Fire Alarm Systems | FMC 120 DKM Manual Call Points
FMC 120 DKM Manual Call Points
www.boschsecurity.com
The FMC-120-DKM Manual Call Points handle manual alarm triggering and are used with conventional technology.
Functions
5 |
|
1 |
1 |
2 |
|
4 |
|
3 |
|
3 |
2 |
In the event of an alarm, the glass pane (2) is broken first, then the manual call point (3) is pressed hard. This activates the micro switch for alarm triggering and the indicator LED (4) blinks.
A locking mechanism holds the pressed manual call point.
The manual call point can be reset with the reset lever
(5). The indicator LED (4) goes out.
This does not reset the alarm on the fire panel.
uAdjustment of the manual call point after alarm triggering
uIndicator LED for alarm or for inspection evaluation
uSecond contact with connections for panel control
uVariants for indoor and outdoor use
Variants
The design of the manual call points for indoor
(form G) and outdoor use (form H) are identical. Three color variants, red, blue, and yellow are available. Detectors for outdoor use (form H) have a cover equipped with a seal.
Certifications and Approvals
Type Number |
|
Complies with |
FMC 120 DKM G R |
EN54-11:2001/A1:2005 |
|
FMC 120 DKM H R |
EN54-11:2001/A1:2005 |
|
FMC 120 DKM G Y |
EN12094-3:2003 |
|
FMC 120 EST G B |
EN12094-3:2003 |
|
|
|
|
Region |
Certification |
|
|
|
|
Germany |
VdS |
G 298061 FMC-120-DKM-G-R/-H- |
|
|
R_G298061 |
|
VdS |
G 206079 FMC-120-DKM-G- |
|
|
Y_G206079 |
|
VdS |
G 206080 FMC-120-EST-G-B/-H- |
|
|
HE_G206080 |
|
|
|
2 | FMC 120 DKM Manual Call Points
Region |
Certification |
|
|
|
|
|
PTB |
01 ATEX 2163 X OTC/OC 310/410, |
|
|
OT/O/T 300/400, DKM/SKM 120, DM/ |
|
|
SM 210, MPA_01 ATEX 2163 X |
|
PTB |
01 ATEX 2163 X FMC-120-DKM |
Europe |
CE |
FMC-120-EST-G-B / -DKM-G-Y |
|
CE |
FMC-120-DKM-G-R/-H-R |
|
CE |
FMC-120-DKM-G-B/ -H-B |
|
CPD |
0786-CPD-20294 FMC-120-DKM-G/H- |
|
|
R |
|
CPD |
0786-CPD-20231 FMC-120-DKM-G-Y |
|
CPD |
0786-CPD-20232 FMC-120-EST-G-B/- |
|
|
H-HE |
|
|
|
Installation/Configuration Notes
•Manual call points have to be mounted visibly along escape and rescue routes (e.g. exits, passageways, stairwells) and be easily accessible.
•An installation height of 1400 mm ±200 mm, measured from the middle of the manual call point to the floor, must be maintained.
•Manual call points must be illuminated sufficiently with daylight or another light source (including emergency lighting, if present).
•Max. one test detector may be used for primary lines together with automatic detectors. The test detector is connected at the end of the primary line.
•Further standards, guidelines and planning recommendations regarding the installation location etc., should also be taken into consideration (see Fire Detection manual).
•Regulations of local fire departments must be observed.
Installation
•Cables can be inserted surface-mounted or flushmounted.
Ø 3,4
•Installation in fire hose cabinets is possible in three ways:
1 |
|
|
135° |
|
2,5 |
2 |
|
|
140° |
2 |
10 |
3 |
|
|
147 |
139 |
|
Pos. |
Description |
1 |
Installation depth version 1: 36 mm |
2 |
Installation depth version 2: 14 mm |
3 |
Installation depth version 3: approx. 30 mm |
Technical Specifications
Electrical
Operating voltage |
24 V DC (16.2 V DC . . . 30 V DC) |
|
|
Current consumption |
Specified by the respective se- |
|
curity system |
|
|
Mechanics |
|
|
|
Dimensions (W x H x D) |
135 x 135 x 37 mm / |
|
5.31 x 5.31 x 1.4 in. |
|
|
Housing material |
Plastic (ASA) |
|
|
Colors |
Red, RAL 3001 |
|
Blue, RAL 5005 |
|
Yellow, RAL 1003 |
|
|
Weight |
Approx. 224 g |
|
|