacuum pump with a refrigerant canister and start additional charging of refrigerant.
Calculation of additional refrigerant charge amount
Refrigerant charge amount at shipment from the factory does not include the refrigerant for pipes at the local site. For refrigerant to be charged in pipes at the local site, calculate the amount and charge it additionally.
NOTE
If the additional refrigerant amount indicates minus as the result of calculation, use the air conditioner without additional refrigerant.
Table 1
Heat pump
type
Outdoor unit type MAP080 MAP100 MAP120 MAP140 MAP160
Charging amount (kg) 11.5
Cooling only
type
Outdoor unit type MAP080 MAP100 MAP120 MAP140 MAP160
Charging amount (kg) 10.5 10.5 10.5 11.5 11.5
Additional refrigerant charge
amount at local site
=
Real length of liquid pipe
×
Additional refrigerant charge
amount per 1m liquid pipe
(Table 1)
+
Corrective amount of refrigerant
depending on HP of co-
operating outdoor units
(Table 2)
Liquid pipe dia. (mm) 6.4 9.5 12.7 15.9 19.1 22.2
Additional refrigerant amount/1m liquid pipe (kg/m)
0.025 0.055 0.105 0.160 0.250 0.350
20
Table 2
Charging of refrigerant
• Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the liquid side.
• If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and gas sides, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas side. In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
• The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
Combined HP (HP) Combined outdoor units (HP)
C (Corrective amount
of refrigerant) (kg)
Standard type
8 8HP 1.5
10 10HP 2.5
12 12HP 3.5
14 14HP 8.5
16 16HP 10.5
18 10HP 8HP 0.0
20 10HP 10HP 3.0
22 12HP 10HP 5.0
24 12HP 12HP 7.5
26 16HP 10HP 8.5
28 16HP 12HP 9.5
30 16HP 14HP 11.5
32 16HP 16HP 12.5
34 12HP 12HP 10HP 3.0
36 12HP 12HP 12HP 4.0
38 16HP 12HP 10HP 6.0
40 16HP 12HP 12HP 7.0
42 16HP 14HP 12HP 8.0
44 16HP 16HP 12HP 10.0
46 16HP 16HP 14HP 12.0
48 16HP 16HP 16HP 14.0
High Efficiency type
16 8HP 8HP 0.0
24 8HP 8HP 8HP -4.0
26 10HP 8HP 8HP -4.0
28 10HP 10HP 8HP -2.0
30 10HP 10HP 10HP 0.0
32 8HP 8HP 8HP 8HP -6.0
34 10HP 8HP 8HP 8HP -6.0
36 10HP 10HP 8HP 8HP -6.0
38 10HP 10HP 10HP 8HP -6.0
40 10HP 10HP 10HP 10HP -5.0
42 12HP 10HP 10HP 10HP -4.0
44 12HP 12HP 10HP 10HP -2.0
46 12HP 12HP 12HP 10HP 0.0
48 12HP 12HP 12HP 12HP 2.0
21
New Refrigerant (R410A)
This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer.
1. Safety Caution Concerned to New Refrigerant
The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has been also changed. Therefore, be sure that water, dust, the former refrigerant or the former refrigerating oil is not mixed into the refrigerating cycle of the air conditioner with new refrigerant during installation work or service work. If an incorrect work or incorrect service is performed, there is a possibility to cause a serious accident. Use the tools and materials exclusive to R410A to purpose a safe work.
2. Cautions on Installation/Service
(1) Do not mix the other refrigerant or refrigerating oil.
For the tools exclusive to R410A, shapes of all the joints including the service port differ from those of the former refrigerant in order to prevent mixture of them.
(2) As the use pressure of the new refrigerant is high, use material thickness of the pipe and tools which are
specified for R410A.
(3) In the installation time, use clean pipe materials and work with great attention so that water and others do not
mix in because pipes are affected by impurities such as water, oxide scales, oil, etc. Use the clean pipes.
Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.) (4) For the earth protection, use a vacuum pump for air purge. (5) R410A refrigerant is azeotropic mixture type refrigerant. Therefore use liquid type to charge the refrigerant.
(If using gas for charging, composition of the refrigerant changes and then characteristics of the air conditioner
change.)
3. Pipe Materials
For the refrigerant pipes, copper pipe and joints are mainly used. It is necessary to select the most appropriate pipes to conform to the standard. Use clean material in which impurities adhere inside of pipe or joint to a minimum.
(1) Copper pipe
(2) Joint
The flare joint and socket joint are used for joints of the copper pipe. The joints are rarely used for installation
of the air conditioner. However clear impurities when using them.
<Piping>
The pipe thickness, flare finishing size, flare nut and others differ according to a refrigerant type. When using a long copper pipe for R410A, it is recommended to select “Copper or copper-base pipe without seam” and one with bonded oil amount 40mg/10m or less. Also do not use crushed, deformed, discolored (especially inside) pipes. (Impurities cause clogging of expansion valves and capillary tubes.)
<Flare nut>
Use the flare nuts which are attached to the air conditioner unit.
22
4. Tools
(1) Required Tools for R410A
Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc.
Accordingly, the tools to be used are classified into the following three types.
1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))
2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)
3) Tools commonly used for R410A and for conventional refrigerant (R22)
The table below shows the tools exclusive for R410A and their interchangeability.
Tools exclusive for R410A (The following tools for R410A are required.)
Explanation of symbols
: Newly prepared (It is necessary to use it exclusively with R410A, separately from those for R22 or R407C.) : Former tool is available.
(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.
(Note 2) Charging cylinder for R410A is being currently developed.
Used tools Usage Proper use of tools/parts
Gauge manifold
Vacuuming, charging refrigerant and operation check
Exclusive to R410A
Charging hose Exclusive to R410A
Charging cylinder Charging refrigerant Unusable (Use the Refrigerant charging balance.)
Gas leak detector Checking gas leak Exclusive to R410A
Vacuum pump Vacuum drying Usable if a counter-flow preventive adapter is attached
Vacuum pump with counterflow Vacuum drying R22 (Existing article)
Flare tool Flare processing of pipes Usable by adjusting size
Bender Bending processing of pipes R22 (Existing article)
Refrigerant recovery device Recovering refrigerant Exclusive to R410A
Torque wrench Tightening flare nut Exclusive to Ø12.7mm and Ø15.9mm
Pipe cutter Cutting pipes R22 (Existing article)
Refrigerant canister Charging refrigerant
Exclusive to R410A Enter the refrigerate name for identification
Welding machine/Nitrogen gas cylinder
Welding of pipes R22 (Existing article)
Refrigerant charging balance Charging refrigerant R22 (Existing article)
General tools (Conventional tools can be used.)
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary as the general tools.
(1) Vacuum pump
Use vacuum pump by attaching vacuum pump
adapter. (2) Torque wrench (3) Pipe cutter (4) Reamer (5) Pipe bender (6) Level vial
(7) Screwdriver (+, –) (8) Spanner or Monkey wrench (9) Hole core drill (10)Hexagon wrench (Opposite side 4mm) (11)Tape measure (12)Metal saw
Also prepare the following equipments for other installation method and run check. (1) Clamp meter (2) Thermometer
(3) Insulation resistance tester (4) Electroscope
23
1
Wiring Diagrams
1-1. Outdoor Unit
Models: MMY-MAP0804 , MAP1004 , and MAP1204
24
Models: MMY-MAP1404 and MAP1604
25
1-2. Indoor Unit
1-2-1. 4-way Air Discharge Cassette Type
Models: MMU-AP0092H, AP0122H, AP0152H, AP0182H, AP0242H, AP0272H, AP0302H, AP0362H, AP0482H, and AP0562H
2019181716151413121110
20
U1U
2
X Y
19181716151413121110
11
987654321
987654321
654321
654321
54321
54321
521346
521346
54321
54321
321
321
531
531
321
321
54321
54321
54321
54321
54321
54321
54321
54321
22
11 22
11 22
11
2
33
1 2
1
321
2
3 4
TA
CN104
(YEL)
11 22
11
2
33
CN504
(WHI)
CN34
(RED)
CN510
(WHI)
CN333
(WHI)
Fuse, F02
T3.15A, 250V~
SW501
(High Wall setting)
CN71 (CHK)
ON
1 2
Fuse, F01
T6.3A, 250V~
Motor drive
circuit
+
~
~
CN334
(WHI)
CN82 (BLU)
CN81 (BLK)
CN01
(RED)
Control P.C. board
(MCC-1431)
Control P.C. board for Indoor unit
(MCC-1570)
Flow Selector unit (Option)
CN02
(GRN)
FS
(BLU)
LM1
FM
)KLB()DER()IHW(
TCJ
CN102 (RED)
TC2
CN101
(BLK)
TC1
CN100 (BRW)
CN519
(WHI)
CN508 (RED)
1
1 2
3
CN67 (BLK)
CN66
(WHI)
121
2
CN40
(BLU)
BLU BLU
BLK BLK
Outdoor
unit
RED
WHI
Power supply
single phase
220–240V ~ 50Hz
220V ~ 60Hz
CN80
(GRN)
21
CN73
(RED)
(PNL)(EXCT)
(OPTION) (FAN DRIVE)(GRL)
CN01 (WHI)
1. indicates the terminal block. Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring site.
3. indicates the control P.C. board.
CN02 (BLU)
CN001
(WHI)
Adapter
for Wireless
Remote controller
Wired
Remote
controller
BLK
WHI
WHI BLK
CN03 (RED)
Network adaptor
(Option)
TR
21543215 64321
5 64321 215432131321
31
21 21
21 21
21 21
313
1
31
CN70 (WHI)
CN50 (WHI)
CN61 (YEL)
CN32
(WHI)
CN60 (WHI)
CN20 (BLU)
CN309
(YEL)
CN41 (BLU)
Symbol
FM
TA
TC1, TC2, TCJ
LM1, 2, 3, 4
DM FS
PMV
TR
Parts name
Color Indication
Fan Motor Indoor temp. sensor Temp. sensor Louver Motor Drain pump Motor Float Switch Pulse Motor Valve Power supply Transformer
(Fot Nwtwork adapter)
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK
GRY : GRAY PNK : PINK ORN : ORANGE GRN : GREEN BRW : BROWN
(FILTER)T10
Power supply
circuit
DC20V DC15V DC12V DC7V
DM
R(L) S(N)
U1
A B
P01
BLK
PMV
LM3 LM2 LM4
Flow
Selector unit
Earth screw
Indoor unit
Earth screw
A B
1
3
U2
CN72 (DISP)
26
1-2-2. Compact 4-way Cassette Type
Models: MMU-AP0071MH, AP0091MH, AP0121MH, AP0151MH, and AP0181MH
BLK
P301
Fan motor Indoor temp. sensor Temp. sensor Temp. sensor Temp. sensor Louver motor Drain pump motor Float switch Drain control relay Pulse motor valve
Symbol
FM
TA TC1 TCJ TC2
LM1, LM2
DP FS
RY302
PMV
Parts name
Color
indication
RED : RED WHI : WHITE YEL : YELLOW BLU : BLUE BLK : BLACK GRY : GRAY PNK : PINK ORN : ORANGE BRW: BROWN GRN : GREEN
1. indicates the terminal bolock letter. Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site
3. indicates a control P.C. board.
S(N)R(L)
Power supply
single phase
220-240V, 50Hz
220V, 60Hz
Indoor unit
earth screw
CN67 (BLK)
CN304
(GRY)
RY302
DP
CN68 (BLU)
CN334
(WHI)
Motor
drive circuit
CN333
(WHI)
Flow selector
unit earth screw
noitpO)evird naF(
Adapter for
wireless
remote controlle
r
Wireed
remote controller
CN44
(BRW)
CN50 (WHI)
CN66 (WHI)
CN32
(WHI)
CN61 (YEL)
Control P.C. board
for Indoor unit
MCC-1402
CN60
(WHI)
CN81 (BLK)
CN33 (WHI)
CN20 (BLU)
CN70 (WHI)
CN73 (RED)
CN80
(GRN)
CN41 (BLU)
CN40 (BLU)
CN309
(YEL)
CN101
(BLK)
CN102
(RED)
CN104
(YEL)
CN34
(RED)
CN100 (BRW)
TC1
FS
TA TCJ TC2
CN82 (BLU)
LM1
LM2
Outdoor
unit
PNL
EXCT
Filter
GRL
CN001
(WHI)
WHI BLK
BLU
BLU
BLK
BLK
T10
WHI
RED
1
2
3
4
5
1
4
5
1
3
5
1 2 3 4 5 6
1 2 3 4 5 6
6 4 3 1 2 5
6 4 3 1 2 5
1 2 3
3 11 2 1 2 1 2
1 3
1 2 3
1 3
1 2 1 2 1 2
1
3
5
1 2
1 2
1
2
1
3
5
5
1
2
3
4
5
654321 54321654321
3 3
1 1
3 3
1 1
3
1
2
1
2
1
5
4
3
2
1
21
1
2
1
2
(CHK)
2
1
(DISP)
CN71
CN72
2
1
1
2
3
1
2
3
1
2
U2U1
BAU2U1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
5
4
3
2
1
RY303
Fuse
T6.3A
250V
~
Fuse
T3.15A
250V
~
DC20V DC15V DC12V DC 7 V
Power
supply
circuit
PMV
27
1-2-3. 1-way Air Discharge Cassette Type (Compact type)
Models: MMU-AP0071YH, AP0091YH, and AP0121YH
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
5
4
3 2 1
5 4 3 2 1
9 8 769 8 7 6
FAN
CN083
(WHI)
DP
(BLU)
CN068
DM
CN304
(GRY)
Heater
CN301
(BLK)
CN066
(WHI)
WHI
RED
BLU
BLU
BLU
CN067
(BLK)
Indoor control P.C. board
1
2
1
2
TA
TCJ
1
2
121
2
CN100
(BRW)
1
2
1
2
33
CN080
(GRN)
PNL
EXCT
1
2
CN073
(RED)
1
2
Filter
CN070
(WHI)
CN081
(BLK)
CN060
(WHI)
Option
CN032
(WHI)
CN075
(WHI)
CN074
(WHI)
TR
1212345
1
2
3
TC1
1 2 3
4
5 6
CN061
(YEL)
Fan drive
1 2 3 4 5 61 2 3 4 5 6
1 2 3
1 2
3
1 3
1
2
1 2
1 231 2 3
1 2 3
1 2 3
1 2 3
1 2
3
4 5 6
CN050
(WHI)
CN041
(BLU)
CN040
(BLU)
1
2
1 2
CN044
(BRW)
CN01
(WHI)
CN02
(BLU)
Network
adaptor
(Option)
1 2
1
2
3
4
5
1 2
1 2
1 1
2 2
2
1
2
3
3 1
CN03
(RED)
MCC-1401
RY004
1
2
3
1
2
RY002
RY006
RY007
RY005
1 2
BA
YX
S(N)R(L)
U
2
1 2
Remote controller
CN1
(WHI)
Power supply
Single phase
220-240V 50Hz
220V 60Hz
Indoor unit
Earth screw
Outdoor
unit
BLU
BLU
RED
WHI
BLK
BLK
U
1
U
2
U
1
Power supply
circuit
Network
adaptor
P.C. board
Symbol
FM
RC
TR
LM
TA
TC1,TCJ
RY001
RY002
RY004
RY005~007
FS
DM
PMV
Parts name
Fan motor
Running capacitor
Power transformer
Louver motor
Indoor temp sensor
Temp sensor
Flap motor control relay
Drain pump control relay
Heater control relay
Fan motor control relay
Float switch
Drain pump motor
Pulse Motor Valv e
LM
(GRN)
CN033
LM
1 2 3
1 2 3
FS
(RED)
CN030
PMV
(BLU)
CN082
FS
1 2 3
1 2 3
1 2 3
1 2
3
4 5 6
4 5 6
6 436 4 3
1 2 5
1 2 5
RY001
AI-NET
central control
terminal
TR
Fuse
T5.0A
1
2
3
123
CN309
(YEL)
AC IN
123 123
2 1
2 1
212 1
PMV
1
2
1
2
3
4
3
4
5
6
5
6
FM
YEL
BLU
ORN
BLK
RED
H M L UL
RC
1. indicates the terminal block, letter at inside
indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
Closed end
connector
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
CN01
(WHI)
CN02
(YEL)
Sub P.C. board
MCC-1520
Color
indication
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
Line Filter
Flow selector
unit earth
screw
28
1-2-4. 1-way Air Discharge Cassette Type SH 2 series
Models: MMU-AP0152SH, AP0182SH, and AP0242SH
1
3
1
3
CN104
(YEL)
TA
2
1
2
1
CN102
(RED)
TCJ
2
1
2
1
CN101
(BLK)
CN100
(BRW)
1
3
CN80
(GRN)
TC2
PNL
EXCT
2
1
CN73
(RED)
221
Filter
CN70
(WHI)
2
1
2
1
TC1
1 2 1 23 4 5 6 1 2 3 4 5
CN061
(YEL)
1 2 3 4 5 6
CN60
(WHI)
CN32
(WHI)
Fan
drive
T10
GRL
CN20
(BLU)
1 2 3 4 5
Option
CN81
(BLK)
1 2 3 4 5
CN50
(WHI)
CN309
(YEL)
CN02
(BLU)
MCC-1401
AI-NET
TR
Adapter for
wireless remote
controller
Network adapter
(Option)
CN001(WHI)
CN01
(WHI)
CN03
(RED)
CN40
(BLU)
CN41
(BLU)
1
1
1
1
2
2
1
1
2
X
Y
A
B
2
3
3
3
2
1
3
1
321 3
1
3
1
3
1
3
1
3
1
3
1
2
2
CN66
(WHI)
CN68
(BLU)
CN304
(GRY)
CN67
(BLK)
P301
BLK
RY303
RY302
2
1
1
1
DP
1
1
2
2
Wired
remote
controller
Outdoor
unit
WHI
WHI
RED
WHI
RED
BLU
BLU
BLK
BLK
WHI
BLK
BLK
BA
U
2
U
1
U
2
S(N)R(L)
U
1
Power supply
single phase
220-240V 50Hz
220V 60Hz
Indoor unit
earth screw
Closed-end
connector
Flow selector unit
earth screw
5 4 1
5
5
54 3
3
32
1
1
1
CN333
(WHI)
Fuse
T3.15A
250V~
CN82
(BLU)
CN112
(WHI)
CN111
(WHI)
CN110
(WHI)
CN71 (CHK)
High ceiling setup
LM
CN33
(WHI)
CN334
(WHI)
FM
1 2 3 4 5 6
1
1
1
2
1 2
1 2 1 2 1 2
1
2
2
2
3
3
3
4
4
4
5
3
CN34
(RED)
FS
1 2 3
1 3
4
5
1 2 3 4 5
1 2 3 4 5
1 2 3 4 5
5
5
6
6
6
PMV
Motor drive
circuit
Fuse
T6.3A 250V~
Power
supply
circuit
DC20V
DC15V
DC12V
DC7V
CN72 (DISP)
1. indicates the terminal bolock letter.
Letter at inside indicates the terminal number.
2. A dotted line and broken line indicate the wiring at side
3. indicates a control P.C. board.
FMTATC1
TCJ
TC2LMDP
FS
RY302
PMV
TR
Fan motor
Indoor temp sensor
Temp sensor
Temp sensor
Temp sensor
Louver motor
Drain pump motor
Float switsh
Drain control relay
Pulse motor valve
Transformer
Symbol
Parts name
Color
indication
RED: RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY: GRAY
PNK : PINK
ORN: ORANGE
BRN: BRWN
GRN: GREEN
Control P.C. board
for indoor unit
MCC-1402
29
1-2-5. 2-way Air Discharge Cassette Type 1 series
Models: MMU-AP0071WH, AP0091WH, AP0121WH, AP0151WH, AP0181WH, AP0241WH, AP0271WH, AP0301WH
CN104
(YEL)
CN102
(RED)
CN101
(BLK)
5
4
3
2
1
5
4
3
2 1
9 8 769
8 7
6
FAN
CN083
(WHI)
WHI
RED
DP
(BLU)
CN068
DM
CN304
(GRY)
CN066
(WHI)
CN067
(BLK)
CN044
(BRW)
Indoor control P.C. board
1
2
1
2
TA
1
2
1
2
TCJ
1
2
1
2
TC2
CN100
(BRW)
1
2
1
2
33
CN080
(GRN)
PNL
EXCT
1
2
CN073
(RED)
1
2
Filter
CN070
(WHI)
CN081
(BLK)
CN060
(WHI)
Option
CN032
(WHI)
CN075
(WHI)
CN074
(WHI)
TR
1
2
123
4
5
1
2
3
TC1
1 2 3 4 5 6
CN061
(YEL)
Fan drive
1 2
3
4 5 61 2 3 4 5 6
1
2 3
1 2 3
1 2
3
1 2
1 2
1 2 3
1
2
3
1 2 3
1 2 3
4 5
6
1 2 3 4 5 6
1 2 3 4 5 6
1
2 3
4 5
6
1 2
3
4 5 6
CN050
(WHI)
CN041
(BLU)
CN040
(BLU)
CN01
(WHI)
CN02
(BLU)
Network
adaptor
(Option)
1 2
1 2 3
4
5
1 2
1 2
3 3
2
1 1
CN03
(RED)
MCC-1401
2 2
1 1
RY004
123
1
2
1
2
RY002
RY006
RY007
RY005
1 2
BA
YX
S(N)R(L)
U
2
1 2
Remote controller
CN1
(WHI)
Power supply
Single phase
220-240V 50Hz
220V 60Hz
Indoor unit
Earth screw
Outdoor unit
BLU
BLU
BLK
BLK
U
1
U
2
U
1
Flow selector
unit earth
screw
Power supply
circuit
CN01
(WHI)
CN02
(YEL)
Sub P.C. board
MCC-1520
Symbol
FM
RC
TR
LM
TA
TC1,TC2,TCJ
RY001
RY002
RY004
RY005~007
FS
DM
PMV
Parts name
Fan motor
Running capacitor
Transformer
Louver motor
Indoor temp sensor
Temp sensor
Louver control relay
Drain control relay
Heater control relay
Fan motor control relay
Float switch
Drain pump motor
Pulse Motor Valv e
LM
(GRN)
CN033
LM
1 2 3
1 2 3
FS
(RED)
CN030
PMV
(BLU)
CN082
FS
1 2 3
1 2 3
1 2 3
1 2 3
4 5 6
4 5 6
6 4 3
6
4
3
1 2 5
1
2
5
RY001
TR
Fuse
T5.0A
250V~
1
2
3
1
2
3
CN039
(YEL)
1
2
3
1
2
3
1 2
1 2
PMV
1
2
1
2
3
4
3
4
5
6
5
6
77
9
FM
YEL
BLU
ORN
BLK
H M L UL
RC
RED
1. indicates the terminal block, letter at inside
indicates the terminal number.
2. A dotted line and broken line indicate the wiring at site.
3. indicates the control P.C. board.
Closed end
connector
Color
indication
RED : RED
WHI : WHITE
YEL : YELLOW
BLU : BLUE
BLK : BLACK
GRY : GRAY
PNK : PINK
ORN : ORANGE
BRW : BROWN
GRN : GREEN
Line Filter
P301
(BLK)
Loading...
+ 340 hidden pages