Introduction
The tN2 Zone Manager 334 is designed to allow 2-wire tekmarNet®2 Thermostats to connect to a tN4 System Control such
as a 420, 421, 422, 423, 274, or 275. The 334 operates up to four zone valves or zone pumps.
Features:
Only Requires 2 Wires Per Zone
•
For use with tN2 Thermostats 527, 528, 530
•
tN4 System Control Compatible
•
Four Zone Valves or Zone Pumps
•
Time Delay for Thermal Motor Zone Valves
•
CSA C US Certified for use in USA and Canada
•
tN4 C C CWWRRPmp tN4 tN4 C WRtN4 C WRRtN4 C WtN4 RCWtN4
Zn Grp A A tNt Zone A1 tNt Zone A2 tNt Zone A3 tNt Zone A4 tNt Zone A5 tNt Zone A6
1
23456789101112 13 14 15 16 20
tN2
tektra 1029-01
For product literature:
www.tekmarcontrols.com
For product instructions, see brochure
Input Power: 115 V (ac) ±10% 60 Hz, 12 A
Relay Rating: 115 V (ac) 5 A
All Loads Using Input Power: 11.7 A
Zone Power: 115 V (ac) ±10% 60 Hz, 12 A
28 29 30
Input Power Zone Group Zone A1 Zone A2 Zone A3 Zone A4 Zone A5 Zone A6
L
31
Pmp A
N
N
Limited power available, see wiring brochure
Zone Manager 334
Zone Group Pump
Made in Canada
Meets Class B:
Canadian ICES &
FCC Part 15
17 1 8 1 9
Power Zone 1
tN4
Cooling
Fan
Caution! Disconnect All
Power before Opening
32 33 34 35 36 37 38 39 40 41 42 43
Vlv
C
C
21 22 23 242526 27
Zone 2
Zone 3
Zone 4
VlvCVlvCVlvCVlvCVlv
24 V (ac) Fuse: T2.5 A 250 V
A1
A2
Zone Group
A3
Pump A
A4
A5
A6
A1
A2
Zone Group
A3
Pump A Delay
A4
A5
A6
Supply /signal wires 90°C min.
On/Off
H7003B
1 of 4 © 2009 D 334 - 03/09
Sequence of Operation
()
On/Off
Zone Group
Pump Delay
Zone Group
Pump
1
2
3
4
1
2
3
4
General
The 334 can connect to four tekmarNet®2 (tN2) Thermostats.
When a thermostat calls for heat, the 334 turns on the
corresponding zone output which can either provide power
to a zone pump or a zone valve. Zone 4 can be connected
to a Heat – Cool thermostat. When the thermostat is
operating the cooling system, the 334 turns on the cooling
relay. When the thermostat is operating the fan, the 334
operates the fan relay.
The 334 includes two wiring plugs. The top plug provides
tN4 communication and 24 V (ac) to the left hand module.
When the top plug is installed to an outdoor reset module,
the 334 is connected to bus 1. The bottom plug provides
120 V (ac) power.
tekmarNet®2 Operation
The 334 uses tekmarNet®2 (tN2)
communication to connect to tN2
compatible thermostats. The 334
in turn translates the information to
tekmarNet®4 (tN4) communication.
The tN2 thermostats appear on the
tN4 communication bus in the same
manner as tN4 thermostats.
Important Note:
The 334 is NOT compatible with previous
generation tN2 products such as the
Remote Display Module 040 or the
Start / Stop Module 039.
24 V (ac) R & C
tN4 Bus
115 V (ac) L & N
tN4 C
123
tekmarNet®4 Expansion
The 334 has four wiring terminals to allow for tN4 expansion
to other tN4 devices. The tN4 expansion can be used to
connect the 334 to other Zone Managers or Zone Expansion
Modules to add extra heating zones. The tN4 expansion
can also be wired to a Mixing Expansion Module. This
option requires the use of a tN4 Outdoor Reset Control to
operate the mixed water temperature. The tN4 expansion
also allows the installation of a tN4 Timer 033, a single tN4
Thermostat or a single tN4 Setpoint Control. The powered
zone group pump is activated by the Mixing Expansion
Module, Thermostat, or Setpoint Control whenever the
pump input (terminal 4) is powered with 24 V (ac).
tN2 tN2tN2
Zone 1
4
56
tektra 1029-01
18
Zn Grp
Pump
tN2
Zone 2
Supply wires
75°C minimum
Pmp
R
tN4 Expansion
5 VA Max
tN2
For product instructions, see brochure
Input Power: 115 V (ac) ±10% 60 Hz, 12 A
Relay Rating: 115 V (ac) 5 A
All Loads Using Input Power: 11.7 A
Zone Power: 115 V (ac) ±10% 60 Hz, 12 A
16 17
Input Power
L
N
tN2
tN2
tN2
Zone 3
Zone 4
10789
Zone Manager 334
For product literature:
www.tekmarcontrols.com
R / L
tN2
1211
19 20
Zone Power
Power Zone 1
Zone Group Pump
Cooling
21 22
Zone 1
Vlv/Pmp
C / N
tN4
Fan
Caution! Disconnect All
Power before Opening
Vlv/Pmp
C / N
Zone 2
Zone 3
Zone 4
23 24
Zone 2
Zn 4 Cool Fan
13 1514
Vlv/Pmp
C / N
25 26
GYRc
Cool & Fan Relay Rating:
24 V (ac) 2 A
24 V (ac) Fuse: T1.25 A 250 V
Zone Group
Zone Group
Pump Delay
Meets Class B:
Canadian ICES
FCC Part 15
Zone 3
Pump
C / N
1
2
3
4
1
2
3
4
27 28
Vlv/Pmp
On/Off
Zone 4
Made in
Canada
H7017A
C / N
DIP Switch Settings
tN4 Expansion
Zone 1
56
123
5 VA Max
tN2
tektra 1029-01
For product instructions, see brochure
Input Power: 115 V (ac) ±10% 60 Hz, 12 A
Relay Rating: 115 V (ac) 5 A
All Loads Using Input Power: 11.7 A
Zone Power: 115 V (ac) ±10% 60 Hz, 12 A
16 17
18
Input Power
Zn Grp
NL
Pump
Zone 2
Supply wires
75°C minimum
Zone 3
10789
Zone Manager 334
For product literature:
www.tekmarcontrols.com
Zone 4
1211
Power Zone 1
Zone Group Pump
Cooling
21 22
19 20
Zone 1
Zone Power
C / N
Vlv/Pmp C / N
R / L C / N
tN4
Fan
tN2
tN2
tN2
tN2
tN2
tN2 tN2tN2Pmp4tN4 C
R
The DIP switches are found on the right hand side of the 334.
Zone Group Pump
Each zone has a corresponding Zone Group Pump DIP
switch.
Zone Group Pump DIP switch set to On:
The Zone Group Pump turns on when the zone calls
•
for heat.
Zone Group Pump DIP switch set to Off:
The Zone Group Pump does not turn on when the zone
•
calls for heat.
© 2009 D 334 - 03/09 2 of 4
Zn 4 Cool Fan
13 1514
Zone 2
Zone 3
Zone 4
Caution! Disconnect All
Power before Opening
23 24
Zone 2
Vlv/Pmp C / N
GYRc
Cool & Fan Relay Rating:
24 V (ac) 2 A
24 V (ac) Fuse: T1.25 A 250 V
On/Off
1
Zone Group
2
Pump
3
4
1
Zone Group
2
Pump Delay
3
4
Meets Class B:
Canadian ICES
FCC Part 15
25 26
27 28
Zone 3
Zone 4
Vlv/Pmp C / N
Vlv/Pmp
Made in
Canada
H7017A
Zone Group Pump Delay
Each zone has a corresponding Zone Group Pump Delay
DIP switch.
Note: The Zone Group Pump Delay only operates if the
Zone Group Pump DIP switch is set to On.
Zone Group Pump Delay DIP switch set to On:
The Zone Group Pump turns on 3 minutes after the zone
•
calls for heat.
The Zone Group Pump turns off 15 seconds after the
•
zone stops calling for heat.
Zone Group Pump Delay DIP switch set to Off:
The Zone Group Pump turns on when the zone calls
•
for heat.
The Zone Group Pump turns off when the zone stops
•
calling for heat.