tekmar 365 User Manual

- Data Brochure
R
D 365
Mixing Control 365
WWSD
Power
Heat
UnOcc.
Demand
Switch
Max. or
Min.
Setpoint
105 (41)
Pump
is on
Return
Boiler
Pump
90
70
of full
50
output
%
30
10
R
R
LR 58233
E150539
70°F
70°F
(21°C)
(21°C)
35
35
105
(2
(2
(41)
)
)
Occupied
Unoccupied
Mixing Control 365
Variable Speed and 4-20 mA
Control is
maintaining
Minimum Return
System
Unoccupied
temperature
setting
Occupied
temperature
setting
Variable Speed
and 4-20 mA
operating level
Terminal Plugs:
Power and out-
put connections
The tekmar Mixing Control 365 is a microprocessor-based control with a 120 Vac output for operating a variable speed injection pump. A 4-20mA output is available for operating devices such as a 4­20mA actuating motor, modulating gas valve, a mixing valve combination, or for operating a 4-20mA motor drive for larger variable speed pumps. The variable speed pump or mixing valve regulates the supply water temperature to a heating system based on the outdoor air temperature, and optionally, the indoor air temperature. The system is shut down when there is no Heat Demand signal or when the outdoor temperature is warm enough so that the system no longer requires heat (WWSD).
Outdoor Reset Strategy. . pg. 2 Variable Speed Pump . . . pg. 3 Sequence of Operation . . pg. 5
Installation . . . . . . . . . . . . pg. 7
Settings . . . . . . . . . . . . . . . pg. 11
Heating
is required
35 (2)
Occupied
Mixing Control 365
Variable Speed and 4-20 mA
Use Nº 20 AWG or larger copper conductors rated for at least 75°C and 300V.
12 3456
Heat
Dem Pmp
70°F
(21°C)
105 (41)
120Vac power
supply is on
70°F
(21°C)
35
105
(2)
(41)
Unoccupied
Power
System
N
L
Pmp
System is in
Warm Weather
Shut Down
7
Var. Pmp
Power
Heat Demand
Min. Return
Pump
LR 58223
89
Boiler
90
70
50
30
10
R
switched to
Unoccupied
WWSD
UnOcc. Switch
Max. or Setpoint
Boiler
of full
output
%
Listed
5T62
R
E150539
Testing . . . . . . . . . . . . pg. 13
Error Messages . . . . . pg. 15
Technical Data . . . . . . pg. 16
Limited Warranty . . . . pg. 16
System is
Setpoint
123 4
Reset
60
Test
Manufactured in Canada by
Power: 120V 50/60Hz 300VA System pump: 120Vac 12A 1/3 hp, pilot duty 480VA 4A Var pump: 120V 50/60Hz 2.2A 1/6 hp, internally fused Relay: 120Vac 10A 1/4 hp, pilot duty 240VA 2A Enclosed Energy Management Equipment
1000 max
Do not apply power here
13 14
12 15
10 11
Ret
UnO
4-20
Com
+
Sen
Control is
maintaining
Maximum Supply
Boiler on when 25% open External Heat Demand Zone Control
Indoor Sensor Permanent Heat Demand Boiler on when 10% open
2.0
0.4
3.6
Heating Curve
100°F
150
Minimum
Boiler Return
16 17
2K10K
Com Com
SenSw
Sen
RTU
Sen
150°F
100 200
Max./Setpoint
130 sec.
30 230Off
Motor Speed /
Pump Response
2093 1234567
18 19
Sup Out Sen
Sen
Date
R
06/00
Boiler is on
Operating Mode selector switches
Heating Curve
Maximum
/Setpoint
Supply
Minimum Boiler Return
Motor Speed
Test button and LED to test main
S/N
control functions
Terminal Plug: Sensor and timer input
H1073
Input: Heat Demand signal.
Optional
120Vac Power Supply
Output: Turn on
system pump
Output: Control
variable speed pump
Output:
Turn on boiler
OR
Output:
4-20mA device
M
Input: Return
Sensor 071.
Optional
Input:
Unoccupied
signal (030
Timer)
Optional
Input: Indoor
Sensor 074
Optional
Copyright © D 365 - 06/001 of 16
Input: Outdoor
Sensor 070
Included
Input: Supply Universal
Sensor 071.
Included
OR
Input: 2k RTU
Optional
Outdoor Reset Strategy
Correct setting and shifting of the Heating Curve... the key to More Comfort and Energy Savings.
Heating Curve
As outdoor temperatures get colder, heat losses from a building increase, requiring the addition of more heat to prevent the indoor air temperature from also getting colder. This tekmar reset control measures the outdoor temperature and as the outdoor temperature gets colder, it balances the heat loss by making the heating supply water hotter. The Heating Curve is used to calculate how hot to make the supply water at different outdoor temperatures. It is the number of degrees the supply water temperature is raised for each degree that the outdoor temperature falls.
Setting the Heating Curve
Two examples of how the Heating Curve works are given in the following illustration. With a 2.4 Curve, the supply water temperature is raised 2.4 degrees for every degree of outdoor temperature drop.
If WWSD point = 70°F and Outdoor temperature = 30°F, then Supply temperature = 166°F
With a 0.6 Curve, the supply water temperature is raised 0.6 degrees for every degree of outdoor temperature drop.
If WWSD point = 70°F and Outdoor temperature = 30°F, then Supply temperature = 94°F
If the Heating Curve selected is too low;
able to raise the supply temperature high enough to keep the room temperature warm during colder weather.
If the Heating Curve selected is too high;
the building will overheat during colder weather.
Warm Weather Shut Down (WWSD)
At warm outdoor temperatures, the indoor space of a building gains heat from the outdoors; additional heat is not required, and if the heating system is running (even on standby), enough excess heat can be produced to overheat the building, causing discomfort and wasting valuable energy.
This control turns off the system pump and injection pump (or closes a mixing valve), when the outdoor temperature is above the WWSD point.
As outdoor temperatures get colder, there comes a point where the heat gain turns into heat loss; the heat loss causes the indoor temperature to fall below the comfort level, and the heating system must be turned on to start delivering heat.
To provide heat to the building, this control turns on the system pump and starts the injection pump (or opens the mixing valve), delivering heat at the low output required by the Heating Curve near the WWSD point. If the outdoor temperature rises above the WWSD point, the control shuts the system off again, and because the system was operating at a low heat output level, overheating and temperature swings in mild weather are avoided.
When the system is operating near the WWSD point and the building is too cold; When the system is operating near the WWSD point and the building is too warm;
3.0
WWSD
Point
will
shift
up and
down
with
shift of
Heating
Curve
(32)
3.6
Heating
Curve
Parallel Shift of Heating Curve
UP
DOWN
UP
90
70
(21)
50
(10)
Outdoor air temperature
2.4 2.0
DOWN
30
(-1)10(-12)
A very cool room temperature can shift the curve far enough up to bring the control out of WWSD at warm outdoor temperatures. A very warm room temperature can shift the curve far enough down to put the control into WWSD at cool outdoor temperatures.
the heating system will not be
too much heat is delivered and
Shifting the Heating Curve
(a) Manually, at the control:
The Occupied and Unoccupied dials on this control can shift the WWSD point up or down from 35 to 105°F (2 to 41°C).
(b) Automatically, using room temperature feedback:
In addition to a Supply Sensor and an Outdoor Sensor, this control can use a tekmar 2k RTU, 10k Zone Control or 10k Indoor Sensor to provide room temperature feedback for added comfort and system flexibility.
The control still calculates a desired supply temperature based on the
Supply water temperature
Heating Curve setting and the outdoor temperature.
If the air temperature in the room is too cold, the control will shift the Heating Curve (and WWSD point) room warms up again.
If the air temperature in the room is too warm, the control will shift the Heating Curve (and WWSD point)
1.6
1.2
1.0
0.8
0.6
0.4
-10°F
(-23)°C
210 (99)
190 (88)
170 (77)
150 (65)
130 (54)
11 0 (43)
90
(32)
70
(21)
50°F
(10)°C
ture until the room cools down.
3.0
90
(32)
WWSD
Point
Heating
Curve
70
(21)
3.6
50
(10)
Outdoor air temperature
2.4 2.0
30
(-1)10(-12)
the WWSD point should be raised.
the WWSD point should be lowered.
up,
which raises the supply temperature until the
down,
which lowers the supply tempera-
1.6
1.2
1.0
0.8
0.6
0.4
-10°F
(-23)°C
210 (99)
190 (88)
170 (77)
150 (65)
130 (54)
11 0 (43)
Supply water temperature
90
(32)
70
(21)
50°F
(10)°C
Refer to the tekmar Essays E 001 and E 002 for more detailed information regarding control strategy and integration of control functions.
Copyright © D 365 - 06/00 2 of 16
The tekmar Variable Speed Pump Output
Variable Speed Pump
When using a variable speed pump, the injection of high tempera­ture water into the lower temperature heating system loop should be continuous and the volume of water injected should be varied by speeding up (more heat) or slowing down (less heat) the pump rotation speed. This is a flexible and inexpensive method of mixing reset/setpoint control and can be used for a number of applications on systems with a wide variety of flow rates.
Ideally, the variable speed pump should operate near 100 % output during system design temperature conditions (when run­ning in mixing reset mode). Injection rates will vary with changing high temperature loop water temperatures, and correct sizing of the injection pump must take this factor into account. Plumbing arrangements and pump sizing calculations are covered in more detail in the Essay E 021.
Operation
The Mixing Control 365 has a 120Vac 50/60Hz output which has been designed to directly power an injection pump at variable speeds to control the rate at which hot water is added to the heating system loop. The maximum drive capacity for this circuit is 1/6 hp,
2.2 Amp, 120Vac. There are a number of manufacturers produc­ing small circulators that can be operated by this 120Vac output. A permanent capacitor, impedance protected pump motor (no start switch) under 1/6 hp is required. Most small "wet rotor" circulators have proven to be acceptable. Consult the accompa­nying Addendum for a list of the specific pumps tested and approved by their manufacturers. As these companies test and approve new products for use with the tekmar variable speed output, the Addendum will be updated.
Larger pumps require that a compatible 4–20 mA motor drive be used as an interface between the control and the pump motor. Contact the pump manufacturer regarding compatible equipment for specific pumps.
The variable speed ( the same time. If the 120Vac output is used and remote monitoring is important, a remote read out via the 4–20 mA could be connected. The 4–20 mA is proportional to the level of the variable speed output.
Var Pmp
) and the 4–20 mA output operate at
Supply To Low
Temperature Loop
Return from Low
Temperature Loop
Supply To Low
Temperature Loop
Return from Low
Temperature Loop
Mixing Point
Crossover
Flow
Variable Speed Injection Pump
Crossover
Flow
Variable Speed
Injection Mixing
Low Output
Mixing Point
Crossover
Flow
Variable Speed
Injection Pump
Crossover
Flow
Variable Speed
Injection Mixing
High Output
Supply From High Temperature Loop
Return to High
Temperature Loop
Supply From High Temperature Loop
Return to High
Temperature Loop
Variable Speed Pump Start Up
The control gives an initial 100% power output to the motor for 1/5 second to get it started up from a dead stop. This full power output is required to get the pump motor turning. After the 1/5 second starting pulse, the control adjusts the pump speed to meet the heating requirements.
The maximum
rate
at which the motor can change its speed from 0% output to 100% or from 100% output back to 0% output is set by the "Motor Speed/Pump Response" dial. This dial should be set according to system response times and will typically be set somewhere between 30 and 50 seconds. Refer to the "Settings" section, page 12, for more information.
% of Full Output
The control's variable speed output has been designed to provide a linear GPM flow rate over the full operating range of the pump. For example, when the "10 % of full output " LED is on, the control will be running the pump to deliver 10% of its GPM output rather than 10% of its rated rotational speed. As the above illustration indicates, the % output of flow from the pump is directly propor­tional (within 10%) to the "% of full output" scale of the control.
Variable Speed & 4-20 mA Output Operation
100%
80%
60%
40%
Rated GPM of Pump
20%
90
70
50
30
10
20%
% of Full Output Display (Pump GPM output in %)
90
70
50
90
70
50
30
90
70
50
30
90
70
50
30
10
40% 60% 80% 100%
10
Note: Refer to Pump
Manufacturers' Specifications
10
for G.P.M. Output
30
10
Within 10%
(typical)
Copyright © D 365 - 06/003 of 16
Plumbing Arrangements
T
T
F
F
T
F
F
T
T
T
F
F
T
F
F
T
tekmar has developed two significantly different ways of piping variable speed injection pumps for small commercial and residential hydronic heating systems. Each method has its advantages and disadvantages, and designers should read the tekmar essay E 021 thoroughly in order to correctly choose the best arrangement for their particular application.
Reverse Injection
Reverse injection requires that the water from the boiler loop is injected into the low temperature loop upstream of the return to the boiler loop. Mixing occurs directly after the point of injection. Since some of the mixed water is then returned back to the boiler loop, higher injection flow rates are required than in direct injection systems.
Pump Sizing
Reverse Injection
To calculate the required size of the injection pump:
F1 = System Supply flow rate in US GPM T1 = Hot Loop (Boiler) supply temperature available T2 = Low Temperature (System) Supply temperature Ts = Low Temperature (System) temperature drop (T2 – Tr)
Note: All values are to be given at design conditions.
Maximum Variable Flow
(Fv) =
F1 x Ts T1 - T2
Sample Calculation
Values at
Design
Conditions
Are:
T1 = Boiler Supply = 180°F T2 = System Supply = 130°F
Ts = System T = 25°F
F1 = System Flow = 10 GPM
r
1
T
s
Supply To Low
Temperature Loop
1 x Ts 10 x 25 250
F
Fv = = = = 5 GPM
T1 - T2 180 - 130 50
"REVERSE" INJECTION
2
1
Variable
Speed
Injection
Pump
V
V
Supply From High
Temperature Loop
1
Direct Injection
Direct injection requires the water from the hot loop to be injected into the low temperature loop so that the heat rise and the mixing occur directly after the point of injection, down­stream of the return to the hot loop.
Pump Sizing
Direct Injection
To calculate the required size of the injection pump:
F1 = System Supply flow rate in US GPM T1 = Hot Loop (Boiler) supply temperature available T2 = Low Temperature (System) Supply temperature Tr = Low Temperature (System) Return temperature Ts = Low Temperature (System) temperature drop (T2 – Tr)
Note: All values are to be given at design conditions.
Maximum Variable Flow
(Fv) =
F1 x Ts T1 - Tr
Sample Calculation
Values at
Design
Conditions
Are:
T1 = Boiler Supply = 200°F T2 = System Supply = 120°F
Ts = System T = 20°F
F1 = System Flow = 60 GPM Tr = System Return = T2 – Ts = 100°F
Fv = = = = 12 GPM
This example illustrates an important point to consider when designing variable speed systems. The hotter the maximum boiler supply temperature is designed for, or the cooler the maximum system supply temperature is designed for, the less injection flow is required. Quite large systems can be designed with relatively small injection pumps when this is kept in mind.
Supply To Low
Temperature Loop
2
1
T
s
F
1 x Ts 60 x 20 1200
"DIRECT" INJECTION
1
r
Variable
Speed
Injection
Pump
V
V
T1 - Tr 200 - 100 100
Supply From High Temperature Loop
1
For more details on variable speed pumping, refer to tekmar essay E 021
The variable speed injection pump should be sized for full load heat transfer at design conditions. Calculations reveal that in most typical residential and small commercial applications the smallest circulators are of sufficient size and in many cases exceed the maximum required GPM rating. If an appropriate pump size is not available, a larger pump may be used provided a balancing valve is included to reduce flow through the transfer loop.
Copyright © D 365 - 06/00 4 of 16
Sequence of Operation
Zone Control
Boiler on when 25% open
External Heat Demand
Setpoint
123 4
When the Mixing Control 365 is powered-up, the "Power" light will come on and the control will turn on all LEDs for five seconds. If no errors are detected, the control enters the operating mode.
Once in operating mode, the control determines whether to operate in Reset or Setpoint mode based on the setting of the Reset/Setpoint DIP switch.
If the control is configured for Setpoint it will monitor:
a Universal Sensor 071 to continually monitor the system supply water temperature.
Optionally,
a Universal Sensor 071 to continually monitor the boiler return water temperature.
If the control is configured for Reset it will monitor:
an Outdoor Sensor 070 to continually monitor the outdoor temperature.
a Universal Sensor 071 to continually monitor the system supply water temperature.
Optionally,
Optionally,
a Universal Sensor 071 to continually monitor the boiler return water temperature.
the indoor temperature can be monitored through the use of: (a) - a tekmar 2K RTU or 10K Indoor Sensor 074 (DIP switch in "Indoor Sensor" position) or; (b) - a tekmar 10K Zone Control (DIP switch in "Zone Control" position)
While monitoring all of these temperatures, the control recognizes the following temperature conditions and inputs and will respond as described. During operation, the lights of the control will indicate operational status as illustrated.
Heating Operation (Reset Mode)
Selector Switch = Reset
When the control is in the reset mode, its main function is to reset the supply water temperature based on the changing outdoor temperature.
External Heat Demand signal
Selector Switch = External Heat Demand
A heat demand signal is caused by either 24 or 120Vac applied to terminals
Heat Dem Heat Dem
(1 and 2).
AND/OR
An active (calling for heat) 10 K Zone Control connected to terminals
Com Sen 10K Sen
(14 and 15).
Setpoint
123 4
Boiler on when 25% open External Heat Demand
Zone Control
4-20
+
1110
Com –Ret
Reset
12 13
Sen
UnO
Sw
123 4
14
Com
Sen
?
Power
Heat Demand
Min. Return
Pump
90
70
50
30
10
Setpoint
Reset
Indoor Sensor Permanent Heat Demand Boiler on when 10% open
15
16
10K
2K
Sen
RTU
%
17
Com
Sen
WWSD
UnOcc. Switch
Max. or Setpoint
Boiler
of full
output
123 4
12
Heat
Dem Dem
18 19
Sup
Sen
Test
Out
Sen
Permanent Heat Demand signal
Selector Switch = Permanent Heat Demand
A heat demand signal is continuously present unless a10K Zone Control is connected to terminals
Com Sen 10K Sen
(14 and 15).
(If a10K Zone Control is connected, there will only be a heat demand
present when it calls for heat)
Occupied/Unoccupied dial function
With no indoor air temperature feedback, the control will monitor the outdoor and supply temperatures. The Occupied and Unoccupied dial settings become the WWSD points. When in Occupied mode and the outdoor temperature is warmer than the setting of the Occupied dial, the control enters WWSD. When switched into Unoccupied mode – (short circuit) terminals
UnO Sw Com Sen
(13 and 14) together by a switch or isolated timer
Connect
relay contacts (tekmar Timer 030) – the "UnOcc. Switch" light will come on, the Occupied dial will become inactive and the Unoccupied dial will become active
as the control starts to
operate at the temperature of the Unoccupied dial setting.
Indoor Sensor 074 function
Selector switch = Indoor Sensor
The control will monitor the indoor, outdoor and supply temperatures, and shift the Heating Curve (and the WWSD point) up or down to fine adjust the system supply water temperature whenever the room temperature is different than the setting of the Occupied dial. When switched into Unoccupied mode, the "UnOcc. Switch
" light will come on, and the control will operate at the
temperature of the Unoccupied dial setting.
2K RTU function
Selector switch = Indoor Sensor
The control will monitor the indoor, outdoor and supply temperatures, and shift the Heating Curve (and the WWSD point) up or down to fine adjust the system supply water temperature whenever the room temperature is different than the setting of the RTU dial. The Occupied and Unoccupied dials are not functional. A Setback RTU 308 must be used if Unoccupied schedules are desired.
tekmar Zone Control function
Selector switch = Zone Control
The control accepts a zone input signal from a tekmar 10K Zone Control which monitors the indoor temperature of all zones – as well as the outdoor and supply temperatures – and shifts the Heating Curve (and the WWSD point) up or down to fine adjust the system supply water temperature for whichever zone requires the hottest supply water. The Occupied and Unoccu­pied dials are only functional if an external heat demand is given and the dial setting is higher than the zone control desired temperature.
4-20
+
12
1110
Com –Ret
Sen
Reset
Reset
Setpoint
Reset
13 14
UnO SwCom
123 4
123 4
123 4
Copyright © D 365 - 06/005 of 16
123 4
Sen
Indoor Sensor
Permanent Heat Demand
Boiler on when 10% open
15
16
10K
2K
Sen
RTU
Indoor Sensor
Permanent Heat Demand Boiler on when 10% open
Indoor Sensor
Permanent Heat Demand Boiler on when 10% open
Boiler on when 25% open External Heat Demand
Zone Control
17
Com
Sen
18
Sup
Sen
19
Out
Sen
Loading...
+ 11 hidden pages