The Mixing Control 356 is designed to control the supply water temperature to a hydronic system in order to provide outdoor reset or
setpoint operation. The control uses a variable speed injection pump to regulate the supply water temperature, while protecting the
boiler against flue gas condensation. The control has a Liquid Crystal Display (LCD) to view system status and operating information.
Additional functions include:
• Quick Setup for easy installation and programming of control
• User comfort adjustment to increase or decrease building
space temperature
• Advanced settings to fine-tune building requirements
Press & Hold
Item,
to view settings
, to test
Press & Release
Item + + , to adjust menu
tektra 911-02
MIX
• Boiler Control for improved energy savings
• Test sequence to ensure proper component operation
• CSA C US certified (approved to applicable UL standards)
Power:
24 V
±
Var. Pmp:
Relay:
10% 50/60 Hz 3 VA
120 V (ac) 2.4 A 1/6 hp
120 V (ac) 5 A 1/6 hp
Meets Class B:
Canadian ICES
FCC Part 15
VIEW
H1193C
Output
Variable Speed
Injection Pump
(through back
of control)
Input
Supply Sensor
Included
Input
Outdoor Sensor
Included
Terminal Unit
Return Supply
Item
Mixing Control 356
Mixing Control 356
Variable Speed
Variable Speed
Do not apply power
1234
Inst/Adv
Com
Sup
Out
Input
Boiler Sensor
Included
Made in Canada
Signal wiring
must be rated
Boil
at least 300 V
10 30 50 70 90
% Out
Mixing
Demand
C US
Date Code
56789
Boiler
Power
R+
T
Output
Boiler
C-
Input
24 V (ac)
Power Supply
Input
Mixing Demand
Signal
Note:
Mix demand must have an
electrical closure between
terminals 7 and 9 before the
mix injection pump is able
to operate and the boiler
is able to fire.
The 356 uses a Liquid Crystal Display (LCD) as the method of supplying information. You use the LCD in order to set up and monitor
the operation of your system. The 356 has three push buttons (
your control, record your settings in the ADJUST menu table which is found in the second half of this brochure.
Item
The abbreviated name of the selected item will be displayed in the item field of the
display. To view the next available item, press and release the
have reached the last available item, pressing and releasing the
the display to the first item.
Adjust
To make an adjustment to a setting in the control, press and hold simultaneously for 1
second, all 3 buttons. The display will then show the word ADJUST in the top right corner.
Then select the desired item using the
to make the adjustment.
To exit the ADJUST menu, either select the ESC item and press the or button, or leave the adjustment buttons alone for 20
seconds.
Item
button. Finally, use the
Item
, , ) for selecting, viewing, and adjusting settings. As you program
button. Once you
Item
Item
button will return
and / or
button
Item
Item
When the
levels.
Additional information can be gained by observing the status field and pointers of the LCD. The status field will indicate which of the
control’s outputs are currently active. Most symbols in the status field are only visible when the VIEW menu is selected.
Item
button is pressed and held in the VIEW menu, the display scrolls through all the control adjust items in both access
Displays the
current status of
the control’s
inputs, outputs
and operation
Symbol Description
Burner
Displays when the boiler relay is turned on.
°
F, °C
°F, °C
Displays the unit of measure that all of the
temperatures are to be displayed in the control.
Return
1030507090
Supply
% Out
Item
Mixing
Demand
Buttons
Selects Menus, Items
{
and adjusts settings
Pointer
Displays the control operation as indicated by
the text.
Sequence of Operation
Section A
General Operation
Page 3-4
Section B
Mixing
Page 4-6
Section C
Boiler Operation
Page 7
Section A — General Operation
POWERING UP THE CONTROL
When the Mixing Control 356 is powered up, the control displays the control type number in the LCD for 2 seconds. Next, the software
version is displayed for 2 seconds. Finally, the control enters into the normal operating mode and the LCD defaults to displaying the
current outdoor air temperature.
The 356 uses a variable speed injection pump to control the supply water temperature to
a hydronic system. The supply water temperature is based on either the current outdoor
temperature, or a fixed setpoint.
Design Supply
Terminal Unit
Outdoor Reset
When the outdoor design (OUTDR DSGN) setting is not set to OFF, the 356 calculates
a mixing supply temperature based on the current outdoor air temperature and the
acterized Heating Curve
Setpoint Control
When the outdoor design (OUTDR DSGN) setting is set to OFF, the 356 supplies a fixed
mixing supply temperature equal to the MIX TARGET setting. An outdoor sensor is not
required during this mode of operation.
VARIABLE SPEED INJECTION
A standard wet rotor circulator is connected to the 356 at the back of the control. The 356
increases or decreases the power output to the circulator when there is a mixing demand.
The circulator speed varies to maintain the correct mixed supply water temperature at the
mix sensor. For correct sizing and piping of the variable speed injection driven circulator,
refer to essay E 021. A visual indication of the current variable speed output is displayed in
the LCD in the form of a horizontal bar graph.
BOILER PROTECTION (BOIL MIN)
The 356 is capable of providing boiler protection from cold mixing system return water temperatures. If the boiler sensor temperature is cooler
than the BOIL MIN setting while the boiler is firing, the 356 reduces the
output to the variable speed injection pump. This limits the amount of
cool return water to the boiler, and allows the boiler temperature to recover. This feature can only be used if a boiler sensor is installed.
EXERCISING
The 356 has a built-in exercising function. If the pump has not been operated at least once every 3 days, the control turns on the
output for 10 seconds. This minimizes the possibility of the pump seizing during a long period of inactivity.
Note:
The exercising function does not work if power to the control or pump is disconnected.
Indoor Design
Char-
settings.
Outdoor Design
Decreasing Outdoor Temperature
Current output of
variable
speed injection pump
3010705090
% Out
Mixing
sensor
Boiler supply
sensor
or
Boiler return
sensor
Increasing Water Temperature
FACTORY DEFAULTS
The control comes preset with several factory defaults. These defaults are based on the terminal unit selection (see section B2). To
fine-tune building requirements, these defaults may be changed. If a factory default value for a terminal unit is changed, the terminal
unit number will flash when selected in the ADJUST menu.
To reload the factory defaults listed in section B2, power down the control and wait for 10 seconds. Power up the control while
simultaneously holding the
than flashing.
Item
and buttons. The terminal unit number should now be displayed constantly in the LCD rather
Section B: Mixing
Section B1
General
Section B2
Installer
Section B3
Advanced
Section B1: General
MIXING DEMAND
A mixing demand is required in order for the 356 to provide heat. A mixing demand is
generated by connecting terminal T(7) to terminal C-(9) through a switching device. Once
the switching device closes, the
calculates a MIX TARGET supply temperature based on the outdoor air temperature and
settings. If required, the 356 operates the boiler in order to provide heat to the variable
speed injection pump.
When used as a mixing reset control, the 356 varies the supply water temperature based on the outdoor air temperature. The control
takes into account the type of terminal unit that the system is using. Since different types of terminal units transfer heat to a space
using different proportions of radiation, convection and conduction, the supply water temperature must be controlled differently. Once
the control is told what type of terminal unit is used, the control loads the factory defaults and varies the supply water temperature
according to the type of terminal unit. This improves the control of the air temperature in the building.
MIXING TARGET TEMPERATURE (MIX TARGET)
When used as a mixing reset control, the MIX TARGET temperature is determined from the
Characterized Heating Curve
settings
and outdoor air temperature. When used as a setpoint control, the installer will set the MIX TARGET temperature. The control displays
the temperature that it is currently trying to maintain as the mixing supply temperature. If the control does not have a mixing demand,
“---” is displayed as the MIX TARGET.
Section B2: Installer
OUTDOOR DESIGN (OUTDR DSGN)
The OUTDR DSGN is the outdoor air temperature that is the typical
coldest temperature of the year where the building is located. This temperature is used when doing the heat loss calculations for the building.
If a cold outdoor design temperature is selected, the mixing supply temperature rises gradually as the outdoor temperature drops. If a warm
outdoor design temperature is selected, the mixing supply temperature
rises rapidly as the outdoor temperature drops.
SETPOINT OPERATION (MIX TARGET)
For setpoint operation, set the OUTDR DSGN to OFF. The MIX TARGET becomes the setpoint supply temperature that the control is to
maintain. The MIX TARGET temperature is set by the installer in the
ADJUST menu. An outdoor sensor is not required during this mode of
operation.
ROOM (ROOM)
The ROOM is the desired room temperature for the mixing zones, and
it provides a parallel shift of the
temperature desired by the occupants is often different from the design
indoor temperature (MIX INDR). If the room temperature is not correct,
adjusting the ROOM setting increases or decreases the amount of heat
available to the building.
Characterized Heating Curve
MIX DSGN
cold
OUTDR
DSGN
warm
Increasing Water Temperature
. The room
Increasing Water Temperature
MIX INDR
Decreasing Outdoor Temperature
.
p
m
e
T
l
a
u
t
c
A
ROOM
MIX INDR
Decreasing Outdoor Temperature
s
e
D
l
a
m
r
o
N
n
g
i
TERMINAL UNITS
When using a
shape of the
Characterized Heating Curve
Characterized Heating Curve
, the control requires the selection of a terminal unit. The terminal unit determines the
according to how the terminal unit delivers heat into the building space (refer to Essay
E 003). The 356 provides for selection between six different terminal unit types: two types of radiant floor heat, fancoil, fin-tube
convector, radiator and baseboard. When a terminal unit is selected, the control automatically loads the design supply temperature
(MIX DSGN) and maximum supply temperature (MIX MAX). The factory defaults are listed below. To change defaults, refer to section
B3. If a default has been changed, refer to section A to reload the factory defaults.
This type of a hydronic radiant floor is embedded in either a thick concrete or gypsum
pour. This heating system has a large thermal mass and is slow acting.
Default values: MIX DSGN = 120°F (49°C), MIX MAX = 140°F (60°C)
Low Mass Radiant (2)
This type of radiant heating system is either attached to the bottom of a wood sub-floor,
suspended in the joist space, or sandwiched between the sub-floor and the surface.
This type of radiant system has a relatively low thermal mass and responds faster than
a high mass system.
Default values: MIX DSGN = 140°F (60°C), MIX MAX = 160°F (71°C)
Fancoil (3)
A fancoil terminal unit or air handling unit (AHU) consists of a hydronic heating coil and
either a fan or blower. Air is forced across the coil at a constant velocity by the fan or
blower, and is then delivered into the building space.
Default values: MIX DSGN = 190°F (88°C), MIX MAX = 210°F (99°C)
Fin–tube Convector (4)
A convector terminal unit is made up of a heating element with fins on it. This type of
terminal unit relies on the natural convection of air across the heating element to deliver
heated air into the space. The amount of natural convection to the space is dependant
on the supply water temperature to the heating element and the room air temperature.
Default values: MIX DSGN = 180°F (82°), MIX MAX = 200°F (93°C)
Radiator (5)
A radiator terminal unit has a large heated surface that is exposed to the room. A radiator
provides heat to the room through radiant heat transfer and natural convection.
Default values: MIX DSGN = 160°F (71°C), MIX MAX = 180°F (82°C)
Baseboard (6)
A baseboard terminal unit is similar to a radiator, but has a low profile and is installed at
the base of the wall. The proportion of heat transferred by radiation from a baseboard is
greater than that from a fin-tube convector.
Default values: MIX DSGN = 150°F (66°C), MIX MAX = 170°F (77°)
Section B3: Advanced
MIXING INDOOR (MIX INDR)
The MIX INDR is the room temperature used in the original heat loss calculations for the building. This setting establishes the
beginning of the
Characterized Heating Curve
MIXING DESIGN (MIX DSGN)
The MIX DSGN temperature is the supply water temperature required to heat the mixing zones when the outdoor air is as cold as the
OUTDR DSGN temperature.
MIXING MAXIMUM (MIX MAX)
The MIX MAX sets the highest water temperature that the control is allowed to calculate as
the MIX TARGET temperature. If the control does target the MIX MAX setting, and the MIX
temperature is near the MIX MAX, the MAX segment will be displayed in the LCD while
either the MIX TARGET temperature or the MIX temperature is being viewed.
WARM WEATHER SHUT DOWN (WWSD)
When the outdoor air temperature rises above the WWSD setting, the 356 turns on the
WWSD segment in the display. When the control is in Warm Weather Shut Down, the
Mixing Demand
operate the heating system to satisfy this demand. If the control is in setpoint mode, the
WWSD feature is not functional.
pointer is displayed, if there is a demand. However, the control does not
When the 356 determines that boiler operation is required, the
closed, the burner segment in the LCD is displayed.
BOILER MINIMUM (BOIL MIN)
Most boilers require a minimum water temperature in order to prevent flue gas condensation. The BOIL MIN adjustment is set to the
boiler manufacturer’s minimum recommended operating temperature. Only when the boiler temperature is measured by a boiler
sensor can the 356 provide boiler protection. In this case, when the boiler is firing and the boiler temperature is below the BOIL MIN
setting, the 356 turns on the MIN segment and reduces the heating load on the boiler by limiting the output of the variable speed
injection pump. If the installed boiler is designed for low temperature operation, set the BOIL MIN adjustment to OFF.
BOILER PROTECTION
Refer to section A for a description of boiler protection.
Boiler
contact terminals (5 and 6) close. While the
Boiler
contact is
Section C2: Boiler Sensor Placement
BOILER SENSOR ON THE SUPPLY (BOIL =
The boiler sensor can be located on the boiler supply if the 356 is the only control that is
operating the boiler. When in the supply mode, the 356 determines the required operating
temperature of the boiler using
the boiler at the lowest possible supply temperature that is sufficient to satisfy the
requirements of the variable speed injection pump. If this mode of operation is selected,
the boiler pump should operate continuously.
Note:
The boiler pump should not be operated by the boiler’s aquastat, as this may lead to
improper cycling of the boiler because of inconsistent flow past the boiler supply sensor.
Boiler Load Reset
BOILER SENSOR ON THE RETURN (BOIL =
The boiler sensor should be located on the boiler return if the 356 is one of many controls
that can call for boiler operation. When in the return mode, the 356 provides a boiler
enable. The 356 no longer tries to control the boiler supply water temperature directly, but
allows the boiler to operate at its operating aquastat setting when required. If this mode of
operation is selected, the boiler pump should operate continuously.
Note:
The boiler pump should not be operated by the boiler’s aquastat, as this may lead to
improper cycling of the boiler because of inconsistent flow past the boiler return sensor.
NO BOILER SENSOR
The 356 is capable of operating without a boiler sensor if desired. Without a boiler sensor
the 356 provides a boiler enable, and is unable to provide boiler protection. This type of
application is typical if the 356 is drawing heat from a heat source that already incorporates some form of boiler protection.
Improper installation and operation of this control could result in damage to the equipment and possibly even personal injury. It is
your responsibility to ensure that this control is safely installed according to all applicable codes and standards. This electronic
control is not intended for use as a primary limit control. Other controls that are intended and certified as safety limits must be placed
into the control circuit.
STEP ONE
Check the contents of this package. If any of the contents listed are missing or damaged, please contact your wholesaler or tekmar
sales representative for assistance.
Type 356 includes:One Mixing Control 356, One Outdoor Sensor 070, Two Universal Sensors 071, Data Brochures D 356,
Note:
STEP TWO
The control is mounted in accordance with the instructions in the Data Brochure D 001.
STEP THREE
The variable speed injection pump wiring terminates in the electrical box. All other wiring terminates in the two wiring chambers on the
control. Determine whether the low voltage wiring enters the wiring chamber through the back or the bottom of the control. The wiring
is roughed-in to the electrical box prior to installation of the control (see Brochure D 001). Standard 18 AWG solid wire is recommended
for all low voltage wiring, and multi-strand 16 AWG wire is recommended for 120 V (ac) wiring.
Power must not be applied to any of the wires during the rough-in wiring stage.
• Install the Outdoor Sensor 070, Boiler Sensor 071, and Mixing Sensor 071 according to the instructions in the Data Brochure
• Run wire from the boiler to the control.
• Run wires from the 24 V (ac) power to the control. Use a clean power source to ensure proper operation.
Carefully read the details of the
D 070, and run the wiring back to the control.
GETTING READY
D 070, D 001, Application Brochure A 356, Essay E 021.
Sequence of Operation
MOUNTING
ROUGH-IN WIRING
to ensure that you have chosen the proper control for your application.
STEP FOUR
No wires should be connected to the control during testing.
The following tests are to be performed using standard testing practices and procedures, and should only be carried out by properly
trained and experienced persons.
A good quality electrical test meter, capable of reading from at least 0 - 300 V (ac) and at least 0 - 2,000,000 Ohms, is essential to
properly test the wiring and sensors.
Test The Sensors
Ensure the sensor wires are not connected to the control terminals before testing. In
order to test the sensors, the actual temperature at each sensor location must be
measured. A good quality digital thermometer with a surface temperature probe is
recommended for ease of use and accuracy. Where a digital thermometer is not available,
a spare sensor can be strapped alongside the one to be tested, and the readings
compared. Test the sensors according to the instructions in the Data Brochure D 070.
TESTING THE WIRING
Ω
Ω
Ω
V
V
Ω
V
Test The Power Supply
Make sure exposed wires and bare terminals are not in contact with other wires or
grounded surfaces. Turn on the power and measure the voltage across the 24 V (ac)
power supply with an AC voltmeter. The reading should be between 22 and 26 V (ac).
Measure the voltage between the mixing demand wire and the power wire that goes
to R+ of the control. The voltmeter should read between 22 and 26 V (ac) when the
mixing demand device calls for heat.
V
Class II
Transformer
24 V (ac)
V
Ω
Mixing demand
switch
C
R
Test The Outputs
Boiler
Make sure power to the boiler circuit is off and short the boiler wires. When the boiler circuit is powered up, the boiler should fire.
If the boiler does not turn on, refer to any installation or troubleshooting information supplied with the boiler. (The boiler may have
a flow switch that prevents firing until the boiler loop pump is running). If the boiler operates properly, remove power from the
boiler circuit.
Variable Speed Injection Pump
Short the variable speed injection pump wires and power up the pump curcuit; the variable speed pump should operate at full
speed. If the pump does not operate, check the wiring, and refer to any installation or troubleshooting information supplied with
the pump. If the pump operates properly, remove the power from the variable speed injection pump circuit.
STEP FIVE
ELECTRICAL CONNECTIONS TO THE CONTROL
The installer should test to confirm that no voltage is present at any of the wires.
Powered Input Connections
8
Power
R+
24 V (ac) Power
Connect the 24 V (ac) power supply to the
9). This connection provides power to the microprocessor and display of the control.
Power R+
and
Power C-
terminals (8 and
24 V (ac)
9
C-
Mixing Demand
To generate a mixing demand, terminal
through a switching device.
terminals (5 and 6) are an isolated output in the 356. There is no power
available on these terminals from the control. These terminals are to be used as a
switch to either make or break the boiler circuit. When the 356 requires the boiler to
fire, it closes the contact between terminals 5 and 6.
Variable Speed Injection Pump
The 356 can vary the speed of a permanent capacitor, impedance
protected, or equivalent pump motor that has a locked rotor current
of less than 2.4 A. Most small wet rotor circulators are suitable as
described in Essay E 021. The 356 has an internal overload protection circuit which is rated at 2.5 A 250 V (ac). Contact your tekmar
sales representative for details on the repair procedures if this circuit is blown.
Connect one of the wires from the variable speed injection pump to
one of the black wires from the back of the control. Connect the
second black wire from the back to the live (L) side of the 120 V
(ac) power source. The other wire on the variable speed injection
pump must be connected to the neutral (N) side of the 120 V (ac)
power supply. Connect the green wire on the back of the control to
ground.
5
6
Boiler
T
T
T
T
to qualified
rvicing
Refer se
pening voids
personnel. O
STOP
warranty.
Pump
(black)
N
Ground
(green)
120 V or L
(black)
Sensor and Unpowered Input Connections
Do not apply power to these terminals as this will damage the control.
Outdoor Sensor
Connect the two wires from the Outdoor Sensor 070 to the
and 3). The outdoor sensor is used by the 356 to measure the outdoor air temperature.
Com
and
Out
terminals (1
Boiler Sensor
Connect the two wires from the Boiler Sensor 071 to the
Boil
terminals (1 and 4). The boiler sensor is used by the 356 to
measure the boiler temperature.
Com
and
Mixing Sensor
Connect the two wires from the Mixing Sensor 071 to the
Sup
terminals (1 and 2). The mixing sensor is used by the 356 to
measure the supply water temperature after the variable speed
injection pump. Normally the sensor is attached to the pipe downstream of the system pump.
Com
and
Com
Com
3
2
1
Sup
Out
Com
4
3
2
1
Sup
Out
Boil
Boiler supply
sensor
or
Boiler return
sensor
1
2
Sup
Mixing
sensor
System
pump
DIP Switch Setting
ADVANCED / INSTALLER
The
Advanced / Installer
available to be viewed and / or adjusted in the user interface.
The quick setup can be used for both outdoor reset and setpoint operation. To enter the installer programming mode, set the
Installer
OUTDOOR RESET
DIP switch to
Installer
.
Access the ADJUST menu by pressing and holding simultaneously for 1 second, the
Item
, and buttons (all three buttons).
The display will now show the word ADJUST in the top right corner.
ROOM
OUTDR
DSGN
ADJUST
°
F
ADJUST
°
F
The ROOM adjustment is the first item displayed. Use the
ROOM setting is set to the desired room air temperature.
Note:
To increase or decrease space temperature, only adjust the ROOM setting.
Press and release the
Item
button to advance to the OUTDR DSGN adjustment. Use the or button to
or button to set the ROOM temperature. The
set the outdoor design temperature. The OUTDR DSGN setting is set to the typical coldest temperature of
the year.
ADJUST
Press and release the
Item
button to advance to the
Terminal Unit
adjustment. Use the or button to select
the desired terminal unit. The terminal unit number corresponds to the type of terminal that is being used.
The table below lists the terminal units and their default values.
Terminal Unit
Terminal Unit
MIX DSGN
MIX MAX
High Mass Radiant
(1)
120°F (49°C)
140°F (60°C)
Low Mass Radiant
(2)
140°F (60°C)
160°F (71°C)
Fancoil
(3)
190°F (88°C)
210°F (99°C)
Fin-tube Convector
(4)
180°F (82°C)
200°F (93°C)
Radiator
(5)
160°F (71°C)
180°F (82°C)
Baseboard
150°F (66°C)
170°F (77°C)
Advanced /
(6)
ADJUST
°
F
Press and release the
Item
button to advance to the units adjustment. Use the or button to set the scale
to °F or °C.
ADJUST
To exit the ADJUST menu, press and release the
Item
the or button, or leave the buttons alone for 20 seconds.
SETPOINT CONTROL
Access the ADJUST menu by pressing and holding simultaneously for 1 second, the
The display will now show the word ADJUST in the top right corner.
OUTDR
DSGN
ADJUST
Press and release the
Item
button to advance to the OUTDR DSGN adjustment. Press and hold the button
until OFF is displayed.
ADJUST
°
F
ADJUST
°
F
Item
Press and release the
button to advance to the MIX TARGET adjustment. Use the or button to select
the desired temperature. The MIX TARGET setting is set to the desired setpoint supply temperature.
Item
Press and release the
button to advance to the units adjustment. Use the or button to set the scale
MIX
TARGET
to °F or °C.
button to advance to the ESC item. Then either press
Item
, and buttons (all three buttons).
ADJUST
To exit the ADJUST menu, press and release the
Item
button to advance to the ESC item. Then either press
the or button, or leave the buttons alone for 20 seconds..
The Mixing Control 356 has a built-in test routine which is used to test the main control functions. The 356 continually monitors the
sensors and displays an error message whenever a fault is found. See the following pages for a list of the 356’s error messages and
possible causes.
Quick Test
Press and hold the button, the Boiler relay closes and the variiable speed injection pump turns on to 100% of its output speed.
Once the button is released, the output relays return to normal operation.
Troubleshooting
When troubleshooting any heating system, it is always a good idea to establish a set routine to follow. By following a consistent
routine, many hours of potential headaches can be avoided. Below is an example of a sequence that can be used when diagnosing or
troubleshooting problems in a hydronic heating system.
Establish the
Problem
Understand the
Sequence of
Operation
Sketch the
Piping in the
System
Document the
Control
Establish the problem. Get as much information from the customer as possible about the problem. Is there
too much heat, not enough heat, or no heat? Is the problem only in one particular zone or area of the building,
or does the problem affect the entire system? Is this a consistent problem or only intermittent? How long has
the problem existed for? This information is critical in correctly diagnosing the problem.
Understand the sequence of operation of the system. If a particular zone is not receiving enough heat, which
pumps or valves in the system must operate in order to deliver heat to the affected zone? If the zone is
receiving too much heat, which pumps, valves, or check valves must operate in order to stop the delivery
of heat?
Sketch the piping of the system. This is a relatively simple step that tends to be overlooked, however, it can
often save hours of time in troubleshooting a system. Note flow directions in the system paying close
attention to the location of pumps, check valves, pressure bypass valves, and mixing valves. Ensure correct
flow direction on all pumps. This is also a very useful step if additional assistance is required.
Document the control for future reference. Before making any adjustments to the control, note down all of
the items that the control is currently displaying. This includes items such as error messages, current
temperatures and settings, and which devices should be operating as indicated by the LCD. This information
is an essential step if additional assistance is required to diagnose the problem.
Isolate the problem between the control and the system. Now that the sequence of operation is known and
the system is sketched, is the control operating the proper pumps and valves at the correct times? Is the
control receiving the correct signals from the system as to when it should be operating? Are the proper
items selected in the menus of the control for the device that is to be operated?
Test the contacts, voltages and sensors. Using a multimeter, ensure that the control is receiving adequate
voltage to the power terminals and the demand terminals as noted in the technical data. Use the multimeter
to determine if the internal contacts on the control are opening and closing correctly. Follow the instrutions
in the Testing the Wiring section to simulate closed contacts on the terminal blocks as required. Test the
sensors and their wiring as described in the sensor Data Brochures.
Error Messages
OUTDR
OUTDR
MIX
MIX
VIEW
VIEW
VIEW
VIEW
VIEW
The control was unable to read a piece of information from its EEPROM. This error can be caused by a
noisy power source. The control will load the factory defaults and stop operation until all the settings are
verified.
The control is no longer able to read the outdoor sensor due to a short circuit. In this case the control
assumes an outdoor temperature of 32°F (0°C) and continues operation. Locate and repair the problem as
described in the Data Brochure D 070. To clear the error message from the control after the sensor has
been repaired, press the
Item
button.
The control is no longer able to read the outdoor sensor due to an open circuit. In this case the control
assumes an outdoor temperature of 32°F (0°C) and continues operation. Locate and repair the problem as
described in the Data Brochure D 070. To clear the error message from the control after the sensor has
been repaired, press the
Item
button.
The control is no longer able to read the mixing supply sensor due to a short circuit. In this case the control
will operate the injection pump at a fixed output as long as there is a mixing demand. Locate and repair the
problem as described in the Data Brochure D 070. To clear the error message from the control after the
sensor has been repaired, press the
Item
button.
The control is no longer able to read the mixing supply sensor due to an open circuit. In this case the control
will operate the injection pump at a fixed output as long as there is a mixing demand. Locate and repair the
problem as described in the Data Brochure D 070. To clear the error message from the control after the
sensor has been repaired, press the
Item
button.
BOIL
BOIL
VIEW
VIEW
The control is no longer able to read the boiler sensor due to a short circuit. If the BOIL MIN adjustment is
higher than 100°F (38°C), the control closes the
Boiler
contact when the injection pump starts to operate.
The boiler temperature is limited by the operating aquastat. If the BOIL MIN adjustment is lower than 100°F
(38°C), the control does not operate the
Boiler
contact. Locate and repair the problem as described in the
Data Brochure D 070. To clear the error message from the control after the sensor has been repaired,
press the
Item
button.
The control is no longer able to read the boiler sensor due to an open circuit. If the BOIL MIN adjustment is
higher than 100°F (38°C), the control closes the
Boiler
contact when the injection pump starts to operate.
The boiler temperature is limited by the operating aquastat. If the BOIL MIN adjustment is lower than 100°F
(38°C), the control does not operate the
Boiler
contact. Locate and repair the problem as described in the
Data Brochure D 070. If the boiler sensor is deliberately removed, the control must be powered down, and
then powered back up. To clear the error message from the control after the sensor has been repaired,
press the
Literature— D 356, A 356’s, D 001, D 070, E 021.
Control— Microprocessor PID control; This is not a safety (limit) control.
Packaged weight— 1.5 lb. (670 g), Enclosure C, white PVC plastic
Dimensions— 4-3/4” H x 2-7/8” W x 7/8” D (120 x 74 x 22 mm)
Approvals—
Ambient conditions— Indoor use only, 32 to 104° F (0 to 40°C), < 90% RH nonPower supply—
Var. Pump— 120 V (ac) 2.4 A 1/6 hp, fuse T2.5 A 250 V
Relays— 120 V (ac) 5 A 1/6 hp
Mixing demand— 24 V (ac) 2 VA
Sensors included— NTC thermistor, 10 kΩ @ 77°F (25°C ±0.2° C) ß=3892
Optional devices— tekmar Timer 032.
Variable Speed
CSA C US, CSA 22.2 No 24 and UL 873, meets class B: ICES & FCC Part 15.
condensing.
24 V (ac) ±10%, 50/60 Hz, 3 VA
Outdoor Sensor 070 and 2 of Universal Sensor 071.
tektra 911-02
Meets Class B:
Canadian ICES
FCC Part 15
The installer must ensure that this control and its wiring are isolated and/or shielded from strong sources of electromagnetic noise.
Conversely, this Class B digital apparatus complies with Part 15 of the FCC Rules and meets all requirements of the Canadian
Interference-Causing Equipment Regulations. However, if this control does cause harmful interference to radio or television reception,
which is determined by turning the control off and on, the user is encouraged to try to correct the interference by reorienting or relocating
the receiving antenna, relocating the receiver with respect to this control, and/or connecting the control to a different circuit from that
to which the receiver is connected.
Cet appareil numérique de la classe B respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
Caution The nonmetallic enclosure does not provide grounding between conduit connections. Use grounding type bushings and
jumper wires.
Attention Un boîtier nonmétallique n’assure pas la continuité électrique des conduits. Utiliser des manchons ou des fils de accord
spécialement conçus pour la mise á la terre.
Limited Warranty and Product Return Procedure
Limited Warranty The liability of tekmar Control Systems Ltd. and tekmar
Control Systems, Inc. (“tekmar”) under this warranty is limited. The purchaser,
by taking receipt of the tekmar product (“product”), acknowledges receipt of
the terms of the warranty and acknowledges that it has read and
understands same.
tekmar warrants each tekmar product against defects in workmanship and materials, if the product is installed and used in compliance with tekmar's instructions. The
warranty period is for a period of twenty-four (24) months from the production date
if the product is not installed during that period, or twelve (12) months from the
documented date of installation if installed within twenty-four (24) months from the
production date.
The liability of tekmar under this warranty shall be limited to, at tekmar's sole discretion: the cost of parts and labor provided by tekmar to repair defects in materials
and/or workmanship of the defective product; or to the exchange of the defective
product for a replacement product; or to the granting of credit limited to the original
cost of the defective product, and such repair, exchange or credit shall be the sole
remedy available from tekmar, and, without limiting the foregoing in any way,
tekmar is not responsible, in contract, tort or strict product liability, for any
other losses, costs, expenses, inconveniences, or damages, whether direct, indirect, special, secondary, incidental or consequential, arising from ownership or use
of the product, or from defects in workmanship or materials, including any liability
for fundamental breach of contract.
This warranty applies only to those products returned to tekmar during the
warranty period. This warranty does not cover the cost of the parts or labor
to remove or transport the defective product, or to reinstall the repaired or
replacement product. Returned products that are not defective are not covered by this warranty.
This warranty does not apply if the product has been damaged by negligence
by persons other than tekmar, accident, fire, Act of God, abuse or misuse; or
has been damaged by modifications, alterations or attachments made subsequent to purchase which have not been authorized by tekmar; or if the
product was not installed in compliance with tekmar’s instructions and the
local codes and ordinances; or if due to defective installation of the product;
or if the product was not used in compliance with tekmar’s instructions.
This warranty is in lieu of all other warranties, express or implied, which the
Governing Law (being the law of British Columbia) allows parties to contractually exclude, including, without limitation, warranties of merchantability,
fitness for a particular purpose, durability or description of the product, its
non-infringement of any relevant patents or trademarks, and its compliance
with or non-violation of any applicable environmental, health or safety legislation; the term of any other warranty not hereby contractually excluded is
limited such that it shall not extend beyond twenty-four (24) months from the
production date, to the extent that such limitation is allowed by the Governing Law.
Product Return Procedure Products that are believed to have defects in work-
manship or materials must be returned, together with a written description of the
defect, to the tekmar representative for that territory. If the address of the representative is not known, please request it from tekmar at the telephone number
listed below
.
tekmar Control Systems Ltd., Canada
Control Systems
tekmar Control Systems, Inc., U.S.A.
Head Office: 5100 Silver Star Road
Vernon, B.C. Canada V1B 3K4
Tel. (250) 545-7749 Fax. (250) 545-0650
Web Site: www.tekmarcontrols.com