tekmar 356 User Manual

- Data Brochure
D 356
Mixing Control 356
09/08
The Mixing Control 356 is designed to control the supply water temperature to a hydronic system in order to provide outdoor reset or setpoint operation. The control uses a variable speed injection pump to regulate the supply water temperature, while protecting the boiler against flue gas condensation. The control has a Liquid Crystal Display (LCD) to view system status and operating information.
• Quick Setup for easy installation and programming of control
• User comfort adjustment to increase or decrease building space temperature
• Advanced settings to fine-tune building requirements
Press & Hold
Item,
to view settings
, to test
Press & Release
Item + + , to adjust menu tektra 911-02
MIX
• Boiler Control for improved energy savings
• Test sequence to ensure proper component operation
• CSA C US certified (approved to applicable UL standards)
Power:
24 V
±
Var. Pmp: Relay:
10% 50/60 Hz 3 VA 120 V (ac) 2.4 A 1/6 hp 120 V (ac) 5 A 1/6 hp
Meets Class B: Canadian ICES FCC Part 15
VIEW
H1193C
Output
Variable Speed
Injection Pump
(through back
of control)
Input
Supply Sensor
Included
Input
Outdoor Sensor
Included
Terminal Unit
Return Supply
Item
Mixing Control 356
Mixing Control 356
Variable Speed
Variable Speed
Do not apply power
1234
Inst/Adv
Com
Sup
Out
Input
Boiler Sensor
Included
Made in Canada
Signal wiring
must be rated
Boil
at least 300 V
10 30 50 70 90
% Out
Mixing
Demand
C US
Date Code
56789
Boiler
Power
R+
T
Output
Boiler
C-
Input
24 V (ac)
Power Supply
Input
Mixing Demand
Signal
Note:
Mix demand must have an electrical closure between terminals 7 and 9 before the mix injection pump is able to operate and the boiler is able to fire.
Copyright © D 356 -09/081 of 16
How To Use The Data Brochure
This brochure is organized into four main sections. They are: 1)
Troubleshooting
of the
Sequence of Operation
that apply to your installation. For quick installation and setup of the control, refer to the followed by the
The
Control Settings
by the control. The control functions of each adjustable item are described in the
Sequence of Operation
. The
, as this contains important information on the overall operation of the control. Then read the sub-sections
Quick Setup
section (starting at
section.
section has three sub-sections. We recommend reading Section A:
DIP Switch Setting
) of this brochure, describes the various items that are adjusted and displayed
Sequence of Operation
Sequence of Operation
Table of Contents
User Interface .................................................... Pg 2
Description of Display Elements ..................... Pg 3
Sequence of Operation ..................................... Pg 3
Section A: General Operation ..............
Section B: Mixing ..................................
Section C: Boiler Operation .................
Installation ......................................................... Pg 8
Pg 3
Pg 4
Pg 7
Quick Setup ..................................................... Pg 11
Control Settings .............................................. Pg 12
View Menu ...........................................
Adjust Menu ........................................
Testing and Troubleshooting ......................... Pg 14
Error Messages ..................................
Technical Data ................................................. Pg 16
Installation
, 2)
Installation
section,
Control Settings
, 3)
General Operation
DIP Switch Setting
.
Pg 12
Pg 12
Pg 15
, and 4)
section,
DIP Switch Setting .......................................... Pg 10
Reference Material: Essay E 003 “Characterized Heating Curve and Reset Ratio”
Essay E 021 “Mixing Methods and Sizing of Variable Speed Injection Pumps”
Limited Warranty ............................................. Pg 16
User Interface
The 356 uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to set up and monitor the operation of your system. The 356 has three push buttons ( your control, record your settings in the ADJUST menu table which is found in the second half of this brochure.
Item
The abbreviated name of the selected item will be displayed in the item field of the display. To view the next available item, press and release the have reached the last available item, pressing and releasing the the display to the first item.
Adjust
To make an adjustment to a setting in the control, press and hold simultaneously for 1 second, all 3 buttons. The display will then show the word ADJUST in the top right corner. Then select the desired item using the
to make the adjustment.
To exit the ADJUST menu, either select the ESC item and press the or button, or leave the adjustment buttons alone for 20 seconds.
Item
button. Finally, use the
Item
, , ) for selecting, viewing, and adjusting settings. As you program
button. Once you
Item
Item
button will return
and / or
button
Item
Item
When the levels.
Additional information can be gained by observing the status field and pointers of the LCD. The status field will indicate which of the control’s outputs are currently active. Most symbols in the status field are only visible when the VIEW menu is selected.
Item
button is pressed and held in the VIEW menu, the display scrolls through all the control adjust items in both access
Copyright © D 356 -09/08 2 of 16
Display
Item Field
Displays an abbreviated name of the selected item
OUTDR BOIL MIX
DSGN
TARGET
MAXMIN ROOM WWSD INDR
DIFF
Number Field
Displays the current value of the selected item
VIEW ADJUST
°
F
°
C
Menu Field
Displays the current menu
Terminal Unit
Status Field
Displays the current status of the controls inputs, outputs and operation
Symbol Description
Burner
Displays when the boiler relay is turned on.
°
F, °C
°F, °C
Displays the unit of measure that all of the temperatures are to be displayed in the control.
Return
10 30 50 70 90
Supply
% Out
Item
Mixing
Demand
Buttons
Selects Menus, Items
{
and adjusts settings
Pointer
Displays the control operation as indicated by the text.
Sequence of Operation
Section A
General Operation
Page 3-4
Section B
Mixing
Page 4-6
Section C
Boiler Operation
Page 7
Section A — General Operation
POWERING UP THE CONTROL
When the Mixing Control 356 is powered up, the control displays the control type number in the LCD for 2 seconds. Next, the software version is displayed for 2 seconds. Finally, the control enters into the normal operating mode and the LCD defaults to displaying the current outdoor air temperature.
Copyright © D 356 -09/083 of 16
OPERATION
The 356 uses a variable speed injection pump to control the supply water temperature to a hydronic system. The supply water temperature is based on either the current outdoor temperature, or a fixed setpoint.
Design Supply
Terminal Unit
Outdoor Reset
When the outdoor design (OUTDR DSGN) setting is not set to OFF, the 356 calculates a mixing supply temperature based on the current outdoor air temperature and the
acterized Heating Curve
Setpoint Control
When the outdoor design (OUTDR DSGN) setting is set to OFF, the 356 supplies a fixed mixing supply temperature equal to the MIX TARGET setting. An outdoor sensor is not required during this mode of operation.
VARIABLE SPEED INJECTION
A standard wet rotor circulator is connected to the 356 at the back of the control. The 356 increases or decreases the power output to the circulator when there is a mixing demand. The circulator speed varies to maintain the correct mixed supply water temperature at the mix sensor. For correct sizing and piping of the variable speed injection driven circulator, refer to essay E 021. A visual indication of the current variable speed output is displayed in the LCD in the form of a horizontal bar graph.
BOILER PROTECTION (BOIL MIN)
The 356 is capable of providing boiler protection from cold mixing sys­tem return water temperatures. If the boiler sensor temperature is cooler than the BOIL MIN setting while the boiler is firing, the 356 reduces the output to the variable speed injection pump. This limits the amount of cool return water to the boiler, and allows the boiler temperature to re­cover. This feature can only be used if a boiler sensor is installed.
EXERCISING
The 356 has a built-in exercising function. If the pump has not been operated at least once every 3 days, the control turns on the output for 10 seconds. This minimizes the possibility of the pump seizing during a long period of inactivity.
Note:
The exercising function does not work if power to the control or pump is disconnected.
Indoor Design
Char-
settings.
Outdoor Design
Decreasing Outdoor Temperature
Current output of
variable
speed injection pump
3010 7050 90
% Out
Mixing sensor
Boiler supply
sensor
or
Boiler return
sensor
Increasing Water Temperature
FACTORY DEFAULTS
The control comes preset with several factory defaults. These defaults are based on the terminal unit selection (see section B2). To fine-tune building requirements, these defaults may be changed. If a factory default value for a terminal unit is changed, the terminal unit number will flash when selected in the ADJUST menu.
To reload the factory defaults listed in section B2, power down the control and wait for 10 seconds. Power up the control while simultaneously holding the than flashing.
Item
and buttons. The terminal unit number should now be displayed constantly in the LCD rather
Section B: Mixing
Section B1
General
Section B2
Installer
Section B3
Advanced
Section B1: General
MIXING DEMAND
A mixing demand is required in order for the 356 to provide heat. A mixing demand is generated by connecting terminal T(7) to terminal C-(9) through a switching device. Once the switching device closes, the calculates a MIX TARGET supply temperature based on the outdoor air temperature and settings. If required, the 356 operates the boiler in order to provide heat to the variable speed injection pump.
Copyright © D 356 -09/08 4 of 16
Mixing Demand
pointer is displayed in the LCD. The 356
Zone Valve Motor
End Switches
M
M
C R
To control
CHARACTERIZED HEATING CURVE
When used as a mixing reset control, the 356 varies the supply water temperature based on the outdoor air temperature. The control takes into account the type of terminal unit that the system is using. Since different types of terminal units transfer heat to a space using different proportions of radiation, convection and conduction, the supply water temperature must be controlled differently. Once the control is told what type of terminal unit is used, the control loads the factory defaults and varies the supply water temperature according to the type of terminal unit. This improves the control of the air temperature in the building.
MIXING TARGET TEMPERATURE (MIX TARGET)
When used as a mixing reset control, the MIX TARGET temperature is determined from the
Characterized Heating Curve
settings and outdoor air temperature. When used as a setpoint control, the installer will set the MIX TARGET temperature. The control displays the temperature that it is currently trying to maintain as the mixing supply temperature. If the control does not have a mixing demand, ---” is displayed as the MIX TARGET.
Section B2: Installer
OUTDOOR DESIGN (OUTDR DSGN)
The OUTDR DSGN is the outdoor air temperature that is the typical coldest temperature of the year where the building is located. This tem­perature is used when doing the heat loss calculations for the building. If a cold outdoor design temperature is selected, the mixing supply tem­perature rises gradually as the outdoor temperature drops. If a warm outdoor design temperature is selected, the mixing supply temperature rises rapidly as the outdoor temperature drops.
SETPOINT OPERATION (MIX TARGET)
For setpoint operation, set the OUTDR DSGN to OFF. The MIX TAR­GET becomes the setpoint supply temperature that the control is to maintain. The MIX TARGET temperature is set by the installer in the ADJUST menu. An outdoor sensor is not required during this mode of operation.
ROOM (ROOM)
The ROOM is the desired room temperature for the mixing zones, and it provides a parallel shift of the temperature desired by the occupants is often different from the design indoor temperature (MIX INDR). If the room temperature is not correct, adjusting the ROOM setting increases or decreases the amount of heat available to the building.
Characterized Heating Curve
MIX DSGN
cold
OUTDR
DSGN
warm
Increasing Water Temperature
. The room
Increasing Water Temperature
MIX INDR
Decreasing Outdoor Temperature
.
p
m
e
T
l
a
u
t
c
A
ROOM
MIX INDR
Decreasing Outdoor Temperature
s
e
D
l
a
m
r
o
N
n
g
i
TERMINAL UNITS
When using a shape of the
Characterized Heating Curve
Characterized Heating Curve
, the control requires the selection of a terminal unit. The terminal unit determines the
according to how the terminal unit delivers heat into the building space (refer to Essay E 003). The 356 provides for selection between six different terminal unit types: two types of radiant floor heat, fancoil, fin-tube convector, radiator and baseboard. When a terminal unit is selected, the control automatically loads the design supply temperature (MIX DSGN) and maximum supply temperature (MIX MAX). The factory defaults are listed below. To change defaults, refer to section B3. If a default has been changed, refer to section A to reload the factory defaults.
Terminal Unit
MIX DSGN MIX MAX
High Mass Radiant
(1)
120°F (49°C) 140°F (60°C)
Low Mass Radiant
(2)
140°F (60°C) 160°F (71°C)
Fancoil
(3)
190°F (88°C) 210°F (99°C)
Fin-tube Convector
(4)
180°F (82°C) 200°F (93°C)
Radiator
(5)
160°F (71°C) 180°F (82°C)
Baseboard
(6)
150°F (66°C) 170°F (77°C)
Copyright © D 356 -09/085 of 16
Loading...
+ 11 hidden pages