The tekmar Mixing Control 365 is a microprocessor-based control with a 120 Vac output for operating
a variable speed injection pump. A 4-20mA output is available for operating devices such as a 420mA actuating motor, modulating gas valve, a mixing valve combination, or for operating a 4-20mA
motor drive for larger variable speed pumps. The variable speed pump or mixing valve regulates the
supply water temperature to a heating system based on the outdoor air temperature, and optionally,
the indoor air temperature. The system is shut down when there is no Heat Demand signal or when
the outdoor temperature is warm enough so that the system no longer requires heat (WWSD).
Correct setting and shifting of the Heating Curve... the key to More Comfort and Energy Savings.
Heating Curve
As outdoor temperatures get colder, heat losses from a building increase, requiring the addition of more heat to prevent the indoor
air temperature from also getting colder. This tekmar reset control measures the outdoor temperature and as the outdoor
temperature gets colder, it balances the heat loss by making the heating supply water hotter.
The Heating Curve is used to calculate how hot to make the supply water at different outdoor temperatures. It is the number of
degrees the supply water temperature is raised for each degree that the outdoor temperature falls.
Setting the Heating Curve
Two examples of how the Heating Curve works are given in the following illustration.
—With a 2.4 Curve, the supply water temperature is raised 2.4 degrees for every degree of outdoor temperature drop.
If WWSD point = 70°F and Outdoor temperature = 30°F, then Supply temperature = 166°F
—With a 0.6 Curve, the supply water temperature is raised 0.6 degrees for every degree of outdoor temperature drop.
If WWSD point = 70°F and Outdoor temperature = 30°F, then Supply temperature = 94°F
• If the Heating Curve selected is too low;
able to raise the supply temperature high enough to keep the room
temperature warm during colder weather.
• If the Heating Curve selected is too high;
the building will overheat during colder weather.
Warm Weather Shut Down (WWSD)
At warm outdoor temperatures, the indoor space of a building gains heat
from the outdoors; additional heat is not required, and if the heating
system is running (even on standby), enough excess heat can be
produced to overheat the building, causing discomfort and wasting
valuable energy.
This control turns off the system pump and injection pump (or closes a
mixing valve), when the outdoor temperature is above the WWSD point.
As outdoor temperatures get colder, there comes a point where the heat
gain turns into heat loss; the heat loss causes the indoor temperature to
fall below the comfort level, and the heating system must be turned on to
start delivering heat.
To provide heat to the building, this control turns on the system pump and starts the injection pump (or opens the mixing valve),
delivering heat at the low output required by the Heating Curve near the WWSD point. If the outdoor temperature rises above the
WWSD point, the control shuts the system off again, and because the system was operating at a low heat output level, overheating
and temperature swings in mild weather are avoided.
When the system is operating near the WWSD point and the building is too cold;
When the system is operating near the WWSD point and the building is too warm;
3.0
WWSD
Point
will
shift
up and
down
with
shift of
Heating
Curve
(32)
3.6
Heating
Curve
Parallel Shift of Heating Curve
UP
DOWN
UP
90
70
(21)
50
(10)
Outdoor air temperature
2.4 2.0
DOWN
30
(-1)10(-12)
A very cool room temperature can shift the curve far enough up to bring the control out of WWSD at warm outdoor temperatures.
A very warm room temperature can shift the curve far enough down to put the control into WWSD at cool outdoor temperatures.
the heating system will not be
too much heat is delivered and
Shifting the Heating Curve
(a) Manually, at the control:
The Occupied and Unoccupied dials on this control can shift the WWSD
point up or down from 35 to 105°F (2 to 41°C).
(b) Automatically, using room temperature feedback:
In addition to a Supply Sensor and an Outdoor Sensor, this control can use
a tekmar 2k RTU, 10k Zone Control or 10k Indoor Sensor to provide room
temperature feedback for added comfort and system flexibility.
The control still calculates a desired supply temperature based on the
Supply water temperature
Heating Curve setting and the outdoor temperature.
If the air temperature in the room is too cold, the control will shift the Heating
Curve (and WWSD point)
room warms up again.
If the air temperature in the room is too warm, the control will shift the
Heating Curve (and WWSD point)
1.6
1.2
1.0
0.8
0.6
0.4
-10°F
(-23)°C
210
(99)
190
(88)
170
(77)
150
(65)
130
(54)
11 0
(43)
90
(32)
70
(21)
50°F
(10)°C
ture until the room cools down.
3.0
90
(32)
WWSD
Point
Heating
Curve
70
(21)
3.6
50
(10)
Outdoor air temperature
2.4 2.0
30
(-1)10(-12)
the WWSD point should be raised.
the WWSD point should be lowered.
up,
which raises the supply temperature until the
down,
which lowers the supply tempera-
1.6
1.2
1.0
0.8
0.6
0.4
-10°F
(-23)°C
210
(99)
190
(88)
170
(77)
150
(65)
130
(54)
11 0
(43)
Supply water temperature
90
(32)
70
(21)
50°F
(10)°C
Refer to the tekmar Essays E 001 and E 002 for more detailed information regarding control strategy and integration of control functions.
When using a variable speed pump, the injection of high temperature water into the lower temperature heating system loop should
be continuous and the volume of water injected should be varied
by speeding up (more heat) or slowing down (less heat) the pump
rotation speed. This is a flexible and inexpensive method of mixing
reset/setpoint control and can be used for a number of applications
on systems with a wide variety of flow rates.
Ideally, the variable speed pump should operate near 100 %
output during system design temperature conditions (when running in mixing reset mode). Injection rates will vary with changing
high temperature loop water temperatures, and correct sizing of
the injection pump must take this factor into account. Plumbing
arrangements and pump sizing calculations are covered in more
detail in the Essay E 021.
Operation
The Mixing Control 365 has a 120Vac 50/60Hz output which has
been designed to directly power an injection pump at variable
speeds to control the rate at which hot water is added to the heating
system loop. The maximum drive capacity for this circuit is 1/6 hp,
2.2 Amp, 120Vac. There are a number of manufacturers producing small circulators that can be operated by this 120Vac output.
A permanent capacitor, impedance protected pump motor (no
start switch) under 1/6 hp is required. Most small "wet rotor"
circulators have proven to be acceptable. Consult the accompanying Addendum for a list of the specific pumps tested and
approved by their manufacturers. As these companies test and
approve new products for use with the tekmar variable speed
output, the Addendum will be updated.
Larger pumps require that a compatible 4–20 mA motor drive be
used as an interface between the control and the pump motor.
Contact the pump manufacturer regarding compatible equipment
for specific pumps.
The variable speed (
the same time. If the 120Vac output is used and remote monitoring
is important, a remote read out via the 4–20 mA could be
connected. The 4–20 mA is proportional to the level of the variable
speed output.
Var Pmp
) and the 4–20 mA output operate at
Supply To Low
Temperature Loop
Return from Low
Temperature Loop
Supply To Low
Temperature Loop
Return from Low
Temperature Loop
Mixing Point
Crossover
Flow
Variable Speed
Injection Pump
Crossover
Flow
Variable Speed
Injection Mixing
Low Output
Mixing Point
Crossover
Flow
Variable Speed
Injection Pump
Crossover
Flow
Variable Speed
Injection Mixing
High Output
Supply From High
Temperature Loop
Return to High
Temperature Loop
Supply From High
Temperature Loop
Return to High
Temperature Loop
Variable Speed Pump Start Up
The control gives an initial 100% power output to the motor for
1/5 second to get it started up from a dead stop. This full power
output is required to get the pump motor turning. After the 1/5
second starting pulse, the control adjusts the pump speed to meet
the heating requirements.
The maximum
rate
at which the motor can change its speed from
0% output to 100% or from 100% output back to 0% output is set
by the "Motor Speed/Pump Response" dial. This dial should be set
according to system response times and will typically be set
somewhere between 30 and 50 seconds. Refer to the "Settings"
section, page 12, for more information.
% of Full Output
The control's variable speed output has been designed to provide
a linear GPM flow rate over the full operating range of the pump.
For example, when the "10 % of full output " LED is on, the control
will be running the pump to deliver 10% of its GPM output rather
than 10% of its rated rotational speed. As the above illustration
indicates, the % output of flow from the pump is directly proportional (within 10%) to the "% of full output" scale of the control.
tekmar has developed two significantly different ways of piping variable speed injection pumps for small commercial and residential
hydronic heating systems. Each method has its advantages and disadvantages, and designers should read the tekmar essay E 021
thoroughly in order to correctly choose the best arrangement for their particular application.
Reverse Injection
Reverse injection requires that the water from the boiler loop
is injected into the low temperature loop upstream of the
return to the boiler loop. Mixing occurs directly after the point
of injection. Since some of the mixed water is then returned
back to the boiler loop, higher injection flow rates are required
than in direct injection systems.
Pump Sizing
Reverse Injection
To calculate the required size of the injection pump:
F1 = System Supply flow rate in US GPM
T1 = Hot Loop (Boiler) supply temperature available
T2 = Low Temperature (System) Supply temperature
∆Ts = Low Temperature (System) temperature drop (T2 – Tr)
Note: All values are to be given at design conditions.
Direct injection requires the water from the hot loop to be
injected into the low temperature loop so that the heat rise and
the mixing occur directly after the point of injection, downstream of the return to the hot loop.
Pump Sizing
Direct Injection
To calculate the required size of the injection pump:
F1 = System Supply flow rate in US GPM
T1 = Hot Loop (Boiler) supply temperature available
T2 = Low Temperature (System) Supply temperature
Tr= Low Temperature (System) Return temperature
∆Ts = Low Temperature (System) temperature drop (T2 – Tr)
Note: All values are to be given at design conditions.
F1 = System Flow = 60 GPM
Tr= System Return = T2 – ∆Ts = 100°F
Fv = = = = 12 GPM
This example illustrates an important point to consider when designing variable speed systems. The hotter the maximum boiler supply
temperature is designed for, or the cooler the maximum system supply temperature is designed for, the less injection flow is required. Quite
large systems can be designed with relatively small injection pumps when this is kept in mind.
Supply To Low
Temperature Loop
2
1
∆T
s
F
1 x ∆Ts 60 x 20 1200
"DIRECT" INJECTION
1
r
Variable
Speed
Injection
Pump
V
V
T1 - Tr 200 - 100 100
Supply From High
Temperature Loop
1
For more details on variable speed pumping, refer to tekmar essay E 021
The variable speed injection pump should be sized for full load heat transfer at design conditions. Calculations reveal that in most typical
residential and small commercial applications the smallest circulators are of sufficient size and in many cases exceed the maximum
required GPM rating. If an appropriate pump size is not available, a larger pump may be used provided a balancing valve is included to
reduce flow through the transfer loop.
When the Mixing Control 365 is powered-up, the "Power" light will come on and the control will turn on all
LEDs for five seconds. If no errors are detected, the control enters the operating mode.
Once in operating mode, the control determines whether to operate in Reset or Setpoint mode based on
the setting of the Reset/Setpoint DIP switch.
If the control is configured for Setpoint it will monitor:
• a Universal Sensor 071 to continually monitor the system supply water temperature.
•
Optionally,
a Universal Sensor 071 to continually monitor the boiler return water temperature.
If the control is configured for Reset it will monitor:
• an Outdoor Sensor 070 to continually monitor the outdoor temperature.
• a Universal Sensor 071 to continually monitor the system supply water temperature.
•
Optionally,
•
Optionally,
a Universal Sensor 071 to continually monitor the boiler return water temperature.
the indoor temperature can be monitored through the use of:
(a) - a tekmar 2K RTU or 10K Indoor Sensor 074 (DIP switch in "Indoor Sensor" position) or;
(b) - a tekmar 10K Zone Control (DIP switch in "Zone Control" position)
• While monitoring all of these temperatures, the control recognizes the following temperature conditions
and inputs and will respond as described. During operation, the lights of the control will indicate
operational status as illustrated.
Heating Operation (Reset Mode)
Selector Switch = Reset
When the control is in the reset mode, its main function is to reset the supply water
temperature based on the changing outdoor temperature.
External Heat Demand signal
Selector Switch = External Heat Demand
A heat demand signal is caused by either 24 or 120Vac applied to terminals
Heat Dem — Heat Dem
(1 and 2).
AND/OR
An active (calling for heat) 10 K Zone Control connected
to terminals
Com Sen — 10K Sen
(14 and 15).
Setpoint
123 4
Boiler on when 25% open
External Heat Demand
Zone Control
4-20
+
1110
Com –Ret
Reset
12 13
Sen
UnO
Sw
123 4
14
Com
Sen
?
Power
Heat
Demand
Min.
Return
Pump
90
70
50
30
10
Setpoint
Reset
Indoor Sensor
Permanent Heat Demand
Boiler on when 10% open
15
16
10K
2K
Sen
RTU
%
17
Com
Sen
WWSD
UnOcc.
Switch
Max. or
Setpoint
Boiler
of full
output
123 4
12
Heat
Dem Dem
18 19
Sup
Sen
Test
Out
Sen
Permanent Heat Demand signal
Selector Switch = Permanent Heat Demand
A heat demand signal is continuously present unless a10K Zone Control is connected to terminals
Com Sen — 10K Sen
(14 and 15).
(If a10K Zone Control is connected, there will only be a heat demand
present when it calls for heat)
Occupied/Unoccupied dial function
With no indoor air temperature feedback, the control will monitor the outdoor and supply
temperatures. The Occupied and Unoccupied dial settings become the WWSD points.
When in Occupied mode and the outdoor temperature is warmer than the setting of the
Occupied dial, the control enters WWSD. When switched into Unoccupied mode –
(short circuit) terminals
UnO Sw — Com Sen
(13 and 14) together by a switch or isolated timer
Connect
relay contacts (tekmar Timer 030) – the "UnOcc. Switch" light will come on, the Occupied dial
will become inactive and the Unoccupied dial will become active
as the control starts to
operate at the temperature of the Unoccupied dial setting.
Indoor Sensor 074 function
Selector switch = Indoor Sensor
The control will monitor the indoor, outdoor and supply temperatures, and shift the Heating Curve
(and the WWSD point) up or down to fine adjust the system supply water temperature whenever
the room temperature is different than the setting of the Occupied dial. When switched into
Unoccupied mode, the "UnOcc. Switch
" light will come on, and the control will operate at the
temperature of the Unoccupied dial setting.
2K RTU function
Selector switch = Indoor Sensor
The control will monitor the indoor, outdoor and supply temperatures, and shift the Heating Curve
(and the WWSD point) up or down to fine adjust the system supply water temperature whenever
the room temperature is different than the setting of the RTU dial. The Occupied and Unoccupied
dials are not functional. A Setback RTU 308 must be used if Unoccupied schedules are desired.
tekmar Zone Control function
Selector switch = Zone Control
The control accepts a zone input signal from a tekmar 10K Zone Control which monitors the
indoor temperature of all zones – as well as the outdoor and supply temperatures – and shifts the
Heating Curve (and the WWSD point) up or down to fine adjust the system supply water
temperature for whichever zone requires the hottest supply water. The Occupied and Unoccupied dials are only functional if an external heat demand is given and the dial setting is higher than
the zone control desired temperature.