- Data Brochure
Power Manager 345
D 345
02/09
1
Information
Brochure
Choose controls
to match
application
2
Application
Brochure
Design your
mechanical
applications
3
Rough-in
Rough-in
instructions
Wiring
wiring
4
Wiring
Brochure
Wiring and
installation of
specific control
5
Data
Brochure
Control settings
and sequence of
operation
6
Job
Record
Record settings &
wiring details for
future reference
Introduction
The Power Manager 345 has an internal transformer that powers a Reset Module 420, 421, 422, or 423. A single tN4 bus
input is available to allow Zone Managers and in some cases, Mixing Expansion Modules, to be connected.
Features:
• tN4 Compatible
• Internal 56 VA Transformer
• CSA C US Certified for use in USA and Canada
RtN4 C
Aux
1
Pmp
23
1
tektra 996-03
For product literature:
www.tekmarcontrols.com
For product instructions, see brochure
Input Power: 115 V (ac) ±10% 60 Hz, 12 A
Relay Rating: 115 V (ac) 5 A
All Loads Using Input Power: 11.5 A
910
78
Aux Pump
Input Power
Pmp
L
N
C
R
24 V (ac)
Limited power available, see wiring brochure
5
46
Power Manager 345
N
Power
Aux Pump
Caution! Disconnect All
Power before Opening
Made in Canada
Supply/signal wires 90°C min.
24 V (ac) Fuse: T2.5 A 250 V
H7012A
1 of 4 © 2009 D 345 - 02/09
Sequence of Operation
The primary purpose of the 345 is to provide power to a
Reset Module 420, 421, 422, or 423, and to provide power
to other tN4 devices such as tN4 Thermostats or tN4
Setpoint Controls.
Single Zone Application
A basic application allows a 345 to connect to a reset module
and to a single tN4 Thermostat or tN4 Setpoint Control to
operate single zone systems. The auxiliary pump is used
to operate the system pump.
tN4 Thermostat
or
tN4 Setpoint Control
Reset
Module
Test
345 Power
Manager
Remote Manifold Location Application
Another application is to locate the 345 and the Reset
Module in the mechanical room while the Zone Managers
can be located at remote manifold locations.
tN4 Bus
Zone Expansion Module 325
tN4
Test
Reset
Module
345
Power
Manager
System
Pump
Zone
Expansion
Module
Zone
Manager
System
Pump
Mechanical Room Manifold Location
© 2009 D 345 - 02/09 2 of 4