The tekmarNet®4 Gateway 483 allows contractors, building managers and home owners the ability to remotely access
tekmarNet®4 compatible controls through a computer web browser, such as Internet Explorer®, Firefox® and Safari® or
through a mobile device browser. Access can be either direct, through a local area network, or through the Internet.
Temperature adjustment, scheduling, and monitoring of each thermostat is made simple by allowing the installer to name
each thermostat and also group thermostats into areas within the building. Users can select to have scheduled status
reports and system alerts emailed automatically.
Features
tekmarNet® Compatible
•
No Annual Fees
•
Apple Mac® OS X® Computer Required
•
Remotely Accessible Using Windows®,
•
Mac OS X, or Linux
Web Browsers: Internet Explorer, Firefox, Safari
•
Email Status Reports and Alerts
•
Monitor and Adjust Temperatures
•
Adjust Schedules
•
Adjust and Activate Scenes
•
Activate Setpoint Controls
•
Low and High Level Alert Contacts
•
Alert Demand
•
Power
Alert Demand
Low Priority Alert
High Priority Alert
tN4 Gateway 483
USB
1
2
Alert RelaysAlert
Power
N
Input4Low5High
L
6
7
0
C0
tN4
Do not apply power
8
9
10
11
1
C1
2
tN4
C2
tN412C3
13
3
tN414C4
Alert on
break
USB
tN4 Bus 0
tN4 Bus 1
tN4 Bus 2
tN4 Bus 3
tN4 Bus 4
Made in Canada by
tekmar Control Systems Ltd.
tektra 1017-01
Power: 115 V ±10% 60 Hz 45 mA
Demand: 20 to 125 V (ac) 2 VA
Relays: 115 V (ac) 5 A 1/3 hp, pilot duty 240 VA
Caution: Signal wiring must be rated at least 300 V.
•
tekmarNet®2 House Control 400, 401, 402, 403, 406
•
Boiler Reset Module 420
•
Mixing Reset Module 421
•
Universal Reset Module 422, 423
•
Mixing Expansion Module 440, 441, 444
•
tekmarNet®4 User Switch 479, 480, 481
•
tekmarNet®2 Thermostat 527, 528, 529, 530
•
tekmarNet®4
•
543***, 544, 545, 546
tekmarNet® Thermostat 552
•
* 161 versions J1141A and J1141B are not fully compatible
with the 483
** 162 versions J1142A and J1142B are not fully compatible
with the 483
*** 543 versions J1126A to J1126I are not fully compatible
with the 483
Please contact your tekmar sales representative for
assistance with affected 161, 162, and 543 products.
tekmarNet® products not listed may not be compatible
with this version of the 483 software. Contact your tekmar
sales representative for information.
Thermostat 537, 538, 540, 541, 542,
Before You Start
Before connecting the tekmarNet®4 Gateway 483 to a
tekmarNet® system, it is recommended that the system
be fully completed, with no tekmarNet® thermostats or
setpoint control’s being added or removed at a later date.
Also, each tekmarNet® thermostat and setpoint control
device is automatically assigned a tekmarNet® address
when connected to the system. It is recommended that
each device be given a manual address. This address
should be written down together with the room location
for future reference.
The gateway records the address of each tekmarNet®
thermostat and setpoint control. For each address, the
installer can name the room location and building area for
each thermostat and setpoint control.
483 Hardware
Switch Settings
Alert on
break
Alert on
make
Alert on break / Alert on make
When using the Alert Demand (terminals 16 and 17), the
483 can either register an alert when the alert demand is
removed (Alert on break – switch setting in up position) or
it can register an alert when the alert demand is applied
(Alert on make – switch setting in down position).
Unlock / Lock
The Unlock / Lock switch allows the use of a factory default
user ID and password for the tekmarNet® gateway login
web page.
When set to Unlock (switch setting in up position), the user
ID is “installer” and the password is “tekmar”.
After logging in to the tekmarNet® gateway login web page,
create personal accounts for yourself and your customer
through the configuration page. Once the personal
accounts are completed, the Unlock / Lock switch can be
set to Lock. The default user ID and password are then
no longer accepted.
Should the personal account user ID or passwords be
forgotten, the Unlock / Lock switch can be set to Unlock
and the default user ID and password can be used to create
new personal accounts.
Alert Relays
The 483 includes two relay contacts that indicate alerts to
3rd party monitoring equipment such as a security system,
automation system, or telephone auto dialer.
The High Priority Alert Relay closes when the following error
messages are active on the tekmarNet® System Control:
Master Device Error
•
E01 Adjust Error
•
Boiler Sensor Short Circuit Error
•
Boiler Sensor Open Circuit Error
•
Mix Sensor Short Circuit Error
•
Mix Sensor Open Circuit Error
•
Mixing Expansion Module Missing Error
•
Mixing Expansion Module Conflict Error
•
Mixing Expansion Module Sensor Short Circuit Error
•
Mixing Expansion Module Sensor Open Circuit Error
•
The Low Priority Alert Relay closes when the Alert Demand
is present or removed according to the Alert on break /
Alert on make switch setting.
The Low Priority Alert Relay also closes if there is any
error on the tekmarNet® system that is not included on
the high priority list.
Once the error is corrected, the respective Alert Relay
contact is opened.
Note: The 483 is not a UL approved alarm panel.
IMPORTANT NOTE
Once the tekmarNet® Gateway installation is complete, it is
important that the switch setting be left in the Lock position
in order to prevent unauthorized access.
Alert Demand
The Alert Demand terminals (16 and 17) provide a way
for external devices to create a Low Priority Alert and
provide an email notification. The Alert Demand and Low
Priority Alert LEDs turn on when a voltage between 20 to
125 V (ac) is applied or removed depending on the Alert
on break/Alert on make switch setting. This demand also
closes the Low Priority Alert Relay. Through the gateway
web interface, the installer can assign the Alert Demand
to provide a user defined warning message that is sent
through email.
The Alert Demand could be used to detect the low level
switch of a fuel oil tank, or monitor a low water cut off.
Alert demand is present.Alert demand is not present.
A low priority alert is present.No low priority alert.
A high priority alert is present.No high priority alert.
USB communication is present.No USB communication.
tN4 communication on bus 0 is present.No tN4 communication on bus 0.
tN4 communication on bus 1 is present.No tN4 communication on bus 1.
tN4 communication on bus 2 is present.No tN4 communication on bus 2.
tN4 communication on bus 3 is present.No tN4 communication on bus 3.
tN4 communication on bus 4 is present.No tN4 communication on bus 4.
Testing the Control
The 483 includes a built-in test routine that tests the alert
relays.
Start the test routine by pressing the Test button for 1
second. The Test LED turns red.
Test LED
Test
Step 1: The Low Priority Alert Relay is closed for 10
•
seconds and then opened.
Step 2: The High Priority Alert Relay is closed for 10
•
seconds and then opened.
The 483 then exits the test routine and resumes normal
operation.
Pause the test routine by pressing the Test button again
while in the test routine. The Test LED flashes red while
paused. Press the Test button again to resume the test
routine.
If the test routine is paused for more than 5 minutes, the
483 automatically exits the entire test routine.
Cleaning
The 483 exterior can be cleaned using a damp cloth. Moisten the cloth with water and wring out prior to wiping the device.
Do not use solvents or cleaning solutions.
Apple Mac OSX Computer
Background
The Mac OS X computer functions as a web server for
the tekmarNet® Gateway. The web server creates and
maintains the gateway web pages so that any computer
with a web browser and a network connection can access
the gateway. This includes PC’s with Microsoft Windows,
PC’s with Linux, Mac’s with Apple OS X, as well as smart
phones such as an Apple iPhone™.
For applications where the gateway will be accessed remotely
from another computer, it is recommended to purchase an
Apple Mac Mini computer since it does not come bundled
with a keyboard, mouse, or monitor. A keyboard, mouse,
and monitor are required during installation but can be
removed once installation is complete. If possible, complete
all the computer settings, computer network settings, and
install the tekmarNet® Gateway web host software before
installing the computer at the job site to eliminate the need
to bring a monitor, keyboard and mouse to the job site.
For applications where the gateway will be accessed directly,
it is recommended to purchase an Apple iMac® (desktop
computer) or MacBook® (laptop computer).
If using an Apple Mac Mini computer, it is recommended
to mount the computer to the wall using the H-Squared
Mini Mount available from the Apple store.
Installation of Computer
Wire the computer according the instructions provided with
the computer and the Wiring Brochure W483.
Computer Setup
Press the power button (found on the back of the Mac
Mini) and go through the startup screen steps. It is very
important that the computer username and password is
recorded for future reference. Should the username and
password be lost, the operating system must be reinstalled
in order to install any new software.
Power
Button
Mac OS X Basics
System Updates
If the computer is connected to the
Internet, it is recommended to update
to the latest software. Click on the
Apple icon in the top left corner, and
then click “Software Update”.
Shutting the Computer Down
Should you need to shut down the
Mac OS X computer, click the Apple
icon in the top left corner, and then
click “Shut Down”.
Window Operation
Red = close the window
Amber = minimize the window
Green = maximize the window
Dock
By default, the dock is located at the
bottom of the screen. It has icons for
commonly used programs.
Finder File Edit View Go Window Help
Menu Bar (drop down lists)
Close
View Previous /
View Next
Click Triangles
to expand
contents
Desktop
Minimize
DEVICES
SHARED
PLACES
Folders and
links to common
file and device
locations
can be
accessed
from here.
Click on links
to display
contents in
right pane
Maximize
Switch Between
View Modes
Folders
Finder Window
Search Field
Drag with left mouse
button to resize window
Hard Drive (Disk)
Double left
click to view
contents
USB Drive
Finder
Click on the Finder icon to search or
Finder
(View Files & Folders)
browse for files on the computer.
Safari Web Browser
Click on the Safari Web Browser icon
to start the web browser.
System Preferences
Click on the System Preferences icon
to change settings on the computer.
Installation of Web Host Software
To install the tekmarNet® Gateway on the Mac web host
computer, follow these steps.
STEP 1) Insert the Web Host Software USB - P9307 into
the USB port on the computer. The USB drive
will appear as an icon on the computer desktop.
Double click on the USB drive icon.
Safari
(Built-in Web Browser)
Dock (Quick Way to Open Applications, Folders & Files
System Preferences
(Power, Networking, Etc.)
Removing the USB Drive
To remove the USB drive, drag
the Disk icon to the Trash Can
icon. Once the drive icon is not
dipslayed on the desktop, the USB
drive can be safely removed.
STEP 2) The finder window is now open with the USB drive
contents displayed in the right side pane.
STEP 3) Double click the icon called “Install”.
STEP 4) Click Yes when the dialog box asks to install
tekmarNet® Gateway Software.
STEP 5) Click and drag the USB drive icon towards the
garbage can on the dock. The garbage can turns
into an Eject symbol. Drop the USB drive icon
on top of the Eject symbol. It is safe to remove
the USB drive once it is not longer shown on
the desktop.
The tekmarNet® Gateway web host software is now installed.
Click on the amber dot in the upper left corner to minimize
the tekmarNet® Gateway window.
Confi guring Mac OS X
Disable OS X Automatic Updates
The Mac OS X automatic software updates can interfere with
the normal operation of the tekmarNet® Gateway software.
It is recommended to disable the automatic software update
feature. Please note that Mac computer software updates
can still continue to be performed manually.
STEP 1) Click on the System Preferences icon to
change settings on the computer.
STEP 2) Click on Software Update.
STEP 3) Uncheck “Download important updates
automatically”.
STEP 4) Uncheck “Check for updates”.
The window can be closed by clicking on the red dot in
the upper left corner.