HAIER AD48HS1ERA, 1U48LS1EAB, AD60HS1ERA, 1U60IS1ERB, 1U48LS1ERB User Manual [ru]

...
0 (0)

DUCT TYPE AIR CONDITIONER

OPERATION MANUAL AND INSTALLATION MANUAL

Please read this manual carefully before installation.

Keep this operation manual for future reference.

No.0150509256 C

DUCT TYPE AIR CONDITIONER

OPERATION MANUAL AND INSTALLATION MANUAL

AD48HS1ERA

AD60HSIERA

Please read this manual carefully before installation.

Keep this operation manual for future reference.

Contents

Cautions

3

Safety Precautions

4

Parts and Functions

6

Operation

9

Installation Manual For Wire Controller

13

Heating Mode

14

Care and Maintenance

15

Troubleshooting

16

Precaution for Installation

19

Is The Unit Installed Correctly

20

Installation Procedure

21

English

HAIER AD48HS1ERA, 1U48LS1EAB, AD60HS1ERA, 1U60IS1ERB, 1U48LS1ERB User Manual

Cautions

Disposal of the old air conditioner

Before disposing an old air conditioner that goes out of use, please make sure it's inoperative and safe. Unplug the air conditioner in order to avoid the risk of child entrapment.

It must be noticed that air conditioner system contains refrigerants, which require specialized waste disposal. The valuable materials contained in a air conditioner can be recycled. Contact your local waste disposal center for proper disposal of an old air conditioner and contact your local authority or your dealer if you have any question. Please ensure that the pipework of your air conditioner does not get damaged prior to being picked up by the relevant waste disposal center, and contribute to environmental awareness by insisting on an appropriate, anti-pollution method of disposal.

Disposal of the packaging of your new air conditioner

All the packaging materials employed in the package of your new air conditioner may be disposed without any danger to the environment.

The cardboard box may be broken or cut into smaller pieces and given to a waste paper disposal service. The wrapping bag made of polyethylene and the polyethylene foam pads contain no fluorochloric hydrocarbon.

All these valuable materials may be taken to a waste collecting center and used again after adequate recycling.

Consult your local authorities for the name and address of the waste materials collecting centers and waste paper disposal services nearest to your house.

Safety Instructions and Warnings

Before starting the air conditioner, read the information given in the User's Guide carefully. The User's Guide contains very important observations relating to the assembly, operation and maintenance of the air conditioner.

The manufacturer does not accept responsibility for any damages that may arise due to non-observation of the following instruction.

Damaged air conditioners are not to be put into operation. In case of doubt, consult your supplier.

Use of the air conditioner is to be carried out in strict compliance with the relative instructions set forth in the User's Guide.

Installation shall be done by professional people, don't install unit by yourself.

For the purpose of safety, the air conditioner must be properly grounded in accordance with specifications.

Always remember to unplug the air conditioner before opening inlet grill. Never unplug your air conditioner by pulling on the power cord. Always grip plug firmly and pull straight out from the outlet.

All electrical repairs must be carried out by qualified electricians. Inadequate repairs may result in a major source of danger for the user of the air conditoiner.

Do not damage any parts of the air conditioner that carry refrigerant by piercing or perforating the air conditioner's tubes with sharp or pointed items, crushing or twisting any tubes, or scraping the coatings off the surfaces. If the refrigerant spurts out and gets into eyes, it may result in serious eye injuries.

Do not obstruct or cover the ventilation grille of the air conditioner. Do not put fingers or any other things into the inlet/outlet and swing louver.

Do not allow children to play with the air conditioner. In no case should children be allowed to sit on the outdoor unit.

This appliance is not intended for use by persons (including children) with reducedphysical, sensory or mental capabilities, or lack of experience and knowledge, unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety.

Children should be supervised to ensure that they do not play with the appliance.

3

Safety Precautions

Before starting to use the system, read carefully this "SAFETY PRECAUTIONS" to ensure a proper operation of the system.

Safety precautions described here are classified to " WARNING" and " CAUTION". Precautions which are shown in the column of " WANING" means that an improper handing could lead to a grave result like a death, serious injury, etc. However, even if precautions are shown in the column of " CAUTION", a very serious problem could occur depending on situation. Make sure to observe these safety precautions faithfully because they are very important information to ensure the safety.

Symbols which appear frequently in the text have following meanings.

Strictly prohibited.

 

Observe instructions faithfully.

 

Provide a positive grounding.

 

 

 

 

 

When you have read through the manual, keep it always at hand for read consultation. If the operator is replaced, make sure to hand over this manual to the new operator.

CAUTIONS FOR INSTALLATION

WARNING

The system should be applied to places as office, restaurant, residence and the like.

Application to inferior environment such as an engineering shop, could cause equipment malfunction and serious injury or death.

The system should be installed by your dealer or a professional installer.

Installation by yourself is not encouraged because it could cause such problems as water leakage, electrical shock or fire accident by some improper handing.

When you need some optional devices such as a humidifier, electric heater, etc., be sure to use the products which are recommended by us. These devices should be attached by a professional installer.

Installation by yourself is not encouraged because it could cause such problems as water leakage, electrical shock or fire accident by some improper handing.

CAUTION

Do not install nearby the place where may have leakage of flammable gas.

Depending on the place of installation, a circuit breaker may be necessary.

ON

OFF

Drain pipe should be arranged to provide a positive draining.

If the gas leakes and gathers around, it may cause

Unless the circuit breaker is installed, it could cause

If the pipe is arranged improperly, furniture or the

the fire.

elecrical shocks.

likes may be damaged by leaked water.

 

 

 

Where strong winds may prevail, the system

Install on the place where can endure the weight

Make sure the system is grounded.

should be fixed securely to prevent a collapse.

of air conditioner.

 

Bodily injury could result by a collapse.

Bodily injury could result by a careless installation.

Grounding cable should never be connected to

 

 

a gas pipe, city water pipe, lightning conductor

 

 

rod or grounding cable of telephone. If the

 

 

grounding cable is not set properly, it could cause

 

 

electric shocks.

CAUTIONS FOR TRANSFER OR REPAIR

WARNING

Modification of the system is strictly prohibited. When the system needs a repair, consult your dealer.

Improper practice of repair could cause water leakage, electric shock or fire.

When the air conditioner is relocated, contact your dealer or a professional installer.

Improper practice of installation could cause water leakage, electric shock or fire.

4

Safety Precautions

CAUTIONS FOR OPERATION

WARNING

You should refrain from exposing your body directly Do not poke the air inlet or outlet with a bar, etc. to cool wind for a long time.

It could affect your physical condition or cause

Since the internal fan is operating with a high

some health problems.

speed, it could cause an injury.

When any abnormal condition (scorching smell or others) is found, stop the operation immediately and turn off the power switch. Then consult your dealer.

If you continue the operation without removing the cause, it could result in a trouble, electric shock or fire.

CAUTION

The system should never be used for any other

Do not handle switches with a wet hand.

Combustion apparatus should not be placed

purposes than intended such as for preservation

 

allowing a direct exposure to wind of air conditioner.

of food, flora and fauna, precision devices or work

 

 

of art.

 

 

It could cause deterioration of food or other

It could cause electric shocks.

Incomplete combustion could occur on the

problems.

 

apparatus.

Do not wash the air conditioner with water.

Do not install the system where the air outlet

Make sure to use a fuse of proper electric rating.

 

reaches directly the flora and fauna.

 

It could cause electric shocks.

It will not be good for their health.

Use of steel or copper wire in place of a fuse is

 

 

strictly prohibited because it could result in a trouble

 

 

or fire accident.

Neither stand on the air conditioner nor place something on it.

There are risks of falling or injury by collapsed object.

It is strictly prohibited to place a container of combustible gas or liquid near the air conditioner or to spray it directly with the gas or liquid.

It could cause a fire accident.

Do not operate the system while the air outlet grill is removed.

There is a risk of injury.

Do not use the power switch to turn on or off the system.

ON

Do not touch the air outlet section while the swing louver is operating.

Do not use such equipment as a water heater, etc. around the indoor unit or the wire controller.

OFF

It could cause a fire or water leakage.

There is a risk of injury.

If the system is operated at the vicinity of such equipment which generates steam, condensed water may drip during cooling operation or it could cause a fault current or short-circuit.

When operating the system simultaneously with a combustion apparatus, indoor air must be ventilated frequently.

Check occasionally the support structure of the unit for any damage after a use of long period of time.

When cleaning the system, stop the operation and turn off the power switch.

Insufficient ventilation could cause an oxygen

If the structure is not repaired immediately, the

Cleaning should never be done while the internal

deficiency accident.

unit could topple down to cause a personal injury.

fans are running with high speed.

Do not put water containers on the unit such as a flower vase, etc.

If the water enters into the unit and damages the electric insulation material, it may cause electric shock.

5

Safety Precautions

The machine is adaptive in following situation

1. Applicable ambient temperature range:

 

Indoor temperature

max. DB/WB

32/23 C

Cooling

min. DB/WB

18/14 C

 

 

max. DB/WB

 

 

Outdoor temperature

46/26 C

 

min. DB/WB

10/6 C

 

 

 

Indoor temperature

max. DB/WB

27 C

 

min. DB/WB

15 C

Heating

 

 

max. DB/WB

24/18 C

 

Outdoor temperature

 

min. DB/WB

 

 

 

 

2.If the supply cord is damaged, it must be replaced by the manufacturer or its service agent or a similar qualified person.

3.If the fuse on PC board is broken, please change it with the type of T 3.15A /250VAC.

4.The wiring method should be in line with the local wiring standard.

5.The power cable and connecting cable are self-provided. The connecting cable should be H05RN-F 4G 0.75mm2.

All the cables shall have got the European authentication certificate. During installation, when the connecting cables break off, it must be assured that the grouding wire is the last one to be broken off.

6.The breaker of the air conditioner should be all-pole switch, and the distance between its two contacts should be no less than 3mm.

7.The indoor unit installation height is at least 2.5m.

8.In order to obtain the Unit's best performances, the fan speed is recommended according to the following conditions.

outdoor ambient temp.

operation mode

recommended fan speed

> 40 C

cooling

low

< 20 C

cooling

high

< -5 C

heating

low

> 18 C

heating

high

 

 

 

Parts and Functions

Indoor Unit

Air outlet

Duct

Duct

Drain pipe

Air inlet

6

Parts and Functions

Buttons of the wire controller

Mode switch

Choose running mode

Health switch

Used to control oxygen function and negative ion

 

MODE

 

FAN

CENTRAL

 

AUTO

 

AUTO

OPERATION

 

FAN ONLY

 

HIGH

STANDBY

 

COOL

 

MED

PRE-HEAT

 

DRY

 

LOW

DEFROST

 

HEAT

 

FIX

FILTER

 

TES

 

 

 

 

 

 

 

 

 

 

 

HEALTH

CHECK

SWING

 

UNIT NO.

DEMAND

MANUAL

 

CEN. ADD.

 

C

ROOM TEMP.

 

SYS. ADD.

 

SET TEMP.

 

 

F

 

 

 

 

 

 

TIMER CLOCK UP DOWN

VENTILATION

 

ON

 

 

AUTO

 

OFF

 

 

RECOVERY

 

 

 

 

DAILY

 

 

NORMAL

 

 

 

 

 

 

MODE

FAN

SWING

HEALTH

 

TEMP

CLOCK

 

TIME

TIMER

SET

RECOVERY

CHECK

FILTER

 

 

RESET

ON/OFF

Timing switch

It is used for choosing timing running

Self-inspection switch

It is used for inspection service

Filter reset

After cleaning air inlet and filter, press

this switch. The unit begins to run

Fan speed switch

Change wind speed

Swing switch

Open and close air flap

TEMP switch

Used for changing set temperature

Time switch

It is used to regulate setting time.

Clock, timing and address setting

Air change switch

It is used to open and close air change function. The mode is as follows:

No display-air change (automatic)- air change (RECOVERY)-air change (NORMAL)

ON/OFF switch

Do on and off function. The unit is on when pressing it; and is off when pressing it again (needn't to open front cover)

Reset key

When in abnormal state, push the reset key with a spike, which may return the unit to normal

7

Parts and Functions

Display of the wire controller

Air volume display

Display the setting speed

Running mode display

Show the selected mode

 

MODE

FAN

 

AUTO

AUTO

 

FAN ONLY

HIGH

Health function display

COOL

MED

DRY

LOW

 

HEAT

FIX

 

TES

 

 

HEALTH

CHECK

Unit number display

UNIT NO.

DEMAND

 

CEN. ADD.

C

 

SYS. ADD.

F

Temperature

 

TIMER CLOCK UP DOWN

display

ON

 

OFF

 

Display the room

 

DAILY

 

temperature, setting

 

 

temperature, and

 

 

unit number

 

 

Timing operation

 

 

display

 

 

Show timing operation

 

 

content

 

 

Inspection status display

Demand display

When forced to run,"DEMAND" will be displayed.

CENTRAL OPERATION STANDBY PRE-HEAT DEFROST

FILTER

SWING

MANUAL

ROOM TEMP. SET TEMP.

VENTILATION

AUTO

RECOVERY

NORMAL

MODE

FAN

SWING

HEALTH

 

TEMP

CLOCK

 

TIME

TIMER

SET

RECOVERY

CHECK

FILTER

 

 

RESET

ON/OFF

Centralized display

When controlled by centralized controller, this information is shown.

Running display

When the compressor runs, it displays.

Standby display

When the unit is on power and in

standby mode,"standby" is shown.

When in preheating status, "preheating" is shown.

After heating, "defrost" is shown when defrosting.

Filter screen warning sign

When the sign is shown, please clean the filter screen

Air change display

Wind swing display

Remarks

The models in the manual don't have health, filter reset and Air change function.

8

Operation

ON/OFF operation

MODE FAN SWING

MODE FAN

 

OPERATION

HEALTH

TEMP

HIGH

 

COOL

 

 

CLOCK

TIME

C

ROOM TEMP.

TIMER

SET

RECOVERY

 

 

 

CLOCK

 

 

 

 

 

 

CHECK

FILTER

 

 

 

 

 

RESET

 

 

ON/OFF

 

 

2Press ON/OFF switch on line controller directly

4

The line controller displays the running state in the latest

time (timing and swing state may not be displayed).

1. Press "ON/OFF" switch.

5The air conditioner starts operating, and the light on the wired controller is on.

32.Choose operation mode.

Press "mode"switch to change to

"AUTO"---"FAN ONLY"---"COOL"---"DRY"---"HEAT".

 

3.Press "TEMP" switch

 

Change set temperature:press" TEMP " or "TEMP "

 

every time, [SET] will display,and set temperature will

 

increase/reduce

1

4.Press "FAN SPEED" switch

6

FAN ONLY Operation:

Press "FAN SPEED" switch to change to

"HIGH"--"MED"--"LOW"--"HIGH"

In AUTO,COOL,DRY,HEAT Operation: Press "FAN SPEED" switch to change to "AUTO"--"HIGH"--"MED"--"LOW"--"AUTO"

5.Press "swing" switch on the line controller to swing the wind screen.

6.Press "ON/OFF"switch, off.

The light on the line controller is off.

Note

Several seconds after the operation of the line controller, the setting of the unit will change.

Remarks

Avoid pressing "ON/OFF" switch frequently.

Do not press line controller or switches by sharp objects.

The temperature is on the basis of the setting value. The wind temperature may not reach the setting value because of the outer air conditioner and system protection.

When the wired controller is power on, the screen fully displays it for two seconds. and clock zone "8888"-"888"-"88"- "8" flicker for 30 seconds. All the switches are invalid at the time.

9

Operation

Present time setting

The timing is based on the real time. Thus, the real time should be regulated in advance. The clock regulation steps are as follows:

MODE FAN

OPERATION

HIGH

HEAT

C

ROOM TEMP.

 

CLOCK UP

MODE

FAN

SWING

HEALTH

 

TEMP

CLOCK

 

TIME

TIMER

SET

RECOVERY

CHECK

FILTER

 

 

RESET

ON/OFF

1.Press "CLOCK" switch

"CLOCK" flickers, and the time displayed is the real time.

2.Press " " and " " to regulate the time.

The time increases a minute each time you press " " switch. The time decreases a minute each time you press " " switch.

3.Press "setting" switch. The setting is achieved.

Notes

If not in timing, the screen displays the real time.

If in timing, the screen displays the timing time.

If you want to know the real time, go to the first step.

1 3 2

Setting of power failure compensation function

When SW1-6 on PCB of wire controller is OFF, it will be in power failure compensation. If the SW1-6 is ON, it has no compensation function.

When the power is on after blackout, the unit will return to the former state if compensation function is set. Otherwise, it will stop. When restarting the unit, press "ON/OFF" switch on wired controller.

10

Operation

Timing setting

OFF timing: when a set time has elapsed, the unit stops running.

 

 

 

 

 

ON timing: when a set time has elapsed, the unit starts.

 

 

Press "ON/OFF" switch firstly,

 

 

 

 

 

 

 

 

 

and set up operation mode.

 

 

 

 

 

 

 

 

 

Please regulate the clock in

 

 

 

 

 

 

 

 

 

advance before using the

 

 

 

MODE

FAN

 

SWING

 

 

timing function.

 

 

 

 

 

 

 

 

 

MODE

FAN

 

 

 

 

 

 

 

 

 

 

 

HIGH

OPERATION

HEALTH

 

TEMP

1.Press "TIME" switch.

 

 

 

 

 

 

 

 

 

COOL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The display changes with the following sequence:

 

 

 

CLOCK

 

TIME

ON

OFF

on

on

CYCLE

no display

 

 

 

 

 

 

OFF

OFF

 

 

 

 

 

 

 

 

 

 

TIMER

ON

C

ROOM TEMP.

TIMER SET RECOVERY

CHECK FILTER

RESET

ON/OFF

2.Set up "TIMER"

When timing ON or timing OFF flickers, press "" or " " to regulate the time

Press" "or " "set up ON/OFF time.

The setting time increases ten minutes each time you press "" switch.

The setting time decreases ten minutes each time you press " " switch.

When setting timing ON and timing OFF at the same time, press "timing" switch to change the setting item.

1

3

2

3.Time setting is achieved. Press"setting"switch.

 

 

 

Cancel timing

If you want to change the timing mode to normal operation, press "timing" until there is no timing display. When the timing is invalid, the mode is in normal operation.

parts of wired controller explanation :

1.The unit starts or stops at the setting time. Meanwhile, it displays the timing time.

2."ON Timing, OFF timing and circulation"means that the unit is on and off at the setting time everyday.

Notes

The shorter setting time will be carried out firstly.

If the ON timing and OFF timing are the same, the setting is invalid.

Even in timing condition, you may start or close the unit through pressing "ON/OFF" switch.

11

Operation

Query indoor malfunction history:

In the state of power on or power off, press [CHECK] button, enter the malfunction-querying mode of all indoor units in the group. Then [CHECK] and [UNIT NO.] will display, and the actual indoor numbers will be displayed in some sequence (unit number is in decimals). At the same time, in the time region, there will be the current malfunction and the latest time malfunction, the displaying format is [XX:YY], in which XX stands for the current malfunction, if normal, it will display "--"; YY stands for the latest time malfunction. The failure code of every unit will display for 3 seconds. After the failure codes of all indoor units in the whole group are displayed, the mode will quit automatically.

How to change the function switches?

No.

Type

State of switch

Function description

 

 

 

 

SW1-1

Select the master or

ON

set as the slave controller

the slave controller

 

 

 

 

OFF

set as the master controller

 

 

 

 

 

 

 

SW1-2

Select the controller

ON

standard controller

mode

 

 

 

 

 

OFF

air handler controller

 

 

 

 

 

 

 

 

 

 

SW1-3

Room temperature

ON

visible room temperature

display option

 

 

 

 

 

OFF

invisible room temperature

 

 

 

 

 

 

 

 

 

ON

 

o

SW1-4

26o lock

Unavailable 26 lock

 

 

 

OFF

available 26o lock

SW1-5

Temperature sensor

ON

Sensor of the controller

position option

 

 

 

OFF

Sensor in the unit

 

 

 

 

 

 

 

 

SW1-6

Auto restart

ON

unavailable

 

 

 

 

OFF

available

 

 

 

 

 

 

 

 

 

SW1-7

Factory Seting

ON

default setting

 

 

 

 

 

 

SW1-8

Factory Setting

OFF

default setting

 

 

 

 

 

 

Notes

1.

Switches or jumper wire must be adjusted when the wire controller is powered off. If the wire controller is

powered on, the above operations will be invalid.

 

 

2.

Function difference between master wire controller and slave one:

 

Contrastive

Master wire

Slave wire controller

 

items

controller

 

 

 

Function

All of functions

Only with below functions: ON/OFF, MODE, FAN

 

SPEED, SET TEMP., SWING

 

 

 

 

 

 

 

 

 

 

 

12

Installation Manual For Wire Controller

1. Take down wire controller from the holder

 

 

 

 

 

 

Wire controller

52¡ 0.2

 

 

 

 

MODE

FAN

SWING

 

 

MODE

FAN

CENTRAL

 

 

 

 

 

 

AUTO

AUTO

OPERATION

HEALTH

 

TEMP

 

 

 

FAN ONLY

HIGH

STANDBY

 

 

 

 

COOL

MED

PRE-HEAT

 

 

 

 

 

 

DRY

LOW

DEFROST

 

 

 

 

 

 

HEAT

FIX

FILTER

 

 

 

 

 

 

TES

 

 

CLOCK

 

TIME

 

 

 

HEALTH

CHECK

SWING

 

 

 

 

 

 

 

 

 

 

UNIT NO.

DEMAND

MANUAL

 

 

 

 

10.45

5.3

CEN. ADD.

 

ROOM TEMP.

TIMER

SET

RECOVERY

Bracket

TIMER CLOCK UP DOWN

VENTILATION

 

 

SYS. ADD.

C

SET TEMP.

 

 

 

F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

 

AUTO

CHECK

FILTER

 

 

 

OFF

 

RECOVERY

 

 

 

DAILY

 

NORMAL

 

 

RESET

 

 

 

ON/OFF

Screw holes

2. Install the controller holder

According to the position of 2 screw holes on the holder, drill 2 holes on the wall, and strike the wood stopper to the holes respectively.

Then align the 2 screw holes of wired controller holder to the wood stopper, fix the holder on the wall with wood screw.

Note:Try a wall as flat as possible for installation. Don't use excessive force to tighten screws, otherwise, the holder will be damaged.

3.Wiring instruction

Use shielded wire between indoor and wire controller.And be earthed on one side, or the unit will not work normally because of interference.

Note:Confirm the terminal connection firmly, and do not get in tough with shielded wire.

4.Place wire controller on the holder, and pay attention not to pressing any wires. 5. Wiring connections of wire controller:

A

Indoor 1

 

Indoor 2

 

Indoor N

 

Indoor 15

 

Indoor 16(master unit)

 

Wire controller

 

Wire controller

 

Wire controller

 

Wire controller

 

Wire controller

 

 

A B C

A B C

A B C

A B C

A B C

B

Indoor 1

 

C

Indoor 1

 

 

Control wiring

A B C

 

Wire controller

 

Wire controller

 

 

 

 

of wire

 

 

 

A B C

 

 

A B C

 

Wire controller

 

Polar wire

 

Polar wire

 

controller,

 

 

 

 

 

 

Polar wire

polar.

 

A B C

A B C

A B C

Wire controller

Wire controller

Wire controller

There are three methods to connection wire controller and the indoor units:

A.One wired controller can control max. up to 16 sets of indoor units, and 3 pieces of polar wire must connect the wire controller and the master unit (the indoor unit connected with wire controller directly), the others connect with the master unit through 2 pieces of polar wire.

B.One wire controller controls one indoor unit, and the indoor unit connects with the wire controller through 3 pieces of polar wire.

C.Two wired controllers control one indoor unit. The wire controller connected with indoor unit is called master one, the other is called slave one. Master wire controller and indoor unit; master and slave wire controllers are all connected through 3 pieces of polar wire.

6. Communication wiring:

The wire controller is equipped with special communication wiring in the accessories. 3-core terminal (1-white 2-yellow

3-red) is connected with the terminal A, B, C of wire controller respectively.

The communication wiring is 5 meter long; if the actual length is more than it, please distribute wiring according to below table:

Communication wiring length(m)

Dimensions of wiring

 

 

< 100

0.3mm2x3-core shielded wire

100 and <200

0.5mm2x3-core shielded wire

200 and <300

0.75mm2x3-core shielded wire

300 and <400

1.25mm2x3-core shielded wire

400 and <600

2mm2x3-core shielded wire

*One side of the shielded sheet of communication wire must be earthed. 13

Heating Mode

"HOT KEEP" function

"HOT KEEP"is operated in the following cases.

When heating is started:

In order to prevent blowing out of cool wind, the indoor unit fan stopped according to the room temperature which heating operation is started. Wait for approx. 2 to 3 minute, and the operation will be automatically changed to the ordinary heating mode.

Defrosting operation (in the heating mode):

When it is liable to frost, the heating operation is stopped automatically for 5 to 12 minutes once per approx. one hour, and defrosting is operated. After defrosting is completed, operation mode is automatically changed to ordinary heating operation.

When the room thermostat is actuated:

When room temperature increases and room temperature controller actuates, the fan speed is automatically changed to stop under low temperature condition of indoor heat exchanger. When room temperature decreases, air conditioner automatically changes over to ordinary heating operation.

Warming Operation

Heat pump type warming

With the heat pump type warming, the mechanism of heat pump that concentrate heat of outdoor air with the help of refrigerant to warm the indoor space, is utilized.

Defrosting operation

When a room is warmed with a heat pump type air conditioner, frost accumulates on the heat exchanger of outdoor unit along with the drop of indoor temperature. Since the accumulated frost reduces the effect of warming, it is necessery to automatically switch the operation to the defrosting mode. During the defrosting operation, heating operation is interrupted.

Atmospheric temperature and warming capacity

Warming capacity of heat pump type air conditioner decreases along with the drop of outdoor temperature. When the warming capacity is not sufficient, it is recommended to use another heating implement.

Period of warm-up

Since the heat pump type air conditioner employs a method to circulate warm winds to warm the entire space of a room, it takes time before the room temperature rises.

It is recommendable to start the operation a little earlier in a very cold morning.

14

Care and Maintenance

Points to observe

Turn off the power supply switch.

ON

OFF

Do not touch with wet hand.

Do not use hot water or volatile liquid.

 

Thinner

Do not

 

use!

 

 

Benzine

 

 

Tooth powder

CAUTION

Do not open the inlet grill until fan stops completely.

Fan will continue rotating for a while by the law of inertia after operation is being stopped.

Cleaning the air filter

1.Clean the air filter by lightly tapping it or with the cleaner. It is more effective to clean the air filter with water.

If the air filter is very dirty, dissolve neutral detergent in the lukewarm water (approx. 30 C), rinse the air filter in the water, and thoroughly wash the air filter off the detergent

in the plain water.

2.After drying the air filter, set it up on the air conditioner.

CAUTION

Do not dry the air filter with fire.

Do not run the air conditioner without the air filter.

Care and Cleaning of the unit

Clean with soft and dry cloth.

If it is very dirty, dissolve neutral detergent in the lukewarm water and make the cloth wet with the water. After wiping, clean off the detergent using clean water.

Post-Season Care

Operate the unit with FAN mode on a fair day for about half a day to dry the inside of the unit well.

Stop operation and turn off the power supply switch. Electric power is consumed even the air conditioner is in stop. Clean the air filter and set it in the place.

Pre-Season Care

See that there are no obstacles blocking the air inlet and air outlet of both indoor and outdoor units.

Make sure that the air filter is not dirty.

Cut in the power supply switch 12 hours before starting run.

15

Troubleshooting

Please check the following things about your air conditioner before making a servie call.

Unit fails to start

Is the power source switch adjust cut in?

ON

OFF

Power supply switch is not ON.

Is city supply power in normal?

Power stoppage?

Isn't the signal receiving section exposed to the direct sunlight or strong illumination?

Isn't the earth leakage breaker in action?

It is dangerous. Turn off the power supply switch immediately and contact the sales dealer.

Cooling or heating is not sufficient

Is the thermostat adjust as Isn't the air filter dirty? required?

Isn't any doors or windows left open?

Doesn't any obstacle exist at the air inlet or outlet?

Isn't the swing louver horizontal? (At HEATING mode)

If swing louver is horizontal, the blow wind does not reach floor.

Cooling is not sufficient

Isn't sun-shine invading direct?

Isn't any unexpected heating

Isn't the room much crowded?

 

The wind does not blow during

 

 

load generated?

 

 

heating operation

 

 

 

 

Isn't it warming up?

 

 

 

 

 

 

 

 

 

 

When the air conditioner does not operate properly after you have checked the above mentioned items or when the following phenomenon is observed, stop the operation of the air conditioner and contact your sales dealer.

The fuse or breaker often shuts down.

Water drops off during cooling operation.

There is a irregularity in operation or abnormal sound is audible.

When the CHECK LED1 (red) flickers, an irregularity has occurred in the air conditioner.

16

Troubleshooting

The followings are not malfunction

Water flowing sound is heard.

When the air conditioner is started, when the compressor starts or stops during

 

Shuru

operation or when the air conditioner is stopped, it sometimes sounds "shuru shuru"

 

or "gobo gobo". It is the flowing sound of the refrigerant, and it is not a trouble.

 

Shuru

 

 

 

Cracking sound is heard.

This is caused by heat expansion or contraction of plastics.

 

It smells.

 

Air which blows out from the indoor unit sometimes smells. The smell results from

 

 

residents of tobacco smoke or cosmetics stuck inside of unit.

 

During operation, white fog comes

When the air conditioner is used at restaurant etc. where dense edible oil fume is

out of indoor unit.

 

always exists, white fog sometimes blows out of air outlet during operation. In this

 

 

case consult sales dealer for cleaning the heat exchanger.

 

It is switched into the FAN mode

To prevent frost from being accumulated on the indoor unit heat exchanger, it is

during cooling.

 

sometimes automatically switched to the FAN mode but it will soon return to the

 

 

cooling mode.

 

The air conditioner can not be

Even if the operation switch is turned on, cooling, dehumidifying or heating is not

restarted soon

Unit does

operable for three minutes after the conditioner is stopped. Because the

Wait for

after it stops.

protecting circuit is activated (During this time air conditioner operates

not start

three

minutes

 

 

in fan mode).

 

 

 

Air does not blow or the fan speed

When it is excessively cooled during dehumidifying, the blower automatically repeats

can not be changed during

reducing and lowering the fan speed.

 

dehumidifyin.

 

 

 

During operation, operation mode

Isn't the AUTO mode selected?

 

has changed over automatically.

In the case of AUTO mode, operation mode is changed automatically from cooling

 

 

to heating or vise-versa according to the room temperature.

 

Water or steam generates from

This results when frost accumulated on the outdoor unit is removed (during defrosting

the outdoor unit during heating.

operation).

 

17

Troubleshooting

Failure code(from receive board)

Failure code(from wired Failure code(from

Trouble shooting

Possible reasons

 

 

controller)

panel controller)

 

 

Flash times of

Flash times of

 

 

Timing LED(or

Running LED(or

 

 

 

 

indoor PCB LED4)

indoor PCB LED3)

 

 

 

 

 

 

 

 

 

 

0

1

01

E1

Temperature sensor Ta faulty

Sensor disconected,or broken,or

 

 

 

 

 

at wrong position,or short circuit

 

 

 

 

 

 

0

2

02

E2

Temperature sensor Te faulty

Sensor disconected,or broken,or

 

 

 

 

 

at wrong position,or short circuit

 

 

 

 

 

 

0

4

04

F8

EEPROM WRONG

Faulty indoor unit PCB

 

 

 

 

 

 

0

7

07

E9

Abnormal communication

Wrong connection,or the wires be

 

 

 

 

between indoor and outdoor

disconected,or wrong address

 

 

 

 

units

setting of indoor unit,or faulty

 

 

 

 

 

power supply or faulty PCB

 

 

 

 

 

 

0

8

NO EEROR

E8

Abnormal communication

Abnormal communication between

 

 

CODE DISPLAY

 

between indoor wired controller

indoor wired controller and indoor

 

 

 

 

and indoor unit PCB

unit PCB

 

 

 

 

 

 

0

12

0C

E0

Drainage system abnormal

Pump motor disconnected,or at

 

 

 

 

 

wrong position,or the float switch

 

 

 

 

 

broken down,or the float switch

 

 

 

 

 

disconected,or at wrong position.

 

 

 

 

 

 

0

13

OD

EF

Zero cross sigal wrong

Zero cross sigal detected wrong

 

 

 

 

 

 

0

16

10

F3

Indoor mode abnormal

Different from outdoor unit mode

 

 

 

 

 

 

2

1

15

/

Outdoor unit abnormal

 

 

 

 

 

 

 

2

2

16

/

Outdoor unit abnormal

 

 

 

 

 

 

 

2

4

18

/

Outdoor unit abnormal

 

 

 

 

 

 

 

2

5

19

/

Outdoor unit abnormal

 

 

 

 

 

 

 

2

7

1B

/

Outdoor unit abnormal

 

 

 

 

 

 

 

2

8

1C

/

Outdoor unit abnormal

 

 

 

 

 

 

 

2

9

1D

/

Outdoor unit abnormal

 

 

 

 

 

 

 

3

0

1E

/

Outdoor unit abnormal

 

 

 

 

 

 

 

3

1

1F

/

Outdoor unit abnormal

 

 

 

 

 

 

 

3

2

20

/

Outdoor unit abnormal

 

 

 

 

 

 

 

3

3

21

/

Outdoor unit abnormal

 

 

 

 

 

 

 

3

5

23

/

Outdoor unit abnormal

Refer to the outdoor unit trouble

 

 

 

 

 

3

6

24

/

Outdoor unit abnormal

shooting

 

 

 

 

 

list

3

7

25

/

Outdoor unit abnormal

 

 

 

 

 

 

 

3

8

26

/

Outdoor unit abnormal

 

 

 

 

 

 

 

3

9

27

/

Outdoor unit abnormal

 

 

 

 

 

 

 

4

3

2B

/

Outdoor unit abnormal

 

 

 

 

 

 

 

4

4

2C

/

Outdoor unit abnormal

 

 

 

 

 

 

 

4

7

2F

/

Outdoor unit abnormal

 

 

 

 

 

 

 

4

8

30

/

Outdoor unit abnormal

 

 

 

 

 

 

 

4

9

31

/

Outdoor unit abnormal

 

 

 

 

 

 

 

5

8

3A

/

Outdoor unit abnormal

 

 

 

 

 

 

 

5

9

3B

/

Outdoor unit abnormal

 

 

 

 

 

 

 

6

3

3F

/

Outdoor unit abnormal

 

 

 

 

 

 

 

6

4

40

/

Outdoor unit abnormal

 

1. For the indoor failure,only running LED ON remote receiver will indicate.

2. For the outdoor failure,timer LED and running LED will indicate.timer LED of remote receiver stands for ten's place,and running LED stands for one's place.timer LED will flash firstly,2 seconds later,running LED will flash too. Afer that,4 seconds later,they will flash in turns again.Flash times equals to the failure code of outdoor plus.

20.For example,failure code of outdoor is 2,the indoor unit should display 22.As a result,timer LED flashes twice firstly,then running LED flashes twice. 3.To get much more details of outdoor unit failure,Please refer to the the outdoor unit trouble shooting list.

18

Precaution For Installation

Please read these "Safety Precautions" first then accurately execute the installation work.

Though the precautionary points indicated herein are divided under two headings, WARNING and CAUTION, those points which are related to the strong possibility of an installation done in error resulting in death or serious injury are

listed in the WARNING section. However, there is also a possibility of serious consequences in relationship to the points listed in the CAUTION section as well. In either case, important safety related information is indicated, so by all

means, properly observe all that is mentioned.

After completing the installation, along with confirming that no abnormalities were seen from the operation tests, please explain operating methods as well as maintenance methods to the user (customer) of this equipment, based on the owner's manual. Moreover, ask the customer to keep this sheet together with the owner's manual.

WARNING

This system should be applied to places as office, restaurant, residence and the like. Application to inferior environment such as engineering shop could cause equipment malfunction.

Please entrust installation to either the company which sold you the equipment or to a professional contractor. Defects from improper installations can be the cause of water leakage, electric shocks and fires.

Execute the installation accurately, based on following the installation manual. Again, improper installations can result in water leakage, electric shocks and fires.

When a large air-conditioning system is installed to a small room, it is necessary to have a prior planned countermeasure for the rare case of a refrigerant leakage, to prevent the exceeding of threshold concentration. In regards to preparing this countermeasure, consult with the company from which you perchased the equipment, and make the installation accordingly. In the rare event that a refrigerant leakage and exceeding of threshold concentration does occur, there is the danger of a resultant oxygen deficiency accident.

For installation, confirm that the installation site can sufficiently support heavy weight. When strength is insufficient, injury can result from a falling of the unit.

Execute the prescribed installation construction to prepare for earthquakes and the strong winds of typhoons and hurricanes, etc. Improper installations can result in accidents due to a violent falling over of the unit.

For electrical work, please see that a licensed electrician executes the work while following the safety standards related to electrical equipment, and local regulations as well as the installation instructions, and that only exclusive use circuits are used. Insufficient power source circuit capacity and defective installation execution can be the cause of electric shocks and fires.

Accurately connect wiring using the proper cable, and insure that the external force of the cable is not conducted to the terminal connection part, through properly securing it. Improper connection or securing can result in heat generation or fire.

Take care that wiring does not rise upward, and accurately install the lid/service panel. Its improper installation can also result in heat generation or fire.

When setting up or moving the location of the air conditioner, do not mix air etc. or anything other than the designated refrigerant (R410A) within the refrigeration cycle. Rupture and injury caused by abnormal high pressure can result from such mixing.

Always use accessory parts and authorized parts for installation construction. Using parts not authorized by this company can result in water leakage, electric shock, fire and refrigerant leakage.

CAUTION

Execute proper grounding. Do not connect the ground wire to a gas pipe, water pipe, lightning rod or a telephone ground wire. Improper placement of ground wires can result in electric shock.

The installation of an earth leakage breaker is necessary depending on the established location of the unit. Not installing an earth leakage breaker may result in electric shock.

Do not install the unit where there is a concern about leakage of combustible gas. The rare event of leaked gas collecting around the unit could result in an outbreak of fire.

For the drain pipe, follow the installation manual to insure that it allows proper drainage and thermally insulate it to prevent condensation. Inadequate plumbing can result in water leakage and water damage to interior items.

19

Is The Unit Installed Correctly

Confirm the following items for safe and comfortable use of air conditioner.

The installation work is to be burden on the sales dealer, and do not conduct it by yourself.

Installation place

Avoid installing the air conditioner near Install the unit at well ventilated place.

Install the air conditioner firmly on the

the place where possibility of inflammable

foundation that can fully support the

gas leakage exists.

weight of the unit.

Explosion (Ignition) may occur.

If some obstacle exist, it may cause

If not, it may cause vibration or noise.

 

capacity reduction or noise increase.

 

Select the place so as not to annoy

Snow protection work is necessary

It is advisable not to install the air con-

neighbor with the hot air or noise.

where outdoor unit is blocked up by snow.

ditioner at the following special place.

 

 

It may cause malfunction, consult the

 

 

sales dealer when you have to install

 

 

the unit on such a place.

 

For details consult your sales dealer.

The place where corrosive gas generates

 

(Hot spring area etc.)

 

 

The place where salt breeze blows

 

 

(Seaside etc.)

 

 

The place where dense soot smoke exists

 

 

The place where humidity is extraordina-

 

 

rily high

 

 

The place where near the machine which

 

 

radiates the electromagnetic wave

 

 

The place where voltage variation is con-

 

 

siderably large

Electric work

The electric work must be burden on the authorized engineer with qualification for electric work and grounding work, and the work must be conducted in accordance with electric equipment technical standard.

The power source for the unit is to be of exclusive use.

An earth leakage breaker should be installed.(This is necessary to prevent electric shock.) The unit must be grounded.

When you change your address or the installation place

Special technology is required for removal or reinstallation of air conditioner, consult the sales dealer. Besides, construction expense is charged for removal or reinstallation.

For inspection and maintenance

The capacity of air conditioner will decrease by contamination of inside of unit when it is used for about three years although depending upon the circumstances under which it is used, and so in addition to the usual maintenance service, special inspection/maintenance service is necessary. It is recommended to make a maintenance contract (charged) by consulting your sales dealer.

20

Installation Procedure

Indoor Unit

NOTE

All wiring of this installation must comply with NATIONAL, STATE AND LOCAL REGULATIONS. These instructions do not cover all variations for every kind of installation circumstance. Should further information be desired or should particular problems occur, the matter should be referred to your local distributor.

WARNING

BE SURE TO READ THESE INSTRUCTIONS CAREFULLY BEFORE BEGINNING INSTALLATION. FAILURE TO FOLLOW THESE INSTRUCTIONS COULD CAUSE SERIOUS INJURY OR DEATH, EQUIPMENT MALFUNCTION AND/OR PROPERTY DAMAGE.

Before installation (Before finishing installation, do not throw the attached parts installation needs)

Confirm the way to move the unit to the installation place.

Before moving the unit to the installation place, do not remove their packages. When having to remove the package, use a soft material or protection board with rope to lift the unit assembly to avoid unit damage or bumping a scrape.

Choose installation place

The chosen installation place should meet the following requirements and get the user's consent.

Place ensures ideal airflow distribution.

The passage of airflow has no obstacles.

When importing outside air, it should be imported directly from outdoors. (If the pipe can not be extended, it also can not be imported from top)

Place ensures enough space for maintenance.

The pipe length between indoor and outdoor unit is in the permitted limit (referring to outdoor unit installation part).

The indoor unit, outdoor unit, electric wire and connection wire is at least 1m away from television and radio. This is to avoid the image disturbance and noise caused by the above mentioned home appliance. (Even if 1m away, if the electromagnetic wave is too strong, it can also cause noise.)

The indoor unit can install on the ceiling, which height is no more than 3m.

Install and use the hoisting screw. Check if the installation place can bear the weight of unit assembly. If not certain, strengthen it before install the unit.

Over 100

Over 900

Air out

Checking meatus

(600x600)

 

Air in

Installation for indoor unit

1.The position relation among hoisting screw (unit: mm)

Over 200 Over 300

Ceiling

360

1270

250

853

794

Down side

Up side

 

 

 

 

 

 

 

 

 

 

1103

 

 

2.If necessary, cut the opening installation and checking needed on the ceiling. (If having ceiling)

Before installation, finish the preparation work of all the pipes (refrigerant, drainage) and wire (wire controller connection wire, indoor and outdoor unit connection wire) of indoor unit, so that after installation, they can be immediately connected with outdoor unit.

Cut the opening on the ceiling. Maybe it needs to strengthen the ceiling to keep the ceiling even and flat and prevent the ceiling from vibration. For details, please consult to the builder.

21

Installation Procedure

Indoor Unit

3. Hanger bolts installation

Use care of the piping direction when the unit is installed.(Use M10 screw bolt)

In order to bear the weight of the unit, for existed ceiling, using foundation screw bolt, and for new ceiling, using burying embedded screw bolt, burying screw bolt or spot supplied other parts.

Before going on installation, adjust the gaps with ceiling.

4. Installation of indoor unit

Fix the indoor unit to the hanger bolts.

If required, it is possible to suspend the unit to the beam, etc. Directly by use of the bolts without using the hanger bolts.

Note

When the dimensions of main unit and ceiling holes does not match, it can be adjusted with the slot holes of hanging bracket.

5. Adjusting to the levelness

(a)Adjust the out-of levelness using a level or by the following method.

Make adjustment so that the relation between the lower surface of the unit proper and water level in the hose becomes as given below.

(b)Unless the adjustment to the levelness is made properly, malfunctioning or failure of the float switch may occur.

Hole-in anchor

Insert

Hole-in plug

 

 

Concrete

Hanging bolt M10

 

M10 nut

Hanging bolt

M10 washer

 

Main unit

M10 spring washer

 

Piping side

Supply water

Water level

0~5 mm

PVC hose

(0~0.2")

 

Bring the piping side slightly lower.

22

Installation Procedure

Drain Piping

(a)Drain piping should always be in a downhill grade (1/50~1/100) and avoid riding across an elevation or making traps.

 

Good piping

Improper piping

 

Suspension 1.5m ~ 2m

 

Avoid riding across an elevation

bolts

 

 

 

 

Air vent

Keep free from traps

 

A downhill grade

 

Do not pipe under water

Heat

 

 

of 1/100 or more

 

 

insulation

 

 

(b)When connecting the drain pipe to unit, pay suffcient attention not to apply excess force to the piping on the unit side. Also, fix the piping at a point as close as possible to the unit.

(c)For drain pipe, use hard PVC general purpose pipe VP-25(I.D.1") which can be purchased locally. When connecting, insert a PVC pipe end securely into the drain socket before tightening securely using the attached drain hose and clamp. Adhesive must not be used connection of the drain socket and drain hose (accessory).

(d)When constructing drain piping for several units, position the common pipe about 100 mm below the drain outlet of each unit as shown in the sketch. Use VP-30(11/4") or thicker pipe for this purpose.

(e)The stiff PVC pipe put indoor side should be heat insulated.

Stage

Drain socket difference Drain hose part

Drain socket

 

Pipe cover(large)

VP-25 joint

[for insulation]

(field purchased)

(accessory)

 

Main unit

 

Drain hose

VP-25

(accessory)

(field purchased)

Clamp

Adhesion

Pipe cover [for insulation]

(accessory)

 

(field purchased)

Pipe cover(small) [for insulation]

 

(accessory)

Secure the elevation as high as possible (approx. 100 mm)

VP-30

A downhill grade of 1/100 or more

(f)Avoid putting the outlet of drain hose in the places with irritant gas generated. Do not insert the drain hose directly into drainage, where the gas with sulfur may be generated.

(g)Because the drain spout is at the position, which negative pressure may occur. So with the rise of water level in the drain pan, water leakage may occur. In order to prevent water leakage,

we designed a backwater bend. The structure of backwater H1

bend should be able to be cleaned. As the right figure shown,

 

 

 

H1=100mm or the static pressure of

H2

use T type joint. The backwater bend is set near the air

air sending motor

conditioner.

 

 

 

H2=1/2H1 (or between 50~100mm)

As figure shown, set a backwater bend in the middle of drain

 

 

 

 

 

 

 

 

hose.

 

 

 

 

Drainage Test

(1)Conduct a drainage test after completion of the electrical work.

(2)During the trial, make sure that drain flows properly through the piping and that no water leaks from connections.

(3)In case of a new building, conduct the test before it is furnished with the ceiling.

(4) Be sure to conduct this test even when the unit is installed in the heating season.

Procedures

(a)Supply about 1000 cc of water to the unit through the air outlet using a feed water pump.

(b)Check the drain while cooling operation.

23

Installation Procedure

Air Duct

Please consult the after-sales service personnel for the choosing and installation of suction inlet, suction duct, discharging outlet and discharging duct. Calculating the design drawing and outer static pressure, and choose the discharging duct with proper length and shape.

 

muffler cavity (air sending)

 

 

 

Sacking joint

 

Insulation

 

A

Air volume adjuster

 

Air outlet

Air conditioner

Ceiling

 

main unit

 

 

 

Air suction grille with air filter

 

 

Checking meatus

The length difference among every duct is limited below 2:1.

Reduce the length of duct as possible as can.

Reduce the amount of bend as possible as can.

Use heat insulation material to bind and seal the part connecting main unit and the flare part of air discharging duct. Perform duct installation work, before the fitment of ceiling.

Enlarging chart of profile chart A

Vibration resistance hook

Bad example

Bad example

Good example

A Air conditioner

Calculation method of the dimension of the simple quadrate air duct

Presuming the unit length friction impedance of the duct is 1Pa/m, when the dimension of one side of the air duct is fixed as 250mm, as shown below:

B

A

 

Static pressure

Equipped with

A

 

box

air filter (bought)

 

AD48HS1ERA AD60HS1ERA

 

Air volume

Duct

A

2400m3/h(40m3/min)

250x560(mmxmm)

B

600m3/h(10m3/min)

250x190(mmxmm)

The calculation of duct resistance (the simple calculation is as follow table)

Straight part

Calculate as per 1m length 1Pa, 1Pa/m

 

 

Bend part

Each bend takes as a 3~4m long straight duct

 

 

Air out part

Calculate as 25Pa

Static pressure box

Calculate as 50Pa/each

 

 

Air inlet grille (with air filter)

Calculate as 40Pa/each

The chosen chart of simple duct

Note:1Pa/m=0.1mmAg/m

Shape

Square duct

Air volume

Item

Dimension

m3/h(m3/n)

 

(mmxmm)

100

 

250 x 60

200

 

250 x 90

300

 

250 x 120

400

 

250 x 140

500

 

250 x 170

600(10)

 

250 x 190

800

 

250 x 230

1,000

 

250 x 270

1,200(20)

 

250 x 310

1,400

 

250 x 350

1,600

 

250 x 390

Shape

Square duct

Air volume Item

Dimension

m3/h(m3/n)

(mmxmm)

1,800(30)

250 x 430

2000

250 x 470

2400

250 x 560

3,000(50)

250 x 650

3,500

250 x 740

4,000

250 x 830

4,500

250 x 920

5,000

250 x 1000

5,500

250 x 1090

6,000(100)

250 x 1180

24

Installation Procedure

Air Duct

The attentive matters in installation of air suction and discharging duct

Recommend to use anti-frost and sound-absorbing duct. (locally bought)

The duct installation work should be finished before the fitment of ceiling.

The duct must be heat insulated.

The specific air-discharging outlet should be installed at the place where the airflow can be reasonably distributed.

The surface should leave a checking meatus for checking and maintenance.

The examples of improper installation

Do not use air inlet duct and take the ceiling inner side as duct instead. The result is because of the irregular outer air mass, strong wind and sunshine, the humidity is increased.

There may be water drop on the outside of duct. For cement and other new constructions, even if not taking ceiling inner side as duct, the humidity will also be so high. At this time, use glass fiber to perform heat preservation to the whole. (use iron net to bind the glass fiber)

Maybe exceeding the unit operation limit (for example: when indoor dry bulb temperature is 35 C, wet bulb temperature 24 C), it may lead to overload of compressor.

Affected by the capacity of air discharging fan, the strong wind in the outer duct and wind direction, when unit air sending volume exceeds the limit, the discharged water of heat exchanger will overflow, leading to water leakage.

Special air discharging outlet Use screw bolt to fix

Duct

Air

Air

Improper example

Air discharging fan

25

Installation Procedure

Refrigerant Pipe

The gas side pipe, liquid side pipe must be faithfully heat insulated, if no heat insulation, it may cause water leakage.

The outdoor unit has been charged with refrigerant.

When connect the pipe to the unit or dismantling the pipe from the unit, please follow the figure shown, use spanner and torque spanner together.

When connect cone nut, the inner side and outside of cone nut should paste with refrigerant oil. Use hand to twist 3-4 rings, then fasten with spanner.

Referring to Table I to confirm the fasten torque. Too tight may damage nut leading to leakage.

Check if the connection pipe leaks, then do heat insulation treatment, as below figure shown. Only use seal cushion to bind the joint part of air pipe and heat insulation parts.

Paste the refrigerant oil here

Torque spanner

Spanner

Pipe joint

Cone nut

Middle size seal cushion (accessory)

Table I

(Use seal cushion to

Specification

Tighten torque

Cone

 

 

Cone

bind the pipe joint)

dimension

 

 

of pipe

 

 

 

 

 

A (mm)

 

 

 

 

 

 

 

 

 

Clamp

9.52mm

3270~3990 N.cm

 

 

 

 

 

12.0~12.4

 

 

 

 

(333~407 kgf.cm)

 

 

 

Heat insulation (accessory)

 

 

 

 

 

 

 

2

R0.4~0.8

 

 

 

 

(for liquid pipe)

 

6180~7540 N.cm

 

 

15.88mm

18.6~19.0

0.5

45

 

Heat insulation (accessory)

(630~770 kgf.cm)

 

 

 

90

A

 

(for gas pipe)

 

 

 

 

 

9720~11860 N.cm

 

 

 

 

Gas pipe

19.05mm

 

 

 

 

(990~1210 kgf.cm)

22.9~23.3

 

 

 

Liquid pipe

 

 

 

 

 

 

 

 

 

 

 

 

 

80

 

510

 

Liquid pipe

Gas pipe

Electric box

 

 

 

Upper

 

Air inlet

 

310

Air outlet

 

 

 

Drain hose connection mouth

530

Down side

30

 

 

VP25 PVC pipe

26

Installation Procedure

Electrical Wiring

WARNING

DANGER OF BODILY INJURY OR DEATH

TURN OFF ELECTRIC POWER AT CIRCUIT BREAKER OR POWER SOURCE BEFORE MAKING ANY ELECTRIC CONNECTIONS.

GROUND CONNECTIONS MUST BE COMPLETED BEFORE MAKING LINE VOLTAGE CONNECTIONS.

Precautions for Electrical wiring

Electrical wiring work should be conducted only by authorized personnel.

Do not connect more than three wires to the terminal block. Always use round type crimped terminal lugs with insulated grip on the ends of the wires.

Use copper conductor only.

Selection of size of power supply and interconnecting wires

Select wire sizes and circuit protection from table below. (This table shows 20 m length wires with less than 2% voltage drop.)

Item

 

Circuit

breaker

Power source

Earth leakage breaker

Phase

 

 

wire size

 

 

 

Switch breaker

Overcurrent protector

Switch

Leak

Model

(minimum)

 

(A)

rated capacity (A)

breaker(A)

current(mA)

 

(mm2)

AD48HS1ERA

3

30

20

4.0

30

30

AD60HS1ERA

 

 

 

 

 

 

Wiring connection

Make wiring to supply power to the outdoor unit, so that the power for the indoor unit is supplied by terminals.

27

Loading...
+ 104 hidden pages