Ductless Split Heat Pump
|
Indoor |
Outdoor |
|
AM24LP2VHA |
1U24LP2VHA |
|
AM36LP2VHA |
1U36LP2VHA |
|
AM48LP2VHA |
1U48LP2VHA |
|
AL24LP2VHA |
|
|
AL36LP2VHA |
|
|
AL48LP2VHA |
|
Installation Manual |
AW24LP2VHA |
|
AW36LP2VHA |
|
Table of Contents |
|
Nomenclature ............................................................................................................................... |
2 |
................................................................................................................... |
3 |
Safety ........................................................................................................................................... |
4 |
Section A - Outdoor Unit Installation ............................................................................................ |
7 |
Section B - Indoor Unit Installation - Wall Mount ......................................................................... |
13 |
Section C - Indoor Unit Installation - Cassette............................................................................. |
17 |
Section D - Indoor Unit Installation - High ESP Duct................................................................... |
23 |
Section E - Wired Controller YR-E17............................................................................................ |
29 |
Section F - Wireless Remote Controller ....................................................................................... |
37 |
ENGLISH
Nomenclature
Nomenclature
1 U 2418 LPES 2 V H A
Unit Type
A = Indoor Unit
1 = Single Zone Outdoor Product Revision
2 = Two Zone Outdoor
3 = Three Zone Outdoor
4 = Four Zone Outdoor
Unit Type |
|
System Type |
|
H = Heat Pump |
|
U = Outdoor |
|
|
|
C = Cool Only |
|
B = Casse e Type Indoor |
|
|
|
|
|
D = High ESP Duct Type Indoor |
|
|
M=High Static Duct Type Indoor |
|
Compressor Speed |
W = Wall Mount Type Indoor |
|
|
|
V = Variable Speed |
|
L = Large Cassette Type Indoor |
|
|
|
|
|
Nominal Capacity |
|
Voltage |
In Btu/hr (x 1000) |
Product Family |
1 = 115V |
|
- LP:LP=FlexFit Pro Series |
2 = 230V |
PAGE 2 |
INTRODUCTION |
Model |
System |
AW24LP |
AW36LP |
AM24LP |
AM36LP |
AM48LP |
AL24LP |
AL36LP |
AL48LP |
|
|
Outdoor |
1U24LP2VH |
1U36LP2VH |
1U24LP2VH |
1U36LP2VH |
1U48LP2VH |
1U24LP2VH |
1U36LP2VH |
1U48LP2VH |
ENGLISH |
||
|
|||||||||||
Range |
|
-4~75 |
-4~75 |
-4~75 |
-4~75 |
-4~75 |
-4~75 |
-4~75 |
-4~75 |
||
Name |
Indoor |
AW24LP2VH |
AW36LP2VH |
AM24LP2VH |
AM36LP2VH |
AM48LP2VH |
AL24LP2VH |
AL36LP2VH |
AL48LP2VH |
|
|
|
Cooling °F(°C) |
0~115 |
0~115 |
0~115 |
0~115 |
0~115 |
0~115 |
0~115 |
0~115 |
|
|
Operating |
(-18~46) |
(-18~46) |
(-18~46) |
(-18~46) |
(-18~46) |
(-18~46) |
(-18~46) |
(-18~46) |
|
||
|
|
||||||||||
|
Heating °F(°C) |
(-20~24) |
(-20~24) |
(-20~24) |
(-20~24) |
(-20~24) |
(-20~24) |
(-20~24) |
(-20~24) |
|
|
|
|
|
|||||||||
Power |
Voltage, Cycle, |
208- |
208- |
208- |
208- |
208- |
208- |
208- |
208- |
|
|
Supply |
Phase V/Hz/- |
230/60/7 |
230/60/10 |
230/60/8 |
230/60/11 |
230/60/13 |
230/60/9 |
230/60/12 |
230/60/14 |
|
|
|
Compressor |
|
|
|
DC Inverter |
Driven Rotary |
|
|
|
|
|
|
Maximum Fuse |
25.0 |
30 |
25.0 |
30 |
40 |
25.0 |
30 |
40 |
|
|
|
Size A |
|
|||||||||
|
|
|
|
|
|
|
|
|
|
||
|
Minimum Circuit |
21.0 |
26.0 |
21.0 |
26.0 |
35.0 |
21.0 |
26.0 |
35.0 |
|
|
|
Amp A |
|
|||||||||
|
|
|
|
|
|
|
|
|
|
||
|
Dimension: |
38 (965) |
38 (965) |
38 (965) |
38 (965) |
53 1/8 (1350) |
38 (965) |
38 (965) |
53 1/8 (1350) |
|
|
Outdoor |
Height in (mm) |
|
|||||||||
|
|
|
|
|
|
|
|
|
|||
Unit |
Dimension: |
37 3/8(950) |
37 3/8(950) |
37 3/8(950) |
37 3/8(950) |
37 3/8(950) |
37 3/8(950) |
37 3/8(950) |
37 3/8(950) |
|
|
|
Width in (mm) |
|
|||||||||
|
|
|
|
|
|
|
|
|
|
||
|
Dimension: |
14 5/8(370) |
14 5/8(370) |
14 5/8(370) |
14 5/8(370) |
14 5/8(370) |
14 5/8(370) |
14 5/8(370) |
14 5/8(370) |
|
|
|
Depth in (mm) |
|
|||||||||
|
|
|
|
|
|
|
|
|
|
||
|
Weight |
202.8/ 176.4 |
207.2/180.7 |
202.8/ 176.4 |
207.2/180.7 |
260.1/231.5 |
202.8/ 176.4 |
207.2/180.7 |
260.1/231.5 |
|
|
|
(Ship/Net)- lbs |
|
|||||||||
|
(92/80) |
(94/82) |
(92/80) |
(94/82) |
(118/105) |
(92/80) |
(94/82) |
(118/105) |
|
||
|
(kg) |
|
|||||||||
|
|
|
|
|
|
|
|
|
|
||
|
Dimension: |
13 1/4(336) |
14 3/8(365) |
9 7/8 (250) |
9 7/8 (250) |
9 7/8 (250) |
9 5/8 (246) |
9 5/8 (246) |
11 3/8 (288) |
|
|
|
Height in (mm) |
|
|||||||||
|
|
|
|
|
|
|
|
|
|
||
|
Dimension: |
43 7/8(1115) |
51 |
37 5/8 (957) |
59 (1500) |
59 (1500) |
33 1/8(840) |
33 1/8(840) |
33 1/8(840) |
|
|
|
Width in (mm) |
13/16(1316) |
|
||||||||
|
Dimension: |
9 9/16(243) |
10 7/8(275) |
25 3/4 (655) |
28 3/8 (720) |
28 3/8 (720) |
33 1/8(840) |
33 1/8(840) |
33 1/8(840) |
|
|
|
Depth in (mm) |
|
|||||||||
|
|
|
|
|
|
|
|
|
|
||
|
Max. External |
|
|
|
|
|
|
|
|
|
|
|
Static Pressure |
NA |
NA |
0.6(150) |
0.6(150) |
0.6(150) |
NA |
NA |
NA |
|
|
|
in.W.G(Pa) |
|
|
|
|
|
|
|
|
|
|
Indoor Unit |
Drainpipe Size |
NA |
NA |
1 1/4 |
1 1/4 |
1 1/4 |
1 |
1 |
1 |
|
|
|
O.D. in |
|
|||||||||
|
|
|
|
|
|
|
|
|
|
||
|
Internal |
NA |
NA |
Standard |
Standard |
Standard |
Standard |
Standard |
Standard |
|
|
|
Condensate |
|
|||||||||
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
|
|
|
|
Max. Drain-Lift |
NA |
NA |
27 9/16(700) |
27 9/16(700) |
27 9/16(700) |
39 3/8 (1000) |
39 3/8 (1000) |
39 3/8 (1000) |
|
|
|
height in(mm) |
|
|||||||||
|
|
|
|
|
|
|
|
|
|
||
|
Grill Model |
NA |
NA |
NA |
NA |
NA |
PB-950KB |
PB-950KB |
PB-950KB |
|
|
|
Weight |
45.4/37.5(20. |
55.1/46.3(25. |
81.1/68.8 |
130.1/121.3 |
132.3/114.6 |
79.4/68.3 |
79.4/68.3 |
83.8/70.5 |
|
|
|
(Ship/Net)- lbs |
|
|||||||||
|
6/17) |
5/21) |
(36.8/31.2) |
(59/55) |
(60/52) |
(36/31) |
(36/31) |
(38/32) |
|
||
|
(kg) |
|
|||||||||
|
|
|
|
|
|
|
|
|
|
||
|
Connections |
Flare |
Flare |
Flare |
Flare |
Flare |
Flare |
Flare |
Flare |
|
|
|
Liquid O.D. in |
3/8 |
3/8 |
3/8 |
3/8 |
3/8 |
3/8 |
3/8 |
3/8 |
|
|
|
Suction O.D. in |
5/8 |
5/8 |
5/8 |
5/8 |
5/8 |
5/8 |
5/8 |
5/8 |
|
|
Refrigerant |
Factory Charge |
88.2 |
88.2 |
88.2 |
88.2 |
131 |
88.2 |
88.2 |
131 |
|
|
Line |
Oz |
|
|
|
|
|
|
|
|
|
|
Maximum Line |
165 (50) |
165 (50) |
165/50 |
165/50 |
230/75 |
165/50 |
165/50 |
230/75 |
|
||
|
|
||||||||||
|
Length Ft / m |
|
|||||||||
|
|
|
|
|
|
|
|
|
|
||
|
Maximum Height |
100/30 |
100/30 |
100/30 |
100/30 |
100/30 |
100/30 |
100/30 |
100/30 |
|
|
|
Ft / m |
|
|||||||||
|
|
|
|
|
|
|
|
|
|
INTRODUCTION |
PAGE 3 |
SAFETY OVERVIEW
ENGLISH
Read These Safety Precautions
Be sure to read the safety precautions before conducting work. The items are classified into “Warning” and “Caution.” The “Warning" items are especially important since they can lead to death or serious injury if not followed closely. Under certain conditions, the "Caution" items can also lead to accident or injury if they are not followed. Therefore, be sure to observe all safety precautions listed here.
∆ This symbol means be careful when doing this procedure or touching this equipment.
ᴏ This symbol indicates a prohibited action.
• This symbol means that an action must be taken; the action will be listed next to the symbol.
After the repair work is complete, be sure to conduct a test operation to ensure that the equipment operates properly; explain the safety precautions for operating the equipment to the customer.
Warning
Disconnect the power cable from electrical supply before disassembling equipment for repair.
If the refrigerant discharges during the repair work, DO NOT touch the discharging refrigerant. The refrigerant can cause frostbite.
Before disconnecting the suction or discharge pipe of the compressor at the brazed connections, recover the refrigerant in a well-ventilated area. If refrigerant remains inside the compressor, the refrigerant or the refrigerating machine oil will discharge when the pipe is disconnected and may cause injury.
If the refrigerant leaks during the repair work, ventilate the area. The refrigerant can generate toxic gases when it contacts flames.
The step-up capacitor supplies high-voltage electricity to the electrical components of the outdoor unit. Be sure to discharge the capacitor completely before conducting repair work. A charged capacitor can cause electrical shock.
Be sure to use parts listed in the service parts of the applicable model and appropriate tools to conduct repair work. Never attempt to modify
the equipment. The use of inappropriate parts or tools can cause electrical shock, excessive heat generation, or fire.
When relocating the equipment make sure that the new installation site has sufficient strength to withstand the weight of the equipment. If the new installation site does not have sufficient strength and if the installation work is not conducted securely, the equipment can fall and cause injury.
Be sure to install the product correctly by using the standard installation frame provided. Incorrect use of the installation frame and improper installation can cause equipment to fall, resulting in injury.
Do not repair the electrical components with wet hands. Working on equipment with wet hands can cause electrical shock.
Do not clean the equipment by splashing water. Washing the unit with water can cause an electrical shock.
Make sure that the unit is grounded when reparing the equipment in a wet or humid place to avoid electrical shocks.
Be sure to turn off the power switch when cleaning the equipment; the internal fan rotates at a high speed and may cause injury.
Do not tilt the unit when removing it. Water inside the unit can spill, wetting the floor.
Be sure to check that the refrigeration cycle section has cooled down sufficiently before conducting repair work. Working on the unit when the refrigerating cycle is hot can cause burns.
Use the brazing equipment in a well-ventilated place. Using the brazing equipment in an enclosed room can cause oxygen deficiency.
Be sure to use a dedicated power circuit for the equipment; follow appropriate technical standards for the electrical equipment, the internal wiring regulations, and the instruction manual for installation when conducting electrical work.
Insufficient power circuit capacity and improper electrical work can cause an electrical shock or fire.
PAGE 4 |
INTRODUCTION |
SAFETY OVERVIEW
Read These Safety Precautions
Be sure to use the specified cable to connect between the indoor and outdoor units. Make the connections securely and route the cable properly so that there is no force pulling the cable at the connection terminals.
When connecting the cable between the indoor and outdoor units make sure that the terminal cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section can cause an electrical shock, excessive heat generation, or fire.
Do not damage or modify the power cable.
Damaged or modified power cables can cause electrical shock or fire. Placing heavy items on the power cable and heating or pulling the power cable can damage the cable.
Do not introduce air into the refrigerant system. If air enters the refrigerant system, an excessively high pressure results, causing equipment damage and injury.
If the refrigerant leaks, be sure to locate the leak and repair it before charging the system with additional refrigerant. If the leak cannot be located and the repair work cannot be stopped, be sure to perform pump-down and close the service valve to prevent the refrigerant from leaking into the room. The refrigerant itself is harmless, but it can generate toxic gases when it contacts a heat source such as another appliance or an open flame.
When replacing the remote control battery, be sure to safely dispose of the battery.
Do not install the equipment in a place where there is a possibility of combustable gas leaks. If combustible gas leaks and remains near the unit, it may cause a fire.
Be sure to install the packing and seal on the installation frame correctly. If the packing and seal are not properly installed, water can spill out, wetting furniture and the floor.
Replace power cables and lead wires if they are scratched or deteriorated. Damaged cable and wires can cause electrical shock, excessive heat generation, or fire.
Check to see if the parts are mounted correctly, that the wires are connected correctly, and that connections at soldered or crimped terminals are secure. Improper installation and connections can cause excessive heat generation, electrical shock, and fire.
If the installation platform or frame has deteriorated or corroded, replace it. Corroded platform or frames can cause the unit to fall, resulting in injury.
Check to make sure that the equipment is grounded. Repair it if it is not properly grounded. Improper grounding can cause an electrical shock.
Be sure to measure the installation resistance of the repair. Be sure that the resistance is 1 M ohm or higher. Faulty installation can cause an electric shock.
Be sure to check the drainage of the indoor unit after the repair. Faulty drainage can cause a water leak from indoor unit and could cause property damage.
Important Safety Related Installation Information
Indoor Clearances: If noncompliant may lead to temperature control complaints.
Wire Sizing: If noncompliant may lead to communication errors and inverter irregular operation.
Splices in Field Wiring: Splices between the wires that connect between the outdoor and indoor unit should be avoided.
Sealing Penetrations: If penetrations at back of unit are not sealed, unconditioned air may be drawn into the back of the indoor wall mount unit. Temperature control and capacity complaints may occur.
ENGLISH
INTRODUCTION |
PAGE 5 |
[This page intentionally left blank.]
Section A - Outdoor Unit Installation
Step 1 - Installation of the Outdoor Unit
Attaching Drain Elbow to Outdoor Unit
(Heat Pump models only) |
|
|
1.1 Step - 1.1 |
|
|
If attaching the supplied drain elbow to the outdoor unit, |
|
|
do so prior to attaching the refrigerant lines and wiring. |
|
|
Extension piping to attach to this fitting is field supplied. |
Step 1.1 |
Step1.2 |
Electrical Connections for the Outdoor Unit
1.2 Step - 1.2
Remove the cover plate of the outdoor unit to expose the terminal block connections.
1.3 Step - 1.3
Connect the wiring for both the power source and indoor wiring.
Wire the system according to applicable national / local codes.
Verify that the wiring connections for the indoor unit match
wire for wire. Step 1.3 (1-1, 2-2, 3-3, Gnd-Gnd). Failure to wire the system correctly
may lead to improper operation or component damage.
1.4 Step - 1.4
Replace the cover plate.
Step 2 - Connecting the Indoor Unit
*See indoor section A, B, or C for electrical connections.
Piping
The standard lineset length is 25ft. If the installation length is different, adjust the refrigerant charge by 0.5oz/ft.for the 24k,36k,42k and 48k model. (Illustration 4)
Cut the lineset to length, flare and attach the piping to the outdoor unit valves.
Torque the fittings to the specifications shown in the torque chart.
2.1 Step - 2.1
CAUTION
B
Outdoor unit
Outdoor unit
Step 1.4
Outdoor unit
Indoor unit
A |
|
B |
|
|
|
|
A |
Indoor unit |
|
|
Max. Elevation: A Max.
|
= 100ft / 30m (24k / 36k) |
|
|
In case the height of A is more than |
|
Oil trap |
15ft / 5m, an oil trap should be |
|
installed every 16-23ft /5-7m |
||
|
||
Indoor unit |
Max. Length: B Max |
|
|
= 165ft / 50m (24k / 36k) |
Illustration 4
Refrigerant piping connections at the indoor unit are made utilizing flare joints. Follow standard practices for creating pipe flares. When cutting and reaming the tubing, use caution to prevent dirt or debris from entering the tubing. Remember to place the nut on the pipe before creating the flare.
2.2 Step - 2.2 |
Step 2.1 |
Step 2.2 |
To join the lineset piping together, directly align the piping |
|
|
flare to the fitting on the other pipe, then slide the nut onto |
|
|
the fitting and tighten. Misalignment may result in a leaking |
|
|
connection. |
|
|
ENGLISH
A SECTION
INSTALLATION |
PAGE 7 |
ENGLISH
2.3 Step - 2.3
Two wrenches are required to join the flare connections, one standard wrench, and one torque wrench. See Table 1 for the specific torque per piping diameter.
Half union |
|
Forced fastening without careful centering may |
|
|
|
Flare nut damage the threads and cause a leakage of gas. |
|
|
|||
|
|
Pipe Diameter(ǿ) |
Fastening torque |
Step 2.3 |
|
|
|
Liquid side6.35mm(1/4") |
18N.m/13.3Ft.lbs |
|
|
|
|
Liquid/Gas side9.52mm(3/8") |
42 N.m/30.1Ft.lbs |
|
|
Spanner |
Torque wrench |
Gas side 12.7mm(1/2") |
55N.m/40.6Ft.lbs |
|
|
Gas side 15.88mm(5/8") |
60 N.m/44.3Ft.lbs |
|
|
||
|
|
|
|
||
|
|
Table 1 |
|
|
|
|
|
|
Step 3 - Leak Test and Evacuation |
|
|
|
|
Leak Test |
|
|
|
Hazard of Explosion! Never use an open flame to detect |
|
|
|||
refrigerant leaks.. Explosive conditions may occur. Use a leak |
|
|
|||
test solution or other approved methods for leak testing. |
|
|
|||
Failure to follow recommended safe leak test procedures |
|
|
|||
could result In death or serious injury or equipment or |
Step 3.1 |
Step 3.2 |
|||
property damage. |
|
|
|||
|
|
|
|
Use only dry nitrogen with a pressure regulator for pressurizing unit. Do not use acetylene, oxygen or compressed air or mixtures containing them for pressure testing. Do not use mixtures of a hydrogen containing refrigerant and air above atmospheric pressure for pressure testing as they may become flammable and could result in an explosion. Refrigerant used as a trace gas should only be mixed with dry nitrogen for pressurizing units. Failure to follow these recommendations could result in death or serious injury or equipment or property damage.
3.1 Step - 3.1
SECTION A
Using a tank of nitrogen with attached regulator, charge the system with 150 PSIG of dry nitrogen. Use adapter AD-87
(field supplied) to connect to the service valve. Check for leaks at the flare fittings using soap bubbles or other detection methods. If a leak is detected, repair and recheck. If no leaks are detected, proceed to evacuate the system.
System Evacuation
3.2 Step - 3.2
Attach a manifold gauge, micron gauge, and vacuum pump to the suction line port using adapter AD-87 (field supplied).
(Illustration 5)
Evacuate the system to 350 microns.
Close the vacuum pump valve and check the micron gauge. If the gauge rises above 500 microns in 60 seconds, evacuation is incomplete or there is a leak in the system. If the gauge does not rise above 500 microns in 60 seconds, evacuation is complete.
Illustration 5
PAGE 8 |
INSTALLATION |
3.3 Step - 3.3
Remove the adapter and hose connection from the suction line port, and replace the cap. Hoses should not be removed and service valves should not be opened until any additional refrigerant needed for a refrigerant line longer than 25 ft. has first been added.
3.4 Step - 3.4A & 3.4B
Remove the cap from the liquid line valve. Using the hex wrench, open the valve, then replace and tighten the cap.
3.5 Step - 3.5A & 3.5B
Remove the cap from the suction line valve. Using the hex wrench, open the valve, then replace and tighten the cap.
3.6 Step - 3.6
Wrap the lineset, drain line, and wiring starting at the bottom of the bundle with an overlap type wrap, concluding at the piping hole. Use a sealant to seal the piping hole opening
to prevent weather elements from entering the building. (Illustration 6)
Verify the condensate drain line has a constant pitch downward for proper water flow. There should be no kinks or rises in the tubing which may cause a trapping effect resulting in the failure of the condensate to exit the piping.
Step 3.3 |
Step 3.4A |
Step 3.4B |
Step 3.5A |
Step 3.5B |
Step 3.6 |
|
|
|
Less than |
|
|
5cm |
It becomes |
The end is imm- |
It waves. The gap with the There is the bad |
high midway. |
ersed in water. |
ground is too small smell from a sewer |
Illustration 6
ENGLISH
A SECTION
INSTALLATION |
PAGE 9 |
ENGLISH
Step 4 - Charging
See Steps 5.2 - 5.5 for evacuating the system prior to |
System Test |
|
charging. The standard lineset length is 25ft. If the |
||
|
||
installation length is different, adjust the refrigerant charge |
Using the instruction manual, show the customer how to |
|
by .5 oz / ft. for the 24K, 36K and 48K model. (Step 4 - |
||
properly use and care for the equipment. |
||
Illustration 4) |
||
|
Refrigerant Charge Label
This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent into the atmosphere.
Refrigerant type: R410A GWP* value: 1975
GWP = global warming potential
Please fill in with indelible ink,
•1 the factory refrigerant charge of the product
•2 the additional refrigerant amount charged in the field and
•1+2 the total refrigerant charge on the refrigerant charge label supplied with the product.
The filled out label must be adhered in the proximity of the product charging port (e.g. onto the inside of the stop valve cover).
A - contains fluorinated greenhouse gases covered by the Kyoto Protocol
B - factory refrigerant charge of the product: see unit name plate
C - additional refrigerant amount charged in the field
D - total refrigerant charge E - outdoor unit
F - refrigerant cylinder and manifold for charging
Check Items for Test Run
Put check mark √ in boxes
No refrigerant leaks from line sets or other connections?
Are the linesets insulated properly?
Are the connecting wirings of indoor and outdoor firmly inserted to the terminal block?
Is the connecting wiring of indoor and outdoor firmly connected?
Is condensate draining correctly?
Is the indoor unit securely attached?
Is power source voltage correct according to local code?
Is there any noise?
Is the lamp normally lighting?
Are cooling and heating (when in heat pump) performing normally?
Is the operation of room temperature sensor normal?
Contains fluorinated greenhouse gases |
|
covered by the Kyoto Protocol |
A |
R410A |
1= |
oz |
B |
|
2 |
2= |
oz |
C |
|
1 |
||||
|
|
|
||
|
1+2= |
oz |
D |
|
|
|
|
F E
SECTION A
PAGE 10 |
INSTALLATION |
Section 5 - Explaining Operation to the End User
•Using the OPERATING INSTRUCTIONS, explain to the user how to use the air conditioner (the remote controller, removing the air filters, placing or removing the remote controller from the remote controller holder, cleaning methods, precautions for operation, etc.)
•Recommend that the user read the OPERATING INSTRUCTIONS carefully.
Section 6 - Seacoast Application
•The outdoor unit should be installed at least ½ mile away from the salt water, including seacoasts and inland waterways. If the unit installed from ½ mile to 5 miles away from the salt water, including seacoasts and inland waterways, please follow the installation instruction below.
•Install the outdoor unit in a place (such as near buildings etc.) where it can be protected from sea breeze which can damage the outdoor unit.
|
|
ODU |
Sea breeze |
|
Sea breeze |
|
|
ODU |
Sea |
ODU |
Sea |
|
• If you cannot avoid installing the outdoor unit by the seashore, construct a protection wall around it to block the sea breeze.
|
|
|
|
|
|
|
|
• A protection wall should be constructed with a solid material such as |
Protection walls |
|
|
concrete to block the sea breeze and the height and the width of the wall |
|||||
|
||||||||
|
|
|
|
|
|
ODU |
should be 1.5 times larger than the size of the outdoor unit. Also, secure |
|
|
|
|
|
|
|
|
|
over 28 in (700mm) between the protection wall and the outdoor unit for |
Sea breeze |
|
|
|
|
|
|
|
exhausted air to ventilate. |
|
|
|
|
|
||||
|
|
|
|
|
|
|
||
|
|
|
|
|
|
|
|
|
ODU
Sea
•Install the outdoor unit in a place where water can drain smoothly.
•If you cannot find a place satisfying above conditions, please contact manufacturer. Make sure to clean the sea water and the dust on the outdoor coil.
ENGLISH
A SECTION
INSTALLATION |
PAGE 11 |
[This page intentionally left blank.]
Section B - Indoor Unit Installation - Wall Mount
Required Tools for Installation
•Drill
•Wire Snipper
•Hole Saw 2 3/4”
•Vacuum pump
•Soap-and-water solution or gas leakage detector
•Torque wrench
•17mm, 22mm, 26mm
•Tubing cutter
•Flaring tool
•Razor knife
•Measuring tape
•Level
•Micron gauge
•Nitrogen
•Mini-Split AD-87 Adapter (1/4” to 5/16”)
•A - Non-adhesive Tape
•B - Adhesive Tape
•C - Saddle (L.S.) with screws
•D - Electrical wiring
•E - Drain hose (Included)
•F - Insulation
•G - Piping hole cover (Included)
Step 1 - Preparation
Procedure for Selecting the Location
•Choose a place solid enough to bear the weight and vibration of the unit and where the operation noise will not be amplified.
•Choose a location where the hot air discharged from the unit or the operation noise and will not cause a nuisance to the user.
•There must be sufficient space for carrying the unit into and out of the site.
•There must be sufficient space for air passage and no obstructions around the air inlet and air outlet.
•The site must be free from the possibility of flammable gas leakage in a nearby place.
•Install units, power cords and inter-unit cables at least 10ft away from television and radio sets. This is to prevent interference to images and sounds. (Noise may be heard even if they are more than 10ft away depending on radio wave conditions.)
Clearances of Indoor and Outdoor Units
This picture is for reference only. Your product may look different. Read this manual before installation. Explain the operation of the unit to the user according to this manual.
The models adopt HFC free refrigerant R410A
more than 4in. |
Attention must be paid to |
the pitch of drain hose |
more than 4in.
more than 4in.
The marks from A to G in the gure are the name of the parts.
The distance between the indoor unit and the oor should be more than 6 feet.
more than 24in.
Floor fixing dimensions of the outdoor unit (Unit: inch)
more than 4in.
|
|
|
|
|
Z |
|
|
|
1 |
|
2 |
|
|
|
C |
Model |
Dimensions(inches) |
|
||
|
|
|
|
|
||
|
|
1 |
|
x2 |
|
|
|
|
|
|
|
||
more than 4in. |
|
1U24/36/42/48 |
6 7/8” |
23 5/8” |
6 7/8” |
16” |
|
|
LP2VHA |
|
|
|
|
Fixing of outdoor unit
Anchor the outdoor unit to the pad.
When installing the outdoor unit on a roof or a outside wall, the installation should meet the local code.
more than 6in.
ENGLISH
B SECTION
INSTALLATION |
PAGE 13 |