Bosch FLM325IM User Manual

0 (0)
Bosch FLM325IM User Manual

Fire Alarm Systems | FLM 325 IM Contact Module

FLM 325 IM Contact Module

The FLM 325 IM Contact Module provides a variety of fire alarm functions, such as monitoring manual pull stations, waterflow devices, or other dry contact fire alarm activation applications. The module allows for alarm, trouble, and supervisory conditions. The module is mounted inside of a single gang back box and is normally out of view.

System Overview

The FLM 325 IM Contact Module allows compatible fire alarm control panels (FACP) to supervise Form A or B dry contact devices in a polling circuit. The module has an eight bit microprocessor and communicates with the control panel (both power and data) over a two-wire polling circuit. The initiating device circuit (NFPA Style B) connected to the module can have up to 20 normally-open (NO) dry contact devices. Each module can monitor one normally-closed (NC) device (NC devices must be nonalarm applications).

Digital data communications and power provided over a two-wire circuit

Advanced digital communications protocol compatible

Class B circuit for dry contact devices

Module address programming (1-254) with the D5070 Analog Device Programmer

Certifications and Approvals

Region

Certification

 

USA

UL

UOXX: Control Unit Accessories, System

 

 

(ANSI/UL 864)

Installation/Configuration Notes

The following products are compatible with the FLM 325 IM Contact Module:

Category

Product ID

Product Description

Control Panels:

FPA 1000

Analog addressable fire panels

 

Series

 

Pull Stations

FMM 325A

Analog addressable manual pull

 

 

station (single action)

 

FMM 325A D

Analog addressable manual pull

 

 

station (double action)

Programmers:

D5070

Analog device programmer