Mitsubishi CMY-R100XLVBK, CMY-R200XLVBK Installation Manual

0 (0)
Mitsubishi CMY-R100XLVBK, CMY-R200XLVBK Installation Manual

Mitsubishi Electric Air Conditioner CITY MULTI

Twinning Kit Installation Manual

CMY-R100XLVBK

CMY-R200XLVBK

¡For your safety, thoroughly read the following instructions prior to installation.

WT05989X01

Safety Precautions

¡Thoroughly read the following “Safety Precautions” to ensure proper installation. ¡Observe the following important safety precautions at all times.

¡Hazards that can occur from incorrect handling are classified by the symbols below:

WARNING Incorrect handling can result in death or serious injury.

CAUTION Incorrect handling can result in bodily injury and/or structure damage.

WARNING

Only a dealer or qualified technician should perform installation.

¡Improper installation may result in refrigerant gas leakage and equipment damage.

Properly install all parts according to the instructions in the Installation Manual.

¡If the wrong twinning pipe or wrong size connecting pipe is used, air conditioning performance will suffer.

Do not make any modifications or alterations. Consult your dealer for repair.

¡Improper installation may result in water leakage, electric shock, or fire.

In the event of a refrigerant leak, thoroughly ventilate the room.

¡If refrigerant leaks and comes in contact with an open flame, toxic gases will be generated.

When installing or relocating the unit, check that no substance other than the specified refrigerant (R410A) enters the refrigerant circuit.

¡Any presence of foreign substance or air can cause abnormal pressure rise or explosion.

After installation, check for a refrigerant leak.

¡If leaked refrigerant comes in contact with a heat source, such as a fan heater, stove, or electric grill, toxic gases will be generated.

CAUTION

Properly dispose of packing materials.

¡Plastic bags can pose suffocation and choking hazards: keep them out of the reach of children. Tear the plastics bags before disposing of them.

Do not touch the refrigerant pipes and refrigerant circuit components with bare hands during and immediately after operation.

¡During or immediately after operation, certain parts of the unit such as pipes and compressor may be either very cold or hot, depending on the state of the refrigerant in the unit at the time. To reduce the risk of frostbites and burns, do not touch these parts with bare hands.

See the Installation Manual that came with the outdoor unit for installation instructions.

1

1. Confirming the Package Contents

The following items are included with the Twinning Kit (CMY-R100XLVBK, CMY-R200XLVBK). Verify that all items are present before starting installation.

Always use the twinning pipes included in the kit when preparing the twinning kit.

If the field-supplied pipes do not fit the parts in the kit, use the accessory piping parts listed below.

(1)Package contents

Model

1Low-pressure

2High-pressure

3Fixing screw

4Cable tie

5Elbow pipe

6Elbow pipe

7High-pressure pipe

8High-pressure pipe

9Pipe cover

(for routing through

(for routing through

 

twinning kit

twinning pipe

 

 

Ø28.58 [1-1/8]

Ø31.75 [1-1/4]

the bottom)

the front)

 

CMY-R100XLVBK

1

1

1

2

1

1

1

1

1

 

 

 

 

 

 

 

 

 

 

CMY-R200XLVBK

1

1

1

2

1

1

1

1

1

 

 

 

 

 

 

 

 

 

 

Model

0OD31.75 [1-1/4]

AOD22.2 [7/8]

BOD19.05 [3/4]

COD22.2 [7/8]

DOD28.58 [1-1/8]

EOD31.75[1-1/4]

FInstallation Manual

GInsulation cover

HOD34.93[1-3/8]

-ID28.58 [1-1/8]

-ID19.05 [3/4]

-ID22.2 [7/8]

-ID28.58 [1-1/8]

-ID22.2 [7/8]

-ID34.93 [1-3/8]

(this booklet)

-ID41.28 [1-5/8]

CMY-R100XLVBK

1

1

3

1

1

1

1

1

-

 

 

 

 

 

 

 

 

 

 

CMY-R200XLVBK

-

1

3

-

-

1

1

1

1

 

 

 

 

 

 

 

 

 

 

(2)List of field-supplied parts

·Refrigerant pipes other than the ones provided in the kit

·Heat-resistant insulation material (for field-supplied refrigerant pipes)

·Insulation cover tape

2.Selecting the Correct Size Refrigerant Pipes and Using the Twinning Kit

(1)Pipe size

1 Field-supply the pipes to be connected to the kit. 2 Choose the correct size pipe using the table

below. Connect the fieldsupplied pipe to the twinning kit for the sizes in the table that are marked with an asterisk (*).

3 If the pipe was cut with a pipe cutter, remove the burrs and eliminate foreign materials before connecting.

On the low-pressure side, the twinning kit connects to the field-supplied pipes inside the outdoor unit.

The distributor on the low-pressure side must be placed in the outdoor unit that has a larger capacity index of the two, regardless of the relative positions of the outdoor units or their addresses.

If the distributor is placed in the outdoor unit that has a smaller capacity, refrigerant will not be properly distributed and compressor failure may result.

( If outdoor units that have the same capacity are used in combination, the distributor can be placed in either outdoor unit.)

Outdoor unit 1

 

 

 

Outdoor unit 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Twinning kit (Low pressure)

F

C

D

A

To BC controller

 

 

 

E

 

Twinning pipe(High pressure)

B

To BC controller

 

Package unit name

 

 

 

 

 

 

A0

 

 

 

Component unit name

 

Outdoor unit 1

 

 

B0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit 2

 

 

C0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor Twinning Kit

 

 

 

 

 

 

D0

 

 

 

BC controller ~ Twinning pipe

 

High-pressure

 

A

 

E0

 

 

 

 

Low-pressure

 

B

 

F0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

( Unit : mm [in] )

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A0

 

 

B0

C0

 

 

 

D0

 

 

E0

 

F0

PURY- Y(S)JMU

P216

 

P120

P96

 

 

 

 

 

 

 

Ø28.58(*)

PURY- T(S)JMU

P240

 

P120

P120

 

CMY-R100XLVBK

 

Ø28.58

 

[1-1/8]

 

P264

 

P144

P120

 

 

[1-1/8]

 

Ø34.93(*)

 

 

 

 

 

 

 

 

 

P288

 

P144

P144

 

 

 

 

 

 

 

 

 

[1-3/8]

PURY- Y(S)JM

EP600

 

EP350

EP250

 

 

 

 

 

 

 

 

 

Ø28.58(*)

 

EP650

 

EP350

EP300

 

 

 

 

 

Ø28.58

 

[1-1/8]

 

 

 

 

 

 

 

CMY-R100XLVBK

 

[1-1/8]

 

 

 

EP700

 

EP350

EP350

 

 

 

Ø34.93(*)

 

 

 

 

 

 

 

 

 

P800

 

P450

P350

 

 

 

 

 

 

 

 

 

[1-3/8]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P850

 

P450

P400

 

CMY-R200XLVBK

 

Ø28.58

 

Ø41.28(*)

 

P900

 

P450

P450

 

 

[1-1/8]

 

[1-5/8]

 

 

 

 

 

 

 

 

 

 

Unit model

High-pressure

Low-pressure

 

 

C or D

E or F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A1

A2

A3

 

 

 

 

 

 

 

 

Twinning pipe ~ Outdoor unit

 

B1

B2

B3

 

 

 

C1

C2

C3

 

 

 

 

 

( Unit : mm [in] )

 

 

A1

 

B1

 

C1

 

 

 

A2

 

B2

 

C2

 

 

 

A3

 

B3

 

C3

 

 

PURYYJMU

P96

 

P120

 

P144

 

 

PURYTJMU

 

 

 

 

 

 

 

Ø19.05

 

Ø19.05

 

Ø22.2(*)

 

 

 

[3/4]

 

[3/4]

 

[7/8]

 

 

 

 

 

 

 

 

 

 

 

Ø22.2(*)

 

Ø28.58

 

Ø28.58

 

 

 

[7/8]

 

[1-1/8]

 

[1-1/8]

 

 

 

 

 

 

 

 

 

 

PURYYJM

EP250

 

EP300

 

EP350

 

 

 

 

 

 

 

 

 

 

 

Ø19.05

 

Ø19.05

 

Ø19.05

 

 

 

[3/4]

 

[3/4]

 

[3/4]

 

 

 

 

 

 

 

 

 

 

 

Ø22.2(*)

 

Ø22.2(*)

 

Ø28.58

 

 

 

[7/8]

 

[7/8]

 

[1-1/8]

 

 

 

 

 

 

 

 

 

 

 

P350

 

P400

 

P450

 

 

 

Ø19.05

 

Ø22.2(*)

 

Ø22.2(*)

 

 

 

[3/4]

 

[7/8]

 

[7/8]

 

 

 

 

 

 

 

 

 

 

 

Ø28.58

 

Ø28.58

 

Ø28.58

 

 

 

[1-1/8]

 

[1-1/8]

 

[1-1/8]

 

 

 

 

 

 

 

 

 

 

See reverse.

2