Mitsubishi PU-1.6VLJA2, PU-2NJA1, PU-2VJA2, PU-2.5NJA1, PU-2.5VJA2 Service Manual

...
0 (0)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1997

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPLIT-TYPE AIR CONDITIONERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No.OC127

TECHNICAL & SERVICE MANUAL

Outdoor unit [Model names]

PU-1.6VLJA PU-2VJA PU-2NJA PU-2.5VJA PU-2.5NJA PU-3VJA PU-3YJA PU-3NJA PU-4VLJSA PU-4YJSA PU-4TJSA

[Service Ref.]

PU-1.6VLJA2 PU-2VJA2 PU-2NJA1 PU-2.5VJA2 PU-2.5NJA1 PU-3VJA2 PU-3YJA2 PU-3NJA1 PU-4VLJSA2 PU-4YJSA2 PU-4TJSA1

CONTENTS

 

1. COMBINATION OF INDOOR AND OUTDOOR UNITS ·····3

 

2. PART NAMES AND FUNCTIONS·····················3

 

3.

DATA··································································4

 

4. OUTLINES AND DIMENSIONS ························6

 

5.

WIRING DIAGRAM ···········································9

 

6. REFRIGERANT SYSTEM DIAGRAM·············12

Outdoor unit

7. DISASSEMBLY PROCEDURE ·······················13

8. PARTS LIST ····················································15

PU-3J

9. OPTIONAL PARTS ··························Back cover

 

The Slim Line.

From Mitsubishi Electric.

1 COMBINATION OF INDOOR AND OUTDOOR UNITS

Indoor unit

 

 

 

 

Outdoor unit

 

 

 

 

Service

Service

PU-1.6

PU-2

PU-2.5

 

PU-3

 

 

PU-4

 

 

 

 

 

 

 

 

 

 

 

Ref.

Manual No.

VLJA2

VJA2

NJA1

VJA2 NJA1 VJA2

YJA2

NJA1

VLJA2

YJA2

TJA1

 

 

PL-GJ(S)B1

OC138

_

_

_

_

_

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PL-KJC

OC125

 

 

 

 

_

_

_

_

_

_

 

 

 

 

 

 

 

 

 

 

PC-GJ(S)A1

OC134

_

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PE-EJH(S)A1

OC131

_

_

_

_

_

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PS-GJ(S)1

OC143

_

_

_

_

_

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PS-GJ(S)A1

OC141

_

_

_

_

_

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PK-1.6/2FLA3

OC129

 

 

 

 

 

 

 

 

 

 

PK-2.5/3/4FLSA2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 PART NAMES AND FUNCTIONS

Outdoor Unit

Air outlet

Air outlet

(Expels warm air during cooling)

 

Air intake

Air intake

PU-1.6VLJA2

PU-2VJA2

PU-2NJA1

PU-2.5VJA2 PU-2.5NJA1 PU-3VJA2 PU-3YJA2 PU-3NJA1

Air outlet

Air intake

PU-4VLJSA2

PU-4YJSA2

PU-4TJSA2

wUnit of pressure is based on ISO (International Standardization Organization) [kgf/cm2] [Mpa] (1MPa=10.2kgf/cm2)

3

3 DATA

1. ELECTRICAL SPECIFICATIONS

(1) Rating conditions

Indoor : 27˚C(80˚F)DB,19˚C(66˚F)WB ●JIS B 8616 Outdoor : 35˚C(95˚F)DB,24˚C(75˚F)WB

Power supply (1 phase)

 

 

V : 220V 50Hz

 

 

 

 

 

 

 

 

 

V : 230V 50Hz

 

Service Ref.

 

PU-1.6VLJA2

 

PU-2VJA2

 

PU-2.5VJA2

 

PU-1.6VLJA2

 

PU-2VJA2

 

PU-2.5VJA2

Current

A

6.7

 

11.3

 

 

11.4

 

 

 

6.7

 

11.0

 

11.0

Input

kW

1.42

 

2.44

 

 

2.46

 

 

 

1.47

 

2.46

 

2.49

Starting current

A

30

 

48

 

 

45

 

 

 

 

32

 

50

 

47

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply (1 phase)

 

 

V : 240V 50Hz

 

 

 

 

 

 

 

N : 220V 60Hz

 

 

Service Ref.

 

PU-1.6VLJA2

 

PU-2VJA2

 

PU-2.5VJA2

 

PU-2NJA1

 

PU-2.5NJA1

 

 

Current

A

6.9

 

10.8

 

 

10.7

 

 

 

11.4

 

13.4

 

 

Input

kW

1.52

 

2.48

 

 

2.52

 

 

 

2.45

 

2.91

 

 

Starting current

A

33

 

52

 

 

49

 

 

 

 

54

 

58

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply (1 phase)

V : 220V 50Hz

 

 

V : 230V 50Hz

 

 

V : 240V 50Hz

N : 220V 60Hz

Service Ref.

 

PU-3VJA2

PU-4VLJSA2

 

PU-3VJA2

 

PU-4VLJSA2

 

PU-3VJA2

 

PU-4VLJSA2

PU-3NJA2

Current

A

15.1

16.9

 

14.4

 

16.6

 

 

13.9

 

 

16.3

 

17.6

Input

kW

3.18

3.35

 

3.19

 

3.44

 

 

3.20

 

 

3.52

 

3.44

Starting current

A

68

79

 

68

 

79

 

 

68

 

 

79

 

80

 

 

 

 

 

 

 

 

 

 

Power supply (3 phase)

Y : 380/220V 50Hz

 

Y : 400/230V 50Hz

 

 

 

 

 

Service Ref.

 

PU-3YJA2

 

PU-4YJSA2

 

PU-3YJA2

PU-4YJSA2

 

 

 

 

 

Current

A

5.7

5.7

 

5.4

 

 

 

5.5

 

 

 

 

 

Input

kW

3.18

3.29

 

3.19

 

 

 

3.33

 

 

 

 

 

Starting current

A

36

38

 

36

 

 

 

 

38

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply (3 phase)

Y : 415/240V 50Hz

 

T : 200V 60Hz

 

 

 

 

 

 

 

 

 

Service Ref.

 

PU-3YJA2

 

PU-4YJSA2

 

PU-4TJSA1

 

 

 

 

 

 

 

 

 

Current

A

5.3

 

5.5

 

 

12.2

 

 

 

 

 

 

 

 

 

 

Input

kW

3.20

 

3.36

 

 

4.27

 

 

 

 

 

 

 

 

 

 

Starting current

A

36

 

38

 

 

69

 

 

 

 

 

 

 

 

 

 

 

●SSA 385,386

Indoor

: 29˚C(84˚F)DB,19˚C(66˚F)WB

Outdoor : 46˚C(115˚F)DB,24˚C(75˚F)WB

 

 

 

 

 

 

 

 

Power supply

 

 

 

N : 220V (1 phase) 60Hz

 

Service Ref.

 

 

 

PU-2NJA1

PU-2.5NJA1

 

Current

 

A

 

13.6

15.8

 

Input

 

kW

 

2.97

3.44

 

Starting current

 

A

 

54

58

 

 

 

 

 

 

 

 

Power supply

 

 

 

N : 220V (1 phase) 60Hz

T : 220V (3 phase) 60Hz

 

Service Ref.

 

 

 

PU-3NJA1

PU-4TJSA1

 

Current

 

A

20.9

14.0

 

Input

 

kW

4.09

4.97

 

Starting current

 

A

80

69

2. POWER SUPPLY & MODEL NAMES

Power supply

Service Ref. (indoor unit)

 

 

Model name (outdoor unit)/Service Ref.

 

PU-1.6

PU-2

PU-2.5

PU-3

PU-4

 

 

 

50Hz

1ph.

220, 230, 240V

PU-1.6VLJA2

PU-2VJA2

PU-2.5VJA2

PU-3VJA2

PU-4VLJSA2

3ph.

380/220, 400/230, 415/240V

_

 

_

_

PU-3YJA2

PU-4YJSA2

60Hz

1ph.

220V

_

 

PU-2NJA1

PU-2.5NJA1

PU-3NJA1

_

 

 

 

3ph.

220V

_

 

_

 

_

PU-4TJSA1

 

 

 

 

 

 

Notes : 1.Power supply key N1ph,220V,60Hz

 

Y3ph,380/220,400/230,

 

 

 

 

V(L)1ph,220,230,240V,50Hz

415/240V,50Hz,4 wires

 

 

 

 

T3ph,220V,60Hz

 

 

 

 

 

 

4

2. COMPRESSOR TECHNICAL DATA

Compressor

 

Winding resistance(").

 

at 20:

Outdoor unit

 

 

 

 

R-C/U-V

S-C/V-W

W-U

 

Service Ref.

 

 

 

 

 

 

 

 

RH247VFC

2.00

4.55

 

PU-1.6VLJA2

 

 

 

 

 

 

NHJ33NBD

0.70

1.44

 

PU-2NJA1

 

 

 

 

 

 

NHJ41VMD

0.92

2.44

 

PU-2VJA2

 

 

 

 

 

 

NHJ38NBD

0.70

1.42

 

PU-2.5NJA1

 

 

 

 

 

 

NHJ41VMD

0.92

2.44

 

PU-2.5VJA2

 

 

 

 

 

 

NHJ52VND

0.83

2.03

 

PU-3VJA2

 

 

 

 

 

 

NHJ52YDA

3.68

3.68

 

PU-3YJA2

 

 

 

 

 

 

NHJ47NAD

0.58

1.14

3.68

 

PU-3NJA1

 

 

 

 

 

 

NH56VND

0.64

1.55

 

PU-4VLJSA2

 

 

 

 

 

 

NHJ56YDA

3.30

3.30

3.30

 

PU-4YJSA2

 

 

 

 

 

 

NHJ56TKA

0.83

0.83

0.83

 

PU-4TJSA2

 

 

 

 

 

 

3. ADDITIONAL REFRIGERANT CHARGE (R-22……kg (lbs))

Service Ref.

Outdoor unit precharged(kg)

 

Refrigerant piping length (one way)

 

 

 

 

 

 

(up to 20m)

20m (66ft)

25m (82ft)

30m (98ft)

35m (115ft)

40m (131ft)

 

 

 

 

 

 

 

 

 

 

PU-1.6VLJA2

1.3

0

 

 

 

 

 

 

 

PU-2VJA2

1.78

0

0.06 (0.13)

0.12 (0.26)

 

 

 

 

 

 

 

PU-2NJA1

1.9

0

0.06 (0.13)

0.12 (0.26)

 

 

 

 

 

 

 

PU-2.5VJA2

2.4

0

0.06 (0.13)

0.12 (0.26)

 

 

 

 

 

 

 

PU-2.5NJA1

2.4

0

0.06 (0.13)

0.12 (0.26)

 

 

 

 

 

 

 

PU-3VJA2

3.08

0

0.06 (0.13)

0.12 (0.26)

 

 

 

 

 

 

 

PU-3YJA2

2.88

0

0.06 (0.13)

0.12 (0.26)

 

 

 

 

 

 

 

PU-3NJA1

3.5

0

0.06 (0.13)

0.12 (0.26)

 

 

 

 

 

 

 

PU-4VLJSA2

3.8

0

0.15 (0.33)

0.30 (0.66)

0.45 (0.99)

0.6 (1.32)

 

 

 

 

 

 

 

PU-4YJSA2

4.6

0

0.15 (0.33)

0.30 (0.66)

0.45 (0.99)

0.6 (1.32)

 

 

 

 

 

 

 

PU-4TJSA2

4.6

0

0.15 (0.33)

0.30 (0.66)

0.45 (0.99)

0.6 (1.32)

 

 

 

 

 

 

 

5

6

 

 

 

 

 

 

 

Outdoor Unit-necessary surrounding clearance

Outdoor Unit-necessary surrounding clearance

185

 

185

 

 

 

 

 

 

 

200

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Concentrated installation)

The upper side must be open.

(7-9/32)

500(19-11/16)

(7-9/32)

 

 

 

 

 

Note:Allow

adequate

 

 

 

 

 

 

17

10

 

 

 

10

upper

clearance

 

 

 

 

Air intake

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

39.527.5

330(13)

362(14-1/4)

Front opening

 

100

10

200

Air intake

500

150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

 

For 10 units or less

1000

Air outlet

15

 

 

500

Service space

 

 

 

 

 

 

Handle

 

 

 

for moving

 

7 295(11-5/8) 24(1)

 

 

 

Outlet guide

 

 

 

 

 

 

installation hole

 

Rear fresh

 

 

 

air intake

Handle for moving

 

 

 

Side air intake

 

524

 

 

 

138

 

 

339

 

 

77

95

23

33

40

 

Rear piping hole

 

 

Drain hole

870(34-1/4)

302

524

2-12 23 Oval holes (standard bolt M10)

Drain hole

Terminal block for indoor and outdoor unit connection

Terminal block for power line

Ground terminal

Handle for moving

Service panel

 

 

 

 

 

 

-(255/8)

[15.88 3/8F

 

 

 

 

 

 

Refrigerant-pipe flared

 

 

 

 

 

 

connection

 

 

282

297

444

650

[9.52 3/8F

 

45

 

 

 

 

Refrigerant-pipe flared

 

 

 

 

 

 

connection

 

 

60

 

 

Knock out hole

60

53

 

 

Knock out holes for

 

 

for front piping

 

 

 

 

 

 

 

(refrigerant,drainage

120 power line 2-[27

 

 

 

and wiring)

 

 

104

 

33

42

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Bottom piping hole

2-U-shaped notched holes

Knock out hole

 

for front piping

 

(refrigerant,drainage

and wiring)

R

 

20

R6

 

17

65

 

R20

80

25 max.

 

 

Standard bolt length

12

 

 

 

 

Front right piping holes-

 

 

 

 

detail figures

 

 

 

 

 

12NJA-/PU22VJA-/PU26VLJA.1-PU

(inch) mm : Unit

DIMENSIONS AND OUTLINES 4

PU-2.5VJA2/PU-2.5NJA1 PU-3VJA2/PU-3YJA2/PU-3NJA1

surroundingnecessary-Unit clearance

Note:Allowadequate

upper clearance

openingFront

10 Servicespace

500

10

200

 

 

 

150

 

 

 

 

 

500

 

Outdoor

 

10

 

 

 

 

 

362(14-1/4)

 

 

17

330(13)

15

 

 

5.27

5.39

 

185

(7-9/32)

 

 

 

500(19-11/16)

Air intake

185 (7-9/32)

Air outlet

 

Air intake

 

side must be open.

200

1000

clearance

The upper

 

 

Outdoor Unit-necessary surrounding

(Concentrated installation)

100 10

For 10 units or less

Unit : mm (inch)

 

 

 

 

 

 

 

45

53

Knockout holes for

powerline 2-[27

 

 

 

 

 

 

 

 

 

Standardbolt length

 

pipingrightFrontholesfiguresdetail

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

connection

 

 

 

 

 

5/8F15.88connection[

flaredpipe-Refrigerant

holeoutKnock

 

120

 

holeoutKnock

pipingfrontfor

 

 

 

 

25.max

 

 

 

 

 

 

850(33-7/16)

 

 

 

R20

 

 

80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

 

 

 

 

 

 

 

 

 

 

 

outdoorandindoorforblockTerminalunit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

flared

 

[9.52connection3/8F

 

 

 

 

 

 

 

 

 

 

 

 

 

65

 

linepowerforblockTerminal

Ground terminal

movingforHandle

panelService

 

60

pipingfrontfor

(refrigerant,drainage

wiring)and

104

33

(refrigerant,drainage

wiring)and

 

Bottom

holepiping

shaped-U-2

notched

holes

12

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R

20

 

 

 

 

 

 

 

 

 

 

Refrigerant-pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

R6

 

 

 

 

 

 

 

553

 

 

 

 

 

 

45

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

352

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

42

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

337

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

870(34-1/4)

 

 

 

403

 

 

302

 

 

524

2-12 23 Oval holes (standard bolt M10)

Drain hole

 

 

 

524

40

 

 

 

 

Outlet guide installation hole

179

 

Drain hole

 

 

Handlefor moving

441

 

 

24(1)

33

 

 

 

 

 

 

 

 

295(11-5/8)

 

 

 

 

 

 

7

intakeairSide

freshRear intakeair

 

 

 

 

 

23

 

 

 

 

 

 

 

 

 

 

 

 

 

Rear piping hole

 

 

 

Handle movingfor

 

95

 

 

 

 

 

138

 

 

 

 

 

 

 

 

7

Mitsubishi PU-1.6VLJA2, PU-2NJA1, PU-2VJA2, PU-2.5NJA1, PU-2.5VJA2 Service Manual

8

Outdoor Unit-necessary surrounding clearance

Outdoor Unit-necessary surrounding clearance

(Concentrated installation)

300

 

 

 

 

The upper side must be open.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

185

 

185

 

 

 

Note:Allow adequate

 

 

 

 

(7-9/32)

500(19-11/16)

(7-9/32)

 

 

 

 

 

 

 

17

10

10

upper clearance

 

 

 

 

 

Air intake

 

 

 

 

 

 

 

 

Front opening

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

39.527.5

330(13)

362(14-1/4)

150

 

For 10 units or less

1000

 

 

 

500

150

10

300

 

 

 

 

 

 

 

 

 

Air intake

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Terminal block for

10

 

 

 

 

 

 

 

 

 

indoor and outdoor

 

 

 

 

 

Air outlet

 

 

 

Service space

 

 

 

 

 

 

15

unit connection

 

 

 

 

870(34-1/4)

 

500

 

 

 

7 295(11-5/8) 24(1)

 

 

 

 

 

 

 

Outlet guide

302

 

 

 

Terminal block for power line

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

installation hole

 

 

 

 

 

 

 

 

Side air intake

 

 

Service panel

 

 

 

 

 

 

 

 

Handle

 

 

524

Ground

 

 

 

 

terminal

 

 

for moving

 

 

 

 

 

 

 

Handle

 

 

 

 

 

61

1258(49-1/2)

 

 

 

 

 

959

 

 

 

585

 

for moving

 

 

 

Rear fresh

 

 

 

 

 

 

 

air intake

Handle for moving

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

524

 

 

Refrigerant-pipe flared

 

 

 

345

 

382

403

connection [19.05 3/4F

45

138

 

83

Refrigerant-pipe flared

 

 

 

 

connection [9.52 3/8F

 

 

 

 

 

 

 

 

95

Rear piping hole

23

33

40 524

2-12 23 Oval holes (standard bolt M10)

Drain hole

Drain hole

60

 

Knock out hole

 

for front piping

 

 

 

104

 

 

(refrigerant,drainage

 

 

and wiring)

39

52

57

Knock out hole

 

 

 

 

 

 

for front piping

Bottom

(refrigerant,

piping hole

drainage and wiring)

2-U-shaped

R6

 

notched

17

holes

 

60

53

 

Knock out holes for

 

120

power line 2-

[

 

27

R20

R20

 

80

25 max.

 

 

Standard bolt length

65

12

 

 

 

 

Front right piping holes-

 

 

 

 

detail figures

 

 

 

 

 

14TJSA-/PU24YJSA-/PU24VLJSA-PU

(inch) mm : Unit

5 WIRING DIAGRAM

PU-1.6VLJA2

POWER

 

 

 

 

 

 

 

 

 

 

SUPPLY

 

 

 

 

 

 

 

 

 

 

~/N

 

 

 

 

 

 

 

 

 

 

220~240V

 

 

 

 

 

 

 

 

 

 

50Hz

 

 

 

 

 

 

 

 

 

 

TB1

WHT

R

52C

 

BLU

BLU

R

 

L

U

 

 

 

 

 

 

 

C RED

S

 

 

 

 

 

 

 

 

N

BLU

T

W

 

WHT

 

 

C

MC

 

 

 

 

 

 

 

 

49C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GRN/YLW

 

 

BLU

3

BLU

 

 

RED BLU

 

 

 

 

RED

RED

 

 

 

 

 

 

C3 ORN

1

ORN

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

a

 

 

 

WHT 4

WHT

MF3

F3

 

 

63H

 

63L

 

 

49F3

 

52

 

 

 

 

 

 

(5A)

C

 

 

 

 

 

 

 

 

YLW

ORN

b

GRY

GRY

WHT

WHT

 

 

 

 

 

 

 

 

 

A

B

 

P1 52C

52C P3

P3

P2

 

 

 

 

TB3

X14

 

X6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED 1

 

 

 

 

X17

 

 

 

 

1

X14

X17

X6

 

 

CP

 

 

 

 

2

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

WHT

CCOMPRESSOR RUN CAPACITOR

CP

COMPRESSOR PROTECTOR

C3

FAN MOTOR CAPACITOR

F3

FUSE(5A)

MC

COMPRESSOR

MF3

FAN MOTOR

TB1

POWER SUPPLY TERMINAL BLOCK

TB3

INDOOR/OUTDOOR CONNECTING LINE TERMINAL BLOCK

49C

COMPRESSOR INTERNAL THERMOSTAT

49F3

FAN MOTOR INTERNAL THERMOSTAT

52C

COMPRESSOR CONTACTOR

63H

HIGH PRESSURE SWITCH

63L

LOW PRESSURE SWITCH

NOTES:1.THE DOTTED LINES SHOW FIELD WIRING.

2.TO INDOOR UNIT TERMINAL BLOCK.

PU-2VJA2,PU-2.5VJA2

PU-3VJA2

POWER SUPPLY ~/N 220-240V 50Hz

TB1

WHT

 

 

L1/1

52C

T1/2

WHT

L

 

 

 

 

 

 

 

 

 

 

 

 

N

BLU

GRY

L3/5

 

T3/6

BLU

 

 

 

 

 

 

 

 

 

 

 

 

GRN/YLW

 

 

HC

 

 

 

 

 

 

 

 

 

 

 

 

RED BLU

 

GRY

22

 

 

 

 

 

 

52C

 

 

 

 

 

 

21

 

 

 

 

F3

A1

 

 

 

63H

 

 

 

52

 

 

 

 

 

63L

(5A)

C

 

 

 

 

 

 

 

YLW

ORN

A2

 

GRY

13 52C14

GRY

WHT

WHT

 

 

VLT

VLT

A

B

 

 

P1

52C

52C P3

P3

P2

TB3

X14

 

 

 

X6

 

 

 

 

 

 

 

 

 

 

 

 

 

RED 1

 

 

 

 

 

 

 

X17

1

X14

X17

 

X6

 

 

 

 

2

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

WHT

 

 

 

 

 

POWER SUPPLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

~/N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

220-240V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50Hz

TB1

 

 

 

 

 

52C

 

 

 

 

 

 

 

 

 

 

 

 

 

WHT

 

 

 

 

BLU

 

 

BLU

R

MC

 

 

 

 

 

 

L

 

 

L1/1

 

T1/2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GRY

 

 

 

 

 

 

C

RED S

 

 

 

 

C

49C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

RED

S

 

 

N

BLU

 

 

L3/5

 

T3/6

WHT

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

49C

 

 

BLU

R

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MC

 

GRN/YLW

 

 

 

 

 

 

 

 

 

 

 

MF3

 

 

 

 

 

 

 

HC

 

 

 

 

BLU

4

BLU

 

 

 

 

49F3

 

 

 

 

 

 

 

 

 

 

 

 

WHT

2

WHT

 

 

RED

BLU

 

GRY

22

 

 

 

 

RED

2

RED

 

 

C3 RED

RED

 

 

 

 

 

 

 

WHT 3

WHT

 

ORN

3

ORN

 

 

 

 

 

 

 

 

 

 

 

C3

ORN

1

ORN

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BLU

4

BLU

MF3

 

 

 

52C

21

 

 

 

 

 

 

 

49F3

 

 

 

 

 

 

 

F3

A1

 

 

 

63H

 

 

63L

 

 

 

 

 

 

 

 

 

 

 

52

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(5A)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

 

 

13 52C14

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A2

 

 

WHT

WHT

 

 

 

 

 

 

 

 

 

 

 

YLW

ORN

 

GRY

VLT

VLT

GRY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

 

 

P1

52C

52C

P3

P3

P2

 

 

 

 

 

 

 

 

 

 

TB3

 

X14

 

 

 

X6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RED 1

 

 

 

 

 

 

 

 

CP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CP

 

 

 

 

 

 

 

 

 

 

 

 

X17

 

 

 

 

 

 

 

 

 

 

1

 

 

 

X6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X14

X17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHT

PU-3NJA1

POWER

 

 

 

 

 

 

 

 

 

 

SUPPLY

 

 

 

 

 

 

 

 

 

 

~/N

 

 

 

 

 

 

 

 

 

 

220V 60Hz

 

 

 

 

 

 

 

 

 

 

TB1

WHT

 

 

52C

BLU

 

 

BLU

R

MC

L

 

L1/1

T1/2

 

 

 

 

 

 

 

GRY

 

 

 

C RED S

 

 

 

 

 

 

 

 

 

 

 

 

 

 

N

BLU

 

L3/5

T3/6

WHT

 

 

C

 

 

 

 

 

 

 

 

49C

 

 

 

 

 

 

 

 

 

 

GRN/YLW

 

HC

 

 

BLU

4

BLU

 

MF3

 

 

 

 

 

 

 

 

 

 

 

 

RED

RED

 

 

 

 

 

 

 

 

 

 

RED

BLU

GRY

22

 

C3

WHT

2

WHT

 

 

3

 

 

 

 

 

 

ORN

1

ORN

 

 

 

 

 

52C

21

 

 

 

 

49F3

F3

A1

 

 

63H

 

 

63L

 

52

 

 

 

 

 

 

(5A)

 

 

 

 

 

 

 

 

C

 

13 52C14

 

 

 

 

 

 

 

 

 

 

A2

 

WHT

WHT

YLW

ORN

GRY

VLT

VLT

GRY

 

A

B

 

 

P1

52C

52C

P3

P3

P2

TB3

X14

 

 

X6

 

 

 

 

 

 

 

 

 

 

 

 

CP

RED

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

X17

1

X14

 

X17

X6

 

 

 

 

2

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

WHT

CCOMPRESSOR RUN CAPACITOR

CP

COMPRESSOR PROTECTOR

C3

FAN MOTOR CAPACITOR

F3

FUSE(5A)

HC

CRANKCASE HEACITOR

MC

COMPRESSOR

MF3

FAN MOTOR

TB1

POWER SUPPLY TERMINAL BLOCK

TB3

INDOOR/OUTDOOR CONNECTING LINE TERMINAL BLOCK

49C

COMPRESSOR INTERNAL THERMOSTAT

49F3

FAN MOTOR INTERNAL THERMOSTAT

52C

COMPRESSOR CONTACTOR

63H

HIGH PRESSURE SWITCH

63L

LOW PRESSURE SWITCH

NOTES:1.THE DOTTED LINES SHOW FIELD WIRING.

2.TO INDOOR UNIT TERMINAL BLOCK.

9

PU-2NJA1,PU-2.5NJA1

POWER

 

 

 

 

 

 

 

 

 

 

SUPPLY

 

 

 

 

 

 

 

 

 

 

~/N

 

 

 

 

 

 

 

 

 

 

220V 60z

TB1

 

 

 

52C

 

 

 

 

 

 

RED

L1/1

 

 

 

 

C 49C

 

L

T1/2

WHT

 

 

 

 

 

 

 

 

C RED

S

 

 

 

 

 

 

 

 

N

BLU

L3/5

T3/6

BLU

BLU

R

 

 

 

 

 

 

 

 

 

MC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WHT

 

 

49F3

 

 

 

GRN/YLW

 

 

3

WHT

 

 

RED BLU

 

 

 

 

ORN

ORN

 

 

 

 

 

 

C3 RED

1

RED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

BLU

BLU

 

 

 

 

 

 

 

4

 

 

 

A1

 

 

 

 

 

 

MF3

 

F3

 

 

63H

 

 

 

 

 

 

52

 

 

63L

 

 

 

 

(5A)

C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YLW

ORN

A2

GRY

GRY

WHT

WHT

 

 

 

 

 

 

 

 

 

A

B

 

P1 52C

52C P3

P3

P2

 

 

 

TB3

 

X14

 

X6

 

 

 

 

 

 

RED 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X17

 

 

 

 

1

X14

X17

X6

 

 

CP

 

 

 

 

2

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

WHT

CCOMPRESSOR RUN CAPACITOR

CP

COMPRESSOR PROTECTOR

F3

FAN MOTOR CAPACITOR

MC

FUSE(5A)

MC

COMPRESSOR

MF3

FAN MOTOR

TB1

POWER SUPPLY TERMISTOR BLOCK

TB3

INDOOR/OUTDOOR CONNECTING LINE TERMISTOR BLOCK

49C

COMPRESSOR INTERNAL THERMOSTAT

49F3

FAN MOTOR INTERNAL THERMOSTAT

52C

COMPRESSOR CONTACTOR

63H

HIGH PRESSURE SWITCH

63L

LOW PRESSURE SWITCH

NOTES:1.THE DOTTED LINES SHOW FIELD WIRING.

2.TO INDOOR UNIT TERMINAL BLOCK.

PU-3YJSA2

POWER SUPPLY

 

 

 

 

3N~

 

 

 

 

380/220~415/240V 50Hz

 

 

WHT

 

TB1

52C

51C

MF3

RED

L1/1

RED

T1/2

L1

 

 

 

 

L2

L3

N

GRN /YLW

RED

F3

(5A) YLW

A

TB3

WHT

BLK

 

GRY

GRY

22

 

A1

21

 

52 C

A2

B

X14

L2/3

L3/5

BLU

WHT

RED

R S T 47

1HC 26C

2

YLW

 

52C

47

 

 

 

GRY

 

 

 

 

 

A

52C14

 

ORN

BLU

13

BRN

VLT

 

VLT

 

P1

52C

52C

P3

 

 

X6

 

 

 

YLW

51C

 

95

96

C 36HA

 

WHT

63LYLW

WHT

 

P3

P2

 

T2/4

WHT

 

 

 

T3/6

BLU

 

 

 

 

 

 

W

MF4

 

WHT

 

BLU

 

4

 

 

RED

2

RED

 

C3

 

 

 

ORN

1

ORN

 

 

BLU

3

WHT

 

 

 

 

GRY

 

 

49F3

 

 

 

 

 

RED 1

 

X17

CP

1

 

X6

2

X14

X17

 

2

 

 

 

WHT

 

 

 

CP

COMPRESSOR PROTECTOR

 

C3

FAN MOTOR CAPACITOR

 

F3

FUSE(5A)

 

HC

CRANKCASE HEATER

 

MC

COMPRESSOR

 

MF3

FAN MOTOR

 

TB1

TERMINAL BLOCK (POWER SUPPLY)

TB3

TERMINAL BLOCK (CONNECTING WIRES INDOOR/OUTDOOR)

26C

THERMAL SWITCH

 

47

ANTI-PHASE PROTECTOR

 

49F3

INTERNAL THERMOSTAT

 

51C

TERMINAL RELAY

 

52C

COMPRESSOR CONTACTOR

 

63H

HIGH PRESSURE SWITCH

 

63L

LOW PRESSURE SWITCH

 

NOTES:1.THE DOTTED LINES SHOW FIELD WIRING.

2.TO INDOOR UNIT TERMINAL BLOCK.

PU-4VLJSA2

POWER

 

 

 

 

 

 

 

 

 

SUPPLY

 

 

 

 

 

 

 

 

 

~/N

 

 

 

 

 

 

 

 

 

220V-240V

 

 

 

 

 

 

 

 

 

50Hz

TB1

 

 

 

 

 

52C

 

 

 

RED

 

 

 

 

 

 

L

 

L1/1

T2/1

 

 

 

 

 

 

 

 

 

 

 

N

BLU

GRY

L3/5

T3/6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GRN/YLW

 

 

HC

 

 

 

 

 

 

 

 

 

 

 

 

 

RED

BLU

 

GRY

 

31

 

26C

 

 

 

52C

 

32

 

 

 

 

 

 

 

 

 

 

 

 

 

A1

GRY

 

63H

 

 

 

F3

52

 

 

 

 

 

 

 

 

 

 

 

 

(5A)

C

 

 

 

13

52C14

63L

 

 

A2

 

 

 

YLW

ORN

 

GRY

VLT

VLT

GRY

WHT

BLU

WHT

BLU

WHT

C3

C4

WHT

R

BLU

C RED S

C

49C

BLURED 42 BLURED

ORN 1 ORN WHT 3 WHT

49F3

BLUBRN 42 BLURED

YLW 1 ORN WHT 3 WHT

49F4

MC

MF3

MF4

A B

P1 52C 52C P3 P3 P2

X14

X6

TB3 RED 1

CP

X17

1

X6

2 X14 X17

2

WHT

CCOMPRESSOR RUN CAPACITOR

CP

COMPRESSOR PROTECTOR

C3,4

FAN MOTOR CAPACITOR

F3

FUSE(5A)

HC

CRANKCASE HEATOR

MC

COMPRESSOR

MF3,4

FAN MOTOR

TB1

POWER SUPPLY TERMINAL BLOCK

TB3

INDOOR/OUTDOOR CONNECTING LINE TERMISTOR BLOCK

49C

COMPRESSOR INTERNAL THERMOSTAT

49F3,4

FAN MOTOR INTERNAL THERMOSTAT

52C

COMPRESSOR CONTACTOR

63H

HIGH PRESSURE SWITCH

63L

LOW PRESSURE SWITCH

NOTES:1.THE DOTTED LINES SHOW FIELD WIRING.

2.TO INDOOR UNIT TERMINAL BLOCK.

10