Fire Alarm Systems | FAD-325-DH Analog Duct Smoke Detector Replacement Head

FAD-325-DH Analog Duct Smoke Detector

Replacement Head

www.boschsecurity.com

The FAD 325 DH Analog Duct Smoke Detector Replacement is a replacement detector for the FAD 325 Duct Smoke Detector Housing. It detects smoke particles which typically result from wood, paper, and fabric combustion. Use it in heating, ventilation, and air conditioning (HVAC) systems.

It uses a LED and photodiode to measure particulate levels in its detection chamber. These measurements are transmitted via the DCP protocol to the fire panel.

Functions

Fire Panel Connections

The detector is controlled by a microprocessor and communicates with the fire panel (both power and data) over a two wire polling circuit.

Sensitivity levels

The system allows for adjusting sensitivity levels by the detector over a range of 0.88 %/ft to 2.75 %/ft (2.9%/m to 9%/m) obscuration. The unique detection chamber design prevents external light from affecting the photodiode.

uSmoke density range of 0.88 %/ft to 2.75 %/ft (2.9%/m to 9%/m)

uAdjustable threshold smoke level (determined by panel)

uProvides automatic compensation values in case of detector contamination

uReplacement detector for FAD 325 Analog Duct Smoke Detector Housing

uEasy detector removal for cleaning and servicing

Status Display

The detector has two LEDs that flash every time the device is polled and can be switched on steady when the module goes into active condition.

Certifications and approvals

Region

Certification

 

 

 

USA

UL

UROX: Smoke-automatic Fire Detectors

 

 

(ANSI/UL 268)

 

CSFM

see our website

 

 

 

Installation/configuration notes

Compatible Products

The following products are compatible with the FAD 325 DH Photoelectric Smoke Detector Replacement:

Category