Mitsubishi PLH-P3AAH.UK, PLH-P4AAH.UK, PLH-P5AAH.UK, PLH-P6AAH.UK, PLH-P3AAH1.UK Service Manual

...
0 (0)

SPLIT-TYPE, HEAT PUM PAIR CONDITIONERS

No. OC236

REVISED EDITION-A

TECHNICAL & SERVICE MANUAL

Series PLH

Indoor unit [Model names]

PLH-P3AAH

PLH-P4AAH

PLH-P5AAH

PLH-P6AAH

Ceiling Cassettes R407C

[Service Ref.]

PLH-P3AAH.UK PLH-P3AAH1.UK PLH-P4AAH.UK PLH-P4AAH1.UK PLH-P5AAH.UK PLH-P5AAH1.UK PLH-P6AAH.UK PLH-P6AAH1.UK

PLH-P3AAH1.UK, PLHP4AAH1.UK, PLH-P5AAH1.UK and PLH-P6AAH1 are added in REVISED EDITION-A. Outdoor units PUHP3,4VGAA.UK and PUH-

P3,4,5,6YGAA.UK which are connected to those indoor units are also added in it.

Please void OC236.

Refer to the OCT03 REVISED EDITION-C as for control relation. This manual does not cover outdoor units. When serving them, please refer to the service manual No.OC180REVISED EDI- TION-A, OC261 and this manual in a set.

INDOOR UNIT

CHECK TESTRUN

 

 

 

 

 

 

MODEL SELECT

˚C

 

 

 

 

 

 

AMPM

 

 

 

 

 

 

AMPM

 

CENTRALLY CONTROLLED

1Hr.

 

 

 

 

 

 

 

FILTER

 

ON OFF

 

˚C

ON/OFF

TEMP

 

CHECK

CLOCK

 

 

CHECK MODE

 

 

FILTER

 

 

 

 

 

 

 

TEST RUN

˚C

 

 

CHECK MODE

 

 

 

 

TEST RUN

ON/OFF

 

STAND BY

 

ERROR CODE

NOT AVAILABLE

FUNCTION

 

DEFROST

 

 

 

 

 

TEMP.

 

 

ON/OFF

CONTENTS

1.TECHNICAL CHANGES ············

2.COMBINATION OF INDOOR AND OUTDOOR UNITS··2

3.SAFETY PRECAUTION ·············

4.PART NAMES AND FUNCTIONS ········

5.SPECIFICATIONS ···············

6.DATA ·····················

7.OUTLINES AND DIMENSIONS ·········

8.WIRING DIAGRAM ················

9.REFRIGERANT SYSTEM DIAGRAM·········

10.TROUBLESHOOTING ·············

11.DISASSEMBLY PROCEDURE ··········

12.PARTS LIST ··················

13.OPTIONAL PARTS ···············

PLH-P•AAH.UK PLH-P•AAH1.UK

PLH-P•AAH.UK

PLH-P•AAH1.UK

WIRELESS REMOTE

WIRED REMOTE

CONTROLLER

CONTROLLER

1 TECHNICAL CHANGES

PLH-P3AAH.UK PLH-P3AAH1.UK PLH-P4AAH.UK PLH-P4AAH1.UK PLH-P5AAH.UK PLH-P5AAH1.UK PLH-P6AAH.UK PLH-P6AAH1.UK

REMOTE CONTROLLER has changed.(PAR-S27A-E PAR-20MAA-E, PAR-SL95A-E PAR-SL97A-E)

Outdoor units which are connected to PLH-P•AAH.UK and PLH-P•AAH1.UK have been added.

2 COMBINATION OF INDOOR AND OUTDOOR UNITS

 

 

 

 

 

 

Outdoor unit

 

 

 

 

 

 

 

 

 

 

Heat pump type

 

 

 

 

 

Indoor unit

 

 

 

 

 

PUH-P

 

 

 

 

 

 

 

 

 

3

 

 

4

 

 

5

 

6

 

 

VGA

YGA

VGAA.UK YGAA.UK

YGA

VGAA.UK YGAA.UK

YGA

YGAA.UK

YGA

YGAA.UK

 

PLH-P3AAH.UK

 

 

 

 

 

PLH-P3AAH1.UK

 

 

 

PLH-P4AAH.UK

 

 

 

Heat pump with

PLH-P4AAH1.UK

 

 

electric heater

PLH-P5AAH.UK

 

 

 

 

 

 

PLH-P5AAH1.UK

 

 

PLH-P6AAH.UK

 

 

 

PLH-P6AAH1.UK

 

3 SAFETY PRECAUTION

Cautions for devices that use R407C refrigerant.

· Do not use the existing refrigerant piping.

-The old refrigerant and lubricating oil in the existing piping contains a large amount of chlorine which may cause the lubricating oil of the new unit to deteriorate.

· Use “low residual oil piping”.

-If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the lubricating oil will result.

·Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)

-If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.

·Use Suniso 4GS or 3GS (small amount) as the lubricating oil to coat flares and flange connection parts.

-The lubricating oil used with the air conditioner is highly hygroscopic. If it is used, water may be mixed in and deterioration of the lubricating oil may result.

· Use liquid refrigerant to charge the system.

-If gas refrigerant is used to charge the system, the composition of the refrigerant in the cylinder will change and performance may drop.

· Do not use a refrigerant other than R407C.

-If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the lubricating oil to deteriorate.

· Use a vacuum pump with a reverse flow check valve.

-The vacuum pump oil may flow back into the refrigerant cycle and cause the lubricating oil to deteriorate.

2

[1] Service tools

Use the below service tools as exclusive tools for R407C refrigerant.

No.

Tool name

Specifications

1

Gauge manifold

·Only for R407C.

 

 

·Use the existing fitting SPECIFICATIONS. (UNF7/16)

 

 

·Use high-tension side pressure of 35kgf/cm2 or over.

2

Charge hose

·Only for R407C.

 

 

·Use pressure performance of 52kgf/cm2 or over.

3

Electronic scale

 

4

Gas leak detector

·Use the detector for R134a or R407C.

5

Adapter for reverse flow check.

·Attach on vacuum pump.

6

Refrigerant charge base.

 

7

Refrigerant cylinder.

·For R407C ·Top of cylinder (Brown)

 

 

·Cylinder with syphon

8

Refrigerant recovery equipment.

 

[2] Notice on repair service

·After recovering all the refrigerant in the unit, work may be started. ·Do not release the refrigerant in the air.

·After completing the repair service, recharge the system with the specified amount of the liquid refrigerant.

[3]Refrigerant recharging

(1)Refrigerant recharging process

Direct charging from the cylinder.

·Confirm that the cylinder is suitable for syphoning.

·Raise the cylinder and recharge the unit by syphoning liquid refrigerant.

Unit

Gravimeter

(2) Recharge when refrigerant leakage has occurred.

·After recovering all the refrigerant in the unit, work may be started.

·Do not release the refrigerant in the air.

·After completing the repair service, recharge the system with the specified amount of the liquid refrigerant.

3

4 PART NAMES AND FUNCTIONS

Indoor (Main) Unit

PLH-P3AAH.UK, PLH-P4AAH.UK, PLH-P5AAH.UK, PLH-P6AAH.UK PLH-P3AAH1.UK, PLH-P4AAH1.UK, PLH-P5AAH1.UK, PLH-P6AAH1.UK

Filter

Removes dust and pollutants

from intake air

Horizontal Air Outlet

Sets airflow of horizontal automatically during cooling or dehumidifying.

Grille

Auto Air Swing Vane Disperses airflow up and down and adjusts the angle of airflow direction.

Air Intake

Intakes air from room.

Wired remote controller

On the controls are set, the same operation mode can be repeated by simply pressing the ON/OFF button.

PLH-P3AAH.UK, PLH-P4AAH.UK, PLH-P5AAH.UK, PLH-P6AAH.UK

Operation buttons [ PAR-S27A-E ]

button

This switches between continuous operation and the timer operation.

button

Press this button to switch the cooling, electronic dry (dehumidify), automatic and heating modes.

TEMP. button

This sets the room temperature, The temperature setting can be performed in 1°C units

Setting range

Cooling 19°C to 30°C Heating 17°C to 28°C

This model name of the remote controller is indicated.

button

 

button

 

 

 

 

 

 

ON/OFF button

This sets the current time. start

 

This sets the ventilation fan

 

 

speed.

 

 

time and stop time.

 

 

This switches between the operation

 

 

 

 

 

 

 

 

 

 

 

 

 

and stop modes each time it is

 

 

 

 

 

 

 

 

pressed. The lamp on this button

 

 

 

 

lights during operation.

 

 

 

 

 

PAR-S27AA

button

This switches the horizontal fan motion ON and OFF.

(Not available for this model.)

button

This sets the ventilation fan speed.

button

This adjusts the vertical angle of the ventilation.

FILTER button

This resets the filter cleaning indication display.

CHECK-TEST RUN button

Only press this button to perform an inspection check or test operation, Do not use it for normal operation.

4

Display

CENTRALLY CONTROLLED display

This indicates when the unit is controlled by optional features such as central control type remote controller.

CHECK display

This indicates when a malfunction has occurred in the unit which should be checked.

OPERATION MODE display

This indicates the operation mode.

STANDBY display

The [STANDBY] symbol is only displayed from the time the heating operation starts until the heated air begins to blow.

display

The current time , start time and stop time can be displayed in ten second intervals by pressing the time setting button. The start time or stop time is always displayed during the timer operation.

display

This displays the air direction.

In this display example on the bottom left, a condition where all display lamps light is shown for explanation purposes although this differs from actual operation.

display

The selected fan speed is displayed.

display

The temperature of the suction air is displayed during operation. The display range is 10° to 35°C. The display flashes 10°C when the actual temperature is less than 10° and flashes 35°C when the actual temperature is greater than 35°C.

Operation lamp

This lamp lights during operation, goes off when the unit stops and flashes when a malfunction occurs.

DEFROST display

This indicates when the defrost operation is performed.

display

This indicates when the continuous operation and time operation modes are set.

It also display the time for the timer operation at the same time as when it is set.

display

This displays the selected setting temperature.

CHECK MODE

display

TEST RUN

This display lights in the check mode or when a test operation is performed.

display

FILTER

display

This lamp lights when electricity is

This lamp lights when the filter need

supplied to the unit.

to be cleaned.

 

Caution

Only the display lights when the unit is stopped and power supplied to the unit.

When power is turned ON for the first time the (CENTRAL CTRL) display appears to go off momentarily but this is not a malfunction.

When the central control remote control unit, which is sold separately, is used the ON-OFF button, button and

TEMP. button do not operate.

“NOT AVAILABLE” is displayed when the button are pressed.This indicates that this room unit is not equipped with the fan direction adjustment function and the louver function.

When power is turned ON for the first time , it is normal that “HO” is displayed on the room temperature indication (For max. 2minutes ).

Please wait until this “HO” indication disappear than start the operation.

5

PLH-P3AAH1.UK, PLH-P4AAH1.UK, PLH-P5AAH1.UK, PLH-P6AAH1.UK

Operation buttons [ PAR-20MAA-E ]

TEMP. ADJUSTMENT button

TIME SETTING button

AIR SPEED button

This sets the room temperature. The

This sets the current time, start time

This sets the ventilation fan speed.

temperature setting can be performed

and stop time.

 

 

 

 

 

in 1: units

 

 

 

 

 

Setting range

 

 

 

 

 

Cooler 19: to 30:

 

 

 

 

ON/OFF button

Heater 17: to 28:

 

 

 

 

 

 

 

 

 

This switches between the operation

 

 

 

 

 

and stop modes each time it is pressed.

 

 

 

 

 

The lamp on this button lights during

TIMER button

 

CENTRALLY CONTROLLED

1Hr.

operation.

 

 

 

This switches between continuous

 

 

ON OFF

˚C

 

 

CHECK

CLOCK

FILTER

 

operation and the timer operation.

 

˚C

 

CHECK MODE

AIR DIRECTION button

DEFROST

 

TEST RUN

 

 

 

NOT AVAILABLE FUNCTION

 

STAND BY

 

ERROR CODE

 

 

 

 

 

 

 

 

 

TEMP.

 

ON/OFF

This adjusts the vertical angle of the

 

 

 

 

 

 

 

 

 

 

ventilation.

 

 

 

 

FILTER

 

OPERATION SWITCH button

 

 

 

CHECK TEST

 

 

 

 

 

 

Press this button to switch the cooler,

PAR-20MAA

TIMER SET

 

FILTER button

electronic dry (dehumidify), automatic

 

 

 

 

 

and heater modes.

 

 

 

 

This resets the filter service indication

 

 

 

 

 

display

LOUVER button

 

 

 

CHECK-TEST RUN button

This switch the horizontal fan motion

 

 

Only press this button to perform an

ON and OFF.

 

 

 

inspection check or test operation.

 

 

 

 

Do not use it for normal operation.

(Not available for this model.)

 

 

 

 

 

6

Display

CENTRALLY CONTROLLED display

This indicates when the unit is controlled by optional features such as central control type remote controller.

CLOCK display

The current time , start time and stop time can be displayed in ten second intervals by pressing the time switch button. The start time or stop time is always displayed during the timer operation.

In this display example on the bottom left, a condition where all display lamps light is shown for explanation purposes although this differs from actual operation.

TIMER display

This indicates when the continuous operation and time operation modes are set.

It also display the time for the timer operation at the same time as when it is set.

OPERATION MODE display

This indicates the operation mode.

STANDBY display

The [STANDBY] symbol is only displayed from the time the heating operation starts unit the heated air begins to blow.

DEFROST display

This indicates when the defrost operation is performed.

AIR DIRECTION display

This displays the air direction.

 

CENTRALLY CONTROLLED

1Hr.

 

 

 

ON OFF

 

˚C

 

CHECK

CLOCK

 

 

 

 

 

 

 

 

 

 

FILTER

 

˚C

 

 

CHECK MODE

STAND BY

ERROR CODE

 

TEST RUN

 

NOT AVAILABLE

FUNCTION

DEFROST

 

 

 

 

TEMP.

 

 

ON/OFF

FILTER

CHECK TEST

PAR-20MAA

TIMER SET

AIR SPEED display

The selected fan speed is displayed.

ROOM TEMPERATURE display

The temperature of the suction air is displayed during operation. The display range is 8°C to 39°C. The display flashes 8°C when the actual temperature is less than 8°C and flashes 39°C when the actual temperature is greater than 39°C.

Operation lamp

This lamp lights during operation, goes off when the unit stops and flashes when a malfunction occurs.

CHECK MODE

display

TEST RUN

This display lights in the check mode or when a test operation is performed.

CHECK display

 

 

 

 

 

 

SET TEMPERATURE display

 

POWER display

This indicates when a malfunction

 

 

 

 

has occurred in the unit which should

 

This displays the selected setting

 

This lamp lights when electricity is

be checked.

 

 

 

temperature.

 

supplied to the unit.

 

 

 

 

 

 

 

 

Caution

FILTER display

This lamp lights when the filter need to be cleaned.

Only the Power display lights when the unit is stopped and power supplied to the unit.

When the central control remote control unit, which is sold separately, is used the ON-OFF button, operation switch button and TEMP. adjustment button do not operate.

“NOT AVAILABLE” is displayed when the Air speed button are pressed.This indicates that this room unit is not equipped with the fan direction adjustment function and the louver function.

When power is turned ON for the first time, it is normal that “H0” is displayed on the room temperature indication (For max. 2minutes). Please wait until this “H0” indication disappear then start the operation.

7

Wireless remote controller

PLH-P3AAH.UK, PLH-P4AAH.UK, PLH-P5AAH.UK, PLH-P6AAH.UK

● When cover is open. [ PAR-SL95A-E ]

display

Lights up while transmission to the indoor unit is mode using switches.

display

OPERATION MODE display

Operation mode display indicates which operation mode is in effect.

• FUNCTION display

Lights up when function are set.

TEST RUN CHECK display

CHECK&TEST RUN display indicates that the unit is being checked or test-run.

display

Displays when batteries are dead.

display

The vertical direction of airflow is indicated.

display

FAN SPEED display indicates which fan speed has been selected.

display

The unit is turned ON and OFF alternately each time the button is pressed.

● When cover is open.

MODE SELECT button

Used to switch the operation mode between cooling , drying , blowing , heating and auto mode.

FAN SPEED SELECT button

Used to change the fan speed.

VANE CONTROL button

Used to change the airflow direction.

ADDRESS display

 

 

display

Displays the refrigerant address.

SET TEMP. display indicates desired tempera-

 

 

 

UNIT NO. display

ture set.

 

 

 

 

 

 

 

 

Displays the number of unit..

 

 

 

 

 

FUNCTION NO. display

CLOCK display

 

 

 

 

 

Displays the mode.

 

DIsplays the current time.

 

 

 

SELECTION NO. display

”display

Displays the selection number..

 

 

 

 

 

 

 

 

Flashes when the current time is displayed.

 

 

 

TIMER display

 

ADDRESS

 

Displays when in timer operation or when set-

 

UNIT No.

 

 

FUNCTION No.

˚C

ting timer.

 

 

 

SELECTION No.

 

 

 

 

AM

” “

 

” display

 

 

PM

 

FUNCTION

 

AM

 

 

 

 

TEST RUN

 

 

 

 

 

 

 

PM

 

 

 

 

 

 

 

 

 

 

 

 

CHECK

 

 

 

 

 

 

 

 

 

TEMP.

Displays the order of timer operation.

 

 

 

 

 

 

 

ON/OFF

 

 

 

” “

 

” display

 

 

 

 

 

 

 

START

Displays whether timer is on or off.

 

 

 

MODE

FAN

STOP

 

 

 

 

 

 

VANE

HR.

” “

” display

 

 

 

 

 

 

 

 

 

Displays when the current time and the timer

 

 

MIN.

time can be changed.

RESET

TEMP. button

TEMP.

ON/OFF

 

 

START

MODE

FAN

STOP

VANE HR.

MIN.

RESET

SET TEMPERATURE button sets any desired room temperature.

TIMER CONTROL buttons

STOP (OFF timer): when this switch is set, the air conditioner will be automatically stopped at the preset time.

START (ON timer): when this switch is set, the air conditioner will be automatically started at the preset time.

HR. and MIN.buttons

Buttons used to set the “hour and minute” of the current time and timer settings.

button

RESET button

8

PLH-P3AAH1.UK, PLH-P4AAH1.UK, PLH-P5AAH1.UK, PLH-P6AAH1.UK

● When cover is open. [ PAR-SL97A-E ]

CHECK TESTRUN display

CHECK&TEST RUN display indicates that the unit is being checked or test-run.

display

OPERATION MODE display

Operation mode display indicates which operation mode is in effect.

display

The vertical direction of air flow is indicated.

display

FAN SPEED display indicates which fan speed has been selected.

ON/OFF button

The unit is turned ON and OFF alternately each time the button is pressed.

FAN SPEED SELECT button

Used to change the fan speed.

MODE SELECT button

Used to switch the operation mode between cooling, drying, blowing, heating and auto mode.

CHECK-TEST RUN button

Only press this button to perform an inspection check or test operation.

Do not use it for normal operation.

VANE CONTROL button

Used to change the air flow direction.

MODEL SELECT display

Blinks when model is selected.

CHECK TESTRUN

MODEL SELECT ˚C

AMPM

AMPM

NOT AVAILABLE

ON/OFF TEMP

 

FAN

AUTO STOP

MODE

VANE

AUTO START

CHECK

LOUVER

h

TEST RUN

 

min

SET

RESET CLOCK

display

Lights up while transmission to the indoor unit is mode using switches.

display

SET TEMP. display indicates desired temperature set.

CLOCK display

Displays the current time.

TIMER display

Displays when in timer operation or when setting timer.

” “ ” display

Displays the order of timer operation.

” “” display

Displays whether timer is on or off.

button

SET TEMPERATURE button sets any desired room temperature.

TIMER CONTROL buttons

AUTO STOP (OFF timer): when this switch is set, the air conditioner will be automatically stopped at the preset time.

AUTO START (ON timer): when this switch is set, the air conditioner will be automatically started at the preset time.

h and min buttons

Buttons used to set the “hour and minute” of the current time and timer settings.

LOUVER button

This switch the horizontal fan motion ON and OFF.

(Not available for this model.)

CLOCK button

RESET button

SET button

9

LING SSETTE

5

 

 

SPECIFICATIONS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

 

 

 

 

 

 

Service Ref.

 

 

PLH-P3AAH.UK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Function

 

 

 

 

 

 

 

Cooling

 

Heating

 

 

Capacity

 

w1

 

 

 

Btu/h

 

26,600

 

31,700 [38,900]

 

 

 

 

 

 

W

 

7,800

 

9,300 [11,400]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total input

 

w1

 

 

 

k W

 

3.51

 

3.65 [5.75]

 

 

 

 

 

Service Ref.

 

 

 

 

 

 

 

PLH-P3AAH.UK

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply (phase, cycle,voltage)

 

Single phase, 50Hz, 220–230–240V

 

 

 

 

 

 

Input

 

 

w2

 

kW

 

0.17

 

0.17 <2.10>

 

 

 

 

 

 

Running current

w2

 

A

 

0.81

 

0.81 <8.75>

 

 

 

 

 

 

Starting current

w2

 

A

 

1.0

 

1.0 <8.75>

 

 

 

 

 

External finish

 

 

 

 

 

 

Munsell 0.70Y 8.59/0.97

 

 

 

 

 

Heat exchanger

 

 

 

 

 

 

 

Plate fin coil

 

 

unit

 

 

Fan (drive) o No.

 

 

 

 

 

Turbo fan (direct) o 1

 

 

 

Fan

Fan motor output

 

 

kW

 

 

0.070

 

 

Indoor

 

Airflow (Lo-Mi2-Mi1-Hi)

 

K/ min (CFM)

 

15-16-18-20 (530-565-635-705)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External static pressure

 

Pa (mmAq)

 

 

0 (direct blow)

 

 

 

 

 

Booster heater

 

 

 

 

kW

 

 

<2.1>

 

 

 

 

 

Operation control & Thermostat

 

 

 

Remote controller & built-in

 

 

 

 

 

Sound level (Lo-Mi2-Mi1-Hi)

 

dB

 

 

28-30-32-34

 

 

 

 

 

Unit drain pipe I.D.

 

 

 

mm (in.)

 

 

32 (1-1/4)

 

 

 

 

 

 

 

 

W

 

 

mm (in.)

 

UNIT : 840 (33-1/16)

PANEL : 950 (37-3/8)

 

 

 

 

 

Dimensions

 

D

 

 

mm (in.)

 

UNIT : 840 (33-1/16)

PANEL : 950 (37-3/8)

 

 

 

 

 

 

 

 

H

 

 

mm (in.)

 

UNIT : 258 (10-1/2)

PANEL : 30 (1-3/16)

 

 

 

 

 

Weight

 

 

 

 

 

kg (lbs.)

 

UNIT : 26 (57)

PANEL : 5 (11)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Service Ref.

 

 

 

 

 

 

PUH-P3VGA / PUH-P3YGA

 

 

 

 

 

Power supply (phase, cycle, voltage)

Single phase, 50Hz, 220–230–240V / 3 phases, 50Hz, 380–400–415V (4wires)

 

 

 

 

 

 

Running current

 

 

A

 

14.64/5.46

 

15.43/5.76

 

 

 

 

 

 

Starting current

 

 

A

 

 

93/41

 

 

 

 

 

External finish

 

 

 

 

 

 

 

Munsell 5Y 8/1

 

 

 

 

 

Refrigerant control

 

 

 

 

 

 

Linear expansion valve

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

Hermetic

 

 

 

 

 

 

Model

 

 

 

 

 

 

NE52VNJM / NE52YDJM

 

 

unit

 

 

Motor output

 

 

 

kW

 

 

2.5

 

 

 

 

Starter type

 

 

 

 

 

 

Line start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor

 

 

Protection devices

 

 

Internal thermostat, HP switch, Discharge thermo. / Thermal relay, Discharge thermo., HP switch, Anti-phase protector

 

 

 

Heat exchanger

 

 

 

 

 

 

 

Plate fin coil

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan (drive) o No.

 

 

 

 

 

Propeller (direct) o 1

 

 

 

 

 

Fan

Fan motor output

 

 

kW

 

 

0.070

 

 

 

 

 

 

Airflow

 

 

 

 

K/ min (CFM)

 

 

50 (1,770)

 

 

 

 

 

Crankcase heater

 

 

 

W

 

 

38

 

 

 

 

 

Defrost method

 

 

 

 

 

 

 

Reverse cycle

 

 

 

 

 

Sound level

 

Cooling

 

dB

 

 

49

 

 

 

 

 

 

Heating

 

dB

 

 

51

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

W

 

 

mm (in.)

 

 

900 (35-7/16)

 

 

 

 

 

Dimensions

 

D

 

 

mm (in.)

 

 

330+20 (13+3/4)

 

 

 

 

 

 

 

 

H

 

 

mm (in.)

 

 

855 (33-5/8)

 

 

 

 

 

Weight

 

 

 

 

 

kg (lbs.)

 

 

82 (181)

 

 

 

 

 

Refrigerant

 

 

 

 

 

 

 

R407C

 

 

piping

 

 

Charge

 

 

 

kg (lbs.)

 

 

3.7 (8.2)

 

 

 

 

Oil (Model)

 

 

 

L

 

 

1.6 (MEL56)

 

 

 

 

 

 

 

 

 

 

 

 

 

Refrigerant

 

Pipe size O.D.

 

Liquid

 

mm (in.)

 

 

9.52 (3/8)

 

 

 

 

 

 

Gas

 

mm (in.)

 

 

15.88 (5/8)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Connection method

Indoor side

 

 

 

 

Flared

 

 

 

 

 

Outdoor side

 

 

Flared

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Between the indoor &

Height difference

 

 

Max. 50m

 

 

 

 

 

outdoor units

 

Piping length

 

 

Max. 50m

 

 

NOTE:

 

1. Rating conditions (ISO T1)

 

 

 

 

 

 

 

 

 

 

 

 

Cooling : Indoor

: D.B. 27: (80˚F)

W.B. 19: (66˚F)

Outdoor

: D.B. 35: (95˚F)

W.B. 24: (75˚F)

 

 

 

 

Heating : Indoor

: D.B. 20: (68˚F)

 

 

Outdoor

: D.B. 7: (45˚F)

W.B. 6: (43˚F)

 

Refrigerant piping length (one way) : 5m (16ft.)

 

 

 

 

2. Guaranteed operating range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

Outdoor

 

w1 : [ ] Shows the total rating.

 

Cooling

Upper limit

D.B. 35˚C,

W.B. 22.5˚C

D.B. 46˚C

 

w2 : < > Shows the only booster heater rating.

 

 

 

Lower limit

D.B. 19˚C,

W.B. 15˚C

D.B. -5˚C

3. Above data based on indicated voltage

 

 

Upper limit

D.B. 28˚C

 

D.B. 24˚C, W.B. 18˚C

 

Heating

 

Indoor unit

Single phase 240V 50Hz

 

Lower limit

D.B. 17˚C

 

D.B. -11˚C, W.B. -12˚C

 

 

Outdoor unit

Single phase 240V 50Hz / 3 phases 415V 50Hz

 

 

 

 

 

 

 

10

Mitsubishi PLH-P3AAH.UK, PLH-P4AAH.UK, PLH-P5AAH.UK, PLH-P6AAH.UK, PLH-P3AAH1.UK Service Manual

Item

 

 

 

 

Service Ref.

 

 

 

 

 

 

Function

 

 

 

 

 

 

Capacity

 

w1

 

 

Btu/h

 

 

 

W

 

 

 

 

 

 

 

Total input

 

w1

 

 

kW

 

 

Service Ref.

 

 

 

 

 

 

Power supply (phase, cycle,voltage)

 

 

 

 

Input

 

 

w2

kW

 

 

 

Running current

w2

A

 

 

 

Starting current

w2

A

 

 

External finish

 

 

 

 

 

 

Heat exchanger

 

 

 

 

unit

 

 

Fan (drive) o No.

 

 

 

Fan

Fan motor output

 

kW

Indoor

 

Airflow (Lo-Mi2-Mi1-Hi)

K/ min (CFM)

 

 

 

 

 

 

 

 

External static pressure

Pa (mmAq)

 

 

Booster heater

 

 

 

kW

 

 

Operation control & Thermostat

 

 

 

Sound level (Lo-Mi2-Mi1-Hi)

dB

 

 

Unit drain pipe I.D.

 

 

mm (in.)

 

 

 

 

 

W

 

mm (in.)

 

 

Dimensions

 

D

 

mm (in.)

 

 

 

 

 

H

 

mm (in.)

 

 

Weight

 

 

 

 

kg (lbs.)

 

 

Service Ref.

 

 

 

 

 

 

Power supply (phase, cycle, voltage)

 

 

 

 

Running current

 

A

 

 

 

Starting current

 

A

 

 

External finish

 

 

 

 

 

 

Refrigerant control

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

Model

 

 

 

 

unit

 

 

Motor output

 

 

kW

 

 

Starter type

 

 

 

 

 

 

 

 

 

Outdoor

 

 

Protection devices

 

 

Heat exchanger

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan (drive) o No.

 

 

 

 

Fan

Fan motor output

 

kW

 

 

 

Airflow

 

 

 

K/ min (CFM)

 

 

Crankcase heater

 

 

W

 

 

Defrost method

 

 

 

 

 

 

Sound level

 

Cooling

dB

 

 

 

Heating

dB

 

 

 

 

 

 

 

 

 

 

W

 

mm (in.)

 

 

Dimensions

 

D

 

mm (in.)

 

 

 

 

 

H

 

mm (in.)

 

 

Weight

 

 

 

 

kg (lbs.)

 

 

Refrigerant

 

 

 

 

piping

 

 

Charge

 

 

kg (lbs.)

 

 

Oil (Model)

 

 

L

 

 

 

 

 

Refrigerant

 

Pipe size O.D.

 

Liquid

mm (in.)

 

 

Gas

mm (in.)

 

 

 

 

 

 

 

 

 

 

Connection method

Indoor side

 

 

 

Outdoor side

 

 

 

 

 

 

 

 

 

Between the indoor &

Height difference

 

 

outdoor units

 

Piping length

 

 

 

 

 

 

 

 

 

PLH-P4AAH.UK

 

 

Cooling

 

Heating

33,100

 

36,200 [45,000]

9,700

 

10,600 [13,200]

3.62

 

3.80 [6.40]

PLH-P4AAH.UK

Single phase, 50Hz, 220–230–240V

0.26

 

0.26 <2.60>

1.25

 

1.25 <10.83>

2.0

 

2.0 <10.83>

Munsell 0.70Y 8.59/0.97

Plate fin coil

Turbo fan (direct) o 1

0.120

 

20-23-26-28 (705-810-920-990)

0 (direct blow)

<2.6>

 

Remote controller & built-in

33-36-39-41

32 (1-1/4)

UNIT : 840 (33-1/16)

PANEL : 950 (37-3/8)

UNIT : 840 (33-1/16)

PANEL : 950 (37-3/8)

UNIT : 298 (11-3/4)

PANEL : 30 (1-3/16)

UNIT : 32 (71)

PANEL : 5 (11)

 

PUH-P4YGA

3 phases, 50Hz, 380–400–415V (4wires)

5.49

 

5.79

 

45

 

Munsell 5Y 8/1

 

Linear expansion valve

 

Hermetic

 

NE56YDJM

 

2.7

 

Line start

Anti-phase protector, Thermal relay, Discharge thermo., HPswitch

Plate fin coil

Propeller (direct) o 2

0.070+0.070

85 (3,000)

38

Reverse cycle

51

53

900 (35-7/16)

330+20 (13+3/4)

1,260 (49-5/8)

96 (212)

R407C

4.0 (8.8)

1.6 (MEL56)

9.52 (3/8)

19.05 (3/4)

Flared

Flared

Max. 50m

Max. 50m

NOTE: 1.

Rating conditions (ISO T1)

 

 

 

 

Cooling : Indoor

: D.B. 27: (80˚F), W.B. 19: (66˚F)

Outdoor

: D.B. 35: (95˚F)

W.B. 24: (75˚F)

 

Heating : Indoor

: D.B. 20: (68˚F)

Outdoor

: D.B. 7: (45˚F)

W.B. 6: (43˚F)

 

Refrigerant piping length (one way) : 5m (16ft.)

 

 

 

2.

Guaranteed operating range

 

 

 

 

 

Indoor

Outdoor

Cooling

Upper limit

D.B. 35: , W.B. 22.5:

D.B. 46:

Lower limit

D.B. 19 :, W.B. 15:

D.B. -5:

 

Heating

Upper limit

D.B. 28:

D.B. 24: , W.B. 18:

Lower limit

D.B. 17:

D.B. -11:, W.B. -12:

 

w1

: [ ] Shows the total rating.

w2

: < > Shows the only booster heater rating.

3. Above data based on indicated voltage

Indoor unit

Single phase 240V 50Hz

Outdoor unit

3 phases 415V 50Hz

11

Service Ref.

Item

Function

Capacity

 

w1

 

 

Btu/h

 

 

 

W

 

 

 

 

 

 

Total input

 

w1

 

 

k W

 

Service Ref.

 

 

 

 

 

Power supply (phase, cycle,voltage)

 

 

 

Input

 

 

w2

kW

 

 

Running current

w2

A

 

 

Starting current

w2

A

 

External finish

 

 

 

 

 

Heat exchanger

 

 

 

 

unit

 

Fan (drive) o No.

 

 

Fan

Fan motor output

 

kW

Indoor

Airflow (Lo-Mi2-Mi1-Hi)

K/ min (CFM)

 

 

 

 

 

External static pressure

Pa (mmAq)

 

Booster heater

 

 

 

kW

 

Operation control & Thermostat

 

 

Sound level (Lo-Mi2-Mi1-Hi)

dB

 

Unit drain pipe I.D.

 

 

mm (in.)

 

 

 

 

W

 

mm (in.)

 

Dimensions

 

D

 

mm (in.)

 

 

 

 

H

 

mm (in.)

 

Weight

 

 

 

 

kg (lbs.)

 

Service Ref.

 

 

 

 

 

Power supply (phase, cycle, voltage)

 

 

 

Running current

 

A

 

 

Starting current

 

A

 

External finish

 

 

 

 

 

Refrigerant control

 

 

 

 

Compressor

 

 

 

 

 

 

Model

 

 

 

 

unit

 

Motor output

 

 

kW

 

Starter type

 

 

 

 

 

 

 

 

Outdoor

 

Protection devices

 

Heat exchanger

 

 

 

 

 

 

 

 

 

 

 

Fan (drive) o No.

 

 

 

Fan

Fan motor output

 

kW

 

 

Airflow

 

 

 

K/ min (CFM)

 

Crankcase heater

 

 

W

 

Defrost method

 

 

 

 

 

Sound level

 

Cooling

dB

 

 

Heating

dB

 

 

 

 

 

 

 

 

W

 

mm (in.)

 

Dimensions

 

D

 

mm (in.)

 

 

 

 

H

 

mm (in.)

 

Weight

 

 

 

 

kg (lbs.)

 

Refrigerant

 

 

 

 

piping

 

Charge

 

 

kg (lbs.)

 

Oil (Model)

 

 

L

 

 

 

 

Refrigerant

Pipe size O.D.

 

Liquid

mm (in.)

 

Gas

mm (in.)

 

 

 

 

 

 

 

Connection method

Indoor side

 

 

Outdoor side

 

 

 

 

 

 

 

Between the indoor &

Height difference

 

outdoor units

 

Piping length

 

 

PLH-P5AAH.UK

 

Cooling

Heating

43,700

54,600

[64,800]

12,800

16,000

[19,000]

5.55

5.93

[8.93]

PLH-P5AAH.UK

Single phase, 50Hz, 220–230–240V

0.30

 

0.30 <3.00>

1.43

 

1.43 <12.50>

2.0

 

2.0 <12.50>

Munsell 0.70Y 8.59/0.97

Plate fin coil

Turbo fan (direct) o 1

0.120

 

22-25-28-30 (775-880-990-1,060)

0 (direct blow)

<3.0>

 

Remote controller & built-in

35-38-41-43

32 (1-1/4)

UNIT : 840 (33-1/16)

PANEL : 950 (37-3/8)

UNIT : 840 (33-1/16)

PANEL : 950 (37-3/8)

UNIT : 298 (11-3/4)

PANEL : 30 (1-3/16)

UNIT : 32 (71)

PANEL : 5 (11)

 

PUH-P5YGA

3 phases, 50Hz, 380–400–415V (4wires)

8.39

8.74

79

Munsell 5Y 8/1

Linear expansion valve

Hermetic

HE86YAA

4.3

Line start

Internal thermostat, Anti-phase protector, Thermal relay, HP switch, LP switch, Discharge thermo.

Plate fin coil

Propeller (direct) o 2

0.075+0.075

95(3,360)

38

Reverse cycle

53

55

1,050 (41-5/16)

330+20 (13+3/4)

1,260 (49-5/8)

122 (269)

R407C

5.8(12.8)

2.0(MEL32)

9.52(3/8)

19.05(3/4) Flared Flared

Max. 50m

Max. 50m

NOTE: 1.

Rating conditions (ISO T1)

 

 

 

 

Cooling : Indoor

: D.B. 27: (80˚F), W.B. 19: (66˚F)

Outdoor

: D.B. 35: (95˚F)

W.B. 24: (75˚F)

 

Heating : Indoor

: D.B. 20: (68˚F)

Outdoor

: D.B. 7: (45˚F)

W. B. 6 : (43˚F)

 

Refrigerant piping length (one way) : 5m (16ft.)

 

 

 

2.

Guaranteed operating range

 

 

 

 

 

Indoor

Outdoor

Cooling

Upper limit

D.B. 35:, W.B. 22.5:

D.B. 46:

Lower limit

D.B. 19: , W.B. 15:

D.B. -5:

 

Heating

Upper limit

D.B. 28:

D.B. 24: , W.B. 18:

Lower limit

D.B. 17:

D.B. -11:, W.B. -12:

 

w1

: [ ] Shows the total rating.

w2

: < > Shows the only booster heater rating.

3. Above data based on indicated voltage

Indoor unit

Single phase 240V 50Hz

Outdoor unit

3 phases 415V 50Hz

12

Service Ref.

Item

Function

Capacity

 

w1

 

 

Btu/h

 

 

 

W

 

 

 

 

 

 

Total input

 

w1

 

 

kW

 

Service Ref.

 

 

 

 

 

Power supply (phase, cycle,voltage)

 

 

 

Input

 

 

w2

kW

 

 

Running current

w2

A

 

 

Starting current

w2

A

 

External finish

 

 

 

 

 

Heat exchanger

 

 

 

 

unit

 

Fan (drive) o No.

 

 

Fan

Fan motor output

 

kW

Indoor

Airflow (Lo-Mi2-Mi1-Hi)

K/ min (CFM)

 

 

 

 

 

External static pressure

Pa (mmAq)

 

Booster heater

 

 

 

kW

 

Operation control & Thermostat

 

 

Sound level (Lo-Mi2-Mi1-Hi)

dB

 

Unit drain pipe I.D.

 

 

mm (in.)

 

 

 

 

W

 

mm (in.)

 

Dimensions

 

D

 

mm (in.)

 

 

 

 

H

 

mm (in.)

 

Weight

 

 

 

 

kg (lbs.)

 

Service Ref.

 

 

 

 

 

Power supply (phase, cycle, voltage)

 

 

 

Running current

 

A

 

 

Starting current

 

A

 

External finish

 

 

 

 

 

Refrigerant control

 

 

 

 

Compressor

 

 

 

 

 

 

Model

 

 

 

 

unit

 

Motor output

 

 

kW

 

Starter type

 

 

 

 

 

 

 

 

Outdoor

 

Protection devices

 

Heat exchanger

 

 

 

 

 

 

 

 

 

 

 

Fan (drive) o No.

 

 

 

Fan

Fan motor output

 

kW

 

 

Airflow

 

 

 

K/ min (CFM)

 

Crankcase heater

 

 

W

 

Defrost method

 

 

 

 

 

Sound level

 

Cooling

dB

 

 

Heating

dB

 

 

 

 

 

 

 

 

W

 

mm (in.)

 

Dimensions

 

D

 

mm (in.)

 

 

 

 

H

 

mm (in.)

 

Weight

 

 

 

 

kg (lbs.)

 

Refrigerant

 

 

 

 

piping

 

Charge

 

 

kg (lbs.)

 

Oil (Model)

 

 

L

 

 

 

 

Refrigerant

Pipe size O.D.

 

Liquid

mm (in.)

 

Gas

mm (in.)

 

 

 

 

 

 

 

Connection method

Indoor side

 

 

Outdoor side

 

 

 

 

 

 

 

Between the indoor &

Height difference

 

outdoor units

 

Piping length

 

 

PLH-P6AAH.UK

 

Cooling

Heating

48,000

57,300

[67,600]

14,300

16,800

[19,800]

6.70

6.77

[9.77]

PLH-P6AAH.UK

Single phase, 50Hz, 220–230–240V (4wires)

0.34

 

0.34 <3.00>

1.64

 

1.64 <12.50>

2.0

 

2.0 <12.50>

Munsell 0.70Y 8.59/0.97

Plate fin coil

Turbo fan (direct) o 1

0.120

 

22-25-28-30 (775-880-990-1,060)

0 (direct blow)

<3.0>

 

Remote controller & built-in

37-40-43-45

32 (1-1/4)

UNIT : 840 (33-1/16)

PANEL : 950 (37-3/8)

UNIT : 840 (33-1/16)

PANEL : 950 (37-3/8)

UNIT : 298 (11-3/4)

PANEL : 30 (1-3/16)

UNIT : 34 (75)

PANEL : 5 (11)

 

PUH-P6YGA

3 phases, 50Hz, 380–400–415V (4wires)

10.17

 

10.28

 

84

 

Munsell 5Y 8/1

 

Linear expansion valve

 

Hermetic

 

HE101YAA

 

5.1

 

Line start

Internal thermostat, Anit-phase protector, Thermal relay, HP switch, LP switch, Discharge thermo.

Plate fin coil

Propeller (direct) o 2

0.075+0.075

100 (3,530)

38

Reverse cycle

55

57

1,050 (41-5/16)

330+20(13+3/4)

1,260 (49-5/8)

122 (269)

R407C

5.8 (12.8)

2.0 (MEL32)

9.52 (3/8)

19.05 (3/4)

Flared

Flared

Max. 50m

Max. 50m

NOTE: 1.

Rating conditions (ISO T1)

 

 

 

 

Cooling : Indoor

: D.B. 27: (80˚F), W.B. 19: (66˚F)

Outdoor

: D.B. 35: (95˚F)

W.B. 24: (75˚F)

 

Heating : Indoor

: D.B. 20: (68˚F)

Outdoor

: D.B. 7: (45˚F)

W.B. 6 : (43˚F)

 

Refrigerant piping length (one way) : 5m (16ft.)

 

 

 

2.

Guaranteed operating range

 

 

 

 

 

Indoor

Outdoor

Cooling

Upper limit

D.B. 35:, W.B. 22.5:

D.B. 46:

Lower limit

D.B. 19: , W.B. 15:

D.B. -5:

 

Heating

Upper limit

D.B. 28:

D.B. 24: , W.B. 18:

Lower limit

D.B. 17:

D.B. -11:, W.B. -12:

 

w1

: [ ] Shows the total rating.

w2

: < > Shows the only booster heater rating.

3. Above data based on indicated voltage

Indoor unit

Single phase 240V 50Hz

Outdoor unit

3 phases 415V 50Hz

13

Service Ref.

Item

Function

Capacity

 

w1

 

 

Btu/h

 

 

 

W

 

 

 

 

 

 

Total input

 

w1

 

 

k W

 

Service Ref.

 

 

 

 

 

Power supply (phase, cycle,voltage)

 

 

 

Input

 

 

w2

kW

 

 

Running current

w2

A

 

 

Starting current

w2

A

 

External finish

 

 

 

 

 

Heat exchanger

 

 

 

 

unit

 

Fan (drive) o No.

 

 

Fan

Fan motor output

 

kW

Indoor

Airflow (Lo-Mi2-Mi1-Hi)

K/ min (CFM)

 

 

 

 

 

External static pressure

Pa (mmAq)

 

Booster heater

 

 

 

kW

 

Operation control & Thermostat

 

 

Sound level (Lo-Mi2-Mi1-Hi)

dB

 

Unit drain pipe I.D.

 

 

mm (in.)

 

 

 

 

W

 

mm (in.)

 

Dimensions

 

D

 

mm (in.)

 

 

 

 

H

 

mm (in.)

 

Weight

 

 

 

 

kg (lbs.)

 

Service Ref.

 

 

 

 

 

Power supply (phase, cycle, voltage)

 

 

 

Running current

 

A

 

 

Starting current

 

A

 

External finish

 

 

 

 

 

Refrigerant control

 

 

 

 

Compressor

 

 

 

 

 

 

Model

 

 

 

 

unit

 

Motor output

 

 

kW

 

Starter type

 

 

 

 

 

 

 

 

Outdoor

 

Protection devices

 

Heat exchanger

 

 

 

 

 

 

 

 

 

 

 

Fan (drive) o No.

 

 

 

Fan

Fan motor output

 

kW

 

 

Airflow

 

 

 

K/ min (CFM)

 

Crankcase heater

 

 

W

 

Defrost method

 

 

 

 

 

Sound level

 

Cooling

dB

 

 

Heating

dB

 

 

 

 

 

 

 

 

W

 

mm (in.)

 

Dimensions

 

D

 

mm (in.)

 

 

 

 

H

 

mm (in.)

 

Weight

 

 

 

 

kg (lbs.)

 

Refrigerant

 

 

 

 

piping

 

Charge

 

 

kg (lbs.)

 

Oil (Model)

 

 

L

 

 

 

 

Refrigerant

Pipe size O.D.

 

Liquid

mm (in.)

 

Gas

mm (in.)

 

 

 

 

 

 

 

Connection method

Indoor side

 

 

Outdoor side

 

 

 

 

 

 

 

Between the indoor &

Height difference

 

outdoor units

 

Piping length

 

 

 

 

 

 

 

 

PLH-P3AAH.UK / PLH-P3AAH1.UK

Cooling

Heating

26,600

31,700 [38,900]

7,800

9,300 [11,400]

3.44

3.50 [5.60]

PLH-P3AAH.UK / PLH-P3AAH1.UK

Single phase, 50Hz, 220–230–240V

0.17

0.17 <2.10>

0.81

0.81 <8.75>

1.0

1.0 <8.75>

Munsell 0.70Y 8.59/0.97

Plate fin coil

Turbo fan (direct) o 1

0.070

15-16-18-20 (530-565-635-705)

0 (direct blow)

<2.1>

Remote controller & built-in

28-30-32-34

32 (1-1/4)

UNIT : 840 (33-1/16)

PANEL : 950 (37-3/8)

UNIT : 840 (33-1/16)

PANEL : 950 (37-3/8)

UNIT : 258 (10-1/2)

PANEL : 30 (1-3/16)

UNIT : 26 (57)

PANEL : 5 (11)

PUH-P3VGAA.UK / PUH-P3YGAA.UK

Single phase, 50Hz, 220–230–240V / 3 phases, 50Hz, 380–400–415V (4wires)

14.81/ 5.29

15.76/ 5.63

93/ 47

Munsell 5Y 7/1

Linear expansion valve

Hermetic

NE52VNJMT/ NE52YDJMT

2.5

Line start

Internal thermostat, HP switch, Discharge thermo. / Thermal relay , HPswitch, Discharge thermo.

Plate fin coil

Propeller (direct) o 1

0.070

50(1,770)

38

Reverse cycle

49

51

900 (35-7/16)

330+20 (13+3/4)

855 (33-5/8)

82 (181)

R407C

3.3(7.3)

1.3(Ester) MEL56 9.52 (3/8)

15.88 (5/8)

Flared

Flared

Max. 50m

Max. 50m

NOTE: 1.

Rating conditions (ISO T1)

 

 

 

 

Cooling : Indoor

: D.B. 27: (80˚F) W.B. 19: (66˚F)

Outdoor

: D.B. 35: (95˚F)

W.B. 24: (75˚F)

 

Heating : Indoor

: D.B. 20: (68˚F)

Outdoor

: D.B. 7: (45˚F)

W.B. 6: (43˚F)

 

Refrigerant piping length (one way) : 5m (16ft.)

 

 

 

2.

Guaranteed operating range

 

 

 

 

 

Indoor

Outdoor

 

Cooling

Upper limit

D.B. 35˚C,

W.B. 22.5˚C

D.B. 46˚C

 

 

Lower limit

D.B. 19˚C,

W.B. 15˚C

D.B. -5˚C

Heating

Upper limit

D.B. 28˚C

 

D.B. 24˚C, W.B. 18˚C

Lower limit

D.B. 17˚C

 

D.B. -11˚C, W.B. -12˚C

w1

: [ ] Shows the total rating.

w2

: < > Shows the only booster heater rating.

3. Above data based on indicated voltage

Indoor unit

Single phase 240V 50Hz

Outdoor unit

Single phase 240V 50Hz / 3 phases 415V 50Hz

14

Item

 

 

 

 

Service Ref.

 

 

 

 

 

 

Function

 

 

 

 

 

 

Capacity

 

w1

 

 

Btu/h

 

 

 

W

 

 

 

 

 

 

 

Total input

 

w1

 

 

kW

 

 

Service Ref.

 

 

 

 

 

 

Power supply (phase, cycle,voltage)

 

 

 

 

Input

 

 

w2

kW

 

 

 

Running current

w2

A

 

 

 

Starting current

w2

A

 

 

External finish

 

 

 

 

 

 

Heat exchanger

 

 

 

 

unit

 

 

Fan (drive) o No.

 

 

 

Fan

Fan motor output

 

kW

Indoor

 

Airflow (Lo-Mi2-Mi1-Hi)

K/ min (CFM)

 

 

 

 

 

 

 

 

External static pressure

Pa (mmAq)

 

 

Booster heater

 

 

 

kW

 

 

Operation control & Thermostat

 

 

 

Sound level (Lo-Mi2-Mi1-Hi)

dB

 

 

Unit drain pipe I.D.

 

 

mm (in.)

 

 

 

 

 

W

 

mm (in.)

 

 

Dimensions

 

D

 

mm (in.)

 

 

 

 

 

H

 

mm (in.)

 

 

Weight

 

 

 

 

kg (lbs.)

 

 

Service Ref.

 

 

 

 

 

 

Power supply (phase, cycle, voltage)

 

 

 

 

Running current

 

A

 

 

 

Starting current

 

A

 

 

External finish

 

 

 

 

 

 

Refrigerant control

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

Model

 

 

 

 

unit

 

 

Motor output

 

 

kW

 

 

Starter type

 

 

 

 

 

 

 

 

 

Outdoor

 

 

Protection devices

 

 

Heat exchanger

 

 

 

 

 

 

 

 

 

 

 

 

 

Fan (drive) o No.

 

 

 

 

Fan

Fan motor output

 

kW

 

 

 

Airflow

 

 

 

K/ min (CFM)

 

 

Crankcase heater

 

 

W

 

 

Defrost method

 

 

 

 

 

 

Sound level

 

Cooling

dB

 

 

 

Heating

dB

 

 

 

 

 

 

 

 

 

 

W

 

mm (in.)

 

 

Dimensions

 

D

 

mm (in.)

 

 

 

 

 

H

 

mm (in.)

 

 

Weight

 

 

 

 

kg (lbs.)

 

 

Refrigerant

 

 

 

 

piping

 

 

Charge

 

 

kg (lbs.)

 

 

Oil (Model)

 

 

L

 

 

 

 

 

Refrigerant

 

Pipe size O.D.

 

Liquid

mm (in.)

 

 

Gas

mm (in.)

 

 

 

 

 

 

 

 

 

 

Connection method

Indoor side

 

 

 

Outdoor side

 

 

 

 

 

 

 

 

 

Between the indoor &

Height difference

 

 

outdoor units

 

Piping length

 

 

 

 

 

 

 

 

 

PLH-P4AAH.UK / PLH-P4AAH1.UK

Cooling

Heating

33,100

36,200

[43,300]

9,700

10,600 [12,700]

3.69

3.93

[6.03]

PLH-P4AAH.UK / PLH-P4AAH1.UK

Single phase, 50Hz, 220–230–240V

0.26

 

0.26 <2.60>

1.25

 

1.25 <10.83>

2.0

 

2.0 <10.83>

Munsell 0.70Y 8.59/0.97

Plate fin coil

Turbo fan (direct) o 1

0.120

 

20-23-26-28 (705-810-920-990)

0 (direct blow)

<2.6>

 

Remote controller & built-in

33-36-39-41

32 (1-1/4)

UNIT : 840 (33-1/16)

PANEL : 950 (37-3/8)

UNIT : 840 (33-1/16)

PANEL : 950 (37-3/8)

UNIT : 298 (11-3/4)

PANEL : 30 (1-3/16)

UNIT : 32 (71)

PANEL : 5 (11)

PUH-P4VGAAH.UK / PUH-P4YGAA.UK

Single phase, 50Hz, 220–230–240V/ 3 phases, 50Hz, 380–400–415V (4wires)

15.71/ 5.55

16.58/ 5.86

99/ 49

Munsell 5Y 7/1

Linear expansion valve

Hermetic

NE56VNJMT/ NE56YDKMT

2.7

Line start

Internal thermostat, HP switch, Discharge thermo./ Thermal relay, HP switch, Discharge thermo.

Plate fin coil

Propeller (direct) o 2

0.070+0.070

85(3,000)

38

Reverse cycle

51

53

900 (35-7/16)

330+20 (13+3/4)

1,260 (49-5/8)

96 (212)

R407C

4.0(8.8)

1.3(Ester) MEL56 9.52 (3/8)

19.05 (3/4)

Flared

Flared

Max. 50m

Max. 50m

NOTE: 1. Rating conditions (ISO T1)

 

 

 

Cooling : Indoor

: D.B. 27: (80˚F), W.B. 19: (66˚F)

Outdoor

: D.B. 35: (95˚F)

W.B. 24: (75˚F)

Heating : Indoor

: D.B. 20: (68˚F)

Outdoor

: D.B. 7: (45˚F)

W.B. 6: (43˚F)

 

Refrigerant piping length (one way) : 5m (16ft.)

 

 

 

2. Guaranteed operating range

 

 

 

 

 

 

 

 

w1 : [ ] Shows the total rating.

 

 

 

Indoor

Outdoor

 

Cooling

Upper limit

D.B. 35: , W.B. 22.5:

D.B. 46:

w2 : < > Shows the only booster heater rating.

 

Lower limit

D.B. 19 :, W.B. 15:

D.B. -5:

3. Above data based on indicated voltage

 

 

 

 

Upper limit

D.B. 28:

D.B. 24: , W.B. 18:

 

Heating

Indoor unit

Single phase 240V 50Hz

 

Lower limit

D.B. 17:

D.B. -11:, W.B. -12:

 

Outdoor unit

Single phase 240V 50Hz/ 3 phases 415V 50Hz

 

 

 

 

 

15

Service Ref.

Item

Function

Capacity

 

w1

 

 

Btu/h

 

 

 

W

 

 

 

 

 

 

Total input

 

w1

 

 

k W

 

Service Ref.

 

 

 

 

 

Power supply (phase, cycle,voltage)

 

 

 

Input

 

 

w2

kW

 

 

Running current

w2

A

 

 

Starting current

w2

A

 

External finish

 

 

 

 

 

Heat exchanger

 

 

 

 

unit

 

Fan (drive) o No.

 

 

Fan

Fan motor output

 

kW

Indoor

Airflow (Lo-Mi2-Mi1-Hi)

K/ min (CFM)

 

 

 

 

 

External static pressure

Pa (mmAq)

 

Booster heater

 

 

 

kW

 

Operation control & Thermostat

 

 

Sound level (Lo-Mi2-Mi1-Hi)

dB

 

Unit drain pipe I.D.

 

 

mm (in.)

 

 

 

 

W

 

mm (in.)

 

Dimensions

 

D

 

mm (in.)

 

 

 

 

H

 

mm (in.)

 

Weight

 

 

 

 

kg (lbs.)

 

Service Ref.

 

 

 

 

 

Power supply (phase, cycle, voltage)

 

 

 

Running current

 

A

 

 

Starting current

 

A

 

External finish

 

 

 

 

 

Refrigerant control

 

 

 

 

Compressor

 

 

 

 

 

 

Model

 

 

 

 

unit

 

Motor output

 

 

kW

 

Starter type

 

 

 

 

 

 

 

 

Outdoor

 

Protection devices

 

Heat exchanger

 

 

 

 

 

 

 

 

 

 

 

Fan (drive) o No.

 

 

 

Fan

Fan motor output

 

kW

 

 

Airflow

 

 

 

K/ min (CFM)

 

Crankcase heater

 

 

W

 

Defrost method

 

 

 

 

 

Sound level

 

Cooling

dB

 

 

Heating

dB

 

 

 

 

 

 

 

 

W

 

mm (in.)

 

Dimensions

 

D

 

mm (in.)

 

 

 

 

H

 

mm (in.)

 

Weight

 

 

 

 

kg (lbs.)

 

Refrigerant

 

 

 

 

piping

 

Charge

 

 

kg (lbs.)

 

Oil (Model)

 

 

L

 

 

 

 

Refrigerant

Pipe size O.D.

 

Liquid

mm (in.)

 

Gas

mm (in.)

 

 

 

 

 

 

 

Connection method

Indoor side

 

 

Outdoor side

 

 

 

 

 

 

 

Between the indoor &

Height difference

 

outdoor units

 

Piping length

 

 

 

 

 

 

 

 

PLH-P5AAH.UK / PLH-P5AAH1.UK

Cooling

Heating

43,700

50,800

[61,100]

12,800

14,900

[17,900]

5.00

5.34

[8.34]

PLH-P5AAH.UK / PLH-P5AAH1.UK

Single phase, 50Hz, 220–230–240V

0.30

 

0.30 <3.00>

1.43

 

1.43 <12.50>

2.0

 

2.0 <12.50>

Munsell 0.70Y 8.59/0.97

Plate fin coil

Turbo fan (direct) o 1

0.120

 

22-25-28-30 (775-880-990-1,060)

0 (direct blow)

<3.0>

 

Remote controller & built-in

35-38-41-43

32 (1-1/4)

UNIT : 840 (33-1/16)

PANEL : 950 (37-3/8)

UNIT : 840 (33-1/16)

PANEL : 950 (37-3/8)

UNIT : 298 (11-3/4)

PANEL : 30 (1-3/16)

UNIT : 32 (71)

PANEL : 5 (11)

 

PUH-P5YGAA.UK

3 phases, 50Hz, 380–400–415V (4wires)

7.60

8.15

65.5

Munsell 5Y 7/1

Linear expansion valve

Hermetic

ZR61KCE-TFD

3.5

Line start

Internal thermostat,Thermal relay, HPswitch, Discharge thermo.

Plate fin coil

Propeller (direct) o 2

0.070+0.070

95 (3,360)

38

Reverse cycle

55

56

1,050 (41-5/16)

330+20 (13+3/4)

1,260 (49-5/8)

122 (269)

R407C

4.6 (10.1)

1.690 (Ester) MMMA-POE

9.52 (3/8)

19.05 (3/4)

Flared

Flared

Max. 50m

Max. 50m

NOTE: 1.

Rating conditions (ISO T1)

 

 

 

 

Cooling : Indoor

: D.B. 27: (80˚F), W.B. 19: (66˚F)

Outdoor

: D.B. 35: (95˚F)

W.B. 24: (75˚F)

 

Heating : Indoor

: D.B. 20: (68˚F)

Outdoor

: D.B. 7: (45˚F)

W.B. 6 : (43˚F)

 

Refrigerant piping length (one way) : 5m (16ft.)

 

 

 

2.

Guaranteed operating range

 

 

 

 

 

Indoor

Outdoor

Cooling

Upper limit

D.B. 35:, W.B. 22.5:

D.B. 46:

Lower limit

D.B. 19: , W.B. 15:

D.B. -5:

 

Heating

Upper limit

D.B. 28:

D.B. 24: , W.B. 18:

Lower limit

D.B. 17:

D.B. -11:, W.B. -12:

 

w1

: [ ] Shows the total rating.

w2

: < > Shows the only booster heater rating.

3. Above data based on indicated voltage

Indoor unit

Single phase 240V 50Hz

Outdoor unit

3 phases 415V 50Hz

16

Service Ref.

Item

Function

Capacity

 

w1

 

 

Btu/h

 

 

 

W

 

 

 

 

 

 

Total input

 

w1

 

 

kW

 

Service Ref.

 

 

 

 

 

Power supply (phase, cycle,voltage)

 

 

 

Input

 

 

w2

kW

 

 

Running current

w2

A

 

 

Starting current

w2

A

 

External finish

 

 

 

 

 

Heat exchanger

 

 

 

 

unit

 

Fan (drive) o No.

 

 

Fan

Fan motor output

 

kW

Indoor

Airflow (Lo-Mi2-Mi1-Hi)

K/ min (CFM)

 

 

 

 

 

External static pressure

Pa (mmAq)

 

Booster heater

 

 

 

kW

 

Operation control & Thermostat

 

 

Sound level (Lo-Mi2-Mi1-Hi)

dB

 

Unit drain pipe I.D.

 

 

mm (in.)

 

 

 

 

W

 

mm (in.)

 

Dimensions

 

D

 

mm (in.)

 

 

 

 

H

 

mm (in.)

 

Weight

 

 

 

 

kg (lbs.)

 

Service Ref.

 

 

 

 

 

Power supply (phase, cycle, voltage)

 

 

 

Running current

 

A

 

 

Starting current

 

A

 

External finish

 

 

 

 

 

Refrigerant control

 

 

 

 

Compressor

 

 

 

 

 

 

Model

 

 

 

 

unit

 

Motor output

 

 

kW

 

Starter type

 

 

 

 

 

 

 

 

Outdoor

 

Protection devices

 

Heat exchanger

 

 

 

 

 

 

 

 

 

 

 

Fan (drive) o No.

 

 

 

Fan

Fan motor output

 

kW

 

 

Airflow

 

 

 

K/ min (CFM)

 

Crankcase heater

 

 

W

 

Defrost method

 

 

 

 

 

Sound level

 

Cooling

dB

 

 

Heating

dB

 

 

 

 

 

 

 

 

W

 

mm (in.)

 

Dimensions

 

D

 

mm (in.)

 

 

 

 

H

 

mm (in.)

 

Weight

 

 

 

 

kg (lbs.)

 

Refrigerant

 

 

 

 

piping

 

Charge

 

 

kg (lbs.)

 

Oil (Model)

 

 

L

 

 

 

 

Refrigerant

Pipe size O.D.

 

Liquid

mm (in.)

 

Gas

mm (in.)

 

 

 

 

 

 

 

Connection method

Indoor side

 

 

Outdoor side

 

 

 

 

 

 

 

Between the indoor &

Height difference

 

outdoor units

 

Piping length

 

PLH-P6AAH.UK / PLH-P6AAH1.UK

Cooling

Heating

48,000

58,300

[68,600]

14,300

17,100

[20,100]

5.94

6.36

[9.36]

PLH-P6AAH.UK / PLH-P6AAH1.UK

Single phase, 50Hz, 220–230–240V

0.34

 

0.34 <3.00>

1.64

 

1.64 <12.50>

2.0

 

2.0 <12.50>

Munsell 0.70Y 8.59/0.97

Plate fin coil

Turbo fan (direct) o 1

0.120

 

22-25-28-30 (775-880-990-1,060)

0 (direct blow)

<3.0>

 

Remote controller & built-in

37-40-43-45

32 (1-1/4)

UNIT : 840 (33-1/16)

PANEL : 950 (37-3/8)

UNIT : 840 (33-1/16)

PANEL : 950 (37-3/8)

UNIT : 298 (11-3/4)

PANEL : 30 (1-3/16)

UNIT : 34 (75)

PANEL : 5 (11)

 

PUH-P6YGAA.UK

3 phases, 50Hz, 380–400–415V (4wires)

9.03

9.56

74

Munsell 5Y 7/1

Linear expansion valve

Hermetic

ZR72KCE-TFD

4.2

Line start

Internal thermostat, Thermal relay, HP switch, Discharge thermo.

Plate fin coil

Propeller (direct) o 2

0.070+0.070

100(3,530)

38

Reverse cycle

57

58

1,050 (41-5/16)

330+20(13+3/4)

1,260 (49-5/8)

122 (269)

R407C

4.9 (10.8)

1.774 (Ester) MMMA-POE

9.52 (3/8)

19.05 (3/4)

Flared

Flared

Max. 50m

Max. 50m

NOTE: 1.

Rating conditions (ISO T1)

 

 

 

 

Cooling : Indoor

: D.B. 27: (80˚F), W.B. 19: (66˚F)

Outdoor

: D.B. 35: (95˚F)

W.B. 24: (75˚F)

 

Heating : Indoor

: D.B. 20: (68˚F)

Outdoor

: D.B. 7: (45˚F)

W.B. 6 : (43˚F)

 

Refrigerant piping length (one way) : 5m (16ft.)

 

 

 

2.

Guaranteed operating range

 

 

 

 

 

Indoor

Outdoor

Cooling

Upper limit

D.B. 35:, W.B. 22.5:

D.B. 46:

Lower limit

D.B. 19: , W.B. 15:

D.B. -5:

 

Heating

Upper limit

D.B. 28:

D.B. 24: , W.B. 18:

Lower limit

D.B. 17:

D.B. -11:, W.B. -12:

 

w1

: [ ] Shows the total rating.

w2

: < > Shows the only booster heater rating.

3. Above data based on indicated voltage

Indoor unit

Single phase 240V 50Hz

Outdoor unit

3 phases 415V 50Hz

17

6 DATA

1.PERFORMANCE DATA

1.1COOLING CAPACITY (1)

PLH-P3AAH.UK / PUH-P3VGA, PUH-P3YGA

 

 

 

 

 

 

 

 

(240V)

Indoor

Indoor

 

 

 

 

 

Outdoor intake air DB (:)

 

 

 

 

 

intake air

intake air

 

 

20

 

 

 

 

25

 

 

 

30

 

DB (:)

WB (:)

CA

SHC

 

SHF

P.C.

CA

 

SHC

 

SHF

P.C.

CA

SHC

 

SHF

P.C.

20

16

7,722

4,942

 

0.64

2.81

7,488

 

4,792

 

0.64

2.97

7,254

4,643

 

0.64

3.14

20

18

8,268

4,299

 

0.52

2.86

8,034

 

4,178

 

0.52

3.02

7,761

4,036

 

0.52

3.23

20

20

8,892

3,557

 

0.40

2.95

8,697

 

3,479

 

0.40

3.09

8,463

3,385

 

0.40

3.30

22

16

7,722

5,560

 

0.72

2.81

7,488

 

5,391

 

0.72

2.97

7,254

5,223

 

0.72

3.14

22

18

8,268

4,961

 

0.60

2.86

8,034

 

4,820

 

0.60

3.02

7,761

4,657

 

0.60

3.23

22

20

8,892

4,268

 

0.48

2.95

8,697

 

4,175

 

0.48

3.09

8,463

4,062

 

0.48

3.30

24

16

7,722

6,178

 

0.80

2.81

7,488

 

5,990

 

0.80

2.97

7,254

5,803

 

0.80

3.14

24

18

8,268

5,622

 

0.68

2.86

8,034

 

5,463

 

0.68

3.02

7,761

5,277

 

0.68

3.23

24

20

8,892

4,980

 

0.56

2.95

8,697

 

4,870

 

0.56

3.09

8,463

4,739

 

0.56

3.30

24

22

9,477

4,170

 

0.44

3.02

9,282

 

4,084

 

0.44

3.19

9,048

3,981

 

0.44

3.40

26

16

7,722

6,795

 

0.88

2.81

7,488

 

6,589

 

0.88

2.97

7,254

6,384

 

0.88

3.14

26

18

8,268

6,284

 

0.76

2.86

8,034

 

6,106

 

0.76

3.02

7,761

5,898

 

0.76

3.23

26

20

8,892

5,691

 

0.64

2.95

8,697

 

5,566

 

0.64

3.09

8,463

5,416

 

0.64

3.30

26

22

9,477

4,928

 

0.52

3.02

9,282

 

4,827

 

0.52

3.19

9,048

4,705

 

0.52

3.40

28

16

7,722

7,413

 

0.96

2.81

7,488

 

7,188

 

0.96

2.97

7,254

6,964

 

0.96

3.14

28

18

8,268

6,945

 

0.84

2.86

8,034

 

6,749

 

0.84

3.02

7,761

6,519

 

0.84

3.23

28

20

8,892

6,402

 

0.72

2.95

8,697

 

6,262

 

0.72

3.09

8,463

6,093

 

0.72

3.30

28

22

9,477

5,686

 

0.60

3.02

9,282

 

5,569

 

0.60

3.19

9,048

5,429

 

0.60

3.40

30

16

7,722

7,722

 

1.00

2.81

7,488

 

7,488

 

1.00

2.97

7,254

7,254

 

1.00

3.14

30

18

8,268

7,607

 

0.92

2.86

8,034

 

7,391

 

0.92

3.02

7,761

7,140

 

0.92

3.23

30

20

8,892

7,114

 

0.80

2.95

8,697

 

6,958

 

0.80

3.09

8,463

6,770

 

0.80

3.30

30

22

9,477

6,444

 

0.68

3.02

9,282

 

6,312

 

0.68

3.19

9,048

6,153

 

0.68

3.40

32

16

7,722

7,722

 

1.00

2.81

7,488

 

7,488

 

1.00

2.97

7,254

7,254

 

1.00

3.14

32

18

8,268

8,268

 

1.00

2.86

8,034

 

8,034

 

1.00

3.02

7,761

7,761

 

1.00

3.23

32

20

8,892

7,825

 

0.88

2.95

8,697

 

7,653

 

0.88

3.09

8,463

7,447

 

0.88

3.30

32

22

9,477

7,203

 

0.76

3.02

9,282

 

7,054

 

0.76

3.19

9,048

6,876

 

0.76

3.40

34

16

7,722

7,722

 

1.00

2.81

7,488

 

7,488

 

1.00

2.97

7,254

7,254

 

1.00

3.14

34

18

8,268

8,268

 

1.00

2.86

8,034

 

8,034

 

1.00

3.02

7,761

7,761

 

1.00

3.23

34

20

8,892

8,536

 

0.96

2.95

8,697

 

8,349

 

0.96

3.09

8,463

8,124

 

0.96

3.30

34

22

9,477

7,961

 

0.84

3.02

9,282

 

7,797

 

0.84

3.19

9,048

7,600

 

0.84

3.40

NOTE:

CA: Capacity (W)

 

 

 

SHC: Sensible heat capacity (W)

 

 

 

 

 

 

 

P.C.: Power consumption (kW)

SHF: Sensible heat factor

 

 

 

 

 

 

 

 

18