Introduction
The Zone Manager 336 is designed to simplify the wiring between tN4 thermostats and zone pumps. The 336 has an
internal transformer that supplies power to the tekmarNet®4 (tN4) thermostats.
Features:
• tN4 Compatible
• Internal Transformer
• Four Powered Zone Pump Outputs
• One Powered Zone Group Pump Output
• Simple Wiring
• CSA C US Certified for use in USA and Canada
tN4 C C CWWRRPmp tN4 tN4 C WRtN4 C WRtN4
Zn Grp A A tNt Zone A1 tNt Zone A2 tNt Zone A3 tNt Zone A4
1
23456789101112 13 14 15 16 17 18 19
tN4
For product literature:
www.tekmarcontrols.com
Input Power: 115 V (ac) ±10% 60 Hz, 12 A
Relay Rating: 115 V (ac) 5 A
All Loads Using Input Power: 11.7 A
Zone Power: 115 V (ac) ±10% 60 Hz, 12 A
20 21 22
Input Power Zone Group
L
tektra 997-01
N
Pmp A
23
N
Limited power available, see wiring brochure
Zone Manager 336
Zone Group Pump A
For product instructions, see brochure
24
25
Zone Power
L
N
Power
Caution! Disconnect All
Power before Opening
26 27 28
Zone A1 Zone A2
PumpNPump
N
Zone A1
Zone A2
Zone A3
Zone A4
Zone Group
30 31 32
29
PumpNPump
Meets Class B: Canadian
ICES & FCC Part 15
Made in Canada
Supply
H7004B
24 V (ac) Fuse: T1.25 A 250 V
On/Off
A1
A2
Pump A
A3
A4
/signal wires 90°C min.
Zone A3 Zone A4
N
33
1 of 4 © 2005 D 336 - 06/05
Sequence of Operation
On/Off
Zone Group
Pump A
A1
A2
A3
A4
24 V (ac) Powered Outputs
The 336 has an internal transformer that provides powered
outputs for up to four 24 V (ac) thermostats.
The internal transformer has limited power available. Refer
to the Job Records to determine the load on the transformer.
If the load is too large for the transformer, refer to the Wiring
Brochure to add additional power to the system.
115 V (ac) Powered Outputs
The 336 has five internal relays that provide powered outputs
for four zone pumps and one zone group pump.
Refer to the Job Records to determine the allowable loads
for these relays.
tN4 C C CWWRRPmp tN4 tN4 C WRtN4 C WRtN4
Zn Grp A A tNt Zone A1 tNt Zone A2 tNt Zone A3 tNt Zone A4
1
24 V (ac) R & C
tN4 Bus A
2345678910111213141516171819
tN4
tektra 997-01
For product literature:
www.tekmarcontrols.com
Limited power available, see wiring brochure
Sequence of Operation
When a thermostat calls for heat, the Zone LED turns on
and the Zone relay is turned on.
• If the Zone Group Pump DIP switch is set to On, the
Zone Group Pump LED and relay turn on.
• If the Zone Group Pump DIP switch is set to Off, the
Zone Group Pump LED and relay are not turned on.
Pump A Demand
To operate the Zone Group Pump A relay externally, a
powered signal must be sent to the Pmp A terminal on the
336. Refer to the Wiring Brochure for the proper wiring.
H7004B
Zone Manager 336
Power
Zone Group Pump A
Zone A1
Zone A2
Zone A3
Zone A4
24 V (ac) Fuse: T1.25 A 250 V
On/Off
Zone Group
Pump A
A1
A2
A3
A4
Input Power: 115 V (ac) ±10% 60 Hz, 12 A
Relay Rating: 115 V (ac) 5 A
All Loads Using Input Power: 11.7 A
Zone Power: 115 V (ac) ±10% 60 Hz, 12 A
115 V (ac) L & N
20 21 22 23
Input Power Zone Group
L NPmp A
N
DIP Switch Settings
tN4 C C CWWRRPmp tN4 tN4 C WRtN4 C WRtN4
Zn Grp A A tNt Zone A1 tNt Zone A2 tNt Zone A3 tNt Zone A4
1
23456789101112 13 14 15 16 17 18 19
Limited power available, see wiring brochure
tN4
tektra 997-01
For product literature:
www.tekmarcontrols.com
Input Power: 115 V (ac) ±10% 60 Hz, 12 A
Relay Rating: 115 V (ac) 5 A
All Loads Using Input Power: 11.7 A
Zone Power: 115 V (ac) ±10% 60 Hz, 12 A
20 21 22
Input Power Zone Group
LNPmp A
N
Zone Manager 336
Zone Group Pump A
24
23
Zone Power
L
Power
For product instructions, see brochure
Caution! Disconnect All
Power before Opening
26 27 28
25
Zone A1 Zone A2
PumpNPump
N
N
Zone A1
Zone A2
Zone A3
Zone A4
The DIP switches are found on the right hand side of the 336.
29
PumpNPump
24 V (ac) Fuse: T1.25 A 250 V
A1
Zone Group
A2
Pump A
A3
A4
Meets Class B: Canadian
ICES & FCC Part 15
Made in Canada
Supply
/signal wires 90°C min.
30 31 32
Zone A3 Zone A4
N
H7004B
On/Off
33
Meets Class B: Canadian
ICES & FCC Part 15
Made in Canada
Supply
/signal wires 90°C min.
30 31 32 33
Zone A3 Zone A4
Pump NPump
N
24 25
Zone Power
L
For product instructions, see brochure
N
Caution! Disconnect All
Power before Opening
26 27 28 29
Zone A1 Zone A2
Pump NPump
N
Zone Group Pump
Each zone has a corresponding Zone Group Pump DIP
switch.
Zone Group Pump DIP switch set to On:
• The Zone Group Pump turns on when the zone calls for
heat.
Zone Group Pump DIP switch set to Off:
• The Zone Group Pump does not turn on when the zone
calls for heat.
© 2005 D 336 - 06/05 2 of 4