Xylem MM 219J User Manual

!
Snap Switch Models:
150S-HD 150S-M-HD 150S-MD-HD 150S-M-MD-HD 158S-HD 158S-M-HD 158S-MD-HD 158S-M-MD-HD 159S-HD
Replacement head mechanisms can be installed without disturbing existing equalizing connections or disassembly of components, making repair simple and easy.
INSTRUCTION MANUAL
MM-219J
Replacement Head Mechanism
WARNING
N
UTIO
A
C
G
NIN
R
A
W
• Before using this product read and understand instructions.
• Save these instructions for future reference.
• All work must be performed by qualified personnel trained in the proper application, instal­lation, and maintenance of plumbing, steam, and electrical equipment and/or systems in accordance with all applicable codes and ordinances.
• To prevent serious burns, the boiler must be cooled to 80˚F (27˚C) and the pressure must be 0 psi (0 bar) before servicing.
• To prevent electrical shock, turn off the electrical power before making electrical connections.
• This low water cut-off must be installed in series with all other limit and operating controls installed on the boiler. After installation, check for proper operation of all of the limit and operating controls, before leaving the site.
• We recommend that secondary (redundant) Low Water Cut-Off controls be installed on all steam boilers with heat input greater than 400,000 BTU/hour or operating above 15 psi of steam pressure. At least two controls should be connected in series with the burner control circuit to provide safety redundancy protection should the boiler experience a low water condition. Moreover, at each annual outage, the low water cut-offs should be dismantled, inspected, cleaned, and checked for proper calibration and performance.
To prevent serious personal injury from steam blow down, connect a drain pipe to the control opening to avoid exposure to steam discharge.
• To prevent a fire, do not use this low water cut-off to switch currents over 7.4A, 1/3 Hp at 120 VAC or 3.7A, 1/3 Hp at 240 VAC, unless a starter or relay is used in conjunction with it.
Failure to follow this warning could cause property damage, personal injury or death.
2
Enclosure rating: NEMA 1 General Purpose
Pump Circuit Rating (Amperes)
Voltage Full Load Locked Rotor Pilot Duty
120 VAC 7.4 44.4
345 VA at
240 VAC 3.7 22.2
120 or 240 VAC
Approximate
Distance Above
Cast Line Differential
Setting In. (mm) In. (mm)
Pump Off
15
/16 (24)
5
/16 (8)
Pump On
5
/8 (16)
Burner On
5
/8 (16)
3
/8 (16)
Burner Off
1
/4 (6.4)
Pump Off 13/8 (41)
3
/4 (19)
Pump On
5
/8 (16)
Burner On
7
/8 (22)
7
/8 (22)
Burner Off 0 (0)
BURNER OFF
BURNER ON
7
/8"
DIFFERENTIAL
(22mm)
PUMP
OFF
BURNER
OFF
NORMAL BOILER
WATER LINE
1
3
/8"
DIFFERENTIAL
(35mm)
PUMP OFF PUMP ON
3
/4"
DIFFERENTIAL
(19mm)
PUMP OFF PUMP ON
3
/4"
DIFFERENTIAL
(19mm)
PUMP
OFF
BURNER
OFF
NORMAL BOILER
WATER LINE
1
13
/16"
DIFFERENTIAL
(46mm)
OPERATION
Maximum Pressure: 150 psi (10.5 kg/cm2)
Electrical Ratings
Settings and Differential Pressures
Values are ± 8" (3.2mm).
Series 150S and 157S
150 psi (10.5 kg/cm
2
) Levels
150 psi (10.5 kg/cm
2
) Levels
0 psi
(0 kg/
cm2)
150 psi
(10.5 kg/
cm
2
)
Approximate
Distance Above
Cast Line Differential
Setting In. (mm) In. (mm)
Pump Off
15
/16 (24)
3
/8(16)
Pump On
9
/16 (14)
Burner Off 0 (0) N/A
Pump Off 17/16 (37)
3
/4(19)
Pump On 11/16 (17)
Burner Off - 3/8 (-16)
N/A
Model 150S-MD and 157S-MD
0 psi
(0 kg/
cm
2
)
150 psi
(10.5 kg/
cm
2
)
Pressure
Pressure
Alarm Circuit Rating
Voltage Amps
120 VAC 1
240 VAC 1/2
Motor Horsepower
Voltage Hp
120 VAC
1/3
240 VAC 1/3
3
Approximate
Distance Above
Cast Line Differential
Setting In. (mm) In. (mm)
Motorized
15
/16 (24)
Valve Closed
5
/16 (8)
Motorized
5
/8 (16)
Valve Open
Burner On
5
/8 (16)
3
/8(16)
Burner Off
1
/4 (6.4)
Motorized 13/8 (41)
3
/4 (19)
Valve Closed Motorized
5
/8 (16)
Valve Open
Burner On
7
/8 (22)
7
/8(22)
Burner Off 0 (0)
BURNER OFF
BURNER ON
7
/8"
DIFFERENTIAL
(22mm)
MOTORIZED
VALV E
CLOSED
BURNER
OFF
NORMAL BOILER
WATER LINE
1
3
/8"
DIFFERENTIAL
(35mm)
MOTORIZED
VALV E
CLOSED
MOTORIZED
VALV E
OPEN
3
/4"
DIFFERENTIAL
(19mm)
Values are ± 8" (3.2mm).
NOTE: Due to the slower operation of some motorized valves, complete valve opening or closing will occur at slightly different levels than indicated above.
Model 158S
150 psi (10.5 kg/cm
2
) Levels
0 psi
(0 kg/
cm
2
)
150 psi
(10.5 kg/
cm
2
)
Pressure
Settings and Differential Pressures (continued)
150 psi
(10.5 kg/
cm
2
)
MOTORIZED
VALVE
OPEN
CLOSED
3
/4"
DIFFERENTIAL
(19mm)
MOTORIZED
VALV E
CLOSED
BURNER
OFF
NORMAL BOILER
WATER LINE
1
13
/16"
DIFFERENTIAL
(46mm)
Approximate
Distance Above
Cast Line Differential
Setting In. (mm) In. (mm)
Pump Off
15
/16 (24)
3
/8(16)
Pump On
9
/16 (14)
Burner Off 0 (0) N/A
Pump Off 17/16 (37)
3
/4(19)
Pump On 11/16 (17)
Burner Off - 3/8 (-16)
N/A
Model 158S-MD
0 psi
(0 kg/
cm
2
)
Pressure
150 psi (10.5 kg/cm2) Levels
NOTE: Due to the slower operation of some motorized valves, complete valve opening or closing will occur at slightly different levels than indicated above.
4
PUMP #1
OFF
PUMP #1
ON
NORMAL BOILER
WATER LINE
(19mm)
3
/4"
DIFFERENTIAL
PUMP #2 ON AT CAST LINE
7
/8"
DIFFERENTIAL
(22mm)
PUMP #2
ON
PUMP #2
OFF
PUMP #1
OFF
PUMP #2
ON
PUMP #2 ON AT CAST LINE
NORMAL BOILER
WATER LINE
1
3
/8"
DIFFERENTIAL
(35mm)
Values are ± 8" (3.2mm).
150 psi (10.5 kg/cm2) Levels
Approximate
Distance Above
Cast Line Differential
Setting In. (mm) In. (mm)
Pump #1 Off15/16 (24)
5
/16(8)
Pump #1 On5/8 (16)
Pump #2 Off5/8 (16)
3
/8(16)
Pump #2 On1/4 (6.4)
Pump #1 Off 13/8 (41)
3
/4(19)
Pump #1 On5/8 (16)
Pump #2 Off7/8 (22)
7
/8(22)
Pump #2 On
0 (0)
Model 159S
0 psi
(0 kg/
cm
2
)
150 psi
(10.5 kg/
cm
2
)
Pressure
Settings and Differential Pressures (continued)
• To prevent serious burns, the boiler must be cooled to 80˚F (27˚C) and the pressure must be 0 psi (0 bar) before servicing.
• To prevent electrical shock, turn off the electrical power before disconnecting or making electrical connections.
Failure to follow this warning could cause property damage, personal injury or death.
!
WARNING
5
A
B
C
D
c. Remove the existing head mechanism (C)
from the body (D).
a. Drain water in the boiler to a level which is
below the float chamber (A). Allow the boiler to cool to 80˚F (27˚C) and release the boiler pressure to 0 psi (0 bar).
b. Using a flathead screwdriver, remove the junction
box cover (B). Disconnect, mark, and remove the supply wires and conduit connections.
F
E
d. Using a scraper, remove the old gasket (E).
Clean all debris from the float chamber. The gasket sealing surface (F) must be smooth and clean.
STEP 1 - Preparation
INSTALLATION
TOOLS NEEDED:
One (1) pipe wrench, one (1) flathead screwdriver, one (1) scraper, and one (1) 9/16" socket or wrench.
There may be more than one source of power to the boiler.
!
CAUTION
d. Using a wrench, insert the eight (8) bolts and
tighten them to approximately 14-20 ft•lb (19-27 N•m) in an alternating star pattern.
G
J
b. Align the bolt holes of the new head gasket (J)
on the sealing surface of the control body.
a. Carefully remove the new replacement head
mechanism from the carton. Handle it carefully to prevent damage to the float rod (G).
K
D
c. Install the new replacement head (K) on the
body (D) by guiding the float into the control body and aligning the bolt holes.
STEP 2 - Installing the Replacement Head Mechanism
6
7
IMPORTANT: There must be a minimum space of 1/2" (13mm) between connector fittings and electrical live metal parts.
STEP 3 - Electrical Wiring
a. Reconnect conduit and wires which were disconnected prior to head removal.
b. Re-attach the junction box cover (B).
B
Note:
Cover must be installed correctly as shown
• To prevent a fire, do not use this product to switch currents over 7.4A, 1/3 Hp at 120 VAC or 3.7A, 1/3 Hp at 240 VAC, unless a starter or relay is used in conjunction with it.
• To prevent electrical shock, turn off the electrical power before making electrical connections.
• This low water cut-off must be installed in series with all other limit and operating controls installed on the boiler. After installation, check for proper operation of all of the limit and operating controls, before leaving the site.
• Modification of the switch assembly before or after installation could cause damage to the boiler and/or boiler system.
Failure to follow this warning could cause electrical shock, an explosion and/or a fire, which could result in property damage, personal injury or death.
!
WARNING
8
Switch Operation
For all Models except 158S and 159S
For Model 158S
Boiler feed pump off,
burner on, alarm off.
Boiler feed pump on,
burner on, alarm off.
Boiler feed pump on,
burner off, alarm on.
Motorized valve closed,
burner on, alarm off.
Motorized valve open,
burner on, alarm off.
Motorized valve open,
burner off, alarm on.
4 5 6
1 2
3
4 5
1 2
3
4 5
1 2
3
6 6
For Model 159S
Pump #1 off, pump #2 off.
Pump #1 on, pump #2 off.
Pump #1 on,
pump #2 on.
1 2 5 6 1 2 5 6
1 2 5 6
1 2 4 5 6 1 2 4 5 6
1 2 4 5 6
9
WIRING DIAGRAMS
For Motorized Valves, refer to the valve manufacturer's wiring instructions.
Pump Control Only
1. Install a starter or relay in pump control circuit, as shown, to prevent damage to snap switch and help insure proper switch/control operation. Failure to do so may shorten the life of the switch when actual amperage exceeds switch rating.
2. Connect wires from holding coil of pump starter or relay to terminals 1 and 2 as shown.
1. Main Line Switch - For burner circuits within the switch’s electrical rating.
2. Pilot Switch - To holding coil of a starter when the burner circuit exceeds the switch’s electrical rating.
12 456
ALARM
NEUTRAL
HOT
ALARM
NEUTRAL
HOT
12 4 56
12 456
SEE PUMP
CONTROL
CIRCUIT
TO NEUTRAL
TO BURNER CONTROL CIRCUIT
HOT
ALARM
12 456
LOAD
LINE (3 PHASE)
SEE PUMP
CONTROL
CIRCUIT
ALARM
OR
OR
Combination Pump Control, Low Water Cut-Off and Alarm
Alarm Circuit Only
1. Low Water Alarm 2. High Water Alarm
NOTE To help insure most effective operation, balance boiler feed pump(s) to deliver required water feed rate to match boiler steaming requirements.
NOTE For Model 159S, use terminals 5 and 6 from starter or relay for pump #2.
Low Water Cut-Off Only
1. Main Line Switch - For burner circuits within the switch’s electrical rating.
LINE LOAD
12 456
12 456
LOAD
LINE
OR
2. Pilot Switch - To holding coil of a starter when the burner circuit exceeds the switch’s electrical rating.
LINE
12 456
LOAD
K
To prevent serious personal injury from steam pipe blow down, connect a drain pipe to the control opening to avoid exposure to steam discharge.
Failure to follow this caution could cause personal injury.
!
CAUTION
INSTALLATION COMPLETE
10
Snap Switch Models
STEP 4 - Testing
OFF
ON
a. Turn on the electric power to the boiler.The pump should go on
and the burner must remain off.
IMPORTANT: Follow the boiler manufacturer’s start-up and operating instructions along with all applica­ble codes and ordinances.
This control is factory calibrated for specific level settings as shown on pages 2-4 in the “Operation” section.
The following testing procedure is only meant to serve as a verification of proper operating sequence.
If the burner comes on, immediately turn the boiler off and make the necessary corrections.
Failure to follow this warning could cause an explosion or fire and result in property damage, personal injury or death.
!
WARNING
b.
The boiler should begin to fill with water. As the water level rises in the sight glass, the burner should turn on and then the pump should turn off at appropriate levels. For manual reset models, press the reset button (K) when the water reaches appro­priate level. If the burner does not turn on or pump turn off at appropriate levels, immediately turn off the boiler and make necessary corrections.
Location of Manual Reset Button
c.
Blow down the control when the water in the boiler is at its normal level and the burner is on. Follow Blow Down Procedure found in Maintenance Section on page 11 of these instructions.
11
MAINTENANCE
SCHEDULE:
Blow down control as follows when boiler is in operation.
• Daily if operating pressure is above 15 psi.
• Weekly if operating pressure is below 15 psi.
• Remove head assembly and inspect water side components annually. Replace head
assembly if any of the internal components are worn, corroded or damaged or if control no longer operates properly.
• Inspect the float chamber and equalizing piping annually. Remove all sediment and debris.
Replace head mechanism every 5 years.
More frequent replacement may be required when severe conditions exist.
Replacement parts are available from your local authorized McDonnell & Miller Distributor.
The use of parts or components other than those manufactured by McDonnell & Miller will void all warranties and may affect the units compliance with listings or regulating agencies.
BLOW DOWN PROCEDURE:
When blowing down a control at pressure, the blow down valves should be opened slowly. The piping needs to be warmed up and stagnant water in the drain piping needs to be pushed out. Suddenly opening a blow down valve causes steam to condense, which can create water hammer. Damage to components can occur when water hammer occurs due to improper blow down piping. For these reasons, McDonnell & Miller recommends a dual valve blow-down system for each control.
Blow down the control when the water in the boiler is at its normal level and the burner is on.
NOTE: Refer to page 2 for switch operating points.
• Open upper valve (#1)
• Slowly open the lower valve (#2)
• Water in the sight glass should lower.
• As the water in the sight glass lowers, the pump should turn on.
• As the water continues to lower in the sight glass, the burner should turn off.
• Slowly close the lower valve (#2).
• Close the upper valve (#1)
• The water level in the sight glass should rise, first
turning on the burner and then turning off the pump. NOTE: On manual reset models, the reset button
will need to be pressed after the water level has been restored before the burner will operate.
To prevent serious personal injury from steam pipe blow down, connect a drain pipe to the control opening to avoid exposure to steam discharge.
Failure to follow this caution could cause personal injury.
!
CAUTION
NOTE More frequent blow-down may be necessary due to dirty boiler water and/or local codes.
NOTE The control may need to be inspected and cleaned more frequently on systems where there is the potential of excessive scale or sludge build-up. This includes systems:
• With high raw water make-up
• With no condensate return
• With untreated boiler water
• Where significant changes have been made to the boiler-water chemical treatment process
• With oil in the boiler water
NOTE
If this sequence of operation does not occur as described, immediately close all the valves, turn off the boiler and correct the problem. Inspection/cleaning of the float mechanism may be required to determine why the control was not working properly. Retest the control after the problem has been identified and corrected.
Valve #1
Valve #2
Xylem
1) The tissue in plants that brings water upward from the roots;
2) a leading global water technology company.
We’re 12,500 people unified in a common purpose: creating innovative solutions to meet our world’s water needs. Developing new technologies that will improve the way water is used, conserved, and re-used in the future is central to our work. We move, treat, analyze, and return water to the environment, and we help people use water efficiently, in their homes, buildings, factories and farms. In more than 150 countries, we have strong, long-standing relationships with customers who know us for our powerful combination of leading product brands and applications expertise, backed by a legacy of innovation.
For more information on how Xylem can help you, go to www.xyleminc.com
Xylem Inc.
8200 N. Austin Avenue Morton Grove, Illinois 60053 Phone: (847) 966-3700 Fax: (847) 965-8379 www.xyleminc.com/brands/mcdonnellmiller
McDonnell & Miller is a trademark of Xylem Inc. or one of its subsidiaries. © 2012 Xylem Inc. MM-219J August 2012 Part No. 210343
Loading...