The thermostat’s display has four distinct fields. These fields are the Menu field, the Item
field, the Number field and the Status field. The four buttons on the face of the thermostat are
used to navigate through the menus and items to view and / or adjust the desired settings.
The thermostat operation is based on cycles per hour. The number of cycles per hour is
adjustable through the HEAT CYCLE settings in the Adjust menu. During each cycle that
heating is required, the thermostat turns on the Heat relay for a calculated amount of time.
This amount of time is the “on time”. The on time is calculated based on the requirements of
the zone. If the zone requires more heating, the ON time is increased. If the zone requires
less heat, the ON time is reduced.
In order to prevent short cycling of the heating relay(s), the thermostat ensures that the
relay(s) remains on or off for a minimum amount of time.
An Auto Cycle setting is available for the
heating cycle. This setting allows the
thermostat to determine the best number of
cycles per hour that balances both temperature
swings and equipment cycles.
Cycles Per Hour
ononon
offoff
⇐ Cycle Length ⇒
Time
off
EARLY START ( )
The early start function ensures that the
zone is up to the proper temperature at the
beginning of each period. The thermostat
learns the recovery rate over multiple setback
events in order to determine the proper lead
time for the zone. If both an air sensor and
70°F (21°C)
62°F (17°C)
70°F (21°C)
Early Start OFF
Early Start ON
a slab sensor are used, the lead time is the
greater of the air sensor’s or the slab sensor’s
requirements.
62°F (17°C)
UnOccupied
Occupied
NOTE: The Early Start feature occurs when the schedule changes from a low temperature
to a higher temperature.
AUXILIARY SENSORS
The thermostat has a single built-in sensor to measure air temperature at the thermostat. In
addition to the built-in sensor, the thermostat has terminals to connect up to two separate
sensors. These sensors can be either indoor sensors, slab sensors, a remote sensor, or
an outdoor sensor.
An indoor sensor is used to measure the air temperature in the zone that the thermostat is
controlling. The temperature being read by the indoor sensor is used in the calculations of
the on times for the relay in the thermostat. Either one or both of the auxiliary sensor inputs
can be configured for indoor sensors. This setting is made through the Adjust menu of the
thermostat. If more than one sensor, either the built-in sensor or an auxiliary sensor set as
an indoor sensor, is being used to measure the zone temperature, the temperature of the
active sensors is averaged and used to calculate the on time of the relay.
Slab Sensor
A slab sensor is used to measure the slab temperature in the zone that the thermostat
is controlling. The temperature being read by the slab sensor is used in the calculations
of the on time for the Heat relay and allows the thermostat to operate the slab between
the slab minimum and slab maximum settings. If more than one slab sensor is used, the
slab temperatures are averaged by the thermostat.
Remote Sensor
A single remote sensor can be connected to the thermostat. The temperature measured
by a remote sensor does not affect the on time of the relay and is only used for display
purposes.
Outdoor Sensor
A single outdoor sensor can be connected to the thermostat. The temperature measured
by an outdoor sensor does not affect the on time of the relay and is only used for display
purposes.
ACCESS LEVELS
The tekmar Programmable Thermostat has two
access levels. These access levels restrict the
number of items available in the menus of the
thermostat. The two access levels are User and
Installer. This selection is made using the DIP
switch located on the circuit board inside the
thermostat.
The Installer access level allows the installer to
adjust all of the settings in the thermostat including
those required to match the thermostat to the
mechanical system and the devices used.
The User access level allows the end user to
adjust the time, temperatures and schedules
When operating with only an air sensor, the on time for the Heat relay is calculated to
satisfy the requirements of the air sensor.
Slab Sensor Only Operation
When operating with only a slab sensor, the on time for the Heat relay is calculated to
satisfy the requirements of the slab sensor. The thermostat operates to maintain the slab
at the minimum slab temperature setting.
NOTE: Operating with only a slab sensor can lead to either overheating or underheating
of the space.
Air and Slab Sensor Operation
When operating with both air and slab sensors, the thermostat calculates an on time for
the Heat relay to satisfy the slab sensor’s requirements and an on time to satisfy the air
sensor’s requirements. The Heat relay operates for the longer of these two on times.
During light heating loads, overheating can occur due to the minimum slab temperature
requirements.
During heavy heating loads, the maximum slab temperature setting limits the on time of
the Heat relay. In this situation, underheating can occur.
Mode
Heat In the heat mode, the Heat relay is operated to satisfy the temperature requirement
of the zone.
Off In the Off mode, the Heat relay is not operated.
NOTE: If an air or slab sensor is active in the Off mode, a freeze protection is enabled
that allows the Heat relay to be operated to keep the zone above 35°F (2°C).
GETTING READY
Check the contents of this package. If any of the contents are missing or damaged, please
contact your wholesaler or tekmar sales representative for assistance.
Type 510 Includes: •• One Programmable Thermostat 510 •• Data Brochure D 510 •• User
Brochure U 510
Type 511 Includes: •• One Programmable Thermostat 510 •• One Slab Sensor 079 •• Data
Brochure D 510 •• User Brochure U 510
The tekmar Slab Sensor 079 has a stainless steel sleeve which is designed for use in
concrete, thin-set or grout. The 079 is supplied with 10’ (3 m) of 2 conductor zipcord.
Installation - Slab Sensor 079
STEP ONE
INSTALLING THE SENSOR
New Installations
Thin-Set or Thin-Pour Applications
If the floor covering is to be installed over either
a thin-set or thin-pour material of sufficient
depth, the 079 slab sensor can be placed
Electric
Cables
Thin-set
Tiles
directly into either the thin-set material or the
thin-pour material and covered over. Ensure
that the sensor is located in such a position that
the attached wire is able to reach to a suitable
junction location. Splices within the thin-set or
thin-pour should be avoided to ensure trouble free operation. The sensor should be located
mid way between the heating elements to ensure a proper temperature reading.
Thin Floor Coverings (less than 3/8” (10 mm))
If a thin floor covering is to be installed directly
to the subfloor, a groove 1/8” (4 mm) wide by
Hardwood
1/16” (2 mm) deep can be cut into the surface of
the subfloor to accommodate the wire for the
Subfloor
sensor. Ensure that the sensor is located in
such a position that the attached wire is able
to reach to a suitable junction location. Splices
under the floor covering should be avoided to
ensure trouble free operation. A groove 3/16”
(5 mm) wide by 3/16” (5 mm) deep by 1-3/4”
(45 mm) long should be cut to accommodate the sensor. The sensor should be located
mid way between the heating elements to ensure a proper temperature reading.
Thick Floor Coverings (greater than 3/8” (10 mm))
If a thick floor covering is to be installed directly to the subfloor, a groove 1/8” (4 mm) wide
by 1/16” (2 mm) deep can be cut into the back of the flooring material to accommodate
the wire for the sensor. Ensure that the sensor is located in such a position that the
attached wire is able to reach to a suitable junction location.
Splices under the floor covering should be
avoided to ensure trouble free operation. A
groove 3/16” (5 mm) wide by 3/16” (5 mm)
Hardwood
Subfloor
deep by 1-3/4” (45 mm) long should be cut to
accommodate the sensor. The sensor should be
located mid way between the heating elements
to ensure a proper temperature reading.
NOTE: If it is not practical to cut a groove in the surface covering, follow the installation
method used for thin floor coverings.