Bosch 5601P, 5602, 5603, 5604, 5621 Specsheet

...
0 (0)
Bosch 5601P, 5602, 5603, 5604, 5621 Specsheet

Fire Alarm Systems | 5600 Mechanical Heat Detectors

5600 Mechanical Heat Detectors

www.boschsecurity.com

The System Sensor 5600 Series Mechanical Heat Detectors provide low-cost property protection against fire and non-life-safety installations where smoke detectors are inappropriate.

Notice

For life-safety installations, smoke detectors must be used in lieu of or in addition to heat detectors.

Functions

Detector Labeling

The 5601P has a plain, unlabeled housing and is intended for residential applications. All other models have labeled housings to ensure that the proper detector is being used. Alphanumeric characters identify the activation method (FX for fixed temperature or FX/ROR for combination fixed temperature and rate-of-rise units) and the temperature rating in degrees Fahrenheit and degrees Celsius.

Post-activation Fixed-temperature Indicator

When the detector is activated, the collector drops from the unit. This allows easy identification of all units in alarm.

uPost-activation indicator to easily identify units in alarm

uMultiple configurations satisfy a broad range of installations

uBroad range of back box mounting options

uReversible mounting bracket for surface-mount or flush mount installations

Notice

The fixed-temperature sensors cannot be reset so they are not testable. The rate-of-rise sensors automatically reset and can be tested if care is taken to avoid exceeding the fixed-temperature setting of the detector.

Certifications and approvals

System Sensor holds these Listings and Approvals:

 

NYC/MEA

199-03-E

 

 

Region

Certification

 

 

 

USA

UL

UQGS: Heat - Automatic Fire Detectors

 

 

(UL521)

 

FM

5600 Family

 

CSFM

see our website

 

 

 

Installation/configuration notes

Compatibility Information

These mechanical heat detectors are compatible with all UL Listed Fire Alarm Control Panels (FACPs).