Mitsubishi CMY-Y104-G, CMY-Y108-G, CMY-Y1010-G Installation Manual

0 (0)
Mitsubishi CMY-Y104-G, CMY-Y108-G, CMY-Y1010-G Installation Manual

For use with R410A-compatible units

OPTIONAL PARTS

HEADER FOR

4 BRANCHING (CMY-Y104-G)

 

HEADER FOR

8 BRANCHING (CMY-Y108-G)

 

INSTALLATION MANUAL

HEADER FOR 10 BRANCHING (CMY-Y1010-G)

1The following parts are contained in this box. Please identify the quantity with types.

Header for 4 branching (CMY-Y104-G)

1 Instruction

2 Header

3 Header

4 Pipe cover - 1

5 Pipe cover - 2

6 Band

 

 

 

 

 

 

 

 

 

For liquid line

For gas line

 

 

 

Usable for 3/4 branching

 

 

 

 

 

 

 

 

 

 

 

 

(* For 2 branching, use the optional header

This sheet 1 sheet

1 pc.

1pc.

2 pcs.

2 pcs.

4 pcs.

for 2 branching.)

 

Header for 8 branching (CMY-Y108-G)

1 Instruction

2 Header

3 Header

4 Pipe cover - 1

5 Pipe cover - 2

6 Band

7 Sealing material

 

 

 

 

 

 

 

 

Usable for 5/6/7/8 branching

 

 

 

 

 

 

 

This sheet 1 sheet

 

 

Each 2 pcs.

4 pcs.

6 pcs.

Each 1 pc.

 

Header for 10 branching (CMY-Y1010-G)

 

 

 

 

 

 

 

 

 

 

 

 

1 Instruction

2 Header

3 Header

4 Pipe cover - 1

5 Pipe cover - 2

6 Band

7 Sealing material

 

 

 

 

 

 

 

 

 

 

For liquid line

For gas line

 

 

 

 

Usable for 9/10 branching

 

 

 

 

 

 

 

This sheet 1 sheet

pc.

.

Each 2 pcs.

4 pcs.

6 pcs.

Each 1 pc.

 

IDøF IDøF

ODøG

ODøG

Pipe 1 – 7

Pipe 8 – 12

H

Plug 1 – 3

Plug 4·5

Note: When the number of connecting pipes is less than the number of header branches, insert a plug of the appropriate size into each branch that does not have piping connected to it.

Caution

The incorrect selection of the type of branch pipe and the size of connecting pipe does not allow the air conditioner to provide the rated capacity.

Please read this instruction manual carefully for correct mounting work.

Table-1 Accesorry pipes

 

Pipe Connection Specification

 

Quantity

 

 

F (Connecting

G (Outer

CMY-Y104-G CMY-Y108-G CMY-Y1010-G

 

Pipe Size)

Diameter)

 

 

 

Pipe 1

ø9.52

ø12.7

1

1

1

Pipe 2

ø15.88

ø19.05

1

1

2

Pipe 3

ø12.7

ø19.05

1

2

Pipe 4

ø6.35

ø9.52

3

6

5

Pipe 5

ø12.7

ø15.88

3

5

6

Pipe 6

ø19.05

ø25.4

1

1

Pipe 7

ø22.2

ø25.4

1

1

Pipe 8

ø28.58

ø25.4

1

1

Pipe 9

ø15.88

ø12.7

3

Pipe 10

ø9.52

ø6.35

5

Pipe 11

ø19.05

ø15.88

2

1

Pipe 12

ø22.2

ø19.05

1

1

Table-2 Accesorry plugs

 

Pipe Connection Specification

 

Quantity

 

 

H (Connecting Pipe Size)

CMY-Y104-G CMY-Y108-G CMY-Y1010-G

Plug 1

ø6.35

1

2

2

Plug 2

ø9.52

1

2

2

Plug 3

ø12.7

1

2

2

Plug 4

ø15.88

1

2

2

Plug 5

ø19.05

1

1

Note 1) Please prepare the following materials in addition to the items above.

(1) Tape for sealing of insulation material (2) Extension pipe for refrigerant circuit.

2Please observe the items below for the mounting work.

 

1.Observe the limit on refrigerant piping length in Table-3.

2.Observe the limit on the connection of indoor units in Table-4.

3.Connect the header to piping or plug/pipe by brazing. Non-oxidized brazing should be applied.

4.The header is equipped with stopper. Push in the stopper until the pipe to be connected stops.

5.No limitation is applied to the mounting posture.

6.Be careful that foreign materials like dust will not enter into the piping at the connection work.

7.Apply insulation material to all refrigerant pipings.

8.The piping after the header branching can not be branched again.

Be sure to connect it to the indoor unit.

Limitation on refrigerant piping length

 

 

 

Table-3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Item

Pipe section

Allowable value

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Total piping length

A + B + C + D + a +

300 m or less

 

Outdoor unit

 

 

 

 

 

 

b + c + d + e + f + g

 

 

 

 

Length

Farthest piping length (L)

A + C + D + g

150 m or less

 

 

 

 

 

 

 

 

or A + B + d

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Farthest piping length

 

C + D + g

40 m or less

 

 

 

 

 

 

 

 

 

 

 

after 1st branching (R)

 

or B + d

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Height difference between

 

50 m or less

 

 

 

 

 

 

 

 

Height

indoor and outdoor units (H)

 

 

 

 

 

 

 

 

 

 

 

 

above)

below)

 

 

 

 

 

 

difference

Height difference

 

15 m or less

 

 

 

 

 

 

 

 

 

between indoor units (h)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

isunitinstalled

isunitinstalled

1st branch

 

 

 

 

 

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Branch header

 

 

 

outdoor(Whenlessorm50

outdoor(Whenlessorm40

(Branch joint)

 

 

 

 

 

 

 

 

 

 

 

 

 

heightunitsoutdoorlessor15m=hdifference

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

Indoor unit

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Farthest piping length L = 100m or less

 

 

 

 

 

 

Farthest piping length after 1st branching R= 30m or less

 

 

 

Branch joint

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

isH

’His

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor

 

 

Indoor unit

 

Indoor unit

 

 

 

 

 

Indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 1 Note : Branch piping can not be applied after header branching.

Limitation on indoor unit connection

Table-4

Model

Model

Model

Model

Model

Model

Model

Model

Model

Model

Model

Model

Model

Model

 

Condition

200

250

300

350

400

450

500

550

600

650

700

750

800

Connectable

1~13

1~16

1~16

1~20

1~22

1~24

1~24

1~24

1~32

1~32

1~34

1~34

1~34

indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

Connectable

Model

Model

Model

Model

Model

Model

Model

Model

Model

Model

Model

Model

Model

indoor unit

20~250

20~250

20~250

20~250

20~250

20~250

20~250

20~250

20~250

20~250

20~250

20~250

20~250

capacity

 

 

 

 

 

 

 

 

 

 

 

 

 

Total indoor

unit capacity 100~260 125~325 150~390 175~455 200~520 225~585 250~650 275~715 300~780 325~845 350~910 375~910 400~1040

Example 1

Example 2

Outdoor unit

Outdoor unit

Total indoor unit capacity

Model 200 25 × 3 + 32 × 2 + 50 + 63 = 252 Total capacity of indoor units

Model 250 25 × 2 + 32 + 40 + 50 + 63 + 80 = 315

Indoor unit

Indoor unit

Fig. 2

3Selection of refrigerant piping size and use of header

1. Prepare the pipe to be connected in the field.

 

 

 

 

 

Table-8 Between First branching and outdoor unit (Fig.1-A)

 

 

 

 

 

2. Determine the piping sizes of each part from Table-5, 6 and 7.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor unit

Connecting

Model 200

Model 250, 300

Model 350

Model 400

Model 450, 500,

Model

 

3. The header can be connected to all piping sizes selected in the item

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pipe types

 

 

Pipe Size (X)

550, 600, 650

700, 750, 800

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2. To match a specified piping size.

 

 

 

 

 

 

CMY-Y104-G

 

Liquid pipe

ø12.7

Connect with pipe 1

Not connectable

Not connectable

Not connectable

Not connectable

Not connectable

 

(1) use the joint as it is.

 

 

 

 

 

 

 

 

Gas pipe

ø19.05

No need pipe

Not connectable

Not connectable

Not connectable

Not connectable

Not connectable

 

 

Between First branching and outdoor unit

 

CMY-Y108-G

 

Liquid pipe

ø12.7

Connect with pipe 1

Connect with pipe 1

No need pipe

No need pipe

Not connectable

Not connectable

 

(2) use it by connecting the auxiliary pipe.

 

 

 

 

 

 

 

 

 

 

 

 

Gas pipe

ø 25.4

Connect with pipe 6

Connect with pipe 7

Connect with pipe 8

Connect with pipe 8

Not connectable

Not connectable

 

Please conduct actual work by referring Fig 3 and Table-5 ~ 12.

 

 

 

 

 

 

CMY-Y1010-G

 

Liquid pipe

ø15.88 Connect with pipe 1, 5

Connect with pipe 1, 5

Connect with pipe 5

Connect with pipe 5

No need pipe

Not connectable

 

Outdoor unit

 

 

 

 

 

 

Gas pipe

ø25.4

Connect with pipe 6

Connect with pipe 7

Connect with pipe 8

Connect with pipe 8

Connect with pipe 8

Not connectable

 

4. Cover the branch pipe end of the header, which are not in use, with the

 

 

 

 

 

 

 

 

 

 

Note: Pipes on 450-type unit and up cannot be branched using a header (4~10-branch header); use an optional 2-branch

 

 

 

plugs 1 ~ 5 provided.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

joint.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Header

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table-5 Piping size between outdoor unit and 1st branching (Fig.1-A)

Outdoor unit model

Liquid pipe

 

 

Gas pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model 200

ø9.52

 

 

 

 

ø19.05

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model 250

ø9.52 *1

 

 

 

ø22.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model 300

ø9.52 *2

 

 

 

ø22.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model 350

ø12.7

 

 

 

 

ø28.58

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model 400

ø12.7

 

 

 

 

ø28.58

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

 

 

 

Model 450

ø15.88

 

 

 

 

ø28.58

 

 

 

 

Joint

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

6

 

 

 

 

 

 

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model 500

ø15.88

 

 

 

 

ø28.58

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

3

 

 

 

 

 

 

5

 

 

 

 

 

 

7

 

 

 

9

 

 

 

 

 

 

Model 550

ø15.88

 

 

 

 

ø28.58

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model 600

ø15.88

 

 

 

 

ø28.58

 

 

 

 

2-branch joints are

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model 650

ø15.88

 

 

 

 

ø28.58

 

 

 

 

sold separately.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model 700

ø19.05

 

 

 

 

ø34.93

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table-11 8-branch header (CMY-Y108-G) (Fig.1-a~d)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Model 750

ø19.05

 

 

 

 

ø34.93

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor unit

Connecting

Model 20, 25, 32,

Model 71, 80, 100,

 

Model

Model

Model 800

ø19.05

 

 

 

 

ø34.93

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Section

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pipe Size

40, 50

 

125, 140

 

200

 

250

Model 800 over

ø19.05

 

 

 

 

ø41.28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

Liquid pipe

ø9.52

Connect with pipe 4

No need pipe

 

No need pipe

No need pipe

*1 ø12.7 for over 90m

 

 

 

 

 

 

 

 

 

 

Between branchings

 

 

 

 

 

 

 

 

 

 

Fig. 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas pipe

ø19.05

Connect with pipe 3

Connect with pipe 2

 

No need pipe

Connect with pipe 12

*2 ø12.7 for over 40m

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table-9 Between branching (Fig.1-B)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

Liquid pipe

ø9.52

Connect with pipe 4

No need pipe

 

No need pipe

Not connectable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas pipe

ø15.88

Connect with pipe 5

No need pipe

Connect with pipe 11

Not connectable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Down stream

Connecting

 

Model

 

Model

 

Model

 

Model

Model

Model

 

Model

 

 

3

 

Liquid pipe

ø9.52

Connect with pipe 4

No need pipe

 

No need pipe

Not connectable

Table-6 Piping size between branching (Fig.1-B·C·D)

 

 

Pipe types

capacity

Pipe Size (X)

140

141~200

201~300

301~400

401~650

651~800

 

801 or more

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas pipe

ø15.88

Connect with pipe 5

No need pipe

Connect with pipe 11

Not connectable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid pipe

 

Connect with

Connect with

 

Not

 

Not

Not

 

Not

 

 

Not

 

 

 

 

 

Liquid pipe

ø9.52

Connect with pipe 4

No need pipe

 

Not connectable

Not connectable

Total capacity

Liquid pipe

 

Gas pipe

 

 

 

 

 

 

ø12.7

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

Gas pipe

 

pipe 1

 

pipe 1

 

connectable

connectable

connectable

connectable

 

connectable

 

 

 

Gas pipe

ø15.88

Connect with pipe 5

No need pipe

 

Not connectable

Not connectable

of indoor units

 

 

 

 

 

CMY-Y104-G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid pipe

 

Connect with

 

 

 

 

Not

 

Not

Not

 

Not

 

 

Not

 

 

 

 

 

Liquid pipe

ø9.52

Connect with pipe 4

No need pipe

 

Not connectable

Not connectable

~140

ø9.52

 

ø15.88

 

 

 

 

 

 

 

ø19.05

No need pipe

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

Gas pipe

 

pipe 2

 

connectable

connectable

connectable

connectable

 

connectable

 

 

 

Gas pipe

ø15.88

Connect with pipe 5

No need pipe

 

Not connectable

Not connectable

141~200

ø9.52

 

ø19.05

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid pipe

 

Connect with

Connect with

Connect with

 

 

Not

 

Not

 

 

Not

 

 

 

 

 

Liquid pipe

ø6.35

No need pipe

Not connectable

 

Not connectable

Not connectable

201~300

ø9.52

 

ø22.2

 

 

 

 

 

 

 

ø12.7

No need pipe

 

 

 

 

 

6

 

 

 

 

 

 

 

 

 

 

Gas pipe

 

pipe 1

 

pipe 1

 

pipe 1

connectable

connectable

 

connectable

 

 

 

Gas pipe

ø12.7

No need pipe

Not connectable

 

Not connectable

Not connectable

301~400

ø12.7

 

ø28.58

 

 

 

 

 

CMY-Y108-G

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid pipe

 

Connect with

Connect with

Connect with

 

 

Not

 

Not

 

 

Not

 

 

 

 

 

Liquid pipe

ø9.52

Connect with pipe 4

No need pipe

 

Not connectable

Not connectable

401~650

ø15.88

 

ø28.58

 

 

 

 

 

 

 

ø 25.4

No need pipe

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

Gas pipe

 

pipe 2, 6

 

pipe 6

 

pipe 7

connectable

connectable

 

connectable

 

 

 

Gas pipe

ø15.88

Connect with pipe 5

No need pipe

 

Not connectable

Not connectable

651~800

ø19.05

 

ø34.93

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid pipe

 

 

Not

Connect with

Connect with

Connect with

 

 

 

 

Not

 

 

Not

 

 

 

 

 

Liquid pipe

ø6.35

No need pipe

Not connectable

 

Not connectable

Not connectable

801~

ø19.05

 

ø41.28

 

 

 

 

 

 

 

ø15.88

 

No need pipe

 

 

 

 

 

8

 

 

 

 

 

 

 

 

CMY-Y1010-G

Gas pipe

connectable

pipe 1, 5

 

pipe 1, 5

 

pipe 5

connectable

 

connectable

 

 

 

Gas pipe

ø12.7

No need pipe

Not connectable

 

Not connectable

Not connectable

Note: If Indoor unit capacity is 651 or more, it can’t connect to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Liquid pipe

ø25.4

 

Not

Connect with

Connect with

Connect with

Connect with

 

Not

 

 

Not

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig.1-B directly. Then use the 2-branch joints. (Fig.1-C·D)

 

 

 

 

 

Gas pipe

connectable

 

pipe 6

 

pipe 7

 

pipe 8

pipe 8

connectable

 

connectable

 

Table-12 10-branch header (CMY-Y1010-G) (Fig.1-a~d)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table-7 Piping size branching (Fig.1-a~g)

Indoor unit model

Liquid pipe

Gas pipe

 

 

 

20, 25, 32, 40, 50

ø6.35

ø12.7

63, 71, 80, 100, 125, 140

ø9.52

ø15.88

200

ø9.52

ø19.05

250

ø9.52

ø22.2

Note: If indoor unit model is 200 and 250, it can’t use the CMYY104, Y108 and Y1010-G.

Then use the 2-branch joints.

Table-10 4-branch header (CMY-Y104-G) (Fig.1-a~d)

 

Indoor unit

Connecting

Model 20, 25, Model 71, 80,

Model

Model

Section

Pipe Size

32, 40, 50 100, 125, 400

200

250

 

Liquid pipe

ø9.52

Connect with

No need pipe

Not

Not

 

pipe 4

connectable

connectable

1

 

Gas pipe

ø15.88

Connect with

No need pipe

Not

Not

 

 

pipe 5

connectable

connectable

 

 

 

Liquid pipe

ø6.35

No need pipe

Not

Not

Not

 

connectable

connectable

connectable

2

 

Gas pipe

ø12.7

No need pipe

Not

Not

Not

 

 

connectable

connectable

connectable

 

 

 

Liquid pipe

ø9.52

Connect with

No need pipe

Not

Not

 

pipe 4

connectable

connectable

3

 

Gas pipe

ø15.88

Connect with

No need pipe

Not

Not

 

 

pipe 5

connectable

connectable

 

 

 

Liquid pipe

ø9.52

Connect with

No need pipe

Not

Not

 

pipe 4

connectable

connectable

4

 

Gas pipe

ø15.88

Connect with

No need pipe

Not

Not

 

 

pipe 5

connectable

connectable

 

 

 

Indoor unit

Connecting

Model 20, 25, 32,

Model 71, 80, 100,

Model

Model

Section

 

Pipe Size

40, 50

125, 140

200

250

1

Liquid pipe

ø9.52

Connect with pipe 4

No need pipe

No need pipe

No need pipe

Gas pipe

ø19.05

Connect with pipe 3

Connect with pipe 2

No need pipe

Connect with pipe 12

 

2

Liquid pipe

ø6.35

No need pipe

Connect with pipe 10

Connect with pipe 10

Not connectable

Gas pipe

ø15.88

Connect with pipe 5

No need pipe

Connect with pipe 11

Not connectable

 

3

Liquid pipe

ø9.52

Connect with pipe 4

No need pipe

No need pipe

Not connectable

Gas pipe

ø19.05

Connect with pipe 3

Connect with pipe 2

No need pipe

Not connectable

 

4

Liquid pipe

ø6.35

No need pipe

Connect with pipe 10

Not connectable

Not connectable

Gas pipe

ø15.88

Connect with pipe 5

No need pipe

Not connectable

Not connectable

 

5

Liquid pipe

ø9.52

Connect with pipe 4

No need pipe

Not connectable

Not connectable

Gas pipe

ø15.88

Connect with pipe 5

No need pipe

Not connectable

Not connectable

 

6

Liquid pipe

ø6.35

No need pipe

Connect with pipe 10

Not connectable

Not connectable

Gas pipe

ø12.7

No need pipe

Connect with pipe 9

Not connectable

Not connectable

 

7

Liquid pipe

ø9.52

Connect with pipe 4

No need pipe

Not connectable

Not connectable

Gas pipe

ø15.88

Connect with pipe 5

No need pipe

Not connectable

Not connectable

 

8

Liquid pipe

ø6.35

No need pipe

Connect with pipe 10

Not connectable

Not connectable

Gas pipe

ø12.7

No need pipe

Connect with pipe 9

Not connectable

Not connectable

 

9

Liquid pipe

ø9.52

Connect with pipe 4

No need pipe

Not connectable

Not connectable

Gas pipe

ø15.88

Connect with pipe 5

No need pipe

Not connectable

Not connectable

 

10

Liquid pipe

ø6.35

No need pipe

Connect with pipe 10

Not connectable

Not connectable

Gas pipe

ø12.7

No need pipe

Connect with pipe 9

Not connectable

Not connectable

 

4Mounting of cover (insulation material)

(i) CMY-Y104-G

(ii)CMY-Y108-G

Sealing material

 

 

 

 

 

23 Headers

 

 

 

 

Field pipings

 

 

 

Tape (field supply)

 

23 Headers

 

 

4 Pipe cover 1

 

 

 

 

 

Field pipings

Plug (stopping)

 

 

 

4 Pipe cover 1

 

 

 

 

 

 

 

Upper side

 

4 Pipe cover 1

 

 

 

 

 

6 Band

 

 

4 Pipe cover

Sealing material

6 Band

5 Pipe cover 2

 

 

Peel off

 

 

 

4 Pipe cover 1

 

Contact here

Cross section A/A

 

Tape

 

 

 

Peel off

 

 

 

(field supply)

 

 

 

 

 

 

 

 

 

(1)Insert the 23 headers into the pipe cover 1 (2 pcs.) respectively, peel off the paper pasted on the inner surface of the 4 pipe cover, and catch the 23 headers with the 4 pipe cover 1.

(1)Wind sealing material onto A-section of 23 headers, [thin piping-small sealing material, thick piping-large sealing material], insert each header into 4 pipe cover 1, and put 23 headers between 4 pipe cover 1.

Note) For a part where sealing material is overlapped, wind sealing material onto the header so that the overlapped part locates at the upper side when the 10 branch header is installed.

(2)Fasten both ends of the indoor side branching of the 4 pipe cover 1 with the 6 band as shown in the figure above. Cut off the surplus of the band.

(3)Mount the 5 pipe cover 2 onto the positions stopped with the plugs 1 ~ 5 provided.

Fully seal the butting section of the pipe cover with a tape (field supply). (Insufficient sealing causes condensation dripping.)

WT04325X01