WT05134X02
MITSUBISHI ELECTRIC MULTI AIR CONDITIONERS OPTIONAL PARTS
CMY-Y100VBK2,Y200VBK2,Y300VBK2
Outdoor Twinning Kit Installation Manual
• For your safety, thoroughly read the following instructions prior to installation.
Safety Precautions
•Thoroughly read the following “Safety Precautions” to ensure proper installation.
•Observe the following important safety precautions at all times.
•Hazards that can occur from incorrect handling are classified by the symbols below:
WARNING |
Incorrect handling can result in death or serious injury. |
CAUTION |
Incorrect handling can result in bodily injury and/or structure damage. |
|
|
WARNING
Only a dealer or qualified technician should perform |
|
Properly install all parts according to the instructions |
installation. |
|
in the Installation Manual. |
|
|
|
• Improper installation may result in refrigerant gas leakage and |
|
• If the wrong twinning pipe or wrong size connecting pipe is |
equipment damage. |
|
used, air conditioning performance will suffer. |
Do not make any modifications or alterations. |
|
When installing or relocating the unit, check that no |
Consult your dealer for repair. |
|
substance other than the specified refrigerant |
|
|
(R410A) enters the refrigerant circuit. |
• Improper installation may result in water leakage, electric shock, |
||
or fire. |
|
• Any presence of foreign substance or air can cause abnormal |
In the event of a refrigerant leak, thoroughly ventilate |
|
pressure rise or explosion. |
|
|
|
the room. |
|
After installation, check for a refrigerant leak. |
|
|
|
• If refrigerant leaks and comes in contact with an open flame, |
|
|
|
• If leaked refrigerant comes in contact with a heat source, such |
|
toxic gases will be generated. |
|
|
|
|
as a fan heater, stove, or electric grill, toxic gases will be |
|
|
generated. |
|
|
CAUTION |
|
|
Properly dispose of packing materials. |
|
Do not touch the refrigerant pipes and refrigerant |
|
|
|
circuit components with bare hands during and |
|
|
|
• Plastic bags can pose suffocation and choking hazards: keep |
immediately after operation. |
|
them out of the reach of children. Tear the plastics bags before |
||
|
||
• During or immediately after operation, certain parts of the unit |
||
disposing of them. |
||
such as pipes and compressor may be either very cold or hot, |
||
|
||
|
depending on the state of the refrigerant in the unit at the time. |
|
|
To reduce the risk of frostbites and burns, do not touch these |
|
|
parts with bare hands. |
* See the Installation Manual that came with the outdoor unit for installation instructions.
1. Confirming the Package Contents |
|
|
|
|
|
|
|
|
kit |
|
|
|
|
|||||||
The following twinning and accessory piping parts are included with the Twinning Kit (CMY- |
|
|
|
|
Twinning kit |
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
Y100VBK2, CMY-Y200VBK2, and CMY-Y300VBK2). Verify that all items are present |
|
|
L- |
|
|
|
|
|
|
|
|
|||||||||
shape pipe D (After the twinning) |
||||||||||||||||||||
|
|
|
L-shape pipe d (After the twinning) |
|
|
|||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
before starting installation. |
|
|
|
Insulationcover |
|
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
Twinning a |
|
|
|
|
|
|
|
|
||||||
After checking, prepare the twinning kit by connecting the twinning pipes B, C, and D to the |
|
|
|
Twinning A |
|
|
|
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||||
twinning pipe A. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
*Always use the twinning pipes included in the kit when preparing the twinning kit. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
If the field-supplied pipes do not fit the parts in the kit, use the accessory piping parts |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
Pipe b fore the ning) |
|
Pipe c (After the twinning) |
||||||||||
listed below. |
|
|
|
|
|
Pipe |
B (Before the twinning) |
|
Pipe |
C (After the twinning) |
||||||||||
|
|
|
|
|
|
|
|
|
|
|
||||||||||
(1) Twinning pipes |
|
|
|
|
|
|
|
|
|
|
|
|
|
(Unit: mm[in]) |
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
||||||||||
Model |
Section |
Label |
Twinning A |
Pipe B (Before the twinning) |
Pipe C (After the twinning) |
L-shape pipe D (After the twinning) |
Insulation cover |
Instruction |
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Liquid |
A |
ID15.88[5/8]×ID12.7[1/2]× |
OD15.88[5/8]-ID15.88[5/8] |
OD12.7[1/2]-ID12.7[1/2] |
OD12.7[1/2]-ID12.7[1/2] |
|
Small |
|
|
|
|
|||||||
|
|
ID12.7[1/2] |
L83[3-9/32] |
L128[5-1/16] |
|
|
|
|
|
|||||||||||
CMY-Y100VBK2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
Gas |
D |
ID28.58[1-1/8]×ID25.4[1]× |
OD28.58[1-1/8]-ID28.58[1-1/8] |
OD25.4[1]-ID22.2[7/8] |
OD25.4[1]-ID22.2[7/8] |
|
Large |
|
|
|
|
|||||||||
|
|
|
|
|
|
|
||||||||||||||
|
|
ID25.4[1] |
L342[13-15/32] |
L190[7-1/2] |
|
|
|
|
|
|||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
Liquid |
C |
ID19.05[3/4]×ID15.88[5/8]× |
OD19.05[3/4]-ID19.05[3/4] |
OD15.88[5/8]-ID15.88[5/8] |
OD15.88[5/8]-ID15.88[5/8] |
|
Small |
|
|
|
|
|||||||
|
|
ID15.88[5/8] |
L85[3-3/8] |
L123[4-27/32] |
|
|
|
|
|
|||||||||||
CMY-Y200VBK2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
Gas |
B |
ID31.75[1-1/4]×ID28.58 |
OD31.75[1-1/4]-ID34.93[1-3/8] |
OD28.58[1-1/8]-ID28.58[1-1/8] |
OD28.58[1-1/8]-ID28.58[1-1/8] |
|
Large |
|
|
|
|
|||||||||
|
|
[1-1/8]×ID28.58[1-1/8] |
L337[13-9/32] |
L192[7-9/16] |
|
1 |
|
|
||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|||||
|
|
Liquid |
A (Red) |
ID15.88[5/8]×ID12.7[1/2]× |
OD15.88[5/8]-ID19.05[3/4] |
OD12.7[1/2]-ID12.7[1/2] |
OD12.7[1/2]-ID12.7[1/2] |
|
Small |
(This sheet) |
|
|
||||||||
|
|
Second row |
ID12.7[1/2] |
L85[3-3/8] |
L128[5-1/16] |
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
Liquid |
C (Red) |
ID19.05[3/4]×ID15.88[5/8]× |
OD19.05[3/4]-ID19.05[3/4] |
OD15.88[5/8]-ID19.05[3/4] |
OD15.88[5/8]-ID15.88[5/8] |
|
Small |
|
|
|
|
|||||||
|
|
First row |
ID15.88[5/8] |
L85[3-3/8] |
L125[4-15/16] |
|
|
|
|
|
||||||||||
CMY-Y300VBK2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
Gas |
D (Red) |
ID28.58[1-1/8]×ID25.4[1]× |
OD28.58[1-1/8]-ID34.93[1-3/8] |
OD25.4[1]-ID28.58[1-1/8] |
OD25.4[1]-ID28.58[1-1/8] |
|
Large |
|
|
|
|
||||||||
|
|
|
|
|
|
|
||||||||||||||
|
|
Second row |
ID25.4[1] |
L337[13-9/32] |
L192[7-9/16] |
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
Gas |
B (Red) |
ID31.75[1-1/4]×ID28.58 |
OD31.75[1-1/4]-ID38.1[1-1/2] |
OD28.58[1-1/8]-ID34.93[1-3/8] |
OD28.58[1-1/8]-ID28.58[1-1/8] |
|
Large |
|
|
|
|
|||||||
|
|
First row |
[1-1/8]×ID28.58[1-1/8] |
L339[13-3/8] |
L187[7-3/8] |
|
|
|
|
|
||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1
3 Three outdoor units |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Package unit name |
|
|
|
A0 |
|
|
|
|
|
|||||
|
|
|
|
Outdoor unit1 |
|
|
B0 |
|
|
|
|
|
||
Component unit name |
|
|
Outdoor unit2 |
|
|
C0 |
|
|
|
|
|
|||
|
|
|
|
Outdoor unit3 |
|
|
D0 |
|
|
|
|
|
||
Outdoor Twinning Kit |
|
|
|
E0 |
|
|
|
|
|
|||||
Indoor unit~Twinning pipe2 |
|
Liquid |
A |
|
|
F0 |
|
|
|
|
|
|||
|
|
Gas |
B |
|
|
G0 |
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
||||
Twinning pipe1~Twinning pipe2 |
|
Liquid |
C |
|
|
H0 |
|
|
|
|
|
|||
|
|
Gas |
D |
|
|
I0 |
|
|
|
(Unit: mm[in]) |
||||
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
||||
|
A0 |
|
B0 |
C0 |
D0 |
E0 |
F0 |
G0 |
H0 |
I0 |
||||
|
P950 |
|
P400 |
P300 |
P250 |
|
|
|
|
|
|
|||
|
P1000 |
P400 |
P300 |
P300 |
|
|
|
|
|
|
||||
|
P1050 |
P400 |
P350 |
P300 |
|
|
ø19.05 |
ø41.28 |
ø19.05 |
ø34.93 |
||||
|
P1100 |
P400 |
P350 |
P350 |
CMY-Y300VBK2 |
|||||||||
|
|
|
|
|
|
|
|
|
|
[3/4] |
[1-5/8](*) |
[3/4] |
[1-3/8] |
|
|
P1150 |
P450 |
P350 |
P350 |
|
|
||||||||
|
|
|
|
|
|
|
||||||||
|
P1200 |
P450 |
P400 |
P350 |
|
|
|
|
|
|
||||
PUHY-**Y(S)HM |
P1250 |
P450 |
P450 |
P350 |
|
|
|
|
|
|
||||
|
EP700 |
EP300 |
EP200 |
EP200 |
|
|
|
ø34.93 |
|
|
||||
|
EP750 |
EP300 |
P250 |
EP200 |
|
|
ø19.05 |
ø19.05 |
ø34.93 |
|||||
|
|
|
[1-3/8](*) |
|||||||||||
|
EP800 |
EP300 |
EP300 |
EP200 |
CMY-Y300VBK2 |
|||||||||
|
|
|
|
|
|
|
|
|
|
[3/4] |
|
[3/4] |
[1-3/8] |
|
|
EP850 |
EP300 |
EP300 |
P250 |
|
|
ø41.28 |
|||||||
|
|
|
|
|
|
|||||||||
|
EP900 |
EP300 |
EP300 |
EP300 |
|
|
|
[1-5/8](*) |
|
|
||||
|
P950 |
|
P400 |
P300 |
P250 |
|
|
|
|
|
|
|||
|
P1000 |
P400 |
P300 |
P300 |
|
|
|
|
|
|
||||
|
P1050 |
P400 |
P350 |
P300 |
|
|
ø19.05 |
ø41.28 |
ø19.05 |
ø34.93 |
||||
PUHY-**T(S)HM |
P1100 |
P400 |
P350 |
P350 |
CMY-Y300VBK2 |
|||||||||
[3/4] |
[1-5/8](*) |
[3/4] |
[1-3/8] |
|||||||||||
|
P1150 |
P450 |
P350 |
P350 |
|
|
|
|
|
|
||||
|
P1200 |
P450 |
P400 |
P350 |
|
|
|
|
|
|
||||
|
P1250 |
P450 |
P450 |
P350 |
|
|
|
|
|
|
||||
|
P264 |
|
P120 |
P72 |
P72 |
|
|
|
ø34.93 |
|
|
|||
|
P288 |
|
P120 |
P96 |
P72 |
|
|
ø19.05 |
ø19.05 |
ø34.93 |
||||
|
|
|
|
[1-3/8](*) |
||||||||||
PUHY-**Y(S)HMU |
P312 |
|
P120 |
P120 |
P72 |
CMY-Y300VBK2 |
||||||||
|
[3/4] |
|
[3/4] |
[1-3/8] |
||||||||||
|
P336 |
|
P120 |
P120 |
P96 |
|
|
|
ø41.28 |
|
|
|||
|
P360 |
|
P120 |
P120 |
P120 |
|
|
|
[1-5/8](*) |
|
|
|||
|
P264 |
|
P120 |
P72 |
P72 |
|
|
|
ø34.93 |
|
|
|||
|
P288 |
|
P120 |
P96 |
P72 |
|
|
ø19.05 |
ø19.05 |
ø34.93 |
||||
|
|
|
|
[1-3/8](*) |
||||||||||
PUHY-**T(S)HMU |
P312 |
|
P120 |
P120 |
P72 |
CMY-Y300VBK2 |
||||||||
|
[3/4] |
|
[3/4] |
[1-3/8] |
||||||||||
|
P336 |
|
P120 |
P120 |
P96 |
|
|
|
ø41.28 |
|
|
|||
|
P360 |
|
P120 |
P120 |
P120 |
|
|
|
[1-5/8](*) |
|
|
|||
|
P850(-AH) |
P350 |
P300 |
P200 |
|
|
|
|
|
|
||||
|
P900(-AH) |
P350 |
P300 |
P250 |
|
|
|
|
|
|
||||
|
P950 |
|
P400 |
P300 |
P250 |
|
|
|
|
|
|
|||
|
P1000 |
P400 |
P300 |
P300 |
|
|
ø19.05 |
ø41.28 |
ø19.05 |
ø34.93 |
||||
PUHY-**Y(S)HC |
P1050 |
P400 |
P350 |
P300 |
CMY-Y300VBK2 |
|||||||||
[3/4] |
[1-5/8](*) |
[3/4] |
[1-3/8] |
|||||||||||
P1100 |
P400 |
P350 |
P350 |
|
|
|||||||||
|
|
|
|
|
|
|
||||||||
|
P1150 |
P400 |
P400 |
P350 |
|
|
|
|
|
|
||||
|
P1200 |
P400 |
P400 |
P400 |
|
|
|
|
|
|
||||
|
P1250 |
P450 |
P450 |
P350 |
|
|
|
|
|
|
4 Three outdoor units |
|
|
|
|
|
|
|
|
||
|
|
Unit model |
|
Liquid |
Gas |
|
|
|
||
|
|
E or G or I |
F or H or J |
|
|
|||||
|
|
|
A1 |
|
A2 |
A3 |
|
|
|
|
|
|
|
B1 |
|
B2 |
B3 |
|
|
|
|
Twinning pipe~Outdoor unit |
|
C1 |
|
C2 |
C3 |
|
|
|
||
|
D1 |
|
D2 |
D3 |
|
|
|
|||
|
|
|
|
|
|
|
||||
|
|
|
E1 |
|
E2 |
E3 |
|
|
|
|
|
|
|
F1 |
|
F2 |
F3 |
|
(Unit: mm[in]) |
||
|
|
|
|
|
|
|
|
|
|
|
|
A1 |
B1 |
|
C1 |
|
D1 |
|
E1 |
F1 |
|
|
A2 |
B2 |
|
C2 |
|
D2 |
|
E2 |
F2 |
|
|
A3 |
B3 |
|
C3 |
|
D3 |
|
E3 |
F3 |
|
|
P250 |
P300 |
|
P350 |
|
P400 |
P450 |
– |
||
|
ø9.52 |
ø12.7 |
|
ø12.7 |
|
ø15.88 |
ø15.88 |
– |
||
|
[3/8](*) |
[1/2](*) |
|
[1/2](*) |
|
[5/8](*) |
[5/8](*) |
|||
|
|
|
|
|||||||
|
ø22.2 |
ø 22.2 |
|
ø28.58 |
|
ø28.58 |
ø28.58 |
– |
||
|
[7/8](*) |
[7/8](*) |
|
[1-1/8] |
|
[1-1/8] |
[1-1/8] |
|||
PUHY-**YHM |
|
|
|
|||||||
EP200 |
EP300 |
|
– |
|
– |
|
– |
– |
||
|
ø9.52 |
ø12.7 |
|
– |
|
– |
|
– |
– |
|
|
[3/8](*) |
[1/2](*) |
|
|
|
|||||
|
|
|
|
|
|
|
|
|||
|
ø19.05 |
ø 22.2 |
|
– |
|
– |
|
– |
– |
|
|
[3/4](*) |
[7/8](*) |
|
|
|
|||||
|
|
|
|
|
|
|
|
|||
|
P250 |
P300 |
|
P350 |
|
P400 |
P450 |
– |
||
|
ø9.52 |
ø12.7 |
|
ø12.7 |
|
ø15.88 |
ø15.88 |
– |
||
PUHY-**THM |
[3/8](*) |
[1/2](*) |
|
[1/2](*) |
|
[5/8](*) |
[5/8](*) |
|||
|
|
|
||||||||
|
ø22.2 |
ø 22.2 |
|
ø28.58 |
|
ø28.58 |
ø28.58 |
– |
||
|
[7/8](*) |
[7/8](*) |
|
[1-1/8] |
|
[1-1/8] |
[1-1/8] |
|||
|
|
|
|
|||||||
|
P72 |
P96 |
|
P120 |
|
– |
|
– |
– |
|
|
ø9.52 |
ø9.52 |
|
ø12.7 |
|
– |
|
– |
– |
|
PUHY-**YHMU |
[3/8](*) |
[3/8](*) |
|
[1/2](*) |
|
|
||||
|
|
|
|
|
|
|||||
ø19.05 |
ø22.2 |
|
ø22.2 |
|
– |
|
– |
– |
||
|
[3/4](*) |
[7/8](*) |
|
[7/8](*) |
|
|
||||
|
|
|
|
|
|
|
||||
|
P72 |
P96 |
|
P120 |
|
– |
|
– |
– |
|
|
ø9.52 |
ø9.52 |
|
ø12.7 |
|
– |
|
– |
– |
|
PUHY-**THMU |
[3/8](*) |
[3/8](*) |
|
[1/2](*) |
|
|
||||
|
|
|
|
|
|
|||||
|
ø19.05 |
ø22.2 |
|
ø22.2 |
|
– |
|
– |
– |
|
|
[3/4](*) |
[7/8](*) |
|
[7/8](*) |
|
|
||||
|
|
|
|
|
|
|
||||
|
P200 |
P250 |
|
P300 |
|
P350 |
P400 |
P450 |
||
|
ø9.52 |
ø9.52 |
|
ø12.7 |
|
ø12.7 |
ø15.88 |
ø15.88 |
||
PUHY-**YHC |
[3/8](*) |
[3/8](*) |
|
[1/2](*) |
|
[1/2](*) |
[5/8](*) |
[5/8](*) |
||
|
ø19.05 |
ø22.2 |
|
ø22.2 |
|
ø28.58 |
ø28.58 |
ø28.58 |
||
|
[3/4](*) |
[7/8](*) |
|
[7/8](*) |
|
[1-1/8] |
[1-1/8] |
[1-1/8] |
(3) |
Slope of twinning pipes |
|
|
|
|
Make sure the slope of the twinning pipes are at an angle within ±15° to |
|
|
|
|
the horizontal plane. |
|
|
|
|
If the slope exceeds the specified angle, the unit may be damaged. |
Note: Refer to the figure below for the installation |
||
|
|
Note: See the following drawing for the fitting position |
||
(4) |
The length of the straight pipe between indoor units and the twin- |
|
position of the twinning pipe. |
|
|
of the twinning pipe. |
|||
|
ning pipe |
|
TwinningReducerpipe |
|
|
|
|
|
|
|
Use the pipes supplied in the twinning kit, and make sure the section of |
|
|
|
|
the field-supplied pipe that connects to the twinning pipe has at least |
°1515±° |
|
|
|
500 mm [19-11/16 in] of straight section. (The section of the field- |
± |
|
|
|
|
The angle of tilt of the reducer should be within |
|
|
|
|
|
||
|
supplied pipe that connects to the twinning pipe must have at least 500 |
|
|
|
|
|
Slope of the twinning pipes are at an angle within |
|
|
|
mm [19-11/16 in] of straight section.) If the straight section is less than |
|
±15° with the ground. |
|
|
|
±15° to the horizontal plane |
|
|
|
500 mm [19-11/16 in], it may result in equipment damage. |
|
|
|
(5) |
Pipe connection |
|
|
|
|
When connecting the twinning kit to the outdoor unit, note the following: |
|
|
|
·Make sure the pipes from the twinning pipe to the outdoor unit are sloped downwards (towards the twinning pipes).
·If the piping on the outdoor unit side (from the twinning pipe) exceeds 2 m [6 ft], ensure a trap (gas pipe only) within 2 m [6 ft].
Make sure the height of the trap is 200 mm [7-7/8 in] or more.
If there is no trap, oil can accumulate inside the pipe, causing a shortage of oil and may damage the compressor.
<2 m [6 ft] or less> |
<More than 2 m [6 ft] apart> |
||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
100 mm |
|
To Indoor unit |
|
|
200 mm |
|
B |
|
|
|
To Indoor unit |
[7-7/8 in] |
|
|
|||
[3-15/16 |
|
|
A |
|
To Indoor unit |
|||
To Indoor unit |
|
or more |
|
|||||
in] or |
2 m [6 ft] |
|
|
|
Twinning pipe |
|||
Downward slope |
|
Twinning pipe |
|
|
LessWithinthan |
|||
|
|
|
|
|||||
more |
|
Upward slope |
2 m (6 ft) |
|
|
|
|
|
Twinning pipe |
|
|
|
|
2 m [6 ft] |
|
||
|
|
|
|
|
|
|
||
|
|
|
|
|
|
Total pipe length = A+B<10 m [32 ft] |
||
|
· If the twinning pipe is installed above the base |
OutdoorOutoor unitunit1 1 OutdoorOutoor unitunit2 2 OutdoorOutoor unitunit3 3 |
|
|
|
|||
|
|
|
|
|
|
|
||
|
of the outdoor unit, it should be no more than |
|
|
|
|
|
|
|
|
200 mm [7-7/8 in]. |
|
|
|
|
|
|
|
|
|
|
|
Twinning 1 |
Twinning 2 |
ToToIndoorIndoorunit |
|
|
|
|
|
|
Twinning 1 |
Twinning 2 |
|
|
|
|
|
200 mm [7-7/8 in] |
|
|
|
|
|
|
|
|
Less than |
|
|
unit |
|
|
|
|
|
max |
200 mm |
|
|
|
3 |
|
|
|
(7 inch) |
|
|
|
|
||
|
|
|
|
|
|
|
|
(2) Accessory piping parts |
|
|
|
|
|
(Unit: mm[in]) |
|||
Model |
Section |
|
Supplied pipe |
|
|
|
|||
CMY-Y100VBK2 |
Liquid |
OD12.7[1/2]-ID9.52[3/8] (2) |
OD15.88[5/8]-ID12.7[1/2] |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
||
Gas |
OD22.2[7/8]-ID28.58[1-1/8] |
OD22.2[7/8]-ID19.05[3/4] (2) |
|
|
|
|
|
||
|
|
|
|
|
|
||||
CMY-Y200VBK2 |
Liquid |
OD15.88[5/8]-ID12.7[1/2] (2) |
|
|
|
|
|
|
|
Gas |
OD34.93[1-3/8]-ID41.28[1-5/8] |
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|||
|
|
|
|
|
|
|
|
||
CMY-Y300VBK2 |
Liquid |
OD12.7[1/2]-ID9.52[3/8] |
OD12.7[1/2]-ID15.88[5/8] (2) |
OD15.88[5/8]-ID9.52[3/8] |
|
OD15.88[5/8]-ID12.7[1/2] |
|||
Gas |
OD28.58[1-1/8]-ID22.2[7/8] (3) |
OD38.1[1-1/2]-ID41.28[1-5/8] |
OD28.58[1-1/8]-ID19.05[3/4] (2) |
OD38.1[1-1/2]-ID34.93[1-3/8] |
|||||
|
|||||||||
(3) List of field-supplied parts |
|
|
Outdoor unit |
1 |
Outdoor unit 2 |
||||
• Refrigerant pipes other than the ones provided in the kit. |
|
||||||||
|
Outdoor unit 1 |
|
Outdoor unit 2 |
||||||
|
|
• Heat-resistant insulation material (for field-supplied refrigerant pipes)
•Insulation cover tape
2.Selecting the Correct Size Refrigerant Pipes and Using the Twinning Kit
(1)Two outdoor units
1 Field-supply the pipes to be connected to the kit.
2Choose the correct size pipe using the table below. Connect the field-supplied pipe to the twinning kit for the sizes in the
table that are marked with an asterisk (*).
3 If the pipe was cut with a pipe cutter, remove the burrs and |
|
Ee |
Aa |
|
|
C |
c |
To Indoorrunitunit |
|||
|
|||||
eliminate foreign materials before connecting. |
|
|
Liquidtwinning pipe |
||
|
|
Ff |
|
pipe |
|
D |
d |
B |
ToTo Indoorr unitunit |
||
|
|
|
b |
|
Gastwinningpipepipe
1 Two outdoor units |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Package unit name |
|
|
|
|
|
A0 |
|
|
|
|||||
Component unit name |
|
Outdoor unit 1 |
|
|
B0 |
|
|
|
||||||
|
Outdoor unit 2 |
|
|
C0 |
|
|
|
|||||||
|
|
|
|
|
|
|
|
|
||||||
|
|
OutIdoor Twinning Kit |
|
|
D0 |
|
|
|
||||||
Indoor unit~Twinning pipe |
Liquid |
|
|
A |
|
|
E0 |
|
|
|
||||
Gas |
|
|
B |
|
|
F0 |
|
(Unit: mm[in]) |
||||||
|
|
|
|
|
|
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
A0 |
|
B0 |
|
C0 |
|
D0 |
E0 |
F0 |
||
|
|
|
P500 |
|
P250 |
|
P250 |
|
|
|
|
|||
|
|
|
P550 |
|
P300 |
|
P250 |
CMY-Y100VBK2 |
ø15.88 |
ø28.58 |
||||
|
|
|
P600 |
|
P350 |
|
P250 |
[5/8] |
[1-1/8] |
|||||
|
|
|
|
|
|
|
||||||||
|
|
|
P650 |
|
P350 |
|
P300 |
|
|
|
|
|||
|
|
|
P700 |
|
P350 |
|
P350 |
|
|
|
ø34.93 |
|||
|
|
|
P750 |
|
P400 |
|
P350 |
|
|
ø19.05 |
||||
|
|
|
|
|
|
|
[1-3/8] |
|||||||
|
|
|
P800 |
|
P450 |
|
P350 |
CMY-Y200VBK2 |
||||||
|
|
|
|
|
[3/4] |
|
||||||||
|
|
|
P850 |
|
P450 |
|
P400 |
|
|
|
ø41.28 |
|||
PUHY-**Y(S)HM |
|
|
P900 |
|
P450 |
|
P450 |
|
|
|
[1-5/8](*) |
|||
|
|
|
EP400 |
|
EP200 |
|
EP200 |
|
|
ø12.7[1/2] |
|
|||
|
|
|
EP450 |
|
P250 |
|
EP200 |
|
|
|
|
|||
|
|
|
EP500 |
|
EP300 |
|
EP200 |
CMY-Y100VBK2 |
ø15.88 |
ø28.58 |
||||
|
|
|
EP550 |
|
EP300 |
|
P250 |
|||||||
|
|
|
|
|
|
|
[5/8] |
[1-1/8] |
||||||
|
|
|
EP600 |
|
EP300 |
|
EP300 |
|
|
|
|
|||
|
|
|
EP650 |
|
P350 |
|
EP300 |
|
|
|
|
|||
|
|
|
HP400 |
|
HP200 |
|
HP200 |
CMY-Y100VBK2 |
ø15.88 |
ø28.58 |
||||
|
|
|
HP500 |
|
HP250 |
|
HP250 |
[5/8] |
[1-1/8] |
|||||
|
|
|
|
|
|
|
||||||||
|
|
|
P500 |
|
P250 |
|
P250 |
|
|
|
|
|||
|
|
|
P550 |
|
P300 |
|
P250 |
CMY-Y100VBK2 |
ø15.88 |
ø28.58 |
||||
|
|
|
P600 |
|
P350 |
|
P250 |
[5/8] |
[1-1/8] |
|||||
|
|
|
|
|
|
|
||||||||
|
|
|
P650 |
|
P350 |
|
P300 |
|
|
|
|
|||
PUHY-**T(S)HM |
|
|
P700 |
|
P350 |
|
P350 |
|
|
|
ø34.93 |
|||
|
|
|
P750 |
|
P400 |
|
P350 |
|
|
|
||||
|
|
|
|
|
|
|
ø19.05 |
[1-3/8] |
||||||
|
|
|
P800 |
|
P450 |
|
P350 |
CMY-Y200VBK2 |
||||||
|
|
|
|
|
[3/4] |
|
||||||||
|
|
|
P850 |
|
P450 |
|
P400 |
|
|
ø41.28 |
||||
|
|
|
|
|
|
|
|
|||||||
|
|
|
P900 |
|
P450 |
|
P450 |
|
|
|
[1-5/8](*) |
|||
|
|
|
P144 |
|
P72 |
|
P72 |
|
|
|
|
|||
|
|
|
P168 |
|
P96 |
|
P72 |
|
|
ø15.88 |
ø28.58 |
|||
PUHY-**Y(S)HMU |
|
|
P192 |
|
P120 |
|
P72 |
CMY-Y100VBK2 |
||||||
|
|
P216 |
|
P120 |
|
P96 |
|
|
[5/8] |
[1-1/8] |
||||
|
|
|
|
|
|
|
|
|
||||||
|
|
|
P240 |
|
P120 |
|
P120 |
|
|
|
|
|||
|
|
|
P144 |
|
P72 |
|
P72 |
|
|
|
|
|||
|
|
|
P168 |
|
P96 |
|
P72 |
|
|
ø15.88 |
ø28.58 |
|||
|
|
|
P192 |
|
P120 |
|
P72 |
CMY-Y100VBK2 |
||||||
PUHY-**T(S)HMU |
|
|
P216 |
|
P120 |
|
P96 |
|
|
[5/8] |
[1-1/8] |
|||
|
|
|
|
|
|
|
|
|||||||
|
|
|
P240 |
|
P120 |
|
P120 |
|
|
|
|
|||
|
|
|
HP144 |
|
HP72 |
|
HP72 |
CMY-Y100VBK2 |
ø15.88 |
ø28.58 |
||||
|
|
|
HP192 |
|
HP96 |
|
HP96 |
[5/8] |
[1-1/8] |
|||||
|
|
|
|
|
|
|
||||||||
PUHY-**Y(S)HMC |
|
|
HP400 |
|
HP200 |
|
HP200 |
CMY-Y100VBK2 |
ø15.88 |
ø28.58 |
||||
|
|
HP500 |
|
HP250 |
|
HP250 |
[5/8] |
[1-1/8] |
||||||
|
|
|
|
|
|
|
||||||||
|
|
P450(-AH) |
|
P250 |
|
P200 |
|
|
|
|
||||
|
|
|
P500 |
|
P250 |
|
P250 |
|
|
ø15.88 |
ø28.58 |
|||
|
|
|
P550 |
|
P300 |
|
P250 |
CMY-Y100VBK2 |
||||||
|
|
|
P600 |
|
P350 |
|
P250 |
|
|
[5/8] |
[1-1/8] |
|||
|
|
|
|
|
|
|
|
|
||||||
PUHY-**Y(S)HC |
|
|
P650 |
|
P350 |
|
P300 |
|
|
|
|
|||
|
|
P700 |
|
P350 |
|
P350 |
|
|
|
ø34.93 |
||||
|
|
|
|
|
|
|
|
|||||||
|
|
|
P750 |
|
P400 |
|
P350 |
|
|
|
||||
|
|
|
|
|
|
|
ø19.05 |
[1-3/8] |
||||||
|
|
|
P800 |
|
P400 |
|
P400 |
CMY-Y200VBK2 |
||||||
|
|
|
|
|
|
|||||||||
|
|
|
|
|
[3/4] |
|
||||||||
|
|
|
P850 |
|
P450 |
|
P400 |
|
|
ø41.28 |
||||
|
|
|
|
|
|
|
|
|||||||
|
|
|
P900 |
|
P450 |
|
P450 |
|
|
|
[1-5/8](*) |
(2) Three outdoor units
1 Field-supply the pipes to be connected to the kit. 2 Choose the correct size pipe using the table below.
Connect the field-supplied pipe to the twinning kit for the sizes in the table that are marked with an asterisk (*).
3If the pipe was cut with a pipe cutter, remove the burrs and eliminate foreign materials before connecting.
2 Two outdoor units |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Unit model |
|
Liquid |
|
|
Gas |
|
|
|
||||
|
|
|
C or E |
|
D or F |
|
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
A1 |
|
|
|
A2 |
|
|
A3 |
|
|
|
|
|
|
|
B1 |
|
|
|
B2 |
|
|
B3 |
|
|
|
|
Twinning pipe~Outdoor unit |
|
C1 |
|
|
|
C2 |
|
|
C3 |
|
|
|
||
|
D1 |
|
|
|
D2 |
|
|
D3 |
|
|
|
|||
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
E1 |
|
|
|
E2 |
|
|
E3 |
|
|
|
|
|
|
|
F1 |
|
|
|
F2 |
|
|
F3 |
|
(Unit: mm[in]) |
||
|
|
|
|
|
|
|
|
|
|
|
||||
|
A1 |
|
|
B1 |
|
C1 |
|
D1 |
E1 |
F1 |
||||
|
A2 |
|
|
B2 |
|
C2 |
|
D2 |
E2 |
F2 |
||||
|
A3 |
|
|
B3 |
|
C3 |
|
D3 |
E3 |
F3 |
||||
|
P250 |
|
|
P300 |
|
P350 |
|
P400 |
P450 |
– |
||||
|
ø9.52 |
|
|
ø12.7 |
|
ø12.7 |
|
ø15.88 |
ø15.88 |
– |
||||
|
[3/8](*) |
|
|
[1/2] |
|
[1/2](*) |
|
[5/8] |
|
[5/8] |
||||
|
|
|
|
|
|
|
||||||||
|
ø22.2 |
|
|
ø22.2 |
|
ø28.58 |
|
ø28.58 |
ø28.58 |
– |
||||
|
[7/8] |
|
|
[7/8] |
|
[1-1/8](*) |
|
[1-1/8] |
|
[1-1/8] |
||||
|
|
|
|
|
|
|
||||||||
|
EP200 |
|
|
EP300 |
|
– |
|
– |
– |
– |
||||
|
ø9.52 |
|
|
ø12.7 |
|
– |
|
– |
– |
– |
||||
PUHY-**YHM |
[3/8](*) |
|
|
[1/2] |
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|||||
|
ø19.05 |
|
|
ø22.2 |
|
– |
|
– |
– |
– |
||||
|
[3/4](*) |
|
|
[7/8] |
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
||||
|
HP200 |
|
|
HP250 |
|
– |
|
– |
– |
– |
||||
|
ø9.52 |
|
|
ø9.52 |
|
– |
|
– |
– |
– |
||||
|
[3/8](*) |
|
|
[3/8](*) |
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
||||
|
ø19.05 |
|
|
ø22.2 |
|
– |
|
– |
– |
– |
||||
|
[3/4](*) |
|
|
[7/8] |
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
||||
|
P250 |
|
|
P300 |
|
P350 |
|
P400 |
P450 |
– |
||||
|
ø9.52 |
|
|
ø12.7 |
|
ø12.7 |
|
ø15.88 |
ø15.88 |
– |
||||
PUHY-**THM |
[3/8](*) |
|
|
[1/2] |
|
[1/2](*) |
|
[5/8] |
|
[5/8] |
||||
|
|
|
|
|
|
|||||||||
|
ø22.2 |
|
|
ø22.2 |
|
ø28.58 |
|
ø28.58 |
ø28.58 |
– |
||||
|
[7/8] |
|
|
[7/8] |
|
[1-1/8](*) |
|
[1-1/8] |
|
[1-1/8] |
||||
|
|
|
|
|
|
|
||||||||
|
P72 |
|
|
P96 |
|
P120 |
|
– |
– |
– |
||||
|
ø9.52 |
|
|
ø9.52 |
|
ø12.7 |
|
– |
– |
– |
||||
PUHY-**YHMU |
[3/8](*) |
|
|
[3/8](*) |
|
[1/2] |
|
|
||||||
|
|
|
|
|
|
|
|
|
||||||
ø19.05 |
|
|
ø22.2 |
|
ø22.2 |
|
– |
– |
– |
|||||
|
[3/4](*) |
|
|
[7/8] |
|
[7/8] |
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
||||
|
P72 |
|
|
P96 |
|
P120 |
|
– |
– |
– |
||||
|
ø9.52 |
|
|
ø9.52 |
|
ø12.7 |
|
– |
– |
– |
||||
|
[3/8](*) |
|
|
[3/8](*) |
|
[1/2] |
|
|
||||||
|
|
|
|
|
|
|
|
|
|
|||||
|
|
|
|
|
|
|
|
|
|
|
|
|||
|
ø19.05 |
|
|
ø22.2 |
|
ø22.2 |
|
– |
– |
– |
||||
|
[3/4](*) |
|
|
[7/8] |
|
[7/8] |
|
|
||||||
PUHY-**THMU |
|
|
|
|
|
|
|
|
|
|||||
HP72 |
|
|
HP96 |
|
– |
|
– |
– |
– |
|||||
|
ø9.52 |
|
|
ø9.52 |
|
– |
|
– |
– |
– |
||||
|
[3/8](*) |
|
|
[3/8](*) |
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
||||
|
|
|
|
|
|
|
|
|
|
|
|
|
||
|
ø19.05 |
|
|
ø22.2 |
|
– |
|
– |
– |
– |
||||
|
[3/4](*) |
|
|
[7/8] |
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
||||
|
HP200 |
|
|
HP250 |
|
– |
|
– |
– |
– |
||||
|
ø9.52 |
|
|
ø9.52 |
|
– |
|
– |
– |
– |
||||
PUHY-**YHMC |
[3/8](*) |
|
|
[3/8](*) |
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|||||
|
ø19.05 |
|
|
ø22.2 |
|
– |
|
– |
– |
– |
||||
|
[3/4](*) |
|
|
[7/8] |
|
|
||||||||
|
|
|
|
|
|
|
|
|
|
|
||||
|
P200 |
|
|
P250 |
|
P300 |
|
P350 |
P400 |
P450 |
||||
|
ø9.52 |
|
|
ø9.52 |
|
ø12.7 |
|
ø12.7 |
|
ø15.88 |
ø15.88 |
|||
PUHY-**YHC |
[3/8](*) |
|
|
[3/8](*) |
|
[1/2] |
|
|
[1/2](*) |
|
[5/8] |
[5/8] |
||
ø19.05 |
|
|
ø22.2 |
|
ø22.2 |
|
ø28.58 |
ø28.58 |
ø28.58 |
|||||
|
|
|
|
|
||||||||||
|
[3/4](*) |
|
|
[7/8] |
|
[7/8] |
|
|
[1-1/8] |
|
[1-1/8] |
[1-1/8] |
|
|
|
|
|
|
Outdoor unit |
3 |
|
Outdooror unitunit1 |
1 |
Outdoorunitunit2 |
2 |
|||
|
Outdoor unit 3 |
|
|||||
|
|
|
|
|
|
|
|
|
E |
G |
g |
|
cC |
|
I i |
|
Aa |
|
To Indoorunit |
unit |
e |
|
|
|
|
||||||||
|
|
|
|
|||||||||
|
|
|
||||||||||
|
|
|
|
Liquid twinning pipe 1 |
|
Liquid twinning pipe 2 |
|
|||||
|
|
Hh |
Liquid 1 twinning pipe |
Jj |
Liquid 2 |
twinning pipe |
||||||
|
|
|
|
|
|
b |
|
|
|
|||
|
|
|
Dd |
|
|
|
|
|
||||
f F |
|
|
|
|
|
|
B |
To Indoorunit unit |
||||
|
|
|
|
|
||||||||
|
|
|
|
|
|
|
||||||
|
|
|
|
GasGas1 twinningtwinningpipe pipe 1 |
Gas twinning pipe 2 |
|||||||
|
|
|
|
Gas 2 twinning pipe |
2
3. Pipe Connection Example
Connect the pipes between outdoor units, referencing the figures below. <For two outdoor units>
<For three outdoor units>
Field piping
Field-supplied pipe
Field piping
Field-supplied pipe
Twinning kit
Twinning kit
Fieldld-pipingsupplied pipe
The length of the straight pipe must
Straight pipe that is 500 mm be 500 mm (19 inch) or longer.
[19-11/16 in] or more
Twinning kit
Twinning kit
|
FieldField-suppipinglied pipe |
|
Straight pipe that is 500 mm |
|
Twinning kit |
|
Twinning kit |
|
The length of the straight pipe must |
|
[19-11/16 in] or more
be 500 mm (19 inch) or longer.
Field-suppliedpiping pipe
The length of the straight pipe must
be 500 mm (19 inch) or longer.
Straight pipe that is 500 mm [19-11/16 in] or more
4. Insulation Cover Installation
Install the insulation cover on the twinning kit after brazing the pipes and twinning kit.
Insulate all refrigerant pipes. Insulate the liquid and gas pipes separately, and pipes located inside the unit as well as the outside. Use heat-resistant insulation material (Heat resistant: at least 120 °C [248 °F], Thickness: liquid = 10 mm [13/32 in],
gas = 20 mm [13/16 in]). Position the edges of the insulation cover and heat-resistant insulation material so as not to leave a gap, and then wrap the exterior perimeter of the pipe joints and middle with tape (field-supplied).
FieldField-suppliedpipingpipe
FieldField-suppliedipingpipe
Twinningkitkit |
FieldField-suppliedpipingpipe |
|
|
|
Insulation material |
|
As the insulation cover |
|
|
Insulationcover |
|||||
|
|
Heat-resistant insulation |
|
contracts slightly, conduct |
||
|
|
|
(fieldmaterialsupply)(field-supplied) |
|
||
|
|
|||||
|
|
|
|
|
Insulati |
covers can shrink. |
|
|
|
|
|
taping |
onthe field securely by |
|
|
|
|
|
Overlap the tape as shown in |
|
|
|
|
|
|
providing lapped parts as |
|
|
|
|
|
|
the left figure so that there |
|
|
|
|
|
|
shown in the left, so that no gap |
|
|
|
|
|
|
will be no gap in between the |
|
|
|
|
|
|
will exist on the insulation cover |
|
|
|
|
|
|
insulation cover or field- |
|
OverlapLappedmarginspaceof theof tapetaping |
and field supply insulation |
|||||
installed insulation material. |
material.
Tape (field-supplied)
Insulation material (field supply)
Heat-resistant insulation material (field-supplied)
|
Heat-resistant |
|
Insulation m terial |
InsulationInsulationcovercover |
insulation material |
(field supply) |
|
|
(field-supplied) |
Tape(field-supply)supplied)
Tape (field-supplied)
Tape (field supply)
5. Miscellaneous Notes
Secure the field-supplied pipes with a pipe cover and a cable tie in place to keep them from coming in contact with other pipes as |
4 |
necessary. |