Mitsubishi PMH-P1BA, PMH-P1.6BA, PMH-P2BA, PMH-P1BA1, PMH-P1.6BA1 Service Manual

...
0 (0)
TECHNICAL & SERVICE MANUAL
SPLIT-TYPE, HEAT PUMP AIR CONDITIONERS
CONTENTS
1. TECHNICAL CANGES········································2
2. COMBINA TION OF INDOOR AND OUTDOOR UNITS ···3
3. SAFETY PRECAUTION······································3
4. PART NAMES AND FUNCTIONS·······················5
5. SPECIFICATIONS·············································10
7. OUTLINES AND DIMENSIONS························29
8.
WIRING DIAGRAM
···············································30
9.
REFRIGERANT SYSTEM DIAGRAM
·····················31
10. TROUBLE SHOOTING ·····································32
11. DISASSEMBLY PROCEDURE··························35
12. PARTS LIST ······················································38
13. OPTIONAL PARTS············································41
Indoor unit
[Model names] [Service Ref.]
No. OC238
REVISED EDITION-B
2001
• PMH-P1BA1,PMH-P1.6BA1,PMH-P2BA1
are added in REVISED EDITION-B.
• Please void OC238.REVISED EDI-
TION-A.
• Refer to the OCT03 REVISED EDI-
TION-C as regarding control
relation.This manual does not cover
outdoor units. When servicing them,
please refer to the service manual
No.OC180 REVISED EDITION-A,
OC261 and this manual in a set.
[Service Ref.]
<OC180 REVISED EDITION-A>
PUH-P1.6VGA
PUH-P1.6YGA
PUH-P2VGA
PUH-P2YGA
<OC261>
PUH-P1VGAA.UK
PUH-P1.6VGAA.UK
PUH-P1.6YGAA.UK
PUH-P2VGAA.UK
PUH-P2YGAA.UK
INDOOR UNIT
Ceiling Cassettes
Series PMH
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN
FUNCTION
1Hr.
NOT AVAILABLE
STAND BY
DEFROST
TEMP.
R407C
FILTER
CHECK MODE
TEST RUN
PMH-P1BA PMH-P1BA
PMH-P1BA
1
PMH-P1.6BA PMH-P1.6BA
PMH-P1.6BA
1
PMH-P2BA PMH-P2BA
PMH-P2BA
1
REMOTE CONTROLLER
PMH- P1,1.6,2BA
PMH- P1,1.6,2BA
1
2
1
TECHNICAL CHANGES
PMH-P1BA PMH-P1BA1 PMH-P1.6BA PMH-P1.6BA1
PMH-P2BA PMH-P2BA1
Outdoor units which are connected to PMH-P•BA and PMH-P•BA1 have been added.
The parts No. of REMOTE CONTROLLER has changed. (The following parts numbers are interchangeable.)
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN
FUNCTION
1Hr.
NOT AVAILABLE
STAND BY
DEFROST
TEMP.
FILTER
CHECK MODE
TEST RUN
[T7W E00 713]
[T7W E06 713]
3
SAFETY PRECAUTION
3
2
COMBINATION OF INDOOR AND OUTDOOR UNITS
Cautions for using with the outdoor unit which adopts R407C refrigerant.
· Do not use the existing refrigerant piping.
-The old refrigerant and lubricant in the existing piping contains a large amount of chlorine which may cause the lubricant of
the new unit to deteriorate.
· Do not use copper pipes which are broken, deformed or discolour .
In addition, be sure that the inner surfaces of the pipes are clean, free of hazardous sulphur and oxides, or have no dust /
dirt, shaving particles, oils, moisture or any other contamination.
-If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the lubricant will
result.
· Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before
brazing. (Store elbows and other joints in a plastic bag.)
-If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.
· Use ester oil, ether oil or alkyl benzene (small amount) as the lubricant to coat flares and flange connections.
-The lubricant will degrade if it is mixed with a large amount of mineral oil.
Use liquid refrigerant to fill the system.
-If gas refrigerant is used to fill the system, the composition of the refrigerant in the cylinder will change and performance
may drop.
· Do not use a refrigerant other than R407C.
-If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the lubricant to deteriorate.
· Use a vacuum pump with a reverse flow check valve.
-The vacuum pump oil may flow back into the refrigerant cycle and cause the lubricant to deteriorate.
· Do not use the following tools that are used with conventional refrigerant.
(Gauge manifold , charge hose, gas leak detector, reverse flow check valve, refrigerant charge base, vacuum gauge,
refrigerant recovery equipment)
-If the conventional refrigerant and lubricant are mixed in the R407C, the refrigerant may deteriorated.
-If water is mixed in the R407C, the lubricant may deteriorate.
-Since R407C does not contain any chlorine, gas leak detectors for conventional refrigerant will not react to it.
· Do not use a charging cylinder.
-Using a charging cylinder may cause the refrigerant to deteriorate.
· Be especially careful when managing the tools.
-if dust, dirt, or water gets in the refrigerant cycle, the refrigerant may deteriorate.
· Do not use the drier which is sold in the field.
-The drier for R407C refrigerant is per-attached to outdoor unit refrigerant circuit.
-Some drier in the field are not in conformity with R407C refrigerant .
Outdoor unit
PUH-P
PMH-P1BA
PMH-P1.6BA
PMH-P2BA
PMH-P1BA1
PMH-P1.6BA1
PMH-P2BA1
Indoor unit
1.6VGA
1VGAA.UK
1.6YGAA.UK
1.6VGAA.UK
2YGAA.UK
2VGAA.UK
1.6YGA
2VGA
2YGA
4
[3] Refrigerant recharging
(1) Refrigerant recharging process
1Direct charging from the cylinder.
·R407C cylinder are available on the market has a syphon pipe.
·Leave the syphon pipe cylinder standing and recharge it.
(By liquid refrigerant)
(2) Recharge in refrigerant leakage case
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release the refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
Gravimeter
Unit
[1] Service tools
Use the below service tools as exclusive tools for R407C refrigerant.
No. Tool name Specifications
1
Gauge manifold ·Only for R407C.
·Use the existing fitting SPECIFICATIONS. (UNF7/16)
·Use high-tension side pressure of 3.43MPa·G or over.
2
Charge hose ·Only for R407C.
·Use pressure performance of 5.10MPa·G or over.
3
Electronic scale
4
Gas leak detector ·Use the detector for R407C.
5
Adapter for reverse flow check. ·Attach on vacuum pump.
6
Refrigerant charge base.
7
Refrigerant cylinder. ·For R407C ·Top of cylinder (Brown)
·Cylinder with syphon
8
Refrigerant recovery equipment.
[2] Notice on repair service
·After recovering the all refrigerant in the unit, proceed to working.
·Do not release refrigerant in the air.
·After completing the repair service, recharge the cycle with the specified amount of
liquid refrigerant.
5
4
PART NAMES AND FUNCTIONS
Indoor (Main) Unit
PMH-P1BA, PMH-P1BA1
PMH-P1.6BA, PMH-P1.6BA1
PMH-P2BA, PMH-P2BA1
Guide vane
Air flow can be changed to horinzontally
by moving the Guide vane to the left or right.
Air intake
Inhales air from room.
Filters
Remove dust and pollutants
from inhaled air.
Auto Air Swing Vane
Disperses airflow up and
down and adjusts the angle
of airflow direction.
Horizontal Air Outlet
6
TIMER button
Remote controller
Operation buttons
Once the controls are set, the same operation mode can
be repeated by simply pressing the ON/OFF button.
This switches between
continuous operation and
the timer operation.
This sets the fan speed.
AIR SPEED button
Press this button to
switch the cooler elec-
tronic dry (dehumidify)
automatic and heater
modes.
OPERATION SWITCH
button
This sets the room tempera-
ture The temperature setting
can be performed in 1°C
units
Setting range
Cooler 19°C to 30°C
Heater 17°C to 28°C
TEMP. ADJUSTMENT
button
This sets of switches the
current time. start time and
stop time.
TIME SETTING button
(This button does not
operate in this model)
This switches the hori-
zontal fan motion ON
and OFF.
LOUVER button
This switches between the
operation and stop modes
each time it is pressed. The
lamp on this button lights dur-
ing operation.
ON/OFF button
This adjusts the vertical angle
of the ventilation.
AIR DIRECTION button
Only press this button to per-
form an inspection check or
test operation Do not use it
for normal operation.
CHECK-TEST RUN button
This resets the filter cleaning
indication display.
FILTER button
This sets the ventilation fan
speed.
VENTILA TION button
This adjust the current time, start
time and stop time.
TIMER ADJUSTMENT button
PMH-P1BA
PMH-P1.6BA
PMH-P2BA
7
Caution
Only the Power display lights when the unit is stopped and power supplied to the unit.
When power is turned ON for the first time the (CENTRAL CTRL) display appears to go off momentarily but this is not a
malfunction.
When the central control remote control unit, which is sold separately, is used the ON-OFF button, operation switch button
and TEMP. adjustment button do not operate.
“NOT AVAILABLE” is displayed when the Air speed button are pressed.This indicates that this room unit is not equipped
with the fan direction adjustment function and the louver function.
When power is turned ON for the first time, it is normal that “H0” is displayed on the room temperature indication (For max.
2minutes). Please wait until this “H0” indication disappear then start the operation.
CENTRALLY
CONTROLLED display
This indicates when the unit is con-
trolled by optional features such as
central control type remote controller.
TIMER display
This indicates when the continuous
operation and time operation modes
are set.
It also display the time for the timer
operation at the same time as when
it is set.
OPERATION MODE display
This indicates the operation mode.
STANDBY display
This indicates when the standby
mode is set from the time the sleep
operation starts until the heating air
is discharged.
DEFROST display
This indicates when the defrost oper-
ation is performed.
CHECK display
This indicates when a malfunction
has occurred in the unit which should
be checked.
CLOCK display
The current time , start time and stop
time can be displayed in ten second
intervals by pressing the time switch
button. The start time or stop time is
always displayed during the timer
operation.
Display
In this display example on the bot-
tom left, a condition where all dis-
play lamps light is shown for expla-
nation purposes although this differs
from actual operation.
Operation lamp
This lamp lights during operation,
goes off when the unit stops and
flashes when a malfunction occurs.
POWER display
This lamp lights when electricity is
supplied to the unit.
SET TEMPERATURE display
This displays the selected setting
temperature.
FAN SPEED display
The selected fan speed is displayed.
ROOM TEMPERATURE display
The temperature of the suction air is
displayed during operation. The dis-
play range is 8° to 39°C. The display
flashes 8°C when the actual temper-
ature is less than 8° and flashes
39°C when the actual temperature is
greater than 39°C.
display
This display lights in the check mode
or when a test operation is per-
formed.
CHECK MODE
TEST RUN
FILTER display
This lamp lights when the filter need
to be cleaned.
AIR DIRECTION display
This displays the air direction.
8
Remote controller
Once the controls are set, the same operation mode can
be repeated by simply pressing the ON/OFF button.
PMH-P1BA1
PMH-P1.6BA1
PMH-P2BA1
Operation buttons
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN
FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY
DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
Press this button to switch the cooler,
electronic dry (dehumidify), automatic
and heater modes.
OPERATION SWITCH button
This sets the room temperature. The
temperature setting can be performed
in 1: units
Setting range
Cooler 19: to 30:
Heater 17: to 28:
TEMP. ADJUSTMENT button
This switches between continuous
operation and the timer operation.
TIMER button
This switches between the operation
and stop modes each time it is pressed.
The lamp on this button lights during
operation.
ON/OFF button
Only press this button to perform an
inspection check or test operation.
Do not use it for normal operation.
CHECK-TEST RUN button
This sets the ventilation fan speed.
VENTILATION button
This switch the horizontal fan motion
ON and OFF.
(Not available for this model.)
LOUVER button
This adjusts the vertical angle of the
ventilation.
AIR DIRECTION button
This resets the filter service indication
display
FILTER button
This sets the current time, start time
and stop time.
TIME SETTING button
This sets the ventilation fan speed.
AIR SPEED button
9
PAR-20MAA
ON/OFF
CENTRALLY CONTROLLED
ERROR CODE
CLOCK
ON OFF
˚C
CHECK
CHECK MODE
FILTER
TEST RUN
FUNCTION
˚C
1Hr.
NOT AVAILABLE
STAND BY
DEFROST
FILTER
CHECK TEST
TEMP.
TIMER SET
Caution
Only the Power display lights when the unit is stopped and power supplied to the unit.
When the central control remote control unit, which is sold separately, is used the ON-OFF button, operation switch button
and TEMP. adjustment button do not operate.
“NOT AVAILABLE” is displayed when the Air speed button are pressed.This indicates that this room unit is not equipped
with the fan direction adjustment function and the louver function.
When power is turned ON for the first time, it is normal that “H0” is displayed on the room temperature indication (For max.
2minutes). Please wait until this “H0” indication disappear then start the operation.
CENTRALLY
CONTROLLED display
This indicates when the unit is con-
trolled by optional features such as
central control type remote
controller.
TIMER display
This indicates when the continuous
operation and time operation modes
are set.
It also display the time for the timer
operation at the same time as when
it is set.
OPERATION MODE display
This indicates the operation mode.
STANDBY display
The [STANDBY] symbol is only dis-
played from the time the heating
operation starts unit the heated air
begins to blow.
DEFROST display
This indicates when the defrost
operation is performed.
CHECK display
This indicates when a malfunction
has occurred in the unit which should
be checked.
CLOCK display
The current time , start time and stop
time can be displayed in ten second
intervals by pressing the time switch
button. The start time or stop time is
always displayed during the timer
operation.
Display
In this display example on the bot-
tom left, a condition where all dis-
play lamps light is shown for expla-
nation purposes although this differs
from actual operation.
Operation lamp
This lamp lights during operation,
goes off when the unit stops and
flashes when a malfunction occurs.
POWER display
This lamp lights when electricity is
supplied to the unit.
SET TEMPERATURE display
This displays the selected setting
temperature.
AIR DIRECTION display
This displays the air direction.
ROOM TEMPERATURE display
The temperature of the suction air
is displayed during operation. The
display range is 8°C to 39°C. The
display flashes 8°C when the actual
temperature is less than 8°C and
flashes 39°C when the actual tem-
perature is greater than 39°C.
display
This display lights in the check
mode or when a test operation is
performed.
CHECK MODE
TEST RUN
This lamp lights when the filter need
to be cleaned.
AIR SPEED display
The selected fan speed is displayed.
FILTER display
10
Service Ref.
Item
Btu/h
W
kW
kW
A
A
kW
K/min(CFM)
Pa(mmAq)
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
A
A
kW
W
kW
K
/min(CFM
)
dB
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
L
mm(in.)
mm(in.)
Function
Capacity
Total input
Service Ref.
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
Airflow(Lo - Mi2- Mi1 - Hi)
External static pressure
Operation control & Thermostat
Noise level(Lo - Mi2 - Mi1 - Hi)
Unit drain pipe I.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
INDOOR UNITOUTDOOR UNIT
REFRIGERANT PIPING
PMH-P1.6BA
Cooling
15,000
4,400
1.65
0.06
0.29
0.32
36
RE277VHSM
w1
Heating
17,100
5,000
1.70
0.06
0.29
0.32
20
RE277YFKM
w2
W
D
H
Cooling
Heating
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
PMH-P1.6BA
Single Phase, 50Hz, 220-230-240V
Unit : Galvanized sheets with gray heat insulation, Grille munsell 0.98Y 8.99/0.63
Plate fin coil
Lineflow fan (direct) x 1
0.028
7.0-8.0-9.0-10.0(247-282-318-353)
0(direct blow)
Remote controller & built-in
34-36-38-40
26(1)
Munsell 5Y 8/1
Linear Expansion Valve
Hermetic
1.3
Line start
28
Plate fin coil
Propeller (direct) x 1
0.070
45(1,590)
Reverse cycle
46
48
900(35-7/16)
330+20(13+3/4)
650(25-5/8)
55(121)
R407C
2.6(5.7)
1.2(Ester)MEL56
9.52(3/8)
15.88(5/8)
Flared
Flared
Max. 40m
Max. 40m
Notes1. Rating Conditions (ISO T1)
Cooling····Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating
····Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Lower limit
Indoor
D.B. 35˚C W.B. 22.5˚C
D.B. 19˚C W.B. 15˚C
D.B. 28˚C
D.B. 17˚C
Outdoor
D.B. 46˚C
D.B. -5˚C
D.B. 24˚C W.B. 18˚C
D.B. -11˚C W.B. -12˚C
Cooling
Heating
UNIT : 854(33-5/8) PANEL : 1000(39-3/8)
UNIT : 395(15-9/16) PANEL : 470(18-1/2)
UNIT : 230(9-1/16) PANEL : 30(1-3/16)
UNIT : 14(31) PANEL : 3.0(6.6)
PUH-P1.6VGA PUH-P1.6YGA PUH-P1.6VGA PUH-P1.6YGA
Single Phase, 50Hz,
220-230-240V
7.66
3 phase, 50Hz,
380-400-415V(4wires)
2.67
Single Phase, 50Hz,
220-230-240V
8.19
3 phase, 50Hz,
380-400-415V(4wires)
2.86
w1: Inner thermostat, HP switch, Discharge thermo.
w2: Thermal relay, Discharge thermo, HP switch, Anti-phase protector.
3. Above data based on indicated voltage
Indoor Unit Single phase 240V 50Hz
Outdoor Unit Single phase 240V 50Hz
3 phase 415V 50Hz
SPECIFICATIONS5
5-1. SPECIFICATIONS
11
Service Ref.
Item
Btu/h
W
kW
kW
A
A
kW
K/min(CFM)
Pa(mmAq)
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
A
A
kW
W
kW
K
/min(CFM
)
dB
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
L
mm(in.)
mm(in.)
Function
Capacity
Total input
Service Ref.
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
Airflow(Lo - Mi2 - Mi1 - Hi)
External static pressure
Operation control & Thermostat
Noise level(Lo - Mi2 - Mi1 - Hi)
Unit drain pipe I.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
INDOOR UNITOUTDOOR UNIT
REFRIGERANT PIPING
PMH-P2BA
Cooling
18,400
5,400
2.35
0.06
0.29
0.32
74
NE38VMJM
w1
Heating
21,300
6,250
2.42
0.06
0.29
0.32
30
NE38YEJM
w2
W
D
H
Cooling
Heating
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
PMH-P2BA
Single Phase, 50Hz, 220-230-240V
Unit : Galvanized sheets with gray heat insulation, Grille munsell 0.98Y 8.99/0.63
Plate fin coil
Lineflow fan (direct) x 1
0.028
8.0-9.0-10.0-11.0(282-318-353-388)
0(direct blow)
Remote controller & built-in
36-38-40-42
26(1)
Munsell 5Y 8/1
Linear Expansion Valve
Hermetic
1.7
Line start
35
Plate fin coil
Propeller (direct) x 1
0.070
55(1,940)
Reverse cycle
48
49
900(35-7/16)
330+20(13+3/4)
855(33-5/8)
71(157)
R407C
3.1(6.8)
1.2(Ester)MEL56
9.52(3/8)
15.88(5/8)
Flared
Flared
Max. 40m
Max. 40m
Notes1. Rating Conditions (ISO T1)
Cooling····Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating
····Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Lower limit
Indoor
D.B. 35˚C W.B. 22.5˚C
D.B. 19˚C W.B. 15˚C
D.B. 28˚C
D.B. 17˚C
Outdoor
D.B. 46˚C
D.B. -5˚C
D.B. 24˚C W.B. 18˚C
D.B. -11˚C W.B. -12˚C
Cooling
Heating
UNIT : 854(33-5/8) PANEL : 1000(39-3/8)
UNIT : 395(15-9/16) PANEL : 470(18-1/2)
UNIT : 230(9-1/16) PANEL : 30(1-3/16)
UNIT : 14(31) PANEL : 3.0(6.6)
PUH-P2VGA PUH-P2YGA PUH-P2VGA PUH-P2YGA
Single Phase, 50Hz,
220-230-240V
11.11
3 phase, 50Hz,
380-400-415V(4wires)
3.88
Single Phase, 50Hz,
220-230-240V
11.51
3 phase, 50Hz,
380-400-415V(4wires)
4.02
w1: Inner thermostat, HP switch, Discharge thermo.
w2: Thermal relay, Discharge thermo, HP switch, Anti-phase protector.
3. Above data based on indicated voltage
Indoor Unit Single phase 240V 50Hz
Outdoor Unit Single phase 240V 50Hz
3 phase 415V 50Hz
12
Service Ref.
Item
Btu/h
W
kW
kW
A
A
kW
K/min(CFM)
Pa(mmAq)
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
A
A
kW
W
kW
K
/min(CFM
)
dB
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
L
mm(in.)
mm(in.)
Function
Capacity
Total input
Service Ref.
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
Airflow(Lo - Mi2 - Mi1 - Hi)
External static pressure
Operation control & Thermostat
Noise level(Lo - Mi2 - Mi1 - Hi)
Unit drain pipe I.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
INDOOR UNITOUTDOOR UNIT
REFRIGERANT PIPING
PMH-P1BA / PMH-P1BA1
Cooling
10,700
3,150
1.15
0.04
0.19
0.21
4.92
Heating
11,600
3,400
1.06
0.04
0.19
0.21
4.52
W
D
H
Cooling
Heating
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
PMH-P1BA / PMH-P1BA
1
Single Phase, 50Hz, 220-230-240V
Unit : Galvanized sheets with gray heat insulation, Grille munsell 0.98Y 8.99/0.63
Plate fin coil
Lineflow fan (direct) x 1
0.028
6.3-6.8-7.6-8.4(222-240-268-297)
0(direct blow)
Remote controller & built-in
29-31-33-35
26(1)
PUH-P1VGAA.UK
Single Phase, 50Hz,
220-230-240V
30
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
RE189VHSMT
0.85
Line start
Inner thermostat, HP switch, Discharge thermo.
30
Plate fin coil
Propeller (direct) x 1
0.070
45(1,590)
Reverse cycle
46
48
900(35-7/16)
330+20(13+3/4)
650(25-5/8)
50(110)
R407C
1.7(3.7)
0.57(Ester)MEL56
6.35(1/4)
12.7(1/2)
Flared
Flared
Max. 30m
Max. 30m
Notes1. Rating Conditions (ISO T1)
Cooling····Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating
····Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Lower limit
Indoor
D.B. 35˚C W.B. 22.5˚C
D.B. 19˚C W.B. 15˚C
D.B. 28˚C
D.B. 17˚C
Outdoor
D.B. 46˚C
D.B. -5˚C
D.B. 24˚C W.B. 18˚C
D.B. -11˚C W.B. -12˚C
Cooling
Heating
UNIT : 854(33-5/8) PANEL : 1000(39-3/8)
UNIT : 395(15-9/16) PANEL : 470(18-1/2)
UNIT : 230(9-1/16) PANEL : 30(1-3/16)
UNIT : 14(31) PANEL : 3.0(6.6)
3. Above data based on indicated voltage
Indoor Unit Single phase 240V 50Hz
Outdoor Unit Single phase 240V 50Hz
13
Service Ref.
Item
Btu/h
W
kW
kW
A
A
kW
K/min(CFM)
Pa(mmAq)
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
A
A
kW
W
kW
K
/min(CFM
)
dB
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
L
mm(in.)
mm(in.)
Function
Capacity
Total input
Service Ref.
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
Airflow(Lo - Mi2- Mi1 - Hi)
External static pressure
Operation control & Thermostat
Noise level(Lo - Mi2 - Mi1 - Hi)
Unit drain pipe I.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
INDOOR UNITOUTDOOR UNIT
REFRIGERANT PIPING
PMH-P1.6BA / PMH-P1.6BA1
Cooling
15,000
4,400
1.65
0.06
0.29
0.32
36
RE277VHSMT
w1
Heating
17,100
5,000
1.70
0.06
0.29
0.32
20
RE277YFKM
w2
W
D
H
Cooling
Heating
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
PMH-P1.6BA / PMH-P1.6BA
1
Single Phase, 50Hz, 220-230-240V
Unit : Galvanized sheets with gray heat insulation, Grille munsell 0.98Y 8.99/0.63
Plate fin coil
Lineflow fan (direct) x 1
0.028
7.0-8.0-9.0-10.0(247-282-318-353)
0(direct blow)
Remote controller & built-in
34-36-38-40
26(1)
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
1.3
Line start
30
Plate fin coil
Propeller (direct) x 1
0.070
45(1,590)
Reverse cycle
47
49
900(35-7/16)
330+20(13+3/4)
650(25-5/8)
54(119)
R407C
2.5(5.5)
0.57(Ester)MEL56
9.52(3/8)
15.88(5/8)
Flared
Flared
Max. 40m
Max. 40m
Notes1. Rating Conditions (ISO T1)
Cooling····Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating
····Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Lower limit
Indoor
D.B. 35˚C W.B. 22.5˚C
D.B. 19˚C W.B. 15˚C
D.B. 28˚C
D.B. 17˚C
Outdoor
D.B. 46˚C
D.B. -5˚C
D.B. 24˚C W.B. 18˚C
D.B. -11˚C W.B. -12˚C
Cooling
Heating
UNIT : 854(33-5/8) PANEL : 1000(39-3/8)
UNIT : 395(15-9/16) PANEL : 470(18-1/2)
UNIT : 230(9-1/16) PANEL : 30(1-3/16)
UNIT : 14(31) PANEL : 3.0(6.6)
PUH-P1.6VGAA.UK PUH-P1.6YGAA.UK PUH-P1.6VGAA.UK PUH-P1.6YGAA.UK
Single Phase, 50Hz,
220-230-240V
7.36
3 phase, 50Hz,
380-400-415V(4wires)
2.49
Single Phase, 50Hz,
220-230-240V
7.59
3 phase, 50Hz,
380-400-415V(4wires)
2.56
w1: Inner thermostat, HP switch, Discharge thermo.
w2: Thermal relay, Discharge thermo, HP switch, Anti-phase protector.
3. Above data based on indicated voltage
Indoor Unit Single phase 240V 50Hz
Outdoor Unit Single phase 240V 50Hz
3 phase 415V 50Hz
14
Service Ref.
Item
Btu/h
W
kW
kW
A
A
kW
K/min(CFM)
Pa(mmAq)
dB
mm(in.)
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
A
A
kW
W
kW
K
/min(CFM
)
dB
dB
mm(in.)
mm(in.)
mm(in.)
kg(lbs)
kg(lbs)
L
mm(in.)
mm(in.)
Function
Capacity
Total input
Service Ref.
Power supply(phase, cycle, voltage)
Input
Running current
Starting current
External finish
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
Airflow(Lo - Mi2 - Mi1 - Hi)
External static pressure
Operation control & Thermostat
Noise level(Lo - Mi2 - Mi1 - Hi)
Unit drain pipe I.D.
Dimensions
Weight
Service Ref.
Power supply (phase, cycle, voltage)
Running current
Starting current
External finish
Refrigerant control
Compressor
Model
Motor output
Starter type
Protection devices
Crankcase heater
Heat exchanger
Fan Fan(drive) x No.
Fan motor output
Airflow
Defrost method
Noise level
Dimensions
Weight
Refrigerant
Charge
Oil (Model)
Pipe size O.D.
Connection method
Between the indoor &
outdoor unit
INDOOR UNITOUTDOOR UNIT
REFRIGERANT PIPING
PMH-P2BA / PMH-P2BA1
Cooling
18,400
5,400
2.35
0.06
0.29
0.32
62
NE36VMJMT
w1
Heating
21,450
6,250
2.42
0.06
0.29
0.32
31
NE38YEJM
w2
W
D
H
Cooling
Heating
W
D
H
Liquid
Gas
Indoor side
Outdoor side
Height difference
Piping length
PMH-P2BA / PMH-P2BA
1
SinglePhase, 50Hz, 220-230-240V
Unit : Galvanized sheets with gray heat insulation, Grille munsell 0.98Y 8.99/0.63
Plate fin coil
Lineflow fan (direct) x 1
0.028
8.0-9.0-10.0-11.0(282-318-353-388)
0(direct blow)
Remote controller & built-in
36-38-40-42
26(1)
Munsell 5Y 7/1
Linear Expansion Valve
Hermetic
1.6
Line start
38
Plate fin coil
Propeller (direct) x 1
0.070
55(1,940)
Reverse cycle
48
50
900(35-7/16)
330+20(13+3/4)
855(33-5/8)
74(163)
R407C
2.6(5.7)
1.2(Ester)MEL56
9.52(3/8)
15.88(5/8)
Flared
Flared
Max. 40m
Max. 40m
Notes1. Rating Conditions (ISO T1)
Cooling····Indoor : D.B. 27˚C(80˚F), W.B. 19˚C (66˚F) Outdoor : D.B. 35˚C(95˚F), W.B. 24˚C (75˚F)
Heating
····Indoor : D.B. 20˚C(68˚F) Outdoor : D.B. 7˚C(45˚F), W.B. 6˚C (43˚F)
Refrigerant piping length (one way) : 5m (16ft)
2. Guaranteed operating range
Upper limit
Lower limit
Upper limit
Lower limit
Indoor
D.B. 35˚C W.B. 22.5˚C
D.B. 19˚C W.B. 15˚C
D.B. 28˚C
D.B. 17˚C
Outdoor
D.B. 46˚C
D.B. -5˚C
D.B. 24˚C W.B. 18˚C
D.B. -11˚C W.B. -12˚C
Cooling
Heating
UNIT : 854(33-5/8) PANEL : 1000(39-3/8)
UNIT : 395(15-9/16) PANEL : 470(18-1/2)
UNIT : 230(9-1/16) PANEL : 30(1-3/16)
UNIT : 14(31) PANEL : 3.0(6.6)
PUH-P2VGAA.UK PUH-P2YGAA.UK PUH-P2VGAA.UK PUH-P2YGAA.UK
Single Phase, 50Hz,
220-230-240V
10.26
3 phase, 50Hz,
380-400-415V(4wires)
3.70
Single Phase, 50Hz,
220-230-240V
10.57
3 phase, 50Hz,
380-400-415V(4wires)
3.82
w1: Inner thermostat, HP switch, Discharge thermo.
w2: Thermal relay, Discharge thermo, HP switch, Anti-phase protector.
3. Above data based on indicated voltage
Indoor Unit Single phase 240V 50Hz
Outdoor Unit Single phase 240V 50Hz
3 phase 415V 50Hz