Replacement head mechanisms can be installed without
disturbing existing equalizing connections or disassembly
of components, making repair simple and easy.
The Series 150E is a microprocessor based control
which utilizes the conductive properties of the boiler
water to operate relays. All units include redundant low
water cut-off and pump off features to guard against
shorted or fouled probe conditions.
INSTRUCTION MANUAL
MM-415C
Series 150E
WARNING
CAUTION
WARNING
• Before using this product read and understand instructions.
•Save these instructions for future reference.
• All work must be performed by qualified personnel trained in the proper application, instal-
lation, and maintenance of plumbing, steam, and electrical equipment and/or systems in
accordance with all applicable codes and ordinances.
•To prevent serious burns, the boiler must be cooled to 80˚F (27˚C) and the pressure must be
0 psi (0 bar) before servicing.
•To prevent electrical shock, turn off the electrical power before making electrical connections.
• This low water cut-off must be installed in series with all other limit and operating controls
installed on the boiler. After installation, check for proper operation of all of the limit and
operating controls, before leaving the site.
•We recommend that secondary (redundant) low water cut-off controls be installed on all
steam boilers with heat input greater than 400,000 BTU/hour or operating above 15 psi of
steam pressure. At least two controls should be connected in series with the burner control
circuit to provide safety redundancy protection should the boiler experience a low-water
condition. Moreover, at each annual outage, the low water cut-offs should be dismantled,
inspected, cleaned, and checked for proper calibration and performance.
•To prevent serious personal injury from steam blow down, connect a drain pipe to the control
opening to avoid exposure to steam discharge.
•To prevent a fire, do not use this low water cut-off to switch currents over 16A, 1 Hp at
120 VAC or 8A, 1 Hp at 240 VAC, unless a starter or relay is used in conjunction with it.
Failure to follow this warning could cause property damage, personal injury or death.
Burner Delay (DOB): 0 to 60 seconds (Field Adjustable)
Ambient Temp: 120˚F Max.
NOTE: The circuit board is protected with a sensor which will
shut down the unit if the temperature at the board exceeds
176˚F (80˚C). The board will reset when the temperature at
the board drops below 167˚F (75˚C).
FEATURES
Burner Relay Time Delay
There is a field-adjustable time delay (DOB) to prevent nuisance burner shut-down. The number of
seconds water needs to be off the bottom probe
before the burner relay is reactivated can be set
between 0 and 60 seconds.
Redundant Low Water Cut-Off
When the boiler water drops below the middle
probe, a 3 minute timing circuit will be activated. If
water does not return to the middle probe within
three minutes, the burner relay will reactivate. The
Red LED will flash once every second if this
condition occurs.
•Automatic Reset units will automatically reset
when the water level is restored to the middle
probe.
• The reset button on Manual Reset units will
have to be pressed after water is restored to
the middle probe.
NOTE: The timing circuit will automatically reset
if the water level is restored to the middle probe
within 3 minutes.
Redundant Pump Off
The pump relay will be activated after water drops
below the middle probe. If the water level is not
restored to the top probe within 3 minutes the pump
relay will be deactivated. After the pump relay is
deactivated, normal operation is resumed. Water
must again drop off the middle probe to activate the
pump relay. There is no LED signal for this
occurance.
CSD-1 Code Compliance
On Manual Reset units, if the control is in a low
water condition (burner relay deactivated) prior to
an interruption of power, the control will remain in a
low water condition when power is restored. The
reset button will need to be pressed when the water
level again covers the middle probe.
Adjustable Pump Differentials
2
BURNER
CUT-OFF LEVEL
AT CAST LINE
(22mm)
BURNER OFF
BURNER ON
7
/8"
PUMP
OFF
BURNER
OFF
BURNER
CUT-OFF LEVEL
AT CAST LINE
2
1
/16"
(52 mm)
NORMAL BOILER
WATER LINE
1
3
/16"
(30 mm)
PUMP OFF
PUMP ON
NORMAL BOILER
WATER LINE
SWITCH SETTINGS:
BURNER
CUT-OFF LEVEL
AT CAST LINE
(22mm)
BURNER OFF
BURNER ON
7
/8"
PUMP
OFF
BURNER
OFF
BURNER
CUT-OFF LEVEL
AT CAST LINE
1
5
/8"
(41mm)
NORMAL BOILER
WATER LINE
3
/4" (19 mm)
PUMP OFF
PUMP ON
NORMAL BOILER
WATER LINE
Values are ±
3
/16” (6mm).
When the water level in the boiler drops below the
middle probe, the circuit is broken which will activate the pump relay. When the water level rises
above the top probe, the circuit is made and the
pump relay is deactivated.
The distance between the top and middle probes is
adjustable. By turning the flange one bolt hole
clockwise, the distance can be increased by 7/16”.
Approximate
Distance Above
Cast LineDifferential
SettingIn. (mm)In. (mm)
Pump Off15/8 (41)
Pump On
Burner On
7
/8(22)
7
/8(22)
Burner Off0(0)
3
/4(19)
7
/8(22)
When the water level in the boiler drops below the
bottom probe, the circuit is broken which will deactivate the burner relay. When the water level is
restored to the middle probe, the burner relay will
be activated for auto reset controls only.
Flange in “B” PositionFlange in “A” Position
Approximate
Distance Above
Cast LineDifferential
SettingIn. (mm)In. (mm)
Pump Off2
Pump On
Burner On
Burner Off0(0)
1
/16 (52)
7
/8(22)
7
/8(22)
3
/16(30)
1
7
/8(22)
Burner Off has adjustable 0-60 second time delay.
Burner Off has adjustable 0-60 second time delay.
3
A
B
C
D
F
E
INSTALLATION –
!
!
A
B
C
D
TOOLS NEEDED:
One (1) pipe wrench, one (1) flatblade screwdriver, one (1) scraper, and one (1) 9/16" socket or wrench.
STEP 1 - Preparation
WARNING
•To prevent serious burns, the boiler must be cooled to 80˚F (27˚C) and the pressure must be 0 psi (0 bar)
before servicing.
•To prevent electrical shock, turn off the electrical power before disconnecting or making electrical connections.
Failure to follow this warning could cause property damage, personal injury or death.
a. Drain water in the boiler to a level
which is below the float chamber (A).
Allow the boiler to cool to 80˚F
(27˚C) and release the boiler pressure to 0 psi (0 bar).
b. Using a flatblade screwdriver, remove the
junction box cover (B). Disconnect, mark,
and remove the supply wires and conduit
connections.
CAUTION
There may be more than one source of
power to the control.
c. Remove the existing head mechanism (C)
from the body (D).
d. Using a scraper, remove the old gasket (E).
Clean all debris from the float chamber. The
gasket sealing surface (F) must be smooth
and clean.
4
!
J
K
D
STEP 2 - Installing the Replacement Head Mechanism
a. Carefully remove the new replacement head
mechanism from the carton. Handle it carefully
to prevent damage to the probes.
CAUTION
If probes are loose and/or damaged, the control
may leak or not work properly.
b. Align the bolt holes of the new head gasket (J)
on the sealing surface of the control body.
c. Install the new replacement head (K) on the
body (D) by guiding the probes into the control
body and aligning the bolt holes.
NOTE: For increased pump differential locate
tab “B” down (see page 3 Flange Positioning).
d. Using a wrench, insert the eight (8) bolts and
tighten them to approximately 14-20 ft•lb
(19-27 N•m) in an alternating star pattern.
5
Loading...
+ 11 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.