Emerson Liebert FPC User Manual

0 (0)
Emerson Liebert FPC User Manual

AC Power

For Business-Critical Continuity™

Liebert FPC

User Manual - 15 kVA - 300kVA, 3 Phase, 50 & 60 Hz

TABLE OF CONTENTS

1.0 INSTALLATION INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

1.1 Unpacking and Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

1.1.1 Unpacking and Preliminary Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1.1.2 Handling Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 1.1.3 Unit Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.1.4 Location Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 1.1.5 Floor Pedestal Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

1.2 Additional Distribution Mounting & Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

1.2.1 Liebert FDC Distribution Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 1.2.2 Distribution Cabinet Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

1.3 Power and Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

1.3.1 Input Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 1.3.2 Junction Box Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 1.3.3 System Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 1.3.4 Grounding Electrode Conductor for FPCs With Transformer . . . . . . . . . . . . . . . . . . . . . . . . . 16 1.3.5 Output Power Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 1.3.6 Control Wiring Connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

2.0 EQUIPMENT INSPECTION AND STARTUP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23

2.1 Internal Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 2.2 Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

3.0 INSPECTION AND STARTUP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

3.1 Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 3.2 Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 3.3 Monitoring System Check-Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 3.4 Equipment Connection Check-Out of Units With Distribution Cables. . . . . . . . . . . . . . . . . 28

4.0 OPERATING INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29

4.1 Startup Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

4.1.1 Emergency Shutdown—If Emergency Power Off switch is supplied . . . . . . . . . . . . . . . . . . . 29 4.1.2 Normal System Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 4.1.3 Normal System Turn ON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 4.1.4 Manual Restart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

4.2 Basic Monitor Panel (Units Without Monitoring) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 4.3 Power Monitor Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

5.0 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .34

5.1 Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 5.2 Inspection and Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

5.2.1 Inspection Schedule . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

i

FIGURES

Figure 1 Typical cabinet and floor planning dimension data, 23" (584mm) cabinet, 15-125 kVA . . . . . . . . 3 Figure 2 Typical cabinet and floor planning dimension data, 47" (1194mm) cabinet 50-300kVA . . . . . . . . 4 Figure 3 Recommended minimum service and ventilation clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Figure 4 Floor pedestal details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Figure 5 Electrical connection location for 23" (584mm) cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Figure 6 Electrical connection location for 47" (1194mm) cabinet—Front view . . . . . . . . . . . . . . . . . . . . . 10 Figure 7 Electrical connection location for 47" (1194mm) cabinet—Rear view . . . . . . . . . . . . . . . . . . . . . . 10 Figure 8 Electrical connection location for 47" cabinet with SqD I-Line panelboard—Front view. . . . . . . 11 Figure 9 Electrical connection location for 47" cabinet with SqD I-Line panelboard—Rear view . . . . . . . 11 Figure 10 Low voltage control junction box connections, typical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Figure 11 Main input junction box connections, typical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Figure 12 Typical grounding arrangements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Figure 13 Typical Liebert FPC equipment arrangement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Figure 14 Simplified shutdown circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Figure 15 Typical control wiring for units without monitoring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Figure 16 Typical control wiring for units with monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Figure 17 Basic monitoring panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 Figure 18 Power monitor panel. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

TABLES

Table 1 23-inch cabinet weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Table 2 47-inch cabinet weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Table 3 Liebert FPC heat output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Table 4 Suggested minimum input wire size data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Table 5 Main input circuit breaker interrupting rating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Table 6 Main input junction box electrical connections (4 wire) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Table 7 Main input junction box without transformer electrical connections (5 wire) . . . . . . . . . . . . . . . 14 Table 8 Low-voltage (control) junction box dimensions, typical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Table 9 Main input (power) junction box dimensions, typical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Table 10 Minimum grounding electrode conductor size (AWG) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Table 11 Panelboard main circuit breaker torque specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Table 12 Branch circuit breaker torque specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Table 13 Terminal block compression lug torque specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Table 14 Torque specifications, general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Table 15 ASCII interface default parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Table 16 RS-232 ASCII port customer commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Table 17 Monitored parameters data definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

ii

IMPORTANT SAFETY INSTRUCTIONS

NOTE

Read the entire manual before installing or operating the system.

! WARNING

The shipping bands may be under tension. Use appropriate eye, face, and hand protection to safeguard against injury from band backlash.

! WARNING

Verify that all incoming line voltage (power) and low-voltage (control) circuits are de-energized and locked out before installing cables or making connections, whether in the junction box or in the unit.

Equipment inspection and start-up should be performed only by trained personnel. Lethal voltages are present during start-up procedures. Electrical safety precautions must be followed throughout inspection and startup.

Only qualified service personnel should perform maintenance on the Liebert FPC system. All voltage sources to the unit must be disconnected before inspecting or cleaning within the cabinet.

Lethal voltages exist within the equipment during operation. Observe all warnings and cautions in this manual. Failure to comply may result in serious injury or death. Obtain qualified service for this equipment as instructed.

The monitoring system contains a lithium battery for memory backup. There is a danger of explosion if battery is incorrectly replaced. Replace only with same or equivalent type. Dispose of used batteries according to the manufacturer’s instructions.

NOTE

The unit should not be loosened from the shipping pallet until all handling by fork lift or pallet jack is completed.

All power and control wiring should be installed by licensed electricians and must comply with the NEC and applicable codes.

1

Installation Instructions

1.0INSTALLATION INSTRUCTIONS

1.1Unpacking and Installation

NOTE

Read the entire manual before installing and operating the system. Upon receipt of a Liebert FPC™, the installer should perform the following steps to ensure a quality installation.

1.1.1Unpacking and Preliminary Inspection

A quality installation begins on the receiving dock.

1.Inspect the shipping crate(s) for damage or signs of mishandling before unpacking the unit(s). Check the Shock-Watch™ indicator.

2.Remove the packing and inspect the equipment for any obvious shipping damages.

3.If the FPC was shipped in an export crate, open the shipping crate carefully.

Use care to avoid puncturing the container with sharp objects that would damage the contents.

4.Remove the packing and vapor barriers and inspect the equipment for any obvious shipping damages.

NOTE

The units should not be loosened from the shipping pallet until all handling by fork lift or pallet jack is completed. Complete internal inspection should be accomplished only after equipment positioning and prior to electrical hookup.

5.If any damage is observed, immediately file a damage claim with the shipping agency and forward a copy to:

Liebert Corporation 1050 Dearborn Drive P.O. Box 29186

Columbus, Ohio 43229 USA

1.1.2Handling Considerations

The Liebert FPC(and cables, if furnished) is bolted to a wooden pallet to allow handling by forklift equipment.

The Liebert FPC and cable reels are furnished with casters to allow the unit to be rolled into place after it has been unbolted from the pallet. The FPC should be kept on the shipping pallet until it has been moved by forklift as close as practical to its installation location.

Refer to the cabinet drawings furnished with the FPC for the unit’s size and weight. Typical cabinet dimensions and weights are shown in Figures 1 and 2.

The route to the FPC’s installation area should be planned to ensure that all passages, including doorways, elevators, ramps and hallways, are large enough to accommodate the unit and that the floors are strong enough to support the weight. Determine whether any corners or offsets would cause problems in maneuvering the unit.

Liebert recommends removing the exterior side panels, if supplied, before the unit is moved. This will prevent scratches, dents and other damage to the panels.

2

Installation Instructions

Figure 1 Typical cabinet and floor planning dimension data, 23" (584mm) cabinet, 15-125 kVA

Overall Dim. 39-1/2" (1003mm) Including hinge and bezel projection

Overhead clearance

of 18" (457mm) recommended

for cooling airflow

Minimum side

clearance of 42" (1067mm) recommended for service access if unit is equipped with distribution monitoring option

Overall Dimension

 

 

25.2" (640mm)

 

 

including side

 

 

panels

1.2"

 

 

6"

 

(30mm)

34" (864mm)

(152mm)

11-1/2" (292mm)

1.2"

 

 

6" (152mm)

(30mm)

Front

 

 

 

78-1/2" (1995mm)

Shaded area indicates

 

cable access and

 

cooling airflow

Footprint and Floor

Cutout Dimensions

Shaded areas indicate recommended clearance of 42" (1067mm) at front and rear for service access

23-

.4"

36

1/2"

(597mm)

(925mm)

Unit Base Outline

For units with bottom cable access, clearance of 6" (152mm) below unit is recommended for cooling airflow

and cable entry/exit

Cabinet Dimensional Data

36.4" (925mm)

Unit Base Outline

Front

Floor Pedestals available from

6" (152mm) to 18" (457mm)

Optional Floor Pedestals

23-1/2" (597mm)

3.2" (81mm)

8.3"

(211mm)

Dia. location 3/4" (19mm) typical

.56" (14mm) diameter; 4 holes typical

6" (152mm) 6" (152mm)

Table 1

23-inch cabinet weight

 

 

 

 

Weight, lb (kg)

 

Unit

 

 

 

 

 

 

 

 

 

Without

kVa

 

60Hz

50Hz

 

Transformer

15

 

1010 (458)

1060 (480)

 

750 (340)

 

 

 

 

 

 

30

 

1090 (494)

1140 (517)

 

750 (340)

 

 

 

 

 

 

50

 

1160 (526)

1235 (560)

 

750 (340)

 

 

 

 

 

 

75

 

1350 (612)

1450 (658)

 

800 (363)

 

 

 

 

 

 

100

 

1540 (699)

1665 (755)

 

800 (363)

 

 

 

 

 

 

125

 

1650 (748)

1775 (805)

 

800 (363)

 

 

 

 

 

 

3

Installation Instructions

Figure 2 Typical cabinet and floor planning dimension data, 47" (1194mm) cabinet 50-300kVA

Overall Dim. 39-1/2" (1003mm)

Including hinge and bezel

projection

Overhead clearance

of 18" (457mm) recommended

for cooling airflow

Minimum side clearance

of 42" (1067mm) recommended for service access if unit is equipped with distribution monitoring option

Overall Dimension 48.6" (1235mm) including side panels

 

 

1.3"

 

 

(33mm)

 

33.8" (859mm)

6" (152mm)

 

35" (889mm)

 

1.3"

 

6" (152mm)

(33mm)

 

 

Front

Shaded area indicates

 

 

78-1/2"

Footprint and Floor cable access and

(1995mm)

Cutout Dimensions cooling airflow

Shaded areas indicate

47"

.4"

36

recommended clearance

(1194mm)

(925mm)

of 42" (1067mm) at front and

rear for service access

Unit Base Outline

Cabinet Dimensional Data

 

For units with bottom cable access, clearance of 6" (152mm) below unit is recommended for cooling airflow

and cable entry/exit

36.4" (925mm)

Unit Base Outline

Front

47" (1194mm) 43.8"

(1112mm) 1.5" (38mm)

2.3" (58mm)

Floor Pedestals

Dia. location

available from

3/4" (19mm)

typical

6" (152mm) to

 

18" (457mm)

 

Optional Floor Pedestals

(152mm) 6"

9/16" (14mm)

diameter; 4 holes

typical

6" (152mm)

Table 2

47-inch cabinet weight

 

 

 

 

 

Unit

 

 

Weight, lb (kg)

 

 

 

 

kVA

 

60 Hz

50 Hz

Without Transformer

 

 

 

 

 

50

 

1891 (858)

1966 (892)

1335 (606)

75

 

1995 (905)

2095 (950)

1335 (606)

100

 

2191 (994)

2316 (1051)

1335 (606)

125

 

2298 (1042)

2423 (1099)

1360 (617)

150

 

2490 (1129)

2640 (1198)

1360 (617)

200

 

2610 (1184)

2810 (1275)

1360 (617)

225

 

2800 (1270)

3000 (1361)

1390 (631)

300

 

2845(1290)

3045 (1381)

1390 (631)

4

Installation Instructions

1.1.3Unit Preparation

The Liebert FPC may be easily removed from the shipping pallet and installed by customer personnel. A typical procedure is as follows:

1.Set the palletized assembly in a level area where there is enough room to roll the Liebert FPC and entire cable assembly off the pallet onto the floor.

2.Cut the shipping bands.

! WARNING

The shipping bands may be under tension and may snap violently when cut. Use eye, face and hand protection to guard against injury when the bands are cut.

3.Remove the factory-provided ramp from its shipping position.

One ramp is provided for every five units. Ramps are packed either in front of or on top of a set of cable reel(s).

4.Place the ramp adjacent to the pallet to provide a smooth path from pallet to floor.

5.Remove side panels from the Liebert FPC, if supplied. An Allen wrench for the side panels is furnished in the installation packet.

6.Remove the bolts and two mounting brackets holding the unit to the shipping pallet. Mounting brackets are located on either side of the unit.

7.If cables are on wheeled cable reel(s), remove the bolts holding the reel(s) to the pallet and remove the nailed-on shipping blocks.

8.Roll the unit off the pallet onto the floor, carefully guiding the cable reel(s) after it.

9.Roll the FPC and the cable reel(s) to the installation area. For units to be placed on a raised floor, use care when positioning unit over the floor cutout to prevent the casters from falling through the cutout.

! CAUTION

Before maneuvering the unit into its final position, read and follow all advisories in 1.1.4 - Location Considerations.

1.1.4Location Considerations

The Liebert FPC should be placed near the load(s) it will supply, preferably within the data center.

Equipment location should employ the shortest output distribution cable runs consistent with logical equipment arrangement and allowance for expansion.

The FPC is intended for indoor installation in an area with ambient temperatures of 32°F to 104°F (0°C to 40°C) with a relative humidity of 0% to 95% (non-condensing).

Bottom clearance is required for units with bottom entry/exit of cables. This clearance may be provided by a raised floor at least 6" (150mm) high. Figures 1 and 2 show the typical raised-floor cutout dimensions for cables and cooling airflow.

When units are not installed on a raised floor, or if the raised floor will not support the unit, optional floor pedestals may be used. (CSA regulations require FPC arrangements employing a raised floor. Non-raised floor applications are not CSA approved.) Units with top cable exit provisions do not require bottom clearance.

Recommended minimum service clearances are shown in Figure 3. The National Electrical Code (NEC) requires the indicated front and rear clearances for service access. Clearance above the unit is required for cooling airflow (exhaust). Units with optional distribution monitoring also require service access clearance on the left side.

As do all electrical devices, the Liebert FPC produces heat under normal operation. (See Table 3.) This heat must be accounted for when calculating the environmental conditions of the room.

5

Installation Instructions

Figure 3 Recommended minimum service and ventilation clearances

Minimum clearance of 18" (457mm) above unit is recommended for cooling airflow

See Notes 2 and 3.

Front and rear access is required. See Notes 1 and 2.

NOTE

Minimum clearance of 6" (152mm) below unit is recommended

for cable entry and exit

1. Service access is required at the front and rear.

2.Service access clearance dimensions: 36" (914mm) for units up to 150V to ground. 42" (1067mm) for units over 150V to ground.

3.Service access is required on the left side, if unit is equipped with Liebert Distribution Monitoring Option.

Table 3

Liebert FPC heat output

 

 

 

 

 

 

Full Load

 

 

 

Heat Output

 

Unit kVA

 

BTU/Hr (kW)

 

15

 

2,500 (0.73)

 

 

 

 

 

30

 

4,600 (1.35)

 

 

 

 

 

50

 

6,200 (1.82)

 

 

 

 

 

75

 

8,150 (2.39)

 

 

 

 

 

100

 

9,900 (2.90)

 

 

 

 

 

125

 

11,500 (3.37)

 

 

 

 

 

150

 

12,500 (3.66)

 

 

 

 

 

200

 

15,500 (4.54)

 

 

 

 

 

225

 

15,800 (4.63)

 

 

 

 

 

300

 

18,450 (5.40)

 

 

 

 

 

6

Installation Instructions

1.1.5Floor Pedestal Installation

Floor pedestals are optional equipment that provide clearance for bottom cable entry or exit for FPC units not installed on raised flooring. The pedestals are adjustable over a limited range (approximately 3-1/2" [89mm]) to allow leveling the FPC and minor adjustments in the unit’s installed height.

! CAUTION

Floor pedestals may be reverse-assembled for shipping. Before installation, the pedestals should be reassembled as shown in Figure 4. When the pedestal is properly assembled, the washer on top of the welded nut provides a bearing surface for the unit’s weight.

1.Insert the pedestal threaded shaft into the pedestal holes in the cabinet base as shown in

Figures 1 and 2.

2.Adjust the pedestal height by turning the welded nut/shaft assembly into or out of the pedestal base as required.

3.Lock the height by tightening the jam nut against the pedestal base.

The pedestal may be anchored to the floor by means of the four holes in the base. Locations of floor pedestals are shown in Figures 1 and 2.

Figure 4 Floor pedestal details

3"

Threaded

(76mm)

Shaft

 

Washer

 

Welded Nut

 

Jam Nut

Pedestal

Base

.56" (14mm) diameter mounting holes

2-1/4"

(57mm)

6" (152mm)

square

2-1/4" (57mm)

2-1/4" 2-1/4" (57mm) (57mm)

7

Installation Instructions

1.2Additional Distribution Mounting & Wiring

For Liebert FPCs with more than four panelboards, the additional panelboards are furnished in Liebert FDC enclosures, which are shipped separately from the Liebert FPC.

1.2.1Liebert FDC Distribution Mounting

The Liebert FDC distribution cabinet has the same base dimensions as a 23" (584mm) cabinet FPC (23-1/2" wide x 38" deep [597 x 965mm]) and may be mounted on either the left or right side of the FPC.

1.Provide a floor cutout for exit of output cables, as shown in Figure 1.

2.Remove the side panel, internal panel and the lower panel bracket from the FPC.

3.Remove the FDC side panel and internal panel, if supplied, and align the FDC with the FPC and bolt the units’ frames together (hardware provided by others).

If floor pedestals are used for the FPC, two additional floor pedestals are required for the outside corners of the FDC. See Figure 1.

4.Install the lower panel bracket on the opposite side of the FDC cabinet.

5.Make electrical connections. For details, see “Electrical Field Connections” drawings supplied with the unit.

6.Install the FPC side panel on the FDC cabinet.

1.2.2Distribution Cabinet Electrical Connections

Five field-supplied conductors (3-phase conductors, neutral and ground) are needed to connect the FDC cabinet to the FPC cabinet in the field.

For Liebert FPCs with transformers, the distribution cabinet phase conductors are connected directly to the transformer terminals:

Phase A to X1 Phase B to X2 Phase C to X3

The FDC’s neutral and ground conductors are connected to the FPC’s neutral busbar and main ground busbar (see unit wiring diagram for location).

For Liebert FPCs without transformers, the distribution cabinet phase and neutral conductors are connected to the corresponding output power distribution terminal blocks inside the FPC. The distribution cabinet ground conductor is connected to the main ground busbar.

For all Liebert FPCs with current monitoring, route each distribution cabinet conductor through the appropriate current transformer (CT) in the FPC.

NOTE

Distribution cabinet conductors must pass through the current transformers in the same direction as the FPC panelboard conductors. Use the existing FPC panelboard wiring for reference.

1.3Power and Control Wiring

Power and control wiring should be installed by licensed electricians. All power and control wiring must comply with the NEC and applicable local codes.

1.3.1Input Power Connections

If the FPC is furnished with a main input junction box, input power connections are made as detailed in 1.3.2 - Junction Box Installation.

If a junction box is not furnished, the input power feeder is connected to the main input circuit breaker located inside the FPC. (See Figures 5 through 8.)

! WARNING

Verify that all incoming line voltage (power) and low-voltage (control) circuits are de-energized and locked out before installing cables or making connections, whether in the junction box or in the FPC.

8

Loading...
+ 28 hidden pages