WT05134X02

MITSUBISHI ELECTRIC MULTI AIR CONDITIONERS OPTIONAL PARTS

CMY-Y100VBK2,Y200VBK2,Y300VBK2

Outdoor Twinning Kit Installation Manual

• For your safety, thoroughly read the following instructions prior to installation.

Safety Precautions

Thoroughly read the following “Safety Precautions” to ensure proper installation.

Observe the following important safety precautions at all times.

Hazards that can occur from incorrect handling are classified by the symbols below:

WARNING

Incorrect handling can result in death or serious injury.

CAUTION

Incorrect handling can result in bodily injury and/or structure damage.

 

 

WARNING

Only a dealer or qualified technician should perform

 

Properly install all parts according to the instructions

installation.

 

in the Installation Manual.

 

 

 

• Improper installation may result in refrigerant gas leakage and

 

• If the wrong twinning pipe or wrong size connecting pipe is

equipment damage.

 

used, air conditioning performance will suffer.

Do not make any modifications or alterations.

 

When installing or relocating the unit, check that no

Consult your dealer for repair.

 

substance other than the specified refrigerant

 

 

(R410A) enters the refrigerant circuit.

• Improper installation may result in water leakage, electric shock,

or fire.

 

• Any presence of foreign substance or air can cause abnormal

In the event of a refrigerant leak, thoroughly ventilate

 

pressure rise or explosion.

 

 

the room.

 

After installation, check for a refrigerant leak.

 

 

• If refrigerant leaks and comes in contact with an open flame,

 

 

 

• If leaked refrigerant comes in contact with a heat source, such

toxic gases will be generated.

 

 

 

as a fan heater, stove, or electric grill, toxic gases will be

 

 

generated.

 

 

CAUTION

 

Properly dispose of packing materials.

 

Do not touch the refrigerant pipes and refrigerant

 

 

 

circuit components with bare hands during and

 

 

 

• Plastic bags can pose suffocation and choking hazards: keep

immediately after operation.

them out of the reach of children. Tear the plastics bags before

 

• During or immediately after operation, certain parts of the unit

disposing of them.

such as pipes and compressor may be either very cold or hot,

 

 

depending on the state of the refrigerant in the unit at the time.

 

To reduce the risk of frostbites and burns, do not touch these

 

parts with bare hands.

* See the Installation Manual that came with the outdoor unit for installation instructions.

1. Confirming the Package Contents

 

 

 

 

 

 

 

 

kit

 

 

 

 

The following twinning and accessory piping parts are included with the Twinning Kit (CMY-

 

 

 

 

Twinning kit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Y100VBK2, CMY-Y200VBK2, and CMY-Y300VBK2). Verify that all items are present

 

 

L-

 

 

 

 

 

 

 

 

shape pipe D (After the twinning)

 

 

 

L-shape pipe d (After the twinning)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

before starting installation.

 

 

 

Insulationcover

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Twinning a

 

 

 

 

 

 

 

 

After checking, prepare the twinning kit by connecting the twinning pipes B, C, and D to the

 

 

 

Twinning A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

twinning pipe A.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*Always use the twinning pipes included in the kit when preparing the twinning kit.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

If the field-supplied pipes do not fit the parts in the kit, use the accessory piping parts

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pipe b fore the ning)

 

Pipe c (After the twinning)

listed below.

 

 

 

 

 

Pipe

B (Before the twinning)

 

Pipe

C (After the twinning)

 

 

 

 

 

 

 

 

 

 

 

(1) Twinning pipes

 

 

 

 

 

 

 

 

 

 

 

 

 

(Unit: mm[in])

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model

Section

Label

Twinning A

Pipe B (Before the twinning)

Pipe C (After the twinning)

L-shape pipe D (After the twinning)

Insulation cover

Instruction

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid

A

ID15.88[5/8]×ID12.7[1/2]×

OD15.88[5/8]-ID15.88[5/8]

OD12.7[1/2]-ID12.7[1/2]

OD12.7[1/2]-ID12.7[1/2]

 

Small

 

 

 

 

 

 

ID12.7[1/2]

L83[3-9/32]

L128[5-1/16]

 

 

 

 

 

CMY-Y100VBK2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas

D

ID28.58[1-1/8]×ID25.4[1]×

OD28.58[1-1/8]-ID28.58[1-1/8]

OD25.4[1]-ID22.2[7/8]

OD25.4[1]-ID22.2[7/8]

 

Large

 

 

 

 

 

 

 

 

 

 

 

 

 

ID25.4[1]

L342[13-15/32]

L190[7-1/2]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid

C

ID19.05[3/4]×ID15.88[5/8]×

OD19.05[3/4]-ID19.05[3/4]

OD15.88[5/8]-ID15.88[5/8]

OD15.88[5/8]-ID15.88[5/8]

 

Small

 

 

 

 

 

 

ID15.88[5/8]

L85[3-3/8]

L123[4-27/32]

 

 

 

 

 

CMY-Y200VBK2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas

B

ID31.75[1-1/4]×ID28.58

OD31.75[1-1/4]-ID34.93[1-3/8]

OD28.58[1-1/8]-ID28.58[1-1/8]

OD28.58[1-1/8]-ID28.58[1-1/8]

 

Large

 

 

 

 

 

 

[1-1/8]×ID28.58[1-1/8]

L337[13-9/32]

L192[7-9/16]

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid

A (Red)

ID15.88[5/8]×ID12.7[1/2]×

OD15.88[5/8]-ID19.05[3/4]

OD12.7[1/2]-ID12.7[1/2]

OD12.7[1/2]-ID12.7[1/2]

 

Small

(This sheet)

 

 

 

 

Second row

ID12.7[1/2]

L85[3-3/8]

L128[5-1/16]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid

C (Red)

ID19.05[3/4]×ID15.88[5/8]×

OD19.05[3/4]-ID19.05[3/4]

OD15.88[5/8]-ID19.05[3/4]

OD15.88[5/8]-ID15.88[5/8]

 

Small

 

 

 

 

 

 

First row

ID15.88[5/8]

L85[3-3/8]

L125[4-15/16]

 

 

 

 

 

CMY-Y300VBK2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas

D (Red)

ID28.58[1-1/8]×ID25.4[1]×

OD28.58[1-1/8]-ID34.93[1-3/8]

OD25.4[1]-ID28.58[1-1/8]

OD25.4[1]-ID28.58[1-1/8]

 

Large

 

 

 

 

 

 

 

 

 

 

 

 

 

Second row

ID25.4[1]

L337[13-9/32]

L192[7-9/16]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas

B (Red)

ID31.75[1-1/4]×ID28.58

OD31.75[1-1/4]-ID38.1[1-1/2]

OD28.58[1-1/8]-ID34.93[1-3/8]

OD28.58[1-1/8]-ID28.58[1-1/8]

 

Large

 

 

 

 

 

 

First row

[1-1/8]×ID28.58[1-1/8]

L339[13-3/8]

L187[7-3/8]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

3 Three outdoor units

 

 

 

 

 

 

 

 

 

 

 

 

 

Package unit name

 

 

 

A0

 

 

 

 

 

 

 

 

 

Outdoor unit1

 

 

B0

 

 

 

 

 

Component unit name

 

 

Outdoor unit2

 

 

C0

 

 

 

 

 

 

 

 

 

Outdoor unit3

 

 

D0

 

 

 

 

 

Outdoor Twinning Kit

 

 

 

E0

 

 

 

 

 

Indoor unit~Twinning pipe2

 

Liquid

A

 

 

F0

 

 

 

 

 

 

 

Gas

B

 

 

G0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Twinning pipe1~Twinning pipe2

 

Liquid

C

 

 

H0

 

 

 

 

 

 

 

Gas

D

 

 

I0

 

 

 

(Unit: mm[in])

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A0

 

B0

C0

D0

E0

F0

G0

H0

I0

 

P950

 

P400

P300

P250

 

 

 

 

 

 

 

P1000

P400

P300

P300

 

 

 

 

 

 

 

P1050

P400

P350

P300

 

 

ø19.05

ø41.28

ø19.05

ø34.93

 

P1100

P400

P350

P350

CMY-Y300VBK2

 

 

 

 

 

 

 

 

 

 

[3/4]

[1-5/8](*)

[3/4]

[1-3/8]

 

P1150

P450

P350

P350

 

 

 

 

 

 

 

 

 

 

P1200

P450

P400

P350

 

 

 

 

 

 

PUHY-**Y(S)HM

P1250

P450

P450

P350

 

 

 

 

 

 

 

EP700

EP300

EP200

EP200

 

 

 

ø34.93

 

 

 

EP750

EP300

P250

EP200

 

 

ø19.05

ø19.05

ø34.93

 

 

 

[1-3/8](*)

 

EP800

EP300

EP300

EP200

CMY-Y300VBK2

 

 

 

 

 

 

 

 

 

 

[3/4]

 

[3/4]

[1-3/8]

 

EP850

EP300

EP300

P250

 

 

ø41.28

 

 

 

 

 

 

 

EP900

EP300

EP300

EP300

 

 

 

[1-5/8](*)

 

 

 

P950

 

P400

P300

P250

 

 

 

 

 

 

 

P1000

P400

P300

P300

 

 

 

 

 

 

 

P1050

P400

P350

P300

 

 

ø19.05

ø41.28

ø19.05

ø34.93

PUHY-**T(S)HM

P1100

P400

P350

P350

CMY-Y300VBK2

[3/4]

[1-5/8](*)

[3/4]

[1-3/8]

 

P1150

P450

P350

P350

 

 

 

 

 

 

 

P1200

P450

P400

P350

 

 

 

 

 

 

 

P1250

P450

P450

P350

 

 

 

 

 

 

 

P264

 

P120

P72

P72

 

 

 

ø34.93

 

 

 

P288

 

P120

P96

P72

 

 

ø19.05

ø19.05

ø34.93

 

 

 

 

[1-3/8](*)

PUHY-**Y(S)HMU

P312

 

P120

P120

P72

CMY-Y300VBK2

 

[3/4]

 

[3/4]

[1-3/8]

 

P336

 

P120

P120

P96

 

 

 

ø41.28

 

 

 

P360

 

P120

P120

P120

 

 

 

[1-5/8](*)

 

 

 

P264

 

P120

P72

P72

 

 

 

ø34.93

 

 

 

P288

 

P120

P96

P72

 

 

ø19.05

ø19.05

ø34.93

 

 

 

 

[1-3/8](*)

PUHY-**T(S)HMU

P312

 

P120

P120

P72

CMY-Y300VBK2

 

[3/4]

 

[3/4]

[1-3/8]

 

P336

 

P120

P120

P96

 

 

 

ø41.28

 

 

 

P360

 

P120

P120

P120

 

 

 

[1-5/8](*)

 

 

 

P850(-AH)

P350

P300

P200

 

 

 

 

 

 

 

P900(-AH)

P350

P300

P250

 

 

 

 

 

 

 

P950

 

P400

P300

P250

 

 

 

 

 

 

 

P1000

P400

P300

P300

 

 

ø19.05

ø41.28

ø19.05

ø34.93

PUHY-**Y(S)HC

P1050

P400

P350

P300

CMY-Y300VBK2

[3/4]

[1-5/8](*)

[3/4]

[1-3/8]

P1100

P400

P350

P350

 

 

 

 

 

 

 

 

 

 

P1150

P400

P400

P350

 

 

 

 

 

 

 

P1200

P400

P400

P400

 

 

 

 

 

 

 

P1250

P450

P450

P350

 

 

 

 

 

 

4 Three outdoor units

 

 

 

 

 

 

 

 

 

 

Unit model

 

Liquid

Gas

 

 

 

 

 

E or G or I

F or H or J

 

 

 

 

 

A1

 

A2

A3

 

 

 

 

 

 

B1

 

B2

B3

 

 

 

Twinning pipe~Outdoor unit

 

C1

 

C2

C3

 

 

 

 

D1

 

D2

D3

 

 

 

 

 

 

 

 

 

 

 

 

 

E1

 

E2

E3

 

 

 

 

 

 

F1

 

F2

F3

 

(Unit: mm[in])

 

 

 

 

 

 

 

 

 

 

 

A1

B1

 

C1

 

D1

 

E1

F1

 

A2

B2

 

C2

 

D2

 

E2

F2

 

A3

B3

 

C3

 

D3

 

E3

F3

 

P250

P300

 

P350

 

P400

P450

 

ø9.52

ø12.7

 

ø12.7

 

ø15.88

ø15.88

 

[3/8](*)

[1/2](*)

 

[1/2](*)

 

[5/8](*)

[5/8](*)

 

 

 

 

 

ø22.2

ø 22.2

 

ø28.58

 

ø28.58

ø28.58

 

[7/8](*)

[7/8](*)

 

[1-1/8]

 

[1-1/8]

[1-1/8]

PUHY-**YHM

 

 

 

EP200

EP300

 

 

 

 

ø9.52

ø12.7

 

 

 

 

[3/8](*)

[1/2](*)

 

 

 

 

 

 

 

 

 

 

 

 

ø19.05

ø 22.2

 

 

 

 

[3/4](*)

[7/8](*)

 

 

 

 

 

 

 

 

 

 

 

 

P250

P300

 

P350

 

P400

P450

 

ø9.52

ø12.7

 

ø12.7

 

ø15.88

ø15.88

PUHY-**THM

[3/8](*)

[1/2](*)

 

[1/2](*)

 

[5/8](*)

[5/8](*)

 

 

 

 

ø22.2

ø 22.2

 

ø28.58

 

ø28.58

ø28.58

 

[7/8](*)

[7/8](*)

 

[1-1/8]

 

[1-1/8]

[1-1/8]

 

 

 

 

 

P72

P96

 

P120

 

 

 

ø9.52

ø9.52

 

ø12.7

 

 

PUHY-**YHMU

[3/8](*)

[3/8](*)

 

[1/2](*)

 

 

 

 

 

 

 

 

ø19.05

ø22.2

 

ø22.2

 

 

 

[3/4](*)

[7/8](*)

 

[7/8](*)

 

 

 

 

 

 

 

 

 

 

P72

P96

 

P120

 

 

 

ø9.52

ø9.52

 

ø12.7

 

 

PUHY-**THMU

[3/8](*)

[3/8](*)

 

[1/2](*)

 

 

 

 

 

 

 

 

 

ø19.05

ø22.2

 

ø22.2

 

 

 

[3/4](*)

[7/8](*)

 

[7/8](*)

 

 

 

 

 

 

 

 

 

 

P200

P250

 

P300

 

P350

P400

P450

 

ø9.52

ø9.52

 

ø12.7

 

ø12.7

ø15.88

ø15.88

PUHY-**YHC

[3/8](*)

[3/8](*)

 

[1/2](*)

 

[1/2](*)

[5/8](*)

[5/8](*)

 

ø19.05

ø22.2

 

ø22.2

 

ø28.58

ø28.58

ø28.58

 

[3/4](*)

[7/8](*)

 

[7/8](*)

 

[1-1/8]

[1-1/8]

[1-1/8]

(3)

Slope of twinning pipes

 

 

 

 

Make sure the slope of the twinning pipes are at an angle within ±15° to

 

 

 

 

the horizontal plane.

 

 

 

 

If the slope exceeds the specified angle, the unit may be damaged.

Note: Refer to the figure below for the installation

 

 

Note: See the following drawing for the fitting position

(4)

The length of the straight pipe between indoor units and the twin-

 

position of the twinning pipe.

 

of the twinning pipe.

 

ning pipe

 

TwinningReducerpipe

 

 

 

 

 

Use the pipes supplied in the twinning kit, and make sure the section of

 

 

 

 

the field-supplied pipe that connects to the twinning pipe has at least

°1515±°

 

 

 

500 mm [19-11/16 in] of straight section. (The section of the field-

±

 

 

 

 

The angle of tilt of the reducer should be within

 

 

 

 

 

supplied pipe that connects to the twinning pipe must have at least 500

 

 

 

 

Slope of the twinning pipes are at an angle within

 

 

mm [19-11/16 in] of straight section.) If the straight section is less than

 

±15° with the ground.

 

 

 

±15° to the horizontal plane

 

 

500 mm [19-11/16 in], it may result in equipment damage.

 

 

 

(5)

Pipe connection

 

 

 

 

When connecting the twinning kit to the outdoor unit, note the following:

 

 

 

·Make sure the pipes from the twinning pipe to the outdoor unit are sloped downwards (towards the twinning pipes).

·If the piping on the outdoor unit side (from the twinning pipe) exceeds 2 m [6 ft], ensure a trap (gas pipe only) within 2 m [6 ft].

Make sure the height of the trap is 200 mm [7-7/8 in] or more.

If there is no trap, oil can accumulate inside the pipe, causing a shortage of oil and may damage the compressor.

<2 m [6 ft] or less>

<More than 2 m [6 ft] apart>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100 mm

 

To Indoor unit

 

 

200 mm

 

B

 

 

 

To Indoor unit

[7-7/8 in]

 

 

[3-15/16

 

 

A

 

To Indoor unit

To Indoor unit

 

or more

 

in] or

2 m [6 ft]

 

 

 

Twinning pipe

Downward slope

 

Twinning pipe

 

 

LessWithinthan

 

 

 

 

more

 

Upward slope

2 m (6 ft)

 

 

 

 

Twinning pipe

 

 

 

 

2 m [6 ft]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total pipe length = A+B<10 m [32 ft]

 

· If the twinning pipe is installed above the base

OutdoorOutoor unitunit1 1 OutdoorOutoor unitunit2 2 OutdoorOutoor unitunit3 3

 

 

 

 

 

 

 

 

 

 

 

of the outdoor unit, it should be no more than

 

 

 

 

 

 

 

200 mm [7-7/8 in].

 

 

 

 

 

 

 

 

 

 

 

Twinning 1

Twinning 2

ToToIndoorIndoorunit

 

 

 

 

 

 

Twinning 1

Twinning 2

 

 

 

 

200 mm [7-7/8 in]

 

 

 

 

 

 

 

Less than

 

 

unit

 

 

 

 

max

200 mm

 

 

 

3

 

 

(7 inch)

 

 

 

 

 

 

 

 

 

 

 

 

(2) Accessory piping parts

 

 

 

 

 

(Unit: mm[in])

Model

Section

 

Supplied pipe

 

 

 

CMY-Y100VBK2

Liquid

OD12.7[1/2]-ID9.52[3/8] (2)

OD15.88[5/8]-ID12.7[1/2]

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas

OD22.2[7/8]-ID28.58[1-1/8]

OD22.2[7/8]-ID19.05[3/4] (2)

 

 

 

 

 

 

 

 

 

 

 

CMY-Y200VBK2

Liquid

OD15.88[5/8]-ID12.7[1/2] (2)

 

 

 

 

 

 

Gas

OD34.93[1-3/8]-ID41.28[1-5/8]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CMY-Y300VBK2

Liquid

OD12.7[1/2]-ID9.52[3/8]

OD12.7[1/2]-ID15.88[5/8] (2)

OD15.88[5/8]-ID9.52[3/8]

 

OD15.88[5/8]-ID12.7[1/2]

Gas

OD28.58[1-1/8]-ID22.2[7/8] (3)

OD38.1[1-1/2]-ID41.28[1-5/8]

OD28.58[1-1/8]-ID19.05[3/4] (2)

OD38.1[1-1/2]-ID34.93[1-3/8]

 

(3) List of field-supplied parts

 

 

Outdoor unit

1

Outdoor unit 2

• Refrigerant pipes other than the ones provided in the kit.

 

 

Outdoor unit 1

 

Outdoor unit 2

 

 

• Heat-resistant insulation material (for field-supplied refrigerant pipes)

Insulation cover tape

2.Selecting the Correct Size Refrigerant Pipes and Using the Twinning Kit

(1)Two outdoor units

1 Field-supply the pipes to be connected to the kit.

2Choose the correct size pipe using the table below. Connect the field-supplied pipe to the twinning kit for the sizes in the

table that are marked with an asterisk (*).

3 If the pipe was cut with a pipe cutter, remove the burrs and

 

Ee

Aa

 

C

c

To Indoorrunitunit

 

eliminate foreign materials before connecting.

 

 

Liquidtwinning pipe

 

 

Ff

 

pipe

D

d

B

ToTo Indoorr unitunit

 

 

 

b

 

Gastwinningpipepipe

1 Two outdoor units

 

 

 

 

 

 

 

 

 

 

 

 

 

Package unit name

 

 

 

 

 

A0

 

 

 

Component unit name

 

Outdoor unit 1

 

 

B0

 

 

 

 

Outdoor unit 2

 

 

C0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OutIdoor Twinning Kit

 

 

D0

 

 

 

Indoor unit~Twinning pipe

Liquid

 

 

A

 

 

E0

 

 

 

Gas

 

 

B

 

 

F0

 

(Unit: mm[in])

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A0

 

B0

 

C0

 

D0

E0

F0

 

 

 

P500

 

P250

 

P250

 

 

 

 

 

 

 

P550

 

P300

 

P250

CMY-Y100VBK2

ø15.88

ø28.58

 

 

 

P600

 

P350

 

P250

[5/8]

[1-1/8]

 

 

 

 

 

 

 

 

 

 

P650

 

P350

 

P300

 

 

 

 

 

 

 

P700

 

P350

 

P350

 

 

 

ø34.93

 

 

 

P750

 

P400

 

P350

 

 

ø19.05

 

 

 

 

 

 

 

[1-3/8]

 

 

 

P800

 

P450

 

P350

CMY-Y200VBK2

 

 

 

 

 

[3/4]

 

 

 

 

P850

 

P450

 

P400

 

 

 

ø41.28

PUHY-**Y(S)HM

 

 

P900

 

P450

 

P450

 

 

 

[1-5/8](*)

 

 

 

EP400

 

EP200

 

EP200

 

 

ø12.7[1/2]

 

 

 

 

EP450

 

P250

 

EP200

 

 

 

 

 

 

 

EP500

 

EP300

 

EP200

CMY-Y100VBK2

ø15.88

ø28.58

 

 

 

EP550

 

EP300

 

P250

 

 

 

 

 

 

 

[5/8]

[1-1/8]

 

 

 

EP600

 

EP300

 

EP300

 

 

 

 

 

 

 

EP650

 

P350

 

EP300

 

 

 

 

 

 

 

HP400

 

HP200

 

HP200

CMY-Y100VBK2

ø15.88

ø28.58

 

 

 

HP500

 

HP250

 

HP250

[5/8]

[1-1/8]

 

 

 

 

 

 

 

 

 

 

P500

 

P250

 

P250

 

 

 

 

 

 

 

P550

 

P300

 

P250

CMY-Y100VBK2

ø15.88

ø28.58

 

 

 

P600

 

P350

 

P250

[5/8]

[1-1/8]

 

 

 

 

 

 

 

 

 

 

P650

 

P350

 

P300

 

 

 

 

PUHY-**T(S)HM

 

 

P700

 

P350

 

P350

 

 

 

ø34.93

 

 

 

P750

 

P400

 

P350

 

 

 

 

 

 

 

 

 

 

ø19.05

[1-3/8]

 

 

 

P800

 

P450

 

P350

CMY-Y200VBK2

 

 

 

 

 

[3/4]

 

 

 

 

P850

 

P450

 

P400

 

 

ø41.28

 

 

 

 

 

 

 

 

 

 

 

P900

 

P450

 

P450

 

 

 

[1-5/8](*)

 

 

 

P144

 

P72

 

P72

 

 

 

 

 

 

 

P168

 

P96

 

P72

 

 

ø15.88

ø28.58

PUHY-**Y(S)HMU

 

 

P192

 

P120

 

P72

CMY-Y100VBK2

 

 

P216

 

P120

 

P96

 

 

[5/8]

[1-1/8]

 

 

 

 

 

 

 

 

 

 

 

 

P240

 

P120

 

P120

 

 

 

 

 

 

 

P144

 

P72

 

P72

 

 

 

 

 

 

 

P168

 

P96

 

P72

 

 

ø15.88

ø28.58

 

 

 

P192

 

P120

 

P72

CMY-Y100VBK2

PUHY-**T(S)HMU

 

 

P216

 

P120

 

P96

 

 

[5/8]

[1-1/8]

 

 

 

 

 

 

 

 

 

 

 

P240

 

P120

 

P120

 

 

 

 

 

 

 

HP144

 

HP72

 

HP72

CMY-Y100VBK2

ø15.88

ø28.58

 

 

 

HP192

 

HP96

 

HP96

[5/8]

[1-1/8]

 

 

 

 

 

 

 

PUHY-**Y(S)HMC

 

 

HP400

 

HP200

 

HP200

CMY-Y100VBK2

ø15.88

ø28.58

 

 

HP500

 

HP250

 

HP250

[5/8]

[1-1/8]

 

 

 

 

 

 

 

 

 

P450(-AH)

 

P250

 

P200

 

 

 

 

 

 

 

P500

 

P250

 

P250

 

 

ø15.88

ø28.58

 

 

 

P550

 

P300

 

P250

CMY-Y100VBK2

 

 

 

P600

 

P350

 

P250

 

 

[5/8]

[1-1/8]

 

 

 

 

 

 

 

 

 

PUHY-**Y(S)HC

 

 

P650

 

P350

 

P300

 

 

 

 

 

 

P700

 

P350

 

P350

 

 

 

ø34.93

 

 

 

 

 

 

 

 

 

 

 

P750

 

P400

 

P350

 

 

 

 

 

 

 

 

 

 

ø19.05

[1-3/8]

 

 

 

P800

 

P400

 

P400

CMY-Y200VBK2

 

 

 

 

 

 

 

 

 

 

 

[3/4]

 

 

 

 

P850

 

P450

 

P400

 

 

ø41.28

 

 

 

 

 

 

 

 

 

 

 

P900

 

P450

 

P450

 

 

 

[1-5/8](*)

(2) Three outdoor units

1 Field-supply the pipes to be connected to the kit. 2 Choose the correct size pipe using the table below.

Connect the field-supplied pipe to the twinning kit for the sizes in the table that are marked with an asterisk (*).

3If the pipe was cut with a pipe cutter, remove the burrs and eliminate foreign materials before connecting.

2 Two outdoor units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Unit model

 

Liquid

 

 

Gas

 

 

 

 

 

 

C or E

 

D or F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A1

 

 

 

A2

 

 

A3

 

 

 

 

 

 

B1

 

 

 

B2

 

 

B3

 

 

 

Twinning pipe~Outdoor unit

 

C1

 

 

 

C2

 

 

C3

 

 

 

 

D1

 

 

 

D2

 

 

D3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E1

 

 

 

E2

 

 

E3

 

 

 

 

 

 

F1

 

 

 

F2

 

 

F3

 

(Unit: mm[in])

 

 

 

 

 

 

 

 

 

 

 

 

A1

 

 

B1

 

C1

 

D1

E1

F1

 

A2

 

 

B2

 

C2

 

D2

E2

F2

 

A3

 

 

B3

 

C3

 

D3

E3

F3

 

P250

 

 

P300

 

P350

 

P400

P450

 

ø9.52

 

 

ø12.7

 

ø12.7

 

ø15.88

ø15.88

 

[3/8](*)

 

 

[1/2]

 

[1/2](*)

 

[5/8]

 

[5/8]

 

 

 

 

 

 

 

 

ø22.2

 

 

ø22.2

 

ø28.58

 

ø28.58

ø28.58

 

[7/8]

 

 

[7/8]

 

[1-1/8](*)

 

[1-1/8]

 

[1-1/8]

 

 

 

 

 

 

 

 

EP200

 

 

EP300

 

 

 

ø9.52

 

 

ø12.7

 

 

PUHY-**YHM

[3/8](*)

 

 

[1/2]

 

 

 

 

 

 

 

 

 

 

 

 

 

ø19.05

 

 

ø22.2

 

 

 

[3/4](*)

 

 

[7/8]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HP200

 

 

HP250

 

 

 

ø9.52

 

 

ø9.52

 

 

 

[3/8](*)

 

 

[3/8](*)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ø19.05

 

 

ø22.2

 

 

 

[3/4](*)

 

 

[7/8]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P250

 

 

P300

 

P350

 

P400

P450

 

ø9.52

 

 

ø12.7

 

ø12.7

 

ø15.88

ø15.88

PUHY-**THM

[3/8](*)

 

 

[1/2]

 

[1/2](*)

 

[5/8]

 

[5/8]

 

 

 

 

 

 

 

ø22.2

 

 

ø22.2

 

ø28.58

 

ø28.58

ø28.58

 

[7/8]

 

 

[7/8]

 

[1-1/8](*)

 

[1-1/8]

 

[1-1/8]

 

 

 

 

 

 

 

 

P72

 

 

P96

 

P120

 

 

ø9.52

 

 

ø9.52

 

ø12.7

 

PUHY-**YHMU

[3/8](*)

 

 

[3/8](*)

 

[1/2]

 

 

 

 

 

 

 

 

 

 

 

ø19.05

 

 

ø22.2

 

ø22.2

 

 

[3/4](*)

 

 

[7/8]

 

[7/8]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P72

 

 

P96

 

P120

 

 

ø9.52

 

 

ø9.52

 

ø12.7

 

 

[3/8](*)

 

 

[3/8](*)

 

[1/2]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ø19.05

 

 

ø22.2

 

ø22.2

 

 

[3/4](*)

 

 

[7/8]

 

[7/8]

 

 

PUHY-**THMU

 

 

 

 

 

 

 

 

 

HP72

 

 

HP96

 

 

 

ø9.52

 

 

ø9.52

 

 

 

[3/8](*)

 

 

[3/8](*)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ø19.05

 

 

ø22.2

 

 

 

[3/4](*)

 

 

[7/8]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HP200

 

 

HP250

 

 

 

ø9.52

 

 

ø9.52

 

 

PUHY-**YHMC

[3/8](*)

 

 

[3/8](*)

 

 

 

 

 

 

 

 

 

 

 

 

 

ø19.05

 

 

ø22.2

 

 

 

[3/4](*)

 

 

[7/8]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P200

 

 

P250

 

P300

 

P350

P400

P450

 

ø9.52

 

 

ø9.52

 

ø12.7

 

ø12.7

 

ø15.88

ø15.88

PUHY-**YHC

[3/8](*)

 

 

[3/8](*)

 

[1/2]

 

 

[1/2](*)

 

[5/8]

[5/8]

ø19.05

 

 

ø22.2

 

ø22.2

 

ø28.58

ø28.58

ø28.58

 

 

 

 

 

 

[3/4](*)

 

 

[7/8]

 

[7/8]

 

 

[1-1/8]

 

[1-1/8]

[1-1/8]

 

 

 

 

 

 

Outdoor unit

3

 

Outdooror unitunit1

1

Outdoorunitunit2

2

 

Outdoor unit 3

 

 

 

 

 

 

 

 

 

 

E

G

g

 

cC

 

I i

 

Aa

 

To Indoorunit

unit

e

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid twinning pipe 1

 

Liquid twinning pipe 2

 

 

 

Hh

Liquid 1 twinning pipe

Jj

Liquid 2

twinning pipe

 

 

 

 

 

 

b

 

 

 

 

 

 

Dd

 

 

 

 

 

f F

 

 

 

 

 

 

B

To Indoorunit unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GasGas1 twinningtwinningpipe pipe 1

Gas twinning pipe 2

 

 

 

 

Gas 2 twinning pipe

2

3. Pipe Connection Example

Connect the pipes between outdoor units, referencing the figures below. <For two outdoor units>

<For three outdoor units>

Field piping

Field-supplied pipe

Field piping

Field-supplied pipe

Twinning kit

Twinning kit

Fieldld-pipingsupplied pipe

The length of the straight pipe must

Straight pipe that is 500 mm be 500 mm (19 inch) or longer.

[19-11/16 in] or more

Twinning kit

Twinning kit

 

FieldField-suppipinglied pipe

Straight pipe that is 500 mm

 

Twinning kit

 

Twinning kit

The length of the straight pipe must

 

[19-11/16 in] or more

be 500 mm (19 inch) or longer.

Field-suppliedpiping pipe

The length of the straight pipe must

be 500 mm (19 inch) or longer.

Straight pipe that is 500 mm [19-11/16 in] or more

4. Insulation Cover Installation

Install the insulation cover on the twinning kit after brazing the pipes and twinning kit.

Insulate all refrigerant pipes. Insulate the liquid and gas pipes separately, and pipes located inside the unit as well as the outside. Use heat-resistant insulation material (Heat resistant: at least 120 °C [248 °F], Thickness: liquid = 10 mm [13/32 in],

gas = 20 mm [13/16 in]). Position the edges of the insulation cover and heat-resistant insulation material so as not to leave a gap, and then wrap the exterior perimeter of the pipe joints and middle with tape (field-supplied).

FieldField-suppliedpipingpipe

FieldField-suppliedipingpipe

Twinningkitkit

FieldField-suppliedpipingpipe

 

 

 

Insulation material

 

As the insulation cover

 

Insulationcover

 

 

Heat-resistant insulation

 

contracts slightly, conduct

 

 

 

(fieldmaterialsupply)(field-supplied)

 

 

 

 

 

 

 

 

Insulati

covers can shrink.

 

 

 

 

 

taping

onthe field securely by

 

 

 

 

 

Overlap the tape as shown in

 

 

 

 

 

providing lapped parts as

 

 

 

 

 

the left figure so that there

 

 

 

 

 

shown in the left, so that no gap

 

 

 

 

 

will be no gap in between the

 

 

 

 

 

will exist on the insulation cover

 

 

 

 

 

insulation cover or field-

OverlapLappedmarginspaceof theof tapetaping

and field supply insulation

installed insulation material.

material.

Tape (field-supplied)

Insulation material (field supply)

Heat-resistant insulation material (field-supplied)

 

Heat-resistant

 

Insulation m terial

InsulationInsulationcovercover

insulation material

(field supply)

 

(field-supplied)

Tape(field-supply)supplied)

Tape (field-supplied)

Tape (field supply)

5. Miscellaneous Notes