Mitsubishi PMFY-P20VBM, PMFY-P25VBM, PMFY-P32VBM, PMFY-P40VBM SERVICE MANUAL

0 (0)

2000

SPLIT-TYPE,HEAT PUMP AIR CONDITIONERS

No. OC220

TECHNICAL & SERVICE MANUAL

Series PMFY Ceiling Cassettes R407C R22

Indoor unit

 

[Model names]

[Service Ref.]

PMFY-P20VBM

PMFY-P25VBM

PMFY-P32VBM

PMFY-P40VBM

PMFY-P20VBM PMFY-P25VBM PMFY-P32VBM PMFY-P40VBM

CONTENTS

1. SAFETY PRECAUTION ·······················2

2. PART NAMES AND FUNCTIONS ········4

3. SPECIFICATION ···································6

4. OUTLINES AND DIMENSIONS··········10

5. WIRING DIAGRAM ·····························11

6. REFRIGERANT SYSTEM DIAGRAM ···12

7. TROUBLE SHOOTING·······················13

8. DISASSEMBLY PROCEDURE···········19

9. PARTS LIST········································22

INDOOR UNIT

1 SAFETY PRECAUTION

Cautions for devices that use R407C refrigerant.

·Do not use the existing refrigerant piping.

-The old refrigerant and refrigerator oil in the existing piping contains a large amount of chlorine which may cause the refrigerator oil of the new unit to deteriorate.

·Use “low residual oil piping”.

-If there is a large amount of residual oil (hydraulic oil, etc.) inside the piping and joints, deterioration of the refrigerator oil will result.

·Store the piping to be used during installation indoors and keep both ends of the piping sealed until just before brazing. (Store elbows and other joints in a plastic bag.)

-If dust, dirt, or water enters the refrigerant cycle, deterioration of the oil and compressor trouble may result.

·Use Suniso 4GS or 3GS (small amount) as the refrigerator oil to coat flares and flange connection parts.

-The refrigerator oil used with the air conditioner is highly hygroscopic. If it is used, water may be mixed in and deterioration of the refrigerator oil may result.

·Use liquid refrigerant to seal the system.

-If gas refrigerant is used to seal the system, the composition of the refrigerant in the cylinder will change and performance may drop.

·Do not use a refrigerant other than R407.

-If another refrigerant (R22, etc.) is used, the chlorine in the refrigerant may cause the refrigerator oil to deteriorate.

·Use a vacuum pump with a reverse flow check valve.

-The vacuum pump oil may flow back into the refrigerant cycle and cause the refrigerator oil to deteriorate.

2

[1] Service tools

Use the below service tools as exclusive tools for R407C refrigerant.

No.

Tool name

Specifications

1

Gauge manifold

·Only for R407C.

 

 

·Use the existing fitting SPECIFICATIONS. (UNF7/16)

 

 

·Use high-tension side pressure of 35kgf/cm or over.

 

 

2

2

Charge hose

·Only for R407C.

 

 

·Use pressure performance of 52kgf/cm or over.

3

Electronic scale

 

4

Gas leak detector

·Use the detector for R134a or R407C.

5

Adapter for reverse flow check.

·Attach on vacuum pump.

6

Refrigerant charge base.

 

7

Refrigerant cylinder.

·For R407C·Top of cylinder (Brown)

 

 

·Cylinder with syphon

8

Refrigerant recovery equipment.

 

[2] Notice on repair service

·After recovering the all refrigerator in the unit, proceed to working. ·Do not release the refrigerant in the air.

·After complete the repair service, recharge the cycle with the specified amount of the liquid refrigerant.

[3] Refrigerant recharging

(1) Refrigerant recharging process

1Direct enclosure from the bomb.

·Confirm that R407C bomb on the market are syphon pipe.

·Leave the syphon pipe bomb raising and recharge it. (By liquid refrigerant)

Unit

Gravimeter

(2) Recharge in refrigerant leakage case

·After recovering the all refrigerator in the unit, proceed to working. ·Do not release the refrigerant in the air.

·After complete the repair service, recharge the cycle with the specified amount of the liquid refrigerant.

3

2 PART NAMES AND FUNCTIONS

Indoor (Main) Unit

Auto Air Swing Vane

Disperses airflow up and down and adjusts the angle of airflow direction.

Horizontal Air Outlet

Guide vane

Air flow can be changed to horinzontally

by moving the Guide vane to the left or right.

Filters

Air intake

Remove dust and pollutants

Inhales air from room.

from inhaled air.

 

Remote controller

[PAR-F25MA]

 

● Once the controls are set, the same operation mode can

 

be repeated by simply pressing the ON/OFF button.

Operation buttons

 

TIMER button

This switches between continuous operation and the timer operation.

OPERATION SWITCH button

Press this button to switch the cooler electronic dry (dehumidify) automatic and heater modes.

TIME SETTING button

This sets of switches the current time, start time and stop time.

AIR SPEED button

This sets the ventilation fan speed.

ON/OFF button

This switches between the operation and stop modes each time it is pressed. The lamp on this button lights during operation.

TEMP. ADJUSTMENT button

This sets the room temperature the temperature setting can be performed in 1: units

Setting range

Cooler 19: to 30: Heater 17: to 28:

LOUVER button

This switch the horizontal fan motion

NO and OFF.

(This button does not operate in this model)

AIR DIRECTION button

This adjusts the vertical angle of the ventilation.

FILTER button

This resets the filter service indication display

CHECK-TEST RUN button

Only press this button to perform an inspection check or test operation. Do not use it for normal operation.

4

Display

CENTRALLY CONTROLLED display

This indicates when the unit is controlled by optional features such as central control type remote controller.

TIMER display

This indicates when the continuous operation and time operation modes are set.

It also display the time for the timer operation at the same time as when it is set.

OPERATION MODE display

This indicates the operation mode.

STANDBY display

This indicates when the standby mode is set from the time the sleep operation starts until the heating air is discharged.

DEFROST display

This indicates when the defrost operation is performed.

CLOCK display

In this display example on the bot-

tom left, a condition where all dis-

 

The current time , start time and stop

play lamps light is shown for expla-

time can be displayed in ten second

nation purposes although this differs

intervals by pressing the time switch

from actual operation.

button. The start time or stop time is

 

always displayed during the timer

 

operation.

 

 

AIR DIRECTION display

 

The selected fan speed is displayed.

 

FAN SPEED display

 

This displays the air direction.

 

ROOM TEMPERATURE display

 

The temperature of the suction air is

 

displayed during operation. The dis-

 

play range is 8° to 39°C. The display

 

flashes 8°C when the actual temper-

 

ature is less than 8° and flashes

 

39°C when the actual temperature is

 

greater than 39°C.

 

Operation lamp

5

This lamp lights during operation,

 

goes off when the unit stops and

 

flashes when a malfunction occurs.

 

CHECK MODE

 

display

 

TEST RUN

 

This display lights in the check mode

 

or when a test operation is per-

 

formed.

CHECK display

 

 

 

 

 

 

SET TEMPERATURE display

 

POWER display

This indicates when a malfunction

 

 

 

 

 

 

has occurred in the unit which should

 

This displays the selected setting

 

This lamp lights when electricity is

be checked.

 

 

 

temperature.

 

supplied to the unit.

 

 

 

 

 

 

 

 

Caution

FILTER display

This lamp lights when the filter need to be cleaned.

Only the Power display lights when the unit is stopped and power supplied to the unit.

When the central control remote control unit, which is sold separately, is used the ON-OFF button, operation switch button and TEMP. adjustment button do not operate.

“NOT AVAILABLE” is displayed when the Air speed button are pressed.This indicates that this room unit is not equipped with the fan direction adjustment function and the louver function.

When power is turned ON for the first time, it is normal that “H0” is displayed on the room temperature indication (For max. 2minutes). Please wait until this “H0” indication disappear then start the operation.

5

3 SPECIFICATION

3-1. Specification

Item

Power

Cooling capacity

Heating capacity

characteristic

Input

Cooling

 

 

 

 

 

Heating

 

Current

Cooling

 

 

Electric

 

Heating

factor

Heating

 

Power

Cooling

Exterior (munsell symbol)

Height

Dimensions Width

Depth

Heat exchanger

 

Fan No

F

Air flow #3

a

External

n

static pressure

 

Fan motor

 

output

 

Insulator

Air filter

Gas

Pipe side

dimensions Liquid side

Unit drain pipe size

Noise level #3

Product weight

 

PMFY-P20VBM

PMFY-P25VBM

PMFY-P32VBM

PMFY-P40VBM

V·Hz

 

Single phase 220V-240V 50 Hz/220V 60Hz

 

kcal/h

2,000

2,500

3,150

4,000

 

 

 

 

 

kW

2.3

2.9

3.7

4.7

 

 

 

 

 

Btu/h

7,900

9,900

12,500

15,900

kcal/h

2,250

2,800

3,550

4,500

 

 

 

 

 

kW

2.6

3.3

4.1

5.2

 

 

 

 

 

Btu/h

8,900

11,100

14,100

17,900

kW

0.042

0.044

0.044

0.054

kW

0.042

0.044

0.044

0.054

A

0.20

0.21

0.21

0.26

A

0.20

0.21

0.21

0.26

%

95—88

95—87

95—87

94—87

%

95—88

95—87

95—87

94—87

 

-Unit : Galvanized sheets · Standard grills : ABS resin acrylic coating

Munsell<0.98Y 8.99/0.63>

mm

 

 

230<30>

 

mm

 

854<1,000>

 

mm

 

395<470>

 

 

 

 

Cross fin

 

 

 

Line flow fan 1

 

k/min

8.7-8.0-7.2-6.5

9.3-8.6-8.0-7.3

10.7-9.7-8.7-7.7

Pa

 

 

0

 

kW

 

 

0.028

 

 

 

Polyethylene sheet

 

 

 

PP honeycomb fabric

 

[mm

 

12.7(1/2")

 

[mm

 

6.35(1/4")

 

[mm

 

O.D.25 (PVC pipe VP-20 connectable)

 

dB

35-33-30-27

37-36-34-32

39-37-35-33

kg

 

14<3.0>

 

 

 

 

 

 

 

Note 1.

Rating conditions

 

 

 

Cooling:

Indoor:

D.B. 27°C

W.B. 19.5°C

 

 

outdoor:

D.B. 35°C

 

 

Heating:

Indoor:

D.B. 21°C

 

 

 

outdoor:

D.B. 7°C

W.B. 6°C

Note 2.

The number indicated in < > is just for the grille.

Note 3.

Air flow and the noise level are indicated as High-Middium 1-Middium 2-Low.

6

3-2. Air capacity taken from outside

PMFY-P·VBM series are possible to be taken air from outside. When taking air from the outside, the duct fan can be used to. The air capacity should be 20% or less of the air flow SPEC(Hi).

250 288.5

90-

4-{2.8

 

 

100

 

 

{

 

 

108

 

 

{

 

 

122

 

Flesh air intake hole

Flesh air intake hole

 

(Knock out)

(Knock out)

 

Air flow

Air capacity taken outside

 

(Hi)

 

 

PMFY-P20VBM

8.7m3/min

Max 1.74m3/min

PMFY-P25VBM

9.3m3/min

Max 1.86m3/min

PMFY-P32VBM

9.3m3/min

Max 1.86m3/min

PMFY-P40VBM

10.7m3/min

Max 2.14m3/min

Interlocking operation method with duct fan (Booster fan)

●Whenever the indoor unit is operating, the duct fun also operates.

(1)Connect the optional multiple remote controller adapter(PAC-SA88HA-E)to the connector CN51 on the indoor controller board.

(2)Drive the relay after connecting the 12V DC relay between the Yellow and Orange connector lines.

(w)Use a relay under 1W.

MB: Electromagnetic switch power relay for duct fan. X: Auxiliary relay (12V DC LY-1F)

 

 

 

Be sure to secure insulation

~

 

 

 

 

 

 

 

material by tape and such

 

CN51

5

Green

 

 

on

 

 

Yellow

 

 

indoor unit

 

 

 

 

1

 

Orange

 

MB

board

 

 

 

Connector (5P)

Red

 

 

 

Package side

Brown

 

 

 

Multiplr remote

Installation at site

 

 

 

 

 

 

 

 

 

 

 

controller adapter

Be sure to secure insulation

Indoor controller board

 

PAC-SA88HA-E

material by tape and such

 

 

 

 

Distance between indoor controller board and relay must be within 10m.

Multiple remote controller adapter PAC-SA88HA-E

CN51

How to read curves

 

Curve in the

Duct characteristics

1

at site

 

 

left praphs.

 

 

0

 

A

C

 

 

 

Q

B

 

 

 

 

2

C A

E

Q

3

D

A

Q

Qa

Q…Planned amount of fresh air intake <m3/min>

A…Static pressure loss of fresh air intake duct system with air flow amount Q <mmAq>

B…Forced static pressure at air condi - tioner inlet with air flow amount Q <mmAq>

C…Static pressure of booster fan with

air flow amount Q

<mmAq>

D…Static pressure loss

increase

amount of fresh air intake dust system for air flow amount Q

<mmAq> E…Static pressure of indoor unit with

air flow amount Q <mmAq> Qa…Estimated amount of fresh air

intake with out D <m3/min>

Characteristic diagram of air capacity taken from outside of PMFY-P·VBM

(Pa)

50.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.0

 

 

 

 

 

 

 

 

 

 

 

pressure

 

 

 

 

 

 

 

 

 

2 intakes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 intake

 

Static

 

 

 

 

 

 

 

 

 

 

 

-50.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-100.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

2.0

2.5

 

0.0

0.5

1.0

 

 

 

 

 

Air flow (m3/min)

 

 

 

 

7

Mitsubishi PMFY-P20VBM, PMFY-P25VBM, PMFY-P32VBM, PMFY-P40VBM SERVICE MANUAL

3-3. NOISE CRITERION CURVES

PMFY-P20VBM

 

 

NOTCH

SPL(dB)

LINE

 

 

 

 

 

 

Hi

35

 

 

 

 

 

 

 

Mi1

33

 

 

 

 

 

 

 

Mi2

30

 

 

 

 

 

 

 

Lo

27

 

 

90

 

 

 

 

 

 

 

BAR

80

 

 

 

 

 

 

 

MICRO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.002

70

 

 

 

 

 

 

NC-70

 

 

 

 

 

 

 

dB re

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEVEL,

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-60

 

 

 

 

 

 

 

 

PRESSURE

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

40

 

 

 

 

 

 

 

SOUND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-40

 

 

 

 

 

 

 

 

BAND

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-30

OCTAVE

20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-20

 

 

 

 

 

 

 

 

 

APPROTIMATE TERESHOLD OF REARING

 

 

 

 

 

FOR CONTINUOUS NOISE

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

63

125

250

500

1000

2000

4000

8000

BAND CENTER FREQUENCIES, Hz

PMFY-P40VBM

 

 

NOTCH

SPL(dB)

LINE

 

 

 

 

 

 

 

Hi

39

 

 

 

 

 

 

 

 

Mi1

37

 

 

 

 

 

 

 

 

Mi2

35

 

 

 

 

 

 

 

 

Lo

33

 

 

90

 

 

 

 

 

 

 

 

BAR

80

 

 

 

 

 

 

 

 

MICRO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.002

70

 

 

 

 

 

 

 

NC-70

 

 

 

 

 

 

 

 

dB re

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEVEL,

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-60

 

 

 

 

 

 

 

 

 

PRESSURE

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

40

 

 

 

 

 

 

 

 

SOUND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-40

 

 

 

 

 

 

 

 

 

BAND

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-30

OCTAVE

20

APPROTIMATE

 

 

 

 

 

 

 

TERESHOLD OF

 

 

 

 

 

 

 

REARING FOR

 

 

 

 

 

NC-20

 

 

 

 

 

 

 

 

 

CONTINUOUS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOISE

 

 

 

 

 

 

 

 

10

63

125

250

500

1000

2000

4000

8000

 

 

BAND CENTER FREQUENCIES, Hz

PMFY-P25VBM

 

 

NOTCH

SPL(dB)

LINE

PMFY-P32VBM

 

 

 

Hi

37

 

 

 

 

Mi1

36

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Mi2

34

 

 

 

 

 

 

 

 

Lo

32

 

 

90

 

 

 

 

 

 

 

 

BAR

80

 

 

 

 

 

 

 

 

MICRO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.002

70

 

 

 

 

 

 

 

NC-70

 

 

 

 

 

 

 

 

dB re

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEVEL,

60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-60

 

 

 

 

 

 

 

 

 

PRESSURE

50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-50

40

 

 

 

 

 

 

 

 

SOUND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-40

 

 

 

 

 

 

 

 

 

BAND

30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC-30

OCTAVE

20

APPROTIMATE

 

 

 

 

 

 

 

TERESHOLD OF

 

 

 

 

 

 

 

REARING FOR

 

 

 

 

 

NC-20

 

 

 

 

 

 

 

 

 

CONTINUOUS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOISE

 

 

 

 

 

 

 

 

10

63

125

250

500

1000

2000

4000

8000

 

 

BAND CENTER FREQUENCIES, Hz

UNIT

CEILING

1.5m

MICROPHON

Ambient temperature 27:

Test conditions are based on JIS Z8731

8