Bosch FMC-120-DKM User Manual

4 (1)

Fire Alarm Systems | FMC 120 DKM Manual Call Points

FMC 120 DKM Manual Call Points

www.boschsecurity.com

The FMC-120-DKM Manual Call Points handle manual alarm triggering and are used with conventional technology.

Functions

5

 

1

1

2

 

4

 

3

 

3

2

In the event of an alarm, the glass pane (2) is broken first, then the manual call point (3) is pressed hard. This activates the micro switch for alarm triggering and the indicator LED (4) blinks.

A locking mechanism holds the pressed manual call point.

The manual call point can be reset with the reset lever

(5). The indicator LED (4) goes out.

This does not reset the alarm on the fire panel.

uAdjustment of the manual call point after alarm triggering

uIndicator LED for alarm or for inspection evaluation

uSecond contact with connections for panel control

uVariants for indoor and outdoor use

Variants

The design of the manual call points for indoor

(form G) and outdoor use (form H) are identical. Three color variants, red, blue, and yellow are available. Detectors for outdoor use (form H) have a cover equipped with a seal.

Certifications and Approvals

Type Number

 

Complies with

FMC 120 DKM G R

EN54-11:2001/A1:2005

FMC 120 DKM H R

EN54-11:2001/A1:2005

FMC 120 DKM G Y

EN12094-3:2003

FMC 120 EST G B

EN12094-3:2003

 

 

Region

Certification

 

 

 

Germany

VdS

G 298061 FMC-120-DKM-G-R/-H-

 

 

R_G298061

 

VdS

G 206079 FMC-120-DKM-G-

 

 

Y_G206079

 

VdS

G 206080 FMC-120-EST-G-B/-H-

 

 

HE_G206080

 

 

 

Bosch FMC-120-DKM User Manual

2 | FMC 120 DKM Manual Call Points

Region

Certification

 

 

 

 

PTB

01 ATEX 2163 X OTC/OC 310/410,

 

 

OT/O/T 300/400, DKM/SKM 120, DM/

 

 

SM 210, MPA_01 ATEX 2163 X

 

PTB

01 ATEX 2163 X FMC-120-DKM

Europe

CE

FMC-120-EST-G-B / -DKM-G-Y

 

CE

FMC-120-DKM-G-R/-H-R

 

CE

FMC-120-DKM-G-B/ -H-B

 

CPD

0786-CPD-20294 FMC-120-DKM-G/H-

 

 

R

 

CPD

0786-CPD-20231 FMC-120-DKM-G-Y

 

CPD

0786-CPD-20232 FMC-120-EST-G-B/-

 

 

H-HE

 

 

 

Installation/Configuration Notes

Manual call points have to be mounted visibly along escape and rescue routes (e.g. exits, passageways, stairwells) and be easily accessible.

An installation height of 1400 mm ±200 mm, measured from the middle of the manual call point to the floor, must be maintained.

Manual call points must be illuminated sufficiently with daylight or another light source (including emergency lighting, if present).

Max. one test detector may be used for primary lines together with automatic detectors. The test detector is connected at the end of the primary line.

Further standards, guidelines and planning recommendations regarding the installation location etc., should also be taken into consideration (see Fire Detection manual).

Regulations of local fire departments must be observed.

Installation

Cables can be inserted surface-mounted or flushmounted.

Ø 3,4

Installation in fire hose cabinets is possible in three ways:

1

 

 

135°

 

2,5

2

 

 

140°

2

10

3

 

 

147

139

 

Pos.

Description

1

Installation depth version 1: 36 mm

2

Installation depth version 2: 14 mm

3

Installation depth version 3: approx. 30 mm

Technical Specifications

Electrical

Operating voltage

24 V DC (16.2 V DC . . . 30 V DC)

 

 

Current consumption

Specified by the respective se-

 

curity system

 

 

Mechanics

 

 

 

Dimensions (W x H x D)

135 x 135 x 37 mm /

 

5.31 x 5.31 x 1.4 in.

 

 

Housing material

Plastic (ASA)

 

 

Colors

Red, RAL 3001

 

Blue, RAL 5005

 

Yellow, RAL 1003

 

 

Weight

Approx. 224 g

 

 