Toshiba MMU-P0151H, MMU-P0301H, MMU-P0181H, MMU-P0241H, MMU-P0361H Service Manual

...
0 (0)
SERVICE MANUAL
FILE NO. A02-009
Indoor Unit
<4-way Air Discharge Cassette Type>
MMU-P0121H, P0151H, P0181H, P0241H, MMU-P0301H, P0361H, P0481H
<2-way Air Discharge Cassette Type>
MMU-P0071WH, P0091WH, P0121WH, MMU-P0151WH, P0181WH, P0241WH, MMU-P0301WH, P0361WH, P0481WH
<1-way Air Discharge Cassette Type>
MMU-P0091SH, P0121SH, P0151SH, MMU-P0181SH, P0241SH
<Concealed Duct Type>
MMD-P0071BH, P0091BH, P0121BH, MMD-P0151BH, P0181BH, P0241BH, MMD-P0301BH, P0361BH, P0481BH
<Concealed Duct High Static Pressure Type>
MMD-P0181H, P0241H, P0361H, MMD-P0481H, P0721H, P0961H
<Under Ceiling Type>
MMC-P0151H, P0181H, P0241H, MMC-P0361H, P0481H
<High Wall Type>
MMK-P0091H, P0121H, P0151H, MMK-P0181H, P0241H
<Floor Standing Cabinet Type>
MML-P0091H, P0151H, P0181H, MML-P0241H
<Floor Standing Concealed Type>
MML-P0091BH, P0151BH, MML-P0181BH, P0241BH
Outdoor Unit
Cooling Only Model
<Inverter Unit>
MMY-MP0801T8, MP1001T8
<Fixed-Speed Unit>
MMY-MP06018, MP08018 MMY-MP10018
Heat Pump Model
<Inverter Unit>
MMY-MP0801HT8, MP1001HT8
<Fixed-Speed Unit>
MMY-MP0601H8, MP0801H8 MMY-MP1001H8
Heat Pump Model
<Inverter Unit>
MMY-MP0801HT7, MP1001HT7
<Fixed-Speed Unit>
MMY-MP0601H7, MP0801H7 MMY-MP1001H7
PRINTED IN JAPAN, May.,2002 ToMo
WARNINGS ON REFRIGERANT LEAKAGE
Check of Concentration Limit
The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit.
The refrigerant R407C which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer. However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R407C is almost non-existent. With the recent increase in the number of high concentration buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power etc. Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with conventional individual air conditioners. If a single unit of the multi conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur). In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device. The concentration is as given below.
Total amount of refrigerant (kg)
Min. volume of the indoor unit installed room (m³)
Concentration limit (kg/m³)
The concentration limit of R407C which is used in multi air conditioners is 0.3kg/m³.
NOTE 1 :
If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as charged in each independent device.
e.g., charged amount (10kg)
Room A Room B Room C Room D Room E Room F
For the amount of charge in this example:
The possible amount of leaked refrigerant gas in rooms A, B and C is 10kg. The possible amount of leaked refrigerant gas in rooms D, E and F is 15kg.
Outdoor unit
e.g., charged amount (15kg)
Indoor unit
Important
NOTE : 2
The standards for minimum room volume are as follows.
(1) No partition (shaded portion)
(2) When there is an effective opening with the
adjacent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door).
Outdoor unit
Refrigerant tubing
Indoor unit
(3) If an indoor unit is installed in each partitioned
room and the refrigerant tubing is interconnected, the smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object.
Refrigerant tubing
Outdoor unit
Very small room
Small room
Mechanical ventilation device - Gas leak detector
Medium room
Large room
NOTE 3 :
The minimum indoor floor area compared with the amount of refrigerant is roughly as follows: (When the ceiling is 2.7m high)
40
Range below the
35
density limit of 0.3 kg/m³
30
(countermeasures not needed)
25 20 15 10
5
Min. indoor floor area
0
10 20 30
Total amount of refrigerant
Range above the density limit of 0.3 kg/m³ (countermeasures needed)
Indoor unit
kg
This Manual is used for both models, Cooling Only model and Heat Pump model. Positions shaded with screens in the description and tables are applied to the Heat Pump model only. Parts marked with XXX indicate the 60Hz, 380V model only.
CONTENTS
SECTION 3 SERVICE MANUAL ....................................3-1
SAFETY NOTES......................................................................................3-1
SELECTING A LOCATION FOR INSTALLATION ..................................3-2
3-1. PARTS SPECIFICATIONS ...........................................................3-3
3-2. OWNER’S MANU A L....................................................................3-7
3-3. REFRIGERANT PIPING SYSTEMATIC DRAWING ..................3-18
3-4. COMBINED REFRIGERANT PIPING
SYSTEMATIC DRAWING ..........................................................3-22
3-5. OUTLINE OF CONTROL ...........................................................3-26
3-6. TROUBLESHOOTING ...............................................................3-38
3-7. CONTROL CIRCUIT CONFIGURATION .................................3-107
3-8. EMERGENCY OPERATION ....................................................3-131
3-9. FORCED FUNCTION OF OIL LEVEL DETECTION
(OUTDOOR UNIT) ...................................................................3-135
3-10. REFRIGERANT RECOVERY METHOD WHEN
REPLACING THE COMPRESSOR..........................................3-136
3-11. REPLACEMENT OF COMPRESSOR .....................................3-140
3-12. REPLACING METHOD OF PARTS .........................................3-146
3-13. EXPLODED VIEWS AND PARTS LIST ...................................3-148
SECTION 3 SERVICE MANUAL
SAFETY NOTES
• Read these Safety Notes carefully before installing this unit.
• These Safety Notes contain very important safety information. Always be sure to observe these cautions.
• After installation is complete, try the operation of the unit to make sure that it is operating normally. Be certain to instruct the customer about how to operate the unit, and about necessary maintenance.
Give this Installation Manual to the customer along with the Owner’s Manual, and recommend that the customer keeps both for future reference.
WARNINGS
• The dealer or a special contractor must install this unit.
Attempts to install this unit by a customer could result in leaks, electric shock, or fire.
• Follow these instructions carefully when installing this unit.
Improper installation could result in leaks, electric shock, or fire.
• If this unit is installed in a small room, measures must be taken to ensure that, even in the
event of a refrigerant leak, the maximum safe limit for refrigerant concentration levels in the air is not exceeded.
Consult the dealer for details on what measures can be taken to keep from exceeding the maximum safe limit. If a refrigerant leak does cause refrigerant concentration levels in the air to exceed the maximum safe limit, asphyxiation could result.
• Select a location for installation that will be able to safely bear the weight of the unit.
If the installation location is not strong enough to support the unit and the unit falls, injury could result.
• Install the unit in the prescribed manner to withstand strong (hurricane-level) winds and
earthquakes.
Insufficiently secure installation could allow the unit to tip over, fall, or otherwise cause an accident.
• Ventilate the area if any refrigerant leaks during installation.
If the refrigerant comes into contact with an open flame, it will produce a toxic gas.
• After completing installation, make sure that no refrigerant is leaking.
If the refrigerant leaks indoors and comes into contact with an open flame in a water heater, stove, oven, or other such appliance, it will produce a toxic gas.
• Electrical work must be performed by a qualified electrician as described in the Installation
Manual. The unit must be connected to its own independent circuit.
Inadequate circuit capacity or improper installation could result in electric shock or fire.
• Wiring must be performed securely, using the prescribed cables. The cables must be
secured in a manner that prevents any force that pulls on the cables from being relayed to the terminal connectors.
If the cables are not connected or secured properly, fire or other accidents could result.
• The unit must be grounded.
Do not connect the ground wire to a gas pipe, water pipe, lightning rod, or telephone ground wire. When wiring the system to the main power supply, follow the standards established by the local power
company. Inadequate grounding can result in electric shock.
CAUTIONS
• Install a ground fault interrupter.
If a ground fault interrupter is not installed, electric shock could result.
• Do not install the unit in a location where combustible gases could conceivably leak.
Leaking gases that accumulate in the vicinity of the unit could be ignited by the unit.
3-1
SELECTING A LOCATION FOR INSTALLATION
WARNINGS
• Select a location for installation that will be able to safely bear the weight of the unit.
If the installation location is not strong enough to support the unit and the unit falls, injury could result.
CAUTION
• Do not install the unit in a location where combustible gases could conceivably leak.
Leaking gases that accumulate in the vicinity of the unit could be ignited by the unit.
Obtain permission from the customer to install the unit in a location that satisfies the following requirements:
• A location that permits level installation of the unit
• A location that provides enough space to service the unit safely
• A location where water draining from the unit will not pose a problem
Avoid the following types of locations:
• Locations where salt is present in large amounts (seaside areas), or where sulfuric gases are present in
large amounts (hot springs areas) (If the unit is to be used in such areas, special maintenance is necessary.)
• Locations that generate oils (including machine oils), steam, oily smoke, or corrosive gases
• Locations where organic solvents are used
• Locations in the vicinity of equipment that generates high frequency signals
• Locations where the outdoor unit will blow in the direction of a neighbor’s window
• Locations where the noise of the outdoor unit will pose a problem
• Locations with poor air circulation
3-2
3-1. PAR TS SPECIFICATIONS
Indoor unit
4-way Air Discharge Cassette Type
Model MMU- P0121H P0151H P0181H P0241H P0301H P0361H P0481H
Fan motor ICF-230-60-1 MF-200-90-2 Drain pump motor PJD-05230TF Float switch FS-0208-602 Control P.C. board transformer (Control P.C.B) SWT66 Remo-con/Power TT-02 Pulse motor EDM- MD12TF-3
Pulse motor valve EDM­Pressure sensor 150F/160NH6-D
Louver motor (panel) MT8-3-9
B252TF-1
(F25)
B402TF-1
(F40)
1-way Air Discharge Cassette Type
Model MMU- P0091SH P0121SH P0151SH P0181SH P0241SH
Fan motor AF-200-22-4N-1 AF-200-34-4D Running capacitor for fan motor 450V 1.0µF 400V 1.5µF 400V 2.5µF Drain pump PJV-0774 Float switch FS-085-003E FS-0208-601 Control P.C. board transformer TT-03 Pulse motor EDM- MD12TF-3 Pulse motor valve EDM- B252TF-1 (F25) B402TF-1 (F40) Pressure sensor 150F/160NH6-D Louver motor (Panel) MT-8-3-4
PJD-05230TF
B602TF-1
(F60)
Concealed Duct Type
Model MMD- P0071BH P0091BH P0121BH P0151BH P0181BH P0241BH P0301BH P0361BH P0481BH
Fan motor STF- 200-60-4D 200-60-4C 200-100-4E 200-100-4F 200-120-4D 200-140-4G Running capacitor
for fan motor Control P.C. board
(Transformer) Float switch FS-0208-601 Drain pump motor PJD-05230TF Pulse motor EDM- MD12TF-3 Pulse motor valve EDM-B252TF-1 (F25) EDM-B402TF-1 (F40) Pressure sensor 150F/160NH6-D Louver motor MT8-3-6
450V 2µF 500V 2.5µF 400V 5.0µF 400V 6µF 400V 10µF
TT-03
High Wall Type
Model MMK- P0091H P0121H P0151H P0181H P0241H
Fan motor MF-200-30-4A MF-200-30-4B Running capacitor for fan motor 400V 1.0µF 450V 1.5µF Control P.C. board
(Transformer) Pulse motor EDM- MD12TF-3 Pulse motor valve EDM- B252TF-1 (F25) B402TF-1 (F40) Pressure sensor 150F/160NH6-D Louver motor MT8-3-6
TT-03
3-3
Cooling only model
50Hz
Outdoor unit
Model name or rating
Part name
Compressor MG1450CW-21B YG890C-B1 YG1700CW-B1 YG1800CW-B1 Inner overload relay OFF : 115°C
Fan motor
High-pressure SW 20PS-G ON : 3.2MPa, OFF : 2.55MPa, (normal open contact)
High-pressure SW
Pressure sensor (For high pressure)
Pressure sensor (For low pressure)
Crank case heater —— AC240V, 40W AC240V, 74W Heater for accumulator AC 240V, 26W Electronic control valve
(For cooling bypass)
2-way valve
MMY-MP0801T8
(8HP inverter)
ACB-JBD8 OFF : 3.2Mpa, ON : 2.55Mpa,
(normal close contact )
MMY-MP1001T8
(10HP inverter)
STF-200–350A, AC220–240V, 350W
Protection relay OFF : 145°C, ON : 8 6°C
NEV-MOAJ510B0 (Coil), AC220–240V
NEV-MOAJ510B0 (Coil), AC220–240V
MMY-MP06018
(6HP fixed-speed)
150NH4-H, 0–3.3MPa
150NH4-L, 0–0.98MPa
SEV18RC4 (Main unit) A12A15 (Coil), DC12V
NEV202DXF (Main unit)
NEV603DXF (Main unit)
MMY-MP08018
(8HP fixed-speed)
——
MMY-MP10018
(10HP fixed-speed)
Outdoor controller
Model name or rating
Part name
Power supply voltage 3 Phase, AC380 / 400 / 415V, 50Hz Power supply terminal block 60A, 3P (1pc.) and 30A, 3P (1pcs.) Communication line
terminal block Magnet switch
(Fixed compressor) Fuse (Power supply) AC 600V, 20A (3pcs. ) —— Fuse holder AC 600V, 30A (3pcs. ) —— Reactor CH-25 (2pcs.) —— Smoothing capacitor 2200µF, 400V (2pcs .) —— Fan capacitor 8µF, 450VAC (1pcs.) Power supply transformer TT-01 (1pcs.) P.C. board (Noise filter) MCC-1366 —— Line filter (AC) 600µH, 20A (2pcs.) —— P.C. board (Interface) MCC-1343 P.C. board (IPDU) Magnet switch (Power) AC440V, 13A (1pcs.) —— Power complex module 7MBR35SB120 (MCC-1342) —— P.C. board
(Lightning surge)
MMY-MP0801T8
(8HP inverter)
1A, 4P (1pcs. ) 1A, 2P (1pcs. )
MCC-1342
MMY-MP1001T8
(10HP inverter)
—— MCC-1357
MMY-MP06018
(6HP fixed-speed)
3 Phase, AC440V, 15A
MMY-MP08018
(8HP fixed-speed)
——
MMY-MP10018
(10HP fixed-speed)
3-4
Heat pump model
50Hz
Outdoor unit
Model name or rating
Part name
Compressor MG1450CW-21B YG8900-B1 YG1700CW-B1 YG1800CW-B1 Inner overload relay OFF : 115°C
Fan motor High-pressure SW ACB-JB128 ON : 3.2MPa, OFF : 2.55MPa, (normal open contact) High-pressure SW Pressure sensor
(For high pressure) Pressure sensor
(For low pressure) Crank case heater —— AC240V, 40W AC240V, 74W Heater for accumulator AC240V, 26W Electronic control valve
(For main throttle) Electronic control valve
(For cooling bypass)
4-way valve
2-way valve
MMY-MP0801HT8
(8HP inverter)
ACB-JA64 OFF : 3.2Mpa, ON : 2.55Mpa,
(normal close contact)
CHV-0712 (Main unit) CHV-040 1 (Main u n i t ) CHV-0712 (Main unit)
MMY-MP1001HT8
(10HP inverter)
STF-200–350A, AC220–240V, 350W
Protection relay OFF : 145°C, ON : 86°C
CHV-01AJ502E1 (Coil), AC220–240V
NEV-MOAJ510B0 (Coil), AC220–240V
NEV-MOAJ510B0 (Coil), AC220–240V
MMY-MP0601H8
(6HP fixed-speed)
150NH4-H, 0–3.3MPa
150NH4-L, 0–0.98MPa
CEV30RC1 (M ain unit) L12A-03 (Coil), DC12V
SEV18RC4 (Main unit) A12A15 (Coil), DC12V
NEV202DXF (Main unit)
NEV603DXF (Main unit)
MMY-MP0801H8
(8HP fixed-speed)
——
MMY-MP1001H8
(10HP fixed-speed)
Outdoor controller
Model name or rating
Part name
Power supply voltage 3 Phase, AC380 / 400 / 415V, 50Hz Power supply terminal block 60A, 3P (1pc.) and 30A, 3P (1pc.) Communication line
terminal block Magnet switch
(Fixed compressor) Fuse (Power supply) AC 600V, 20A (3pcs.) —— Fuse holder AC 600V, 30A (3pcs.) —— Reactor CH-25 (2pcs.) —— Smoothing capacitor 2200µF, 400V (2pcs .) —— Fan capacitor 8µF, 450VAC (1pc.) Power supply transformer TT-01 (1pc.) P.C. board (Noise filter) MCC-1366 —— Line filter (AC) 600µH, 20A (2pcs.) —— P.C. board (Interface) MCC-1343 P.C. board (IPDU) Magnet switch (Power) AC440V, 13A (1pc.) —— Power complex module 7MBR35SB120 (MCC-1342) —— P.C. board
(Lightning surge)
MMY-MP0801HT8
(8HP inverter)
1A, 4P (1pc.) 1A, 2P (1pc.)
MCC-1342
MMY-MP1001HT8
(10HP inverter)
—— MCC-1357
MMY-MP0601H8
(6HP fixed-speed)
3 Phase, AC440V, 15A
MMY-MP0801H8
(8HP fixed-speed)
——
MMY-MP1001H8
(10HP fixed-speed)
3-5
Heat pump model
60Hz
Outdoor unit
Model name or rating
Part name
Compressor MG1450CW-22B YG8900-3B YG1700CW-3B YG1800CW-3B Inner overload relay OFF : 115°C
Fan motor High-pressure SW ACB-JB128 ON : 3.2MPa, OFF : 2.55MPa, (normal open contact ) High-pressure SW Pressure sensor
(For high pressure) Pressure sensor
(For low pressure) Crank case heater —— AC240V, 40W AC240V, 74W Heater for accumulator AC240V, 26W Electronic control valve
(For main throttle) Electronic control valve
(For cooling bypass)
4-way valve
2-way valve
MMY-MP0801HT7
(8HP inverter)
ACB-JA64 OFF : 3.2Mpa, ON : 2.55Mpa,
(normal close contact)
CHV-0712 (Main unit) CHV-040 1 (Main unit) CHV-0712 (Main unit)
MMY-MP1001HT7
(10HP inverter)
STF-200–350A, AC220V, 350W
Protection relay OFF : 145°C, ON : 8 6°C
CHV-01AJ502E1 (Coil), AC220–240V
NEV-MOAJ510B0 (Coil), AC220–240V
NEV-MOAJ510B0 (Coil), AC220–240V
MMY-MP0601H7
(6HP fixed-speed)
150NH4-H, 0–3.3MPa
150NH4-L, 0–0.98MPa
CEV30RC1 (M ain unit) L12A-03 (Coil), DC12V
SEV18RC4 (Main unit) A12A15 (Coil), DC12V
NEV202DXF (Main unit)
NEV603DXF (Main unit)
MMY-MP0801H7
(8HP fixed-speed)
——
MMY-MP1001H7
(10HP fixed-speed)
Outdoor controller
Model name or rating
Part name
Power supply voltage 3 Phase, AC380V, 60Hz Power supply terminal block 60A, 3P (1pc.) and 30A, 3P (1pc.) Communication line
terminal block Magnet switch
(Fixed compressor) Fuse (Power supply) AC 600V, 20A (3pcs. ) —— Fuse holder AC 600V, 30A (3pcs. ) —— Reactor CH-25 (2pcs.) —— Smoothing capacitor 2200µF, 400V (2pcs .) —— Fan capacitor 10µF, 450VAC (1pc.) Power supply transformer TT-01 (1pc.) P.C. board (Noise filter) MCC-1366 —— Line filter (AC) 600µH, 20A (2pcs.) —— P.C. board (Interface) MCC-1343 P.C. board (IPDU) Magnet switch (Power) AC440V, 13A (1pc.) —— Power complex module 7MBR35SB120 (MCC-1342) —— P.C. board
(Lightning surge)
MMY-MP0801HT7
(8HP inverter)
1A, 4P (1pc.) 1A, 2P (1pc.)
MCC-1342
MMY-MP1001HT7
(10HP inverter)
—— MCC-1357
MMY-MP0601H7
(6HP fixed-speed)
3 Phase, AC440V, 15A
MMY-MP0801H7
(8HP fixed-speed)
——
MMY-MP1001H7
(10HP fixed-speed)
3-6
3-2. OWNERS MANUAL
3-2-1. Name of Each Part
3-2-1-1. Outdoor unit
Air inlet
They are provided at front, rear, left, and right sides.
Fixing leg
3-2-1-2. Indoor unit
[4-way Air Discharge Cassette Type]
Earth screw
It is included in the electric parts box.
Air outlet (Discharge)
Hot air is discharged when cooling operation is performed.
Cold air is diacharged when heating operation is performed.
Power source hole Refrigerant pipe
connecting hole
Connecting valve is included inside here.
Air outlet/Discharge louver
Select air blow direction in cooling or heating operation each.
2-way discharge/3-way discharge
2-way discharge or 3-way discharge can be selected according to the shape or arrangement of the room. For details, consult with the dealer which you have purchased the air conditioner.
Clip
The clip is to open/close the air inlet grille.
[2-way Air Discharge Cassette Type]
Earth screw
It is included in the electric parts box.
Center panel Air inlet
Air in the room is sucked from here.
Air filter
Removes dust and trash. (Air filter is provided in the air grille.)
Air inlet grille
Air in the room is sucked from here.
Air outlet/Discharge louver
Select air blow direction in cooling or heating operation each.
Air filter
Removes dust and trash. (Air filter is provided in the center panel.)
3-7
[1-way Air Discharge Cassette Type]
[Concealed Duct type]
Earth screw
It is included in the electric parts box.
Air outlet/Discharge louver
Select air blow direction in cooling or heating operation each.
Air inlet grille
Air in the room is sucked from here.
Air filter
Removes dust and trash. (Air filter is provided in the air inlet grille.)
Air outlet flange
Discharge duct is connected.
Earth screw
It is included in the electric parts box.
Air filter
Removes dust and trash. (Air filter is provided in the air inlet grille.)
Air inlet
Air in the room is sucked from here.
[1-way Air Discharge Cassette Type]
Air outlet/Discharge louver
Select air blow direction in cooling or heating operation each.
Earth screw
It is included in the electric parts box.
Air inlet grille
Air in the room is sucked from here.
Air filter
Removes dust and trash. (Air filter is provided in the air inlet grille.)
[Concealed Duct High Static Pressure Type]
Air inlet
Suction duct is connected.
Air outlet
Discharge duct is connected.
Earth screw
Earth screws are provided in the electric parts box.
Drain pan
3-8
[Under Ceiling Type] [Floor Standing Cabinet Type]
Air outlet/Discharge louver
Select air blow direction in cooling or heating operation each.
Earth screw
It is included in the electric parts box.
Air inlet grille
Air in the room is sucked from here.
Air filter
Removes dust and trash. (Air filter is provided in the air inlet grille.)
Earth screw Air outlet/Discharge louver
Select air blow direction in cooling or heating operation each.
Air filter
Removes dust and trash. (Air filter is provided in the air inlet grille.)
Air inlet grille
Air in the room is sucked from here.
[High Wall Type] [Floor Standing Concealed Type]
Air outlet
Earth screw
Earth screws are provided in the electric parts box.
Drain receiver (With strainer)
It is an accessory part which is attached at site.
Air inlet grille
Air in the room is sucked from here.
Air inlet
Air filter
Removes dust and trash. (Air filter is provided in the air inlet grille.)
Air outlet grille/ Discharge louver
Select air blow direction in cooling or heating operation each.
Air filter
Removes dust and trash. (Air filter is provided in the front panel.)
Air in the room is sucked from here.
3-9
Front panel (Lower side) Earth screw
Earth screws are provided in the electric parts box.
MODE
FAN
TEMP.
AUTO FIX
CHECK ADDRESS
UNITUNIT
CENTRAL
12
*
F AN COOL
HEAHEAT
STSTANDBYANDBY FILTER PREHEAPREHEAT DEFROST LOUVER MANUAL
Display section
Operation section
Display section
Unit display
Set up temperature display
CHECK
Displayed during check mode.
Operation mode select display
The selected operation mode is displayed.
Air volume fix display
This is displayed only in the Ceiling concealed duct type.
Air volume select display
The selected air volume mode is displayed.
(LOW) (MED.)
(HIGH)
STANDBY display
It is displayed when the operation cannot be performed though it is not an error.
CENTRAL control display
Displayed when used with the central remote controller, etc.
LOUVER/MANUAL display
It is displayed when selecting Louver operation switch on a Model having no auto louver function.
LOUVER display
It is displayed while the discharge louver operates in AUTO mode.
FILTER display
If “FILTER” is displayed, clean the air filter.
PREHEAT/DEFROST display
Displayed when heating operation or defrost operation starts.
Unit No. in which error/fault is displayed in the set up temp. display section.
The selected set up temp. is displayed.
MODEMODE
FANAN
TEMPTEMP.
F ANAN COOLCOOL
HEAHEAT
AUTUTO FIX
CHECKCHECK
ADDRESSADDRESS
UNITUNIT
STANDBYANDBY FILFILTERTER PREHEAPREHEAT DEFRDEFROSTOST LOUVERLOUVER MANUMANUALAL
CENTRALCENTRAL
1212
MODEMODE
ON/OFFON/OFF
FILFILTERTER
CHECKCHECK
(In Ceiling concealed duct type air conditioner, air volume cannot be selected.)
*
3-2-2. Names and Operations of Remote Controller
3-2-2-1. Display section
In the display example, all are displayed for explanation. In real time, the selected contents are indicated. The displayed contents differ according to shape or type.
They are displayed on the Heat Pump model only.
*
3-10
3-2-2-2. Operation section
Push each switch to select a desired operation.
Filter reset switch
Resets (Erases) FILTER display.
Operation select switch
Selects desired operation mode.
Operation lamp
Lamp is lit during the operation. Lamp is off while stopped. Although it flashes when power switch is turned on or when turned on again after power failure, it goes on if the operation has started.
CHECK switch
When an error/fault occurs on the air conditioner, this switch is used to check the check code indicating fault status. Only use for fault diagnosis.
Air volume select switch
Selects the desired air volume mode.
Set up temp. switch
Adjusts the room temperature. Match to the desired set temperature
by pushing .
Operation section
ON/OFF button
When the button has been pushed, the operation starts, and it stops by pushing the button again. When the operation has stopped, the operation lamp and louver display disappear though other displays remain as they are.
Louver operation switch
In case of Model with auto louver, the discharge louver operates or stops during operation of air conditioner.
Central indication
When using a remote controller combined with a central remote controller, etc., contents which can be operated with the standard remote controller and CENTRAL display change by setting at the central remote controller.
Set up on central
remote controller
Last-push priority (No display)
Center Operation inhibit
For application control using Weekly timer or Central remote controller other than this standard remote controller, refer to the Manual attached to each remote controller.
CENTRAL display on
standard remote controller
Goes off
Goes on Flashes
3-11
Functions operated by
standard remote controller
Operated from both standard remote controller and central remote controller, and operated with contents specified later.
ON / OFF only can be operated. Operation not permissible.
LOW MED. HIGH
AUTO
MODE
CHECK
ADDRESS
UNIT
12
COOL HEA
ANDBY
PREHEA DEFR
OST LOUVER MANUALAL
3-2-3. Correct Usage
When you use the air conditioner at the first time or when you change the set up value, follow the procedure below. From the next time, the operation dis-played on the remote controller will start only by pushing ON/OFF button.
Preparation Turn on the power switch.
The operation lamp (Red) flashes.
REQUIREMENT
While using the air conditioner, operate it only with ON/OFF button without turning off the main power switch.
When starting the operation after stop for a long time, turn on the main power switch for 12 hours or more
before start. (This is required because it is necessary to turn on the compressor case heater for heating in order to prevent overload on the compressor when activating the outdoor unit.)
1
Select an operation mode with the “MODE” button.
One push of the button, and the display changes as follows:
2
Select air volume with the FAN button.
One push of the button, and the display changes as follows:
(Air volume cannot be selected in the concealed duct type.)
When air volume is AUTO, power of air differs according to the room temperature.
FAN COOL HEAT
*
3
Determine the set up temperature by pushing the TEMP.
4
Push ON/OFF button.
The operation lamp goes on, and the operation starts.
button.
MODE
F AN COOL
HEA
MODE
CHECK
12
AUTO
T
FIX
TEMP.
UNIT
ADDRESS
CENTRAL
FAN
STOP
FILTER
Push ON/OFF button.
The operation lamp goes off, and the operation stops.
HEAT is displayed on the Heat Pump model only.
*
1
CHECK
2
ON/OFF
4
NOTE
In cooling
When the operation button has been pushed, the operation starts approx.1minute after.
In heating
When the operation button has been pushed, the indoor fan performs pre-heating operation for 3 to 5 minutes as it stops and then blows out hot air.
While the room temperature has attained the set temperature and the outdoor unit stops, the super-low air blows out and air volume becomes excessively small. During defrost operation, the fan stops so that cold air does not blow out, and PRE-HEAT and DEFROST are displayed.
When restarting the operation after stop
In heating operation, the fan operation may continue for approx. 30 seconds after the machine has stopped.
When restarting the operation immediately after stop, the air conditioner does not operate for approx. 3 minutes to protect the machine.
STSTANDBY FILTER PREHEA
T
DEFR
OST LOUVER MANU
3
3-12
MODE
AN
TEMP
AN
COOL HEA
FIX
CHECK
ADDRESS
ANDBY
FIL
TER PREHEA DEFR
OST LOUVER MANUALAL
CENTRAL
MODE
ON/OFF
FIL
TER
CHECK
Center panel
3-2-4. Maintenance
For maintenance, be sure to turn off the power switch.
<Daily maintenance>
t Cleaning of air filter
[4-way Air Discharge Cassette Type]
The suction port opens by pushing the clips of the
MODE
F AN COOL
HEA
MODE
FIL
TER
FAN
CHECK
12
AUTUTO
T
FIX
CHECK
TEMP
.
UNIT
ADDRESS
CENTRAL
suction port laterally. Push up clip of the air filter, and take out the air filter by
ON/OFF
pulling it towards you.
[2-way Air Discharge Cassette Type]
Pull the center panel toward you while lifting up it, and pull it slowly downward. (The center panel moves to either left or right only, so confirm before removing.)
Remove the fall-preventing strings at both ends.
Pull the air filter downward to remove it.
In case of MMU-P0361WH or MMU-P0481WH, pull the air filter downward undoing the clips.
CAUTION
Be sure to attach the fall-preventing strings of the center panel after cleaning.
If the center panel drops injury may occur.
STSTANDBY FIL
TER
PREHEA
T
DEFR
OST LOUVER MANU
FILTER display
Notifies the time to clean the air filter.
FILTER reset
Push the FILTER switch after cleaning.
FILTER” display disappears.
[1-way Air Discharge Cassette Type]
Undo clip of the suction port with both hands, open it slowly downward, push the air filter to inside to remove it from clips, and then remove the air filter.
(MMU-P0091SH and P0121SH model)
Push clips at the center and left/right of the suction port to open the suction port.
Lift up the air filter once, and pull it downward to remove it.
[Concealed Duct Type] [Concealed Duct High Static Pressure
Type]
Cleaning method differs according to the installed air filter type.
Check with person who worked for installation or the dealer which you purchased it.
[Under Ceiling Type]
Pull the air filter towards you to take out it.
Push projection.
Air filter
[High Wall Type]
Push the projection at the center of air filter. Clip is out.
Undo the clip of air filter, pull the air filter downward while pushing it toward the main unit side.
Push the air filter, and pull it downward.
3-13
Front panel (Lower)
Air filter knob
[Floor Standing Cabinet Type]
Pull down the upper part of suction port a little, pull it toward you and remove it, and then take out the air filter inside of the unit.
[Floor Standing Concealed Type]
Pull down the air filter clip at the lower front panel, and take out the air filter by pulling it toward you.
NOTE
For cleaning of air filter, use a cleaner or brush clean. If stain is heavy, it is
effective to wash the air filter in tepid water mixed with neutral detergent.
After washing, rinse it well, and dry it in the shade.
Install again the air filter which has been cleaned.
REQUIREMENT
Insert the air filter until it stops securely.
n Cleaning of main unit/remote controller
Wipe them with soft and dry cloth.
If stain of the main unit is heavy, wipe out stain
with cloth wet in tepid water. (For remote control, wipe outstain with dry cloth without using water.)
Do not use benzene, thinner , polishing powder, or chemical floor-cloth because they may cause deformation or crack on the panel or remote controller.
I will wipe soft and dry cloth!
Polishing
powder
Thinner
Benzene
Do not use.
Chemical floor-cloth
<When the air conditioner is not used for a month or longer>
Perform fan operation for half a day to dry inside of air conditioner well.
Turn off the power switch.
Clean the air filter, and attach it again as it was before.
Use after drying
when it has not been
used for a long time!
<Before season to use cooling function>
(Concealed duct high static pressure type, Floor standing concealed type)
Cleaning of drain pan and drain receiver (with strainer)
CAUTION
Clean drain pan or drain receiver (strainer).
If garbage is clogged in drain pan or drain receiver, water may flood resulted in damp on the ceiling or floor.
Drain receiver (strainer) is provided to Floor standing concealed type only.
REQUIREMENT
For cleaning of drain pan and drain receiver, contact the dealer which you have purchased the air conditioner.
3-14
Dont forget
periodical
check!
Close windows
and doors often!
Dont cool
excessively!
3-2-5. How to Use the Air Conditioner Effectively
For saving of electric cost and comfortable cooling or heating operation.
n Diligent cleaning of air filter
If the air filter is clogged, cooling/ heating effect decreases.
n Close windows and doors often
Close windows and doors so that cool air does not blow through the room.
WARNING
Do not expose your body directly in cool air for a long time.
It may affect the health. Especially, be watchful for person physically
handicapped, children, or senior person.
n Room temperature without unevenness
Adjust the air direction with discharge louver. If you expose yourself in the air flow for a long
time, it may affect your health.
For using the air conditioner effectively, operate it under the following conditions.
Outdoor temperature –5°C or more, 43°C or less Indoor temperature 21°C or more, 32°C or less
Cooling operation
Heating operation
Indoor humidity 80% or less If the air conditioner operates with humidity exceeding 80%, dew adhered to surface of
the panel may fall, or dew may be sprayed from the discharge grille. Outdoor temperature –15°C or more, 21°C or less Indoor temperature 28°C or less
If the air conditioner is operated under conditions other than these conditions, a protective device works and the operation may become unavailable.
3-15
3-2-6. When the Following Symptoms are Found
Check the points described below before asking repair servicing.
Symptom
Outdoor unit White misty cold air
or water is out.
Sometimes, noisePushu ! is heard.
Indoor unit •“Swish sound is
heard sometimes.
Slight Pishi! sound is heard.
Discharge air smells.
The operation lamp
flashes
•“STANDBY indication is lit.
It is not a failure.
Sound or cool air is output from the stand by indoor unit.
When power of the air conditioner is turned on, Ticktock sound is heard.
Cause
Fan of the outdoor unit stops automatically and performs defrost operation.
Solenoid valve works when defrost operation starts or finishes.
When the operation has started, during the operation, or immedi-
ately after the operation has stopped, a sound such as water flows may be heard, and the operation sound may become larger for 2 or 3 minutes immediately after the operation has started. They are flowing sound of refrigerant or draining sound of dehumidifier.
This is sound generated when heat exchanger, etc. expand and contract slightly due to change of temperature.
Various smell such as one of wall, carpet, clothes, cigarette, or cosmetics adhere to the air conditioner.
Flashes when power is turned on again after power failure, or when power switch is turned on.
When cooling operation cannot be performed because another indoor unit performs heating operation.
When the manager of the air conditioner has fixed the operation to COOL or HEAT, and an operation contrary to the setup operation is performed.
When fan operation stopped to prevent discharge of hot air.
Since refrigerant is flowed temporarily to prevent stay of oil or
refrigerant in the stand by indoor unit, sound of flowing refrigerant, Kyururu or Shaa may be heard or white steam when other indoor unit operates in HEAT mode, and cold air in COOL mode may be blow-out.
Sound is generated when the expansion valve operates when power has been turned on.
Operates or stops automatically. Does not operate.
Silent
Air is not cooled or warmed sufficiently.
Check again.
Its strange.
Is the timer ON or OFF?
Is it a power failure?
Is the power switch turned off?
Is the power fuse or breaker blown?
Has the protective device operated? (The operation lamp goes on.)
Is the timer ON? (The operation lamp goes on.)
Are COOL and HEAT selected simultaneously?
(STANDBY indication is lit on the display column of the remote controller.)
Is the suction port or discharge port of the outdoor unit obstructed?
Are any door or window open?
Is the air filter clogged with dust?
Is discharge louver of the indoor unit set at appropriate position?
Is air selection set to LOW” “MED, and is the operation mode set to FAN?
Is the setup temp. the appropriate temperature?
Are COOL and HEAT selected simultaneously?
(STANDBY indication is lit on the display column of the remote controller.)
When the following symptoms are found, stop the operation immediately, turn off the power switch, and contact the dealer which you have purchased the air conditioner.
Activation of switch is unstable.
Fuse or breaker is blown periodically.
Foreign matters or water entered by mistake.
When if activation cause of the protective device has been removed, the operation is not performed.
Other unusual status occurred.
3-16
3-2-7. Confirmation and Check
n Confirmation of check No.
When an error/fault occur on the air conditioner, the check No. indicating the defective status can be confirmed by the CHECK switch on the remote controller.
Before requesting repair, confirm the check No. in the following procedure, and contact the dealer with symptom of the air conditioner.
[Confirmation procedure]
1. Hold the CHECK switch on the remote controller for 1 or 2 seconds. The CHECK display appears, and the unit No. and check No. are displayed in the display section of set up TEMP.
2. The unit No. represents the number of indoor unit in which an error occurred.
3. Check No. is displayed as follows.
When an error/fault does not occur.
When one error/fault occurs.
When two error/fault occur.
CHECK
CHECK 1
CHECK 1
CHECK 2
If you could not read the display sufficiently, push CHECK switch again.
n Check servicing
Though differed according to use status, when the air conditioner has been used for several seasons, inside of
the air conditioner may be stained, and performance may decrease. Separated from daily maintenance, a check servicing (charged) is recommended.
The Ceiling cassette type air conditioner incorporates a drain pump. If it is used in an oily and dusty place, the
pump can be blocked causing the water drain to disable. It is required to clean the pump periodically. For cleaning of drain pump, contact the dealer. (When a drain-up kit is attached to concealed duct type and
under ceiling type are same precautions are recommended.)
3-2-8. Accessories Sold Separately
WARNING
When you require accessory or parts, consult us. Be sure to use the products sold separately which are specified by us.
If using other products than those specified, a fire, electric shock or water leakage may be caused. For installation, ask a special engineer.
3-17
3-3.
REFRIGERANT PIPING SYSTEMATIC DRA WING
Inverter unit (10HP, 8HP)
Cooling Only model : MMY-MP0801T8, MP1001T8 Heat Pump model : MMY-MP0801HT8, MP1001HT8
: MMY-MP0801HT7, MP1001HT7
Propeller fan
M
Fan motor
(Right side)
Strainer
Pulse motor
valve A
(PMV 1 + PMV 2)
Sensor (TE1)
Air heat exchanger at outdoor side
(Left side)
Air heat exchanger at outdoor side
They are not provided to
*
the Cooling Only model.
*
4-Way valve
Check valve
Strainer
Liquid
tank
Sensor
Pulse motor valve B
(Cooling bypass)
(PMV 3)
Sensor
(TK1)
Solenoid valve
(SV3C)
Capillary
Capillary
Sensor
(TK2)
Dryer
Strainer
Oil tank
Solenoid valve (SV3A)
Check valve
Strainer
Sensor
(TD1)
Check
valve
Check valve
High-pressure SW
Sensor
(TK3)
Compressor case oil removal valve
Oil
separator
Check valve
HP
Compressor
Inverter
Solenoid valve
Check joint
Strainer
Solenoid valve
Fixed-speed
Check valve
(SV2)
High-pressure sensor
Capillary
(SV42)
High-pressure
SW
Sensor (TD2)
Low-pressure
sensor
Capillary
HP
Check valve
Check joint
Strainer
(TS)
Accumulator
Capillary
Solenoid valve (SV3B)
Packed v alv e
(balancing pipe)
Packed v alv e
(liquid side)
Service valve
(gas side)
3-18
Fixed-speed unit (10HP, 8HP)
Cooling Only model : MMY-MP08018, MP10018 Heat Pump model : MMY-MP0801H8, MP1001H8
: MMY-MP0801H7, MP1001H7
Propeller fan
M
Fan motor
(Right side)
They are not provided to
*
the Cooling Only model.
Check valve
Strainer
Liquid
tank
Pulse motor
valve A
(PMV 1 + PMV 2)
Sensor
(TK1)
Strainer
Pulse motor valve B
(Cooling bypass)
Solenoid valve
Capillary
Capillary
Capillary
(PMV 3)
(SV3C)
Sensor
(TK2)
Sensor (TE1)
Strainer
Sensor
(TD1)
Check
valve
Air heat exchanger at outdoor side
(Left side)
Air heat exchanger at outdoor side
Solenoid valve
(SV2)
High-pressure sensor
Check joint
Oil
separator
Check
valve
HP
High-pressure SW
Compressor
Strainer
Solenoid
valve
(SV41)
High-pressure
Sensor (TD2)
Capillary
Solenoid
valve
(SV42)
HP
SW
4-Way valve
*
Check joint
Sensor
(TS)
Accumulator
Dryer
Packed v alv e
(balancing pipe)
Packed v alv e
(liquid side)
Strainer
Service valve
(gas side)
Oil tank
Check valve
Solenoid valve (SV3A)
Check valve
Check
valve
Sensor
(TK3)
Compressor case oil removal valve
3-19
Fixed-speed
Fixed-speed
Check valve
Low-pressure
sensor
Capillary
Check valve
Solenoid valve (SV3B)
Strainer
Capillary
Fixed-speed unit (6HP)
Cooling Only model : MMY-MP06018 Heat Pump model : MMY-MP0601H8
: MMY-MP0601H7
Propeller fan
M
Fan motor
(Right side)
They are not provided to
*
the Cooling Only model.
Check valve
Liquid
tank
Strainer
Pulse motor
valve A (PMV1)
Pulse motor valve (Cooling bypass)
Sensor
(TK1)
Capillary
Capillary
Capillary
(PMVB)
Solenoid valve
(SV3C)
Sensor
(TK2)
Sensor (TE1)
Strainer
Air heat exchanger at outdoor side
(Left side)
Air heat exchanger at outdoor side
Solenoid valve
(SV2)
High-pressure sensor
Check joint
Oil
separator
Check valve
Compressor
Strainer
Solenoid valve
(SV41)
High-pressure Sensor (TD1)
Capillary
HP
SW
4-Way valve
*
Check joint
Sensor
(TS)
Accumulator
Dryer
Packed v alv e
(balancing pipe)
Packed v alv e
(liquid side)
Strainer
Service valve
(gas side)
Oil tank
Check valve
Solenoid valve (SV3A)
Check valve
Check
valve
Sensor
(TK3)
Compressor case oil removal valve
3-20
Fixed-speed
Check valve
Low-pressure
sensor
Capillary
Check valve
Solenoid valve (SV3B)
Strainer
Capillary
)
(
Explanation of functional parts
Functional part Functional outline
Solenoid valve
Check valve
Pulse motor valve
Oil separator 1)Early protection of oil level down (Decreases flow-out of discharge oil to cycle) Temp.
sensor
Pressure sensor
Balancing pipe 1)Oil supply path for balancing oil of each outdoor unit.
1. SV3A
2. SV3B 1) Returns oil supplied in the balancing pipe to the compressor.
3. SV3C
4. SV2
5. SV4 (n) (Activation compensating valve for fixed-speed compressor)
Check valve for discharge
Check valve for liquid line
1. PMV A (Two pcs. used) (PMV1 + PMV 2)
2. PMVB (PMV3)
1. TD1 TD2
2. TS1 (Connector: White)
3. TK1 TK2 TK3
4. TE1 (Connector : Blue)
1. High pressure sensor
2. Low pressure sensor
1)Gathers oil in the compressor case to the oil tank of compressor during OFF time.
2)Supplies the gathered oil to the balancing pipe during ON time when pressure is applied to inside of the oil tank.
3
Supplies oil in the case directly to the balancing pipe when pressure is app lie d to inside of the compressor case.
4)Reduces pressure after pressure has been applied to inside of the oil tank
1)Applies pressure to inside of the oil tank during ON time.
2)Detects oil level with temp. system.
(Hot gas bypass)
1)Low-pressure release valve
To protect lowering of low pressure which is difficult
to activating time of Modular multi type)
2)Protects liquid refrigerant gathering in accumulator.
3)Gas balancing in STOP time.
1)For activation of gas balance
2)Deflates gas in discharge pipe. (Protects liquid stagnation in discharge pipe.)
1)Protects counter pressure when the inverter compressor is operating and the constant speed compressor stops.
2)Decreases activation load when fixed-speed compressor is activated. (Shared function with SV4 (n) valve)
Prevents liquid accumulation in heat exchanger of the stopped outdoor unit.
(Connector CN300, 301 : White) * It is provided to the Heat Pump model only.
1)Control function for super heat volume in heating operation (Refrigerant split flow between outdoor units)
2)Liquid line shut-down function while the fixed-speed units stop
3)Liquid line counter-pressure preventive control function during defrost operation
4)Fixed with FULL OPEN in cooling operation.
(Cooling bypass) (Connector CN302 Red)
1)Liquid bypass proportional control function for releasing discharge temperature (Adjustment of refrigerant drying degree during inner reducing operation)
2)Releases low pressure.
(TD1 : Connector: Red, TD2 : Connector: White)
1)Used to protect discharge temperature of the compressor.
2)Used to control cooling bypass for releasing discharge temperature.
1)Used to control super heat of PMV in heating operation.
2)Used to control cooling bypass for releasing discharge temperature.
(TK1 : Connector: Black, TK2 : Connector: Blue, TK3 : Connector: Green)
1)Used to detect oil level judgment. (TH1, TK2)
2)Used to detect dilution status of oil. (TK3)
1)Used to control the cooling fan.
2)Used to control defrost operation in heating operation.
3)Used to control the heating fan.
(Connector : Red)
1)Used to detect high pressure, and compressor capacity.
2)In cooling operation, it is used to detect high pressure, and control the fan in cooling low ambient conditions.
(Connector : Blue)
1) In cooli ng operat ion, it is used to detect low pressure, and control the capacity of the compressor.
2)In heating operation, it is used to detect low pressure and control super heat.
2)Low-pressure bypass function between outdoor units, which recovers the liquid refrigerant stagnated in the stand by outdoor unit.
3)Low-pressure balancing pipe function to secure pressure difference when check valve of every outdoor units aligned on a circuit in parallel are inverted.
It is provided to the Cooling Only model only.
*
(Compressor case bypass)
1)Stirs oil to prevent oil separation into two layers.
3-21
3-4. COMBINED REFRIGERANT PIPING SYSTEMATIC DRAWING
3-4-1. Normal Operation
3-22
They are not provided to the Cooling Only model.
*
(Indoor unit 1)
TC1
Check
joint
Pressure
sensor
(Indoor unit 2)
TC1
Check
joint
Pressure
sensor
Air heat
exchanger
at indoor side
TA (Suction sensor)
exchanger
at indoor side
Air heat
TA (Suction sensor)
TC2
Strainer
Strainer
TC2
Check
valve
Strainer
(Indoor unit 3)
TC1
Check
joint
Pressure
sensor
Air heat
exchanger
at indoor side
TA (Suction sensor)
TC2
Strainer
Dryer
Liquid
tank
Strainer
Pulse motor valve A
(PMV 1 + PMV 2)
Sensor
(TK1)
Strainer
Center unit (Inverter) Terminal unit (Fixed-speed)
Propeller fan
M
Fan motor
Sensor (TE1)
Pulse motor valve B
(Cooling bypass)
(PMV 3)
Strainer
Solenoid valve
(SV3C)
Capillary
Sensor
Capillary
(TD1)
Sensor
(TK2)
Check
valve
Oil tank
Check valve
Solenoid valve (SV3A)
Check valve
(Right side)
Air heat exchanger at outdoor side
(Left side)
Air heat exchanger at outdoor side
Solenoid valve
(SV2)
High-pressure
sensor Check joint Strainer
Oil
separator
High-pressure SW
Sensor
(TK3)
Compressor case oil removal valve
Check valve
HP
Compressor
Inverter
Solenoid valve
Low-pressure
Fixed-speed
Check
Capillary
valve
(SV42)
High-pressure
Sensor
(TD2)
sensor
Capillary
SW
4-Way valve
*
HP
Check valve
Check joint
Sensor
(TS)
Accumulator
Capillary
Solenoid valve (SV3B)
Pulse motor valve A (PMV 1 + PMV 2)
Check
valve
Strainer
Liquid
tank
Dryer
Strainer
Strainer
Sensor (TE1)
Capillary
Pulse motor valve B
(Cooling bypass)
(PMV 3)
Sensor
(TK1)
Solenoid valve
(SV3C)
Capillary
Capillary
Sensor
(TK2)
Oil tank
Check valve
Solenoid valve (SV3A)
Check valve
Air heat exchanger at outdoor side
Air heat exchanger at outdoor side
Strainer
Check
valve
Sensor
(TD1)
High-pressure SW
Check
Sensor
valve
(TK3)
Compressor case oil removal valve
Propeller fan
M
(Right side)
(Left side)
Oil
separator
Check
valve
HP
Compressor
Fixed-speed
Fan motor
Solenoid valve
Check joint Strainer
Solenoid
valve
(SV41)
Fixed-speed
Check valve
(SV2)
High-pressure sensor
Capillary
Solenoid
valve
(SV42)
High-pressure
SW
Sensor (TD2)
Low-pressure
sensor
Capillary
*
4-Way valve
HP
Check valve
Check joint
Sensor
(TS)
Accumulator
Capillary
Solenoid valve (SV3B)
StrainerStrainer
Packed valve (balancing pipe)
valve (liquid side)
valve (gas side)
Service
Packed
(Solid line) High-pressure gas or compressed liquid refrigerant (Dotted line) Evaporating gas refrigerant (Low-pressure gas)
Packed valve (balancing pipe)
Packed valve (liquid side)
Service valve (gas side)
Unit 2 (Fixed-speed)
Packed
Packed
valve
valve
(balancing
(liquid
pipe)
side)
Service valve (gas side)
Unit 3 (Fixed-speed)
Packed
Packed
valve
valve
(balancing
(liquid
pipe)
side)
Service valve (gas side)
Server
Unit 4 (Fixed-speed)
Packed
Packed
valve
valve
(balancing
(liquid
pipe)
side)
Service valve (gas side)
3-4-2. Emergent Operation When IPDU Unit is Failed
3-23
They are not provided to the Cooling Only model.
*
(Indoor unit 1)
TC1
Check
joint
Pressure
sensor
TC1
Check
Pressure
joint
sensor
Air heat
exchanger
at indoor side
TA (Suction sensor)
(Indoor unit 2)
at indoor side
Air heat
exchanger
TA (Suction sensor)
TC2
Strainer
Strainer
TC2
Check
valve
Strainer
Liquid
(Indoor unit 3)
TC1
Check
joint
Pressure
sensor
Air heat
exchanger
at indoor side
TA (Suction sensor)
TC2
Strainer
Dryer
tank
Strainer
Pulse motor valve A
(PMV 1 + PMV 2)
Sensor
(TK1)
Strainer
Center unit (Inverter) Terminal unit (Fixed-speed)
Propeller fan
Temporal set up master unit in emergencyFailure
M
Fan motor
Sensor (TE1)
Pulse motor valve B
(Cooling bypass)
(PMV 3)
Strainer
Solenoid valve
(SV3C)
Capillary
Sensor
Capillary
(TD1)
Sensor
(TK2)
Check
valve
Oil tank
Check valve
Solenoid valve (SV3A)
Check valve
(Right side)
Air heat exchanger at outdoor side
(Left side)
Air heat exchanger at outdoor side
Solenoid valve
(SV2)
High-pressure
sensor
Check joint Strainer
Oil
separator
Solenoid valve
(SV42)
Check valve
HP
High-pressure SW
Sensor
(TK3)
Compressor case oil removal valve
Compressor
Inverter
Fixed-speed
Check valve
High-pressure
Sensor
(TD2)
Low-pressure
sensor
Capillary
Capillary
SW
4-Way valve
*
HP
Check valve
Check joint
Sensor
(TS)
Accumulator
Capillary
Solenoid valve (SV3B)
Strainer
Pulse motor valve A (PMV 1 + PMV 2)
Check
valve
Strainer
Liquid
tank
Dryer
Strainer
Strainer
Sensor (TE1)
Capillary
Pulse motor valve B
(Cooling bypass)
(PMV 3)
Sensor
(TK1)
Solenoid valve
(SV3C)
Capillary
Capillary
Sensor
(TK2)
Oil tank
Check valve
Solenoid valve (SV3A)
Check valve
Air heat exchanger at outdoor side
Air heat exchanger at outdoor side
Strainer
Check
valve
Sensor
(TD1)
High-pressure SW
Check
Sensor
valve
(TK3)
Compressor case oil removal valve
Propeller fan
M
(Right side)
(Left side)
Oil
separator
Check
valve
HP
Compressor
Fixed-speed
Fan motor
Solenoid valve
Check joint Strainer
Solenoid
valve
(SV41)
Fixed-speed
Check valve
(SV2)
High-pressure sensor
Capillary
Solenoid
valve
(SV42)
High-pressure
SW
Sensor (TD2)
Low-pressure
sensor
Capillary
4-Way valve
*
HP
Check valve
Check joint
Sensor
(TS)
Accumulator
Capillary
Solenoid valve (SV3B)
Strainer
(Master unit backup operation)
Packed valve (balancing pipe)
valve (liquid side)
valve (gas side)
Service valves fully closed at liquid gas side.
Service
Packed
(Solid line) High-pressure gas or compressed liquid refrigerant (Dotted line) Evaporating gas refrigerant (Low-pressure gas)
Packed valve (balancing pipe)
Packed valve (liquid side)
Service valve (gas side)
Unit 2 (Fixed-speed)
Packed
Packed
valve
valve
(balancing
(liquid
pipe)
side)
Service valve (gas side)
Unit 3 (Fixed-speed)
Packed
Packed
valve
valve
(balancing
(liquid
pipe)
side)
Service valve (gas side)
Server
Unit 4 (Fixed-speed)
Packed
Packed
valve
valve
(balancing
(liquid
pipe)
side)
Service valve (gas side)
3-4-3. Emergent Operation When Fixed-Speed Unit is Failed
3-24
They are not provided to the Cooling Only model.
*
(Indoor unit 1)
TC1
Check
joint
Pressure
sensor
(Indoor unit 2)
TC1
Check
joint
Pressure
sensor
Air heat
exchanger
at indoor side
TA (Suction sensor)
exchanger
at indoor side
Air heat
TA (Suction sensor)
TC2
Strainer
Strainer
TC2
Check
valve
Strainer
Liquid
(Indoor unit 3)
TC1
Check
joint
Pressure
sensor
Air heat
exchanger
at indoor side
TA (Suction sensor)
TC2
Strainer
Dryer
tank
Strainer
Strainer
Pulse motor valve A
(PMV 1 + PMV 2)
Pulse motor valve B
(Cooling bypass)
Sensor
(TK1)
Solenoid valve
Capillary
Capillary
Sensor
Oil tank
Solenoid valve (SV3A)
Check valve
Center unit (Inverter) Terminal unit (Fixed-speed)
Propeller fan
Propeller fan
Failure
(Right side)
(Left side)
Oil
separator
Check
HP
High-pressure SW
Compressor
(TK3)
Compressor case oil removal valve
M
valve
Fixed-speed
Air heat exchanger at outdoor side Sensor (TE1)
Air heat exchanger at outdoor side
(PMV 3)
Strainer
(SV3C)
Sensor
(TD1)
Check
valve
Check valve
High-pressure SW
Sensor
(TK3)
Compressor case oil removal valve
(TK2)
M
(Right side)
(Left side)
Oil
separator
Check valve
HP
Compressor
Inverter
Fan motor
Solenoid valve
Check joint Strainer
Solenoid valve
Fixed-speed
Check valve
(SV2)
High-pressure sensor
Capillary
(SV42)
High-pressure
SW
Sensor (TD2)
Low-pressure
sensor
Capillary
4-Way valve
*
HP
Check valve
Check joint
Sensor
(TS)
Accumulator
Capillary
Solenoid valve (SV3B)
Strainer
Pulse motor valve A (PMV 1 + PMV 2)
Check
valve
Strainer
Liquid
tank
Dryer
Strainer
Strainer
Sensor (TE1)
Capillary
Pulse motor valve B
(Cooling bypass)
(PMV 3)
Sensor
(TK1)
Solenoid valve
(SV3C)
Capillary
Capillary
Sensor
(TK2)
Check
Oil tank
Check valve
Solenoid valve (SV3A)
Check valve
Air heat exchanger at outdoor side
Air heat exchanger at outdoor side
Strainer
Check
valve
Sensor
(TD1)
Sensor
valve
Fan motor
Solenoid valve
Check joint Strainer
Solenoid
valve
(SV41)
Fixed-speed
Check valve
(SV2)
High-pressure sensor
Capillary
Solenoid
valve
(SV42)
High-pressure
SW
Sensor (TD2)
Low-pressure
sensor
Capillary
*
4-Way valve
HP
Check valve
Check joint
Sensor
(TS)
Accumulator
Capillary
Solenoid valve (SV3B)
Strainer
Packed valve (balancing pipe)
valve (liquid side)
valve (gas side)
Service valve opned fully at balancing pipe.
Service
Packed
(Solid line) High-pressure gas or compressed liquid refrigerant (Dotted line) Evaporating gas refrigerant (Low-pressure gas)
Packed valve (balancing pipe)
Packed valve (liquid side)
Service valve (gas side)
Unit 2 (Fixed-speed)
Packed
Packed
valve
valve
(balancing
(liquid
pipe)
side)
Service valves closed fully at liquid and gas side.
Service valve (gas side)
Unit 3 (Fixed-speed)
Packed
Packed
valve
valve
(balancing
(liquid
pipe)
side)
Service valve (gas side)
Server
Unit 4 (Fixed-speed)
Packed
Packed
valve
valve
(balancing
(liquid
pipe)
side)
Service valve (gas side)
3-4-4. Recovery of Refrigerant in Failed Outdoor Unit
3-25
They are not provided to the Cooling Only model.
*
(Indoor unit 1)
TC1
Check
joint
Pressure
sensor
TC1
Check
Pressure
joint
sensor
Air heat
exchanger
at indoor side
TA (Suction sensor)
(Indoor unit 2)
at indoor side
Air heat
exchanger
TA (Suction sensor)
TC2
Strainer
Strainer
TC2
Check
valve
Strainer
Liquid
(Indoor unit 3)
TC1
Check
joint
Pressure
sensor
Air heat
exchanger
at indoor side
TA (Suction sensor)
TC2
Strainer
Dryer
tank
Strainer
Pulse motor valve A
(PMV 1 + PMV 2)
Pulse motor valve B
Sensor
(TK1)
Strainer
Center unit (Inverter) Terminal unit (Fixed-speed)
Propeller fan
Propeller fan
Failure
M
Fan motor
(Right side)
Air heat exchanger at outdoor side
Air heat exchanger at outdoor side
Strainer
Check
valve
High-pressure SW
Sensor
(TK3)
Compressor case oil removal valve
Sensor (TE1)
(Cooling bypass)
(PMV 3)
Solenoid valve
(SV3C)
Capillary
Capillary
Sensor
(TK2)
Check
valve
Oil tank
Check valve
Solenoid valve (SV3A)
Check valve
(Right side)
Air heat exchanger at outdoor side
(Left side)
Air heat exchanger at outdoor side
Strainer
Sensor
(TD1)
separator
HP
High-pressure SW
Sensor
(TK3)
Compressor case oil removal valve
Oil
Check valve
Compressor
Inverter
Check valve
Solenoid valve
(SV2)
High-pressure
sensor Check joint Strainer
Solenoid valve
(SV42)
High-pressure
Sensor
(TD2)
Low-pressure
sensor
Fixed-speed
Capillary
Capillary
SW
4-Way valve
*
HP
Check valve
Check joint
Sensor
(TS)
Accumulator
Capillary
Solenoid valve (SV3B)
Strainer
Pulse motor valve A (PMV 1 + PMV 2)
Check
valve
Strainer
Liquid
tank
Dryer
Strainer
Strainer
Sensor (TE1)
Capillary
Pulse motor valve B
(Cooling bypass)
(PMV 3)
Sensor
(TK1)
Solenoid valve
(SV3C)
Capillary
Capillary
Sensor
(TK2)
Check
valve
Oil tank
Check valve
Solenoid valve (SV3A) OFF ® ON
Check valve
OFF ON
OFF ON
Sensor
(TD1)
M
(Left side)
Oil
separator
Check
valve
HP
Compressor
Fan motor
Check joint Strainer
Solenoid
Fixed-speed
Fixed-speed
Check valve
Solenoid valve
(SV2)
High-pressure sensor
Capillary
valve
(SV41)
High-pressure Sensor (TD2)
Low-pressure
sensor
Capillary
Solenoid
valve
(SV42)
HP
SW
Check valve
*
4-Way valve
Check joint
Sensor
(TS)
Accumulator
Capillary
Solenoid valve (SV3B)
OFF ON
Strainer
(Normal outdoor unit recovers refrigerant)
Packed valve (balancing pipe)
valve (liquid side)
valve (gas side)
Service
Packed
(Solid line) High-pressure gas or compressed liquid refrigerant (Dotted line) Evaporating gas refrigerant (Low-pressure gas)
Service valve fully opned at balancing pipe.
Service valve fully closed at liquid side.
Packed valve (balancing pipe)
valve (liquid side)
valve (gas side)
Unit 2 (Fixed-speed)
Packed
Packed
valve
valve
(balancing
(liquid
pipe)
side)
Service valve (gas side)
Service
Packed
Fully close the valves of balancing pipe.
Fully close the valves 10 minutes after the operation has started
Unit 3 (Fixed-speed)
Packed
Packed
valve
valve
(balancing
(liquid
pipe)
side)
Service valve (gas side)
Server
Unit 4 (Fixed-speed)
Packed
Packed
valve
valve
(balancing
(liquid
pipe)
side)
Service valve (gas side)
3-5. OUTLINE OF CONTROL
3-5-1. Outdoor Unit
3-5-1-1. Operation start/Operation end
The compressor, solenoid valve, pulse motor valve (PMV A), outdoor fan, etc. are controlled by a command from the indoor controller. The server outdoor unit starts/stops by a command from the master outdoor unit.
Operation signal from indoor Inverter drive Outdoor fan output Fixed-speed MG-SW output Each solenoid valve output
4-way valve output (OFF in cooling operation)
PMV A output
Operation start
OFF
OFF
OFF
OFF
OFF Full
close
ON
ON
ON or OFF
(By command indoor)
ON or OFF
ON
Specified opening
Operation stop
2 minutes and 30 seconds
Full close
3-5-1-2. Thermostat ON/Thermostat OFF
Thermostat ON Thermostat OFF
Operation signal from indoor Inverter drive Outdoor fan output Fixed-speed MG-SW output Each solenoid valve output
4-way valve output (OFF in cooling operation)
PMV A output
OFF
OFF
OFF
OFF
ON
Full close
ON
ON
ON or OFF
(By command indoor)
ON or OFF
Specified opening
2 minutes and 30 seconds
Full close
3-26
3-5-1-3. Outline of main controls
Item
1. Pulse motor valve (PMV A, B) control
Operation explanation and applied data, etc.
(1) PMV A (PMV 1, PMV 2) control (using two PMV)
1) PMV (Pulse Motor Valve) is controlled between 100 to 1000 pulses during operation.
2) In cooling operation, PMV 1, PMV 2 are fixed with FULL OPEN status. (PMV 1 = 500 pulses, PMV 2 = 500 pulses)
3) In heating operation, PMV opening is controlled by detection temperature of TS and TD sensors and detection value of PS pressure. (Super Heat control)
4) Close fully PMV opening when thermostat is OFF, operation stops, and the A.C. stops in trouble.
1000
550 500
100
PMV opening
50
PMV 2
PMV 1
Min. Med. Max.
(2) PMV B (PMV 3) control
The purpose of PMV B control is to control the liquid refrigerant bypass for suppressing discharge temp. increase or compressor internal temp. increase.
1) Opening is controlled with pulses from 0 to 500.
2) PMV opening is controlled with temp. detected by TS/TD sensors.
3) PMV openings are fully closed during thermostat-OFF, operation stop, and emergency stop.
Remarks
2. Outdoor fan control
(1) Cooling fan control
1) Outdoor fan speed (No. of fan driving waves) is controlled by Pd pressure detection value.
2) In a specified time when cooling operation is activated, the master outdoor unit controls the outdoor fan speed (No. of fan driving waves) by Pd pressure detection value. The server outdoor unit controls the outdoor fan speed (No. of fan driving waves) with temperature detected by TE sensor.
Pd pressure
Cooling fan control controls No. of fan driving waves so that
*
the detection value of Pd pressure becomes 1.45 to 1.8MPa.
(MPa)
2.2
2.1
2.0
1.9
1.8
1.7
1.6
1.5
1.4
1.3
1.2
1.1
Max. :
[ ]
16 waves
[-1 wave/20 sec] In down time : From 15 waves to 1 wave
Interval control
[+1 wave/20 sec] From 2 waves to Max.No.of waves
[Hold]
From 1 wave to
Max. No. of waves
In up time : From 0 wave to 1 wave
[0 wave] : 180 sec
[ ]
[1 wave] : 30 sec
[+1 wave/20 sec] (Up to 5 waves)
No. of waves can be controlled between 0 wave (STOP) to 16 waves (All waves).
3-27
Loading...
+ 186 hidden pages