Siemens QFA3100, QFA3101, QFA3160, QFA3160D, QFA3171 Installation Instructions Manual

...
5 (1)
Installation Instructions
QFA3100
Outdoor air humidity sensor (2%), 0 to 10 Vdc
QFA3101
Outdoor air humidity sensor (2%), 4 to 20 mA
QFA3160
Outdoor air humidity sensor (2%), 0 to 10 Vdc/Temp 0 to 10 Vdc
QFA3160D
Outdoor air humidity sensor (2%), display
QFA3171
Outdoor air humidity sensor (2%), 4 to 20 mA/Temp 4 to 20 mA
QFA3171D
Outdoor air humidity sensor (2%), display
QFA4171
Outdoor air humidity sensor (2%), 4 to 20 mA/Temp 4 to 20 mA, certified
QFA4171D
Outdoor air humidity sensor (2%), with displa y
QFA4160
Outdoor air humidity sensor (2%), 0 t 10 Vdc/Temp 0 to 10 Vdc, certified
QFA4160D
Outdoor air humidity sensor (2%), with displa y
Accessories
AQF3101
Sensor filter cap
AQF4150
Replaceable, certified sensor tip
AQF3100
Sun shield
74 662 0104 0
US 1/2-inch rigid conduit adapter
Document No. 129-416
October 5, 2009
and Relative Humidity & Temperature
Product Description
The Q-Series Outdoor Air Relative Humidity, and Relative Humidity & Temperature Sensors monitor and transmit changes in humidity and temperature to the building control systems. These units are especially suited for applications where precise, stable humidity sensing is required. Standard models available are 2% and 2% certified, for both humidity only and combination humidity with temperature sensing. Sensors are offered with either 4 to 20 mA or 0 to 10 Volt output signals.
Product Numbers
Part Number Description
0 to 10 Vdc/Temp 0 to 10 Vdc with
4 to 20 mA/Temp 4 to 20 mA with
Required Tools
Expected Installation Time
30 minutes
Prerequisites
Ensure that the appropriate field wiri ng is
Ensure that all wiring complies with National
Installation
Phillips screwdrivers, sizes No. 1 and No. 2
Medium flat-blade screwdriver
Wire cutters/strippers
Tape measure
Medium-duty electric drill
Drill bit for wall anchor hole
Marker or pencil
Two No. 10 screws and wall anchors
installed. Appropriate wiring is one or more twisted pair or
three conductor cables (plenum or non-plenum as required) within the maximum wiring run length for the humidity/temperature controller. The maximum recommended length is 750 feet (229 m).
Electric Code (NEC) and local regulations.
4 to 20 mA/Temp 4 to 20 mA, certified
0 t 10 Vdc/Temp 0 to 10 Vdc, certified
Item Number 129-416, Rev. BA Page 1 of 2
1. Determine where the sensor is to be located and install the Sun Shield, AQF3100, as shown in Figure 1. The installation surface determines which mounting components are to be used.
NOTE: The shield must be mounted vertically
as shown in Figure 1.
2. Remove sensor cover and install plug in knockout next to sensing probe. See Figure 1 (2).
3. Pull the field wiring through the conduit and into the sensor base. See Figure 2.
Loading...
+ 1 hidden pages