Bosch F.01U.294.092, F.01U.294.091, F.01U.294.090 Datasheet

0 (0)
Bosch F.01U.294.092, F.01U.294.091, F.01U.294.090 Datasheet

Communications Systems | PRS xBxxx Basic Amplifiers

PRS xBxxx Basic Amplifiers

www.boschsecurity.com

u High efficiency class-D amplifier channel(s)

u Switched mode power supply

u Local audio inputs

u Mains and battery operation

u Complete supervision

The basic amplifiers are cost effective alternatives to the regular Praesideo power amplifiers, for situations where no built-in digital signal processing functions, such as equalizers, delay and AVC are required. They do not have a Praesideo network connection. Instead, these amplifiers are connected to the Praesideo network via the PRS-16MCI Multi Channel Interface, which provides the basic amplifier with audio signals and has full control. There are four versions, the PRS 1B500 (1 x 500 W), PRS 2B250 (2 x 250 W), PRS 4B125 (4 x 125 W) and the PRS 8B060

(8 x 60 W).

The basic amplifiers are completely supervised and fault events are reported via the multi channel interface to the Praesideo network controller.

The basic amplifiers provide connections for separate group A and group B loudspeakers for each zone, and support class A loudspeaker loop wiring. The units should be mounted in a 19"-rack with the included mounting brackets.

Notice

Region specific versions of these amplifiers are indicated by a suffix to the typenumber (-EU, - CN, ...). The amplifiers are completely identical, but may differ in certifications, power cord and country of origin.

Functions

Amplification

The PRS 1B500 is a single channel, 500 W unit, the PRS 2B250 is a two-channel amplifier with 250 W per channel, the PRS 4B125 is a four channel amplifier with 125 W per channel and the PRS 8B060 is an eight channel amplifier with 60 W per channel. The power supply is switched mode with low inrush current and the units can run on 48 V, battery stand-by power.

Connection

The amplifiers have built-in output transformers for driving 70 and 100 V loudspeakers. They have separate overload-protected group A and group B loudspeaker connections, which support class-A loop wiring. The separate A and B groups of each channel can be

2 | PRS xBxxx Basic Amplifiers

configured for redundancy. The units connect to the PRS-16MCI Multi Channel Interface for audio, control and supervision, but stand-alone operation is possible.

Audio

The amplifiers have analog audio line inputs for low priority local audio. Networked audio from the multi channel interface overrides the local audio.

Security

The units operate both on mains power and on a 48 V battery power supply for emergency back up, with automatic switchover. They supervise both of the power supplies, as well as themselves. They can optionally monitor loudspeakers and their lines, when used together with the PRS-16MCI Multi Channel Interface. Complete channel separation allows one channel of the amplifier to function as a spare amplifier for the other amplifier channel.

The amplifier has overload and short circuit protection. An overheat protection circuit switches off the power stage and activates the fault LED on the front panel if the internal temperature reaches a critical limit.

Controls and indicators

Front

Two two-color LEDs for mains and battery status

Four amplifier status/level LEDs (per channel)

Back

Mains on/off switch

Mains voltage selector

Rotary volume control for local audio inputs (per channel)

Inside

• 70 V / 100 V selection (per channel)

Interconnection

Back

Mains socket

Battery backup input

Two loudspeaker output screw terminals (per channel)

Spare amplifier input screw terminal (per channel)

Two RJ45 connectors (per channel)

Local audio input screw terminal (per channel)

Certifications and approvals

Safety

acc. to IEC 60065 / EN 60065

 

 

Immunity

acc. to EN 55103 2 / EN 50130 4 /

 

EN 50121 4

 

 

Emissions

acc. to EN 55103-1 / FCC-47 part 15B

 

 

Emergency

acc. to EN 60849 / EN 54 16 /

 

ISO 7240 16

 

 

Maritime

acc. to IEC 60945

 

 

Region Certification

Europe CE

CE DOP

CPD

GL

Parts included

Quantity Component

1PRS-1B500 Basic Amplifier 1x500 W or

PRS-2B250 Basic Amplifier 2x250 W or

PRS 4B125 Basic Amplifier 4x125 W or

PRS 8B060 Basic Amplifier 8x60 W

2/4/8/1 CAT 5 cables (for PRS 1B500 / PRS 2B250 /

6PRS 4B125 / PRS 8B060)

1Power cord

1Set of mounting brackets (large) for 19” rack

1Set connectors

Technical specifications

Electrical

Mains power supply

Voltage

115/230 VAC ±10%, 50/60 Hz

 

 

Power consumption

Pmax -3 dB* / idle** / standby

 

 

 

PRS-1B500

450

/ 52 / 17 W

 

 

 

PRS-2B250

378

/ 46 / 18 W

 

 

 

PRS 4B125

395

/ 62 / 16 W

 

 

 

PRS 8B060

400

/ 80 / 16 W

 

 

 

* Alarm tone level

 

** With pilot tone 15 V

 

 

 

 

 

 

 

 

Battery power supply

 

 

 

 

 

Voltage

48 VDC -10% to +20%

 

 

Power consumption

Pmax -3 dB* / idle** / standby

 

 

 

 

PRS-1B500

365

/ 34

/ 6 W

 

 

 

 

PRS-2B250

370

/ 38

/ 6 W

 

 

 

 

PRS 4B125

375

/ 48

/ 9 W

 

 

 

 

PRS 8B060

385

/ 62

/ 10 W

 

 

 

* Alarm tone level

 

** With pilot tone 15 V

 

 

 

 

 

 

 

 

Performance

 

 

 

 

 

Frequency response

60 Hz to 19 kHz (-3 dB)

 

 

 

 

Loading...