Flowserve MEN User Manual

MEN / MHP, MEN-TI
(Sealed for life
bearings)
ME-TI (AND OTHER PUMPS)
Motor-pump unit reserved exclusively for fire-fighting purposes. Diesel engine cooled with a spent water heat exchanger centrifugal pump
PCN=71576298 - 11-09 (E) Original instructions.
USER INSTRUCTIONS
Installation
Operation
Maintenance
These instructions must be read prior to installing,
operating, using and maintaining this equipment.
®
MEN USER INSTRUCTIONS ENGLISH 71576288 – 11-09
CONTENTS
PAGE
1 INTRODUCTION AND SAFETY ...........................4
1.1 G
ENERAL
1.2 CE
1.3 D
ISCLAIMER
1.4 C
OPYRIGHT
1.5 D
UTY CONDITIONS
1.6 S
AFETY
1.7 N
AMEPLATE AND SAFETY LABELS
1.8 S
PECIFIC MACHINE PERFORMANCE
1.9 N
OISE LEVEL
2 TRANSPORT AND STORAGE .............................7
2.1 C
ONSIGNMENT RECEIPT AND UNPACKING
2.2 H
ANDLING
2.3 L
IFTING
2.4 S
TORAGE
2.5 R
ECYCLING AND END OF PRODUCT LIFE
3 PUMP DESCRIPTION...........................................9
3.1 C
ONFIGURATIONS
3.2 N
OMENCLATURE
4 INSTALLATION....................................................11
4.1 L
OCATION
4.2 F
OUNDATION
4.3 G
ROUTING
4.4 I
NITIAL ALIGNMENT
4.5 P
IPING
4.6 E
LECTRICAL CONNECTIONS
4.7 C
ONNECTION
4.8 B
ATTERIES
4.9 S
WITCHING ON
4.10 C
4.11 F
4.12 P
4.13 O
5 COMMISSIONING, START-UP, OPERATION AND
SHUTDOWN...........................................................18
5.1 G
UARDING
5.2 P
RIMING AND AUXILIARY SUPPLIES
5.3 S
TARTING THE PUMP
5.4 R
UNNING THE PUMP
5.5 S
TOPPING AND SWITCHING OFF
.........................................................4
MARKING AND APPROVALS
......................................................4
......................................................4
............................................4
............................................................5
....................................................7
........................................................7
............................................................8
.........................................................8
.............................................9
.............................................10
.......................................................11
..................................................11
......................................................11
..........................................12
...........................................................13
..................................................16
.....................................................17
................................................17
HARGE STARTER BATTERIES
INAL SHAFT ALIGNMENT CHECK
ROTECTION SYSTEMS THER CHECK
..............................................18
......................................................18
.......................................19
........................................24
...........................4
.......................6
....................6
.............................16
........................17
.....................17
..................................18
...................18
.......................25
............7
..............9
PAGE
6 MAINTENANCE...................................................25
6.1 G
ENERAL
6.2 M
AINTENANCE SCHEDULE
6.3 S
PARE PARTS
6.4 R
ECOMMENDED SPARES AND CONSUMABLE ITEMS
6.5 D
ISASSEMBLY
7 FAULTS; CAUSES AND REMEDIES ..................31
7.1 F
AULTS ON THE PUMP
7.2 E
LECTRICAL FAULTS
8 PARTS LIST AND DRAWINGS ...........................32
8.1 S
ECTIONAL DRAWINGS
8.2 S
ECTIONAL DRAWINGS PART LIST
8.3 G
ENERAL ARRANGEMENT DRAWING
9 CERTIFICATION .................................................35
10 OTHER RELEVANT DOCUMENTATION AND
MANUALS...............................................................35
10.1 S
10.2 C
10.3 A
........................................................25
................................26
..................................................29
.................................................29
.....................................31
........................................32
....................................32
.....................34
UPPLEMENTARY USER INSTRUCTIONS HANGE NOTES DDITIONAL SOURCES OF INFORMATION
............................................35
.................35
..........35
.........35
29
Page 2 of 36
®
MEN USER INSTRUCTIONS ENGLISH 71576288 – 11-09
INDEX
PAGE
Additional sources (10.3).......................................35
Alignment of shafting (see 4.2, 4.4 and 4.11)
Batteries (4.8) ........................................................17
CE marking and approvals (1.2)..............................4
Certification (9) ......................................................35
Change notes (10.2)..............................................35
Charge starter batteries (4.10) ..............................17
Commissioning, start-up, operation (5) .................18
Configurations (3.1) .................................................9
Connection (4.7) ....................................................16
Copyright (1.4).........................................................4
Coupling assembly (4.4.1).....................................12
Disassembly (6.5)..................................................29
Disclaimer (1.3)........................................................4
Dismantling (see 6.5, Disassembly)......................29
Drawings (8.1) .......................................................32
Drive shaft assembly (4.4.2)..................................13
Duty conditions (1.5)................................................4
Electrical connections (4.6) ...................................16
End of product life (2.5) ...........................................9
Faults; causes and remedies (7) ...........................31
Final checks (4.5.3) ..............................................16
Foundation (4.2) ....................................................11
Forces and moments (see 4.5.1)...........................13
General arrangement drawing (8.3) ......................35
Gland packing (6.2.2) ............................................28
Grouting (4.3).........................................................11
Guarding (5.1)........................................................18
Handling (2.2) ..........................................................7
Installation (4) ........................................................11
Lifting (2.3)...............................................................8
Local signalization table (see 5.3.2.1)...................19
Location (4.1).........................................................11
Maintenance (5.3.2.3 and 6)
Maintenance schedule (6.2) ..................................26
Nomenclature (3.2)................................................10
Nameplate and safety labels (1.7)...........................6
Operating limits (see 3.1) ........................................9
Ordering spare parts (6.3.1) ..................................29
Parts lists (8.2).......................................................34
Piping (4.5) ............................................................13
Protection systems (4.12)......................................18
Pump masses (2.2.2) ..............................................8
Receipt and unpacking (2.1)....................................7
Recommended spares (6.4) ..................................29
Recycling (2.5).........................................................8
Replacement parts (see 6.3 and 6.4) ....................29
Running the pump (5.4).........................................24
Safety action (1.6.3).................................................5
Safety markings (1.6.1)............................................5
Safety, protection systems (see 1.6 and 4.12)
Sectional drawings (8.1) ........................................32
Sound level (see 1.9, Noise level)...........................7
Sources, additional information (10.3)...................35
Spare parts (6.3 and 6.4).......................................29
Specific machine performance (1.8)........................6
Standard maintenance (6.2.1) ..............................28
Starting the pump (5.3)..........................................19
Starting the diesel engine (5.3.2)...........................19
Stopping and switching off (5.5) ............................25
Storage, pump (2.4).................................................8
Storage, spare parts (6.3.2)...................................29
Supplementary manuals or information sources
(10.1)......................................................................35
Switching on (4.9) ..................................................17
Thermal expansion (4.4.1.1) .................................12
Transport and storage (2) .......................................7
Trouble-shooting (see 7)........................................31
PAGE
Page 3 of 36
®
MEN USER INSTRUCTIONS ENGLISH 71576288 – 11-09
1 INTRODUCTION AND SAFETY
1.1 General
These instructions must always be kept
close to the product's operating location or directly with the product.
Flowserve’s products are designed, developed and manufactured with state-of-the-art technologies in modern facilities. The unit is produced with great care and commitment to continuous quality control, utilizing sophisticated quality techniques, and safety requirements.
Flowserve is committed to continuous quality improvement and being at service for any further information about the product in its installation and operation or about its support products, repair and diagnostic services.
These instructions are intended to facilitate familiarization with the product and its permitted use. Operating the product in compliance with these instructions is important to help ensure reliability in service and avoid risks. The instructions may not take into account local regulations; ensure such regulations are observed by all, including those installing the product. Always coordinate repair activity with operations personnel, and follow all plant safety requirements and applicable safety and health laws and regulations.
These instructions must be read prior to
installing, operating, using and maintaining the equipment in any region worldwide. The equipment must not be put into service until all the conditions relating to safety noted in the instructions, have been met. Failure to follow and apply the present user instructions is considered to be misuse. Personal injury, product damage, delay or failure caused by misuse are not covered by the Flowserve warranty.
1.2 CE marking and approvals
It is a legal requirement that machinery and equipment put into service within certain regions of the world shall conform with the applicable CE Marking Directives covering Machinery and, where applicable, Low Voltage Equipment, Electromagnetic Compatibility (EMC), Pressure Equipment Directive (PED) and Equipment for Potentially Explosive Atmospheres (ATEX).
Where applicable the Directives and any additional Approvals cover important safety aspects relating to machinery and equipment and the satisfactory provision of technical documents and safety instructions. Where applicable this document incorporates information relevant to these Directives and Approvals. To confirm the Approvals applying and if the product is CE marked, check the serial number plate markings and the Certification. (See section 9, Certification.)
1.3 Disclaimer
Information in these User Instructions is believed to be reliable. In spite of all the efforts of Flowserve Pump Division to provide sound and all necessary information the content of this manual may appear insufficient and is not guaranteed by Flowserve as to its completeness or accuracy.
Flowserve manufactures products to exacting International Quality Management System Standards as certified and audited by external Quality Assurance organizations. Genuine parts and accessories have been designed, tested and incorporated into the products to help ensure their continued product quality and performance in use. As Flowserve cannot test parts and accessories sourced from other vendors the incorrect incorporation of such parts and accessories may adversely affect the performance and safety features of the products. The failure to properly select, install or use authorized Flowserve parts and accessories is considered to be misuse. Damage or failure caused by misuse is not covered by the Flowserve warranty. In addition, any modification of Flowserve products or removal of original components may impair the safety of these products in their use.
1.4 Copyright
All rights reserved. No part of these instructions may be reproduced, stored in a retrieval system or transmitted in any form or by any means without prior permission of Flowserve.
1.5 Duty conditions
This product has been selected to meet the specifications of your purchaser order. The acknowledgement of these conditions has been sent separately to the Purchaser. A copy should be kept with these instructions.
The product must not be operated beyond
the parameters specified for the application. If there is any doubt as to the suitability of the product for the application intended, contact Flowserve for advice, quoting the serial number.
If the conditions of service on your purchase order are going to be changed (for example liquid pumped temperature or duty) it is requested that the user seeks the written agreement of Flowserve before start up.
Page 4 of 36
®
MEN USER INSTRUCTIONS ENGLISH 71576288 – 11-09
1.6 Safety
1.6.1 Summary of safety markings
These User Instructions contain specific safety markings where non-observance of an instruction would cause hazards. The specific safety markings are:
This symbol indicates electrical safety instructions where non-compliance will involve a high risk to personal safety or the loss of life.
This symbol indicates safety instructions where non-compliance would affect personal safety and could result in loss of life.
This symbol indicates “hazardous substances and toxic fluid” safety instructions where non­compliance would affect personal safety and could result in loss of life.
This symbol indicates safety instructions where non-compliance will involve some risk to safe operation and personal safety and would damage the equipment or property.
This sign is not a safety symbol but indicates
an important instruction in the assembly process.
1.6.2 Personnel qualification and training
All personnel involved in the operation, installation, inspection and maintenance of the unit must be qualified to carry out the work involved. If the personnel in question do not already possess the necessary knowledge and skill, appropriate training and instruction must be provided. If required the operator may commission the manufacturer/supplier to provide applicable training.
Always coordinate repair activity with operations and health and safety personnel, and follow all plant safety requirements and applicable safety and health laws and regulations.
1.6.3 Safety action
This is a summary of conditions and actions to prevent injury to personnel and damage to the environment and to equipment. For products used in potentially explosive atmospheres section 1.6.4 also applies.
NEVER DO MAINTENANCE WORK
WHEN THE UNIT IS CONNECTED TO POWER
GUARDS MUST NOT BE REMOVED WHILE
THE PUMP IS OPERATIONAL
DRAIN THE PUMP AND ISOLATE PIPEWORK BEFORE DISMANTLING THE PUMP The appropriate safety precautions should be taken where the pumped liquids are hazardous.
FLUORO-ELASTOMERS (When fitted.) When a pump has experienced temperatures over 250 ºC (482 ºF), partial decomposition of fluoro­elastomers (example: Viton) will occur. In this condition these are extremely dangerous and skin contact must be avoided.
HANDLING COMPONENTS Many precision parts have sharp corners and the wearing of appropriate safety gloves and equipment is required when handling these components. To lift heavy pieces above 25 kg (55 lb) use a crane appropriate for the mass and in accordance with current local regulations.
THERMAL SHOCK Rapid changes in the temperature of the liquid within the pump can cause thermal shock, which can result in damage or breakage of components and should be avoided.
NEVER APPLY HEAT TO REMOVE IMPELLER Trapped lubricant or vapor could cause an explosion.
HOT (and cold) PARTS If hot or freezing components or auxiliary heating supplies can present a danger to operators and persons entering the immediate area action must be taken to avoid accidental contact. If complete protection is not possible, the machine access must be limited to maintenance staff only, with clear visual warnings and indicators to those entering the immediate area. Note: bearing housings must not be insulated and drive motors and bearings may be hot.
If the temperature is greater than 68 °C (155 °F) or below -5 °C (23 °F) in a restricted zone, or exceeds local regulations, action as above shall be taken.
HAZARDOUS LIQUIDS When the pump is handling hazardous liquids care must be taken to avoid exposure to the liquid by appropriate sitting of the pump, limiting personnel access and by operator training. If the liquid is flammable and/or explosive, strict safety procedures must be applied.
Gland packing must not be used when pumping hazardous liquids.
Page 5 of 36
®
MEN USER INSTRUCTIONS ENGLISH 71576288 – 11-09
PREVENT EXCESSIVE EXTERNAL PIPE LOAD Do not use pump as a support for piping. Do not mount expansion joints, unless allowed by Flowserve in writing, so that their force, due to internal pressure, acts on the pump flange.
ENSURE CORRECT LUBRICATION (See section 5, Commissioning, startup, operation and shutdown.)
START THE PUMP WITH OUTLET VALVE PART OPENED (Unless otherwise instructed at a specific point in the User Instructions.)
This is recommended to minimize the risk of overloading and damaging the pump motor at full or zero flow. Pumps may be started with the valve further open only on installations where this situation cannot occur. Pump outlet valve shall may need to be adjusted to comply with the duty following the run-up process. (See section 5, Commissioning start-up, operation and shutdown.)
1.7 Nameplate and safety labels
1.7.1 Nameplate
For details of nameplate, see the Declaration of Conformity, or separate documentation included
with these User Instructions.
1.7.2 Safety labels
NEVER RUN THE PUMP DRY
INLET VALVES TO BE FULLY OPEN WHEN PUMP IS RUNNING Running the pump at zero flow or below the recommended minimum flow continuously will cause damage to the seal.
DO NOT RUN THE PUMP AT ABNORMALLY HIGH OR LOW FLOW RATES Operating at a flow rate higher than normal or at a flow rate with no backpressure on the pump may overload the motor and cause cavitations. Low flow rates may cause a reduction in pump/bearing life, overheating of the pump, instability and cavitations/vibration.
1.6.4 Preventing the build up of explosive mixtures
ENSURE PUMP IS PROPERLY FILLED AND VENTED AND DOES NOT RUN DRY.
Ensure pump and relevant suction and discharge pipeline system is totally filled with liquid at all times during the pump operation, so that an explosive atmosphere is prevented. In addition it is essential to make sure that seal chambers, auxiliary shaft seal systems and any heating and cooling systems are properly filled. If the operation of the system cannot avoid this condition the fitting of an appropriate dry run protection device is recommended (eg liquid detection or power monitor).
Oil lubricated units only:
1.8 Specific machine performance
For performance parameters see section 1.5, Duty conditions. When the contract requirement specifies
these to be incorporated into User Instructions these are included here. Where performance data has been supplied separately to the purchaser these should be obtained and retained with these User Instructions if required.
Page 6 of 36
®
MEN USER INSTRUCTIONS ENGLISH 71576288 – 11-09
1.9 Noise level
Attention must be given to the exposure of personnel to the noise, and local legislation will define when guidance to personnel on noise limitation is required, and when noise exposure reduction is mandatory. This is typically 80 to 85 dBA.
The usual approach is to control the exposure time to the noise or to enclose the machine to reduce emitted sound. You may have already specified a limiting noise level when the equipment was ordered, however if no noise requirements were defined, then attention is drawn to the following table to give an indication of equipment noise level so that you can take the appropriate action in your plant.
Pump noise level is dependent on a number of operational factors, flow rate, pipework design and acoustic characteristics of the building, and so the values given are subject to a 3 dBA tolerance and cannot be guaranteed.
Similarly the motor noise assumed in the “pump and motor” noise is that typically expected from standard and high efficiency motors when on load directly driving the pump. Note that a motor driven by an inverter may show an increased noise at some speeds. If a pump unit only has been purchased for fitting with your own driver then the “pump only” noise levels in the table should be combined with the level for the driver obtained from the supplier. Consult Flowserve or a noise specialist if assistance is required in combining the values.
It is recommended that where exposure approaches the prescribed limit, then site noise measurements should be made. The values are in sound pressure level LpA at 1 m (3.3 ft) from the machine, for “free field conditions over a reflecting plane”.
For estimating sound power level LWA (re 1 pW) then add 17 dBA to the sound pressure value.
In areas where the staff has to intervene, remember that when the level of the sound pressure is:
Below 70 dBA: it is not necessary to take special
precautions.
Above 70 dBA: people working continuously in
the machine room must be supplied with protective devices against noise.
Below 85 dBA: no particular measures need to
be taken for casual visitors staying in the room during a limited period.
Above 85 dBA: the room must be considered as a dangerous area because of the noise and a warning sign must be fixed at each entry warning the people coming into the room, even for a short period, that they must wear hearing protection.
Above 105 dBA: special hearing protection adapted to this noise level and to the spectral noise components must be installed and a warning sign to this effect erected at each entry. The staff in the room must wear ear protection.
Make sure that the noise, which travels through the walls and windows, does not generate too high noise levels in the machine room's surroundings. In areas where the staff has to intervene, remember that when the level of the sound pressure is:
2 TRANSPORT AND STORAGE
2.1 Consignment receipt and unpacking
Immediately after receipt of the equipment it must be checked against the delivery and shipping documents for its completeness and that there has been no damage in transportation.
Note all reserves on the signed shipping note which is given back to the hauler. Later, claims cannot be accepted.
Check any crate, boxes and wrappings for any accessories or spare parts that may be packed separately with the equipment or attached to sidewalls of the box or equipment.
Each product has a unique serial number. Check that this number corresponds with that advised and always quotes this number in correspondence as well as when ordering spare parts or further accessories.
2.2 Handling
2.2.1 General instructions concerning handling
Boxes, crates, pallets or cartons may be unloaded using forklift vehicles or slings dependent on their size and construction.
To lift heavy pieces above 25 kg (55 lb), use a winch adapted to the mass and in accordance with the current local regulations.
To lift machines or pieces with one or several suspension rings, only use hooks and chains in compliance with the local regulations concerning safety. Never put cables, chains or ropes directly on or in the suspension rings. Cables, chains or lifting ropes must never present excessive bending.
Page 7 of 36
®
MEN USER INSTRUCTIONS ENGLISH 71576288 – 11-09
Never bend the lifting hooks, suspension rings, chains, etc., which should only be made to endure stresses within, calculated limits. Remember that the capacity of a lifting device decreases when the direction of the lifting force direction makes an angle with the device axis.
To increase the safety and the efficiency of the lifting device, all the lifting elements must be as perpendicular as possible. If necessary a lifting beam can be placed between the winch and the load.
When heavy pieces are lifted up, never stay or work under the load or in the area, which could be in the path of the load if it were to swing or fall away. Never leave a load hanging from a winch. The acceleration or the slowing-down of lifting equipment must stay in the safety limits for the staff.
A winch must be positioned in such a way that the load will be raised perpendicularly. Where possible necessary precautions must be taken to avoid the swing of the load, using for example two winches making approximately the same angle, below 30°, with the vertical.
2.2.2 Pump masses
The masses of the pumps bare end of shaft are shown on the nameplate.
All motors (for masses see the motor description plate) must be handled with a winch.
Motor pump unit
Bareshaft pump
For masses above 25 kg (55 lb), manual
handling is forbidden.
2.3 Lifting
2.3.1 Slinging of motor pumps units
Use handling means in accordance with motor pump unit mass mentioned on the CE plate. For the masses of the pumps bare end of shaft see table §
2.2.2 and nameplate.
To avoid distortion, the pump unit
should be lifted as shown.
Components weighing less than 25 kg (55 lb) can be handled manually following the correct actions and using the correct posture.
When handling always wear gloves, safety boots and an industrial safety helmet.
For masses above 25 kg (55 lb), manual handling is forbidden.
2.4 Storage
Store the pump in a clean, dry location away from vibration. Leave piping connection covers in place to keep dirt and other foreign material out of pump casing. Turn pump at intervals to prevent brinelling of the bearings and the seal faces, if fitted, from sticking.
Do not store pumps starting on the fan guard. The pump may be stored as above for up to 6
months. Consult Flowserve for preservative actions when a longer storage period is needed.
Page 8 of 36
®
MEN USER INSTRUCTIONS ENGLISH 71576288 – 11-09
2.5 Recycling and end of product life
At the end of the service life of the product or its parts, the relevant materials and parts should be recycled or disposed of using an environmentally acceptable method and local regulations. If the product contains substances which are harmful to the environment, these should be removed and disposed of in accordance with current regulations. This also includes the liquids and or gases in the "seal system" or other utilities.
Make sure that hazardous substances or toxic fluid are disposed of safely and that the correct personal protective equipment is used. The safety specifications must be in accordance with the current regulations at all times.
3 PUMP DESCRIPTION
Refer to the standard instructions if the pump used is different to that indicated below. In all cases the liquid temperature is limited to 25 °C.
3.1 Configurations
This centrifugal pump unit is designed for the pumping of water [taken from a clean, non­aggressive, particle-free water supply].
The MEN pump or MEN-TI or ME-TI or MHP is a single stage centrifugal pump with an axial inlet and a vertical outlet. The dimensions of the volute pump casing of the suction and discharge diameters as well as the settlement feet correspond to standards: DIN 24225 and NF EN 733 (excepted ME-TI and MHP).
* Maximum working pressure at discharge:
- MEN, MEN-T: 16 bars
- ME-TI 200-400, ME-TI 250-400, ME-TI 200-500, ME-TI 250-500 Cast iron GL :12 bars
- ME-TI 200-400 and ME-TI 250-400 Cast iron GS :12 bars
- ME-TI 200-500, ME-TI 250-500 Cast iron GS :15 bars
- MHP : 16 bars * Maximum working pressure at suction : 10 bars * Maximum pumped fluid temperature : 90 °C * Maximum solid suspension : 50 g/m3 * Density : 1 * Viscosity : 1 mm²/s
The nominal speed is shown on the
pump nameplate.
The pump must be stored in a non-explosive, ventilated location, sheltered from bad weather, dust and vibrations.
The reliability of the delivered machine can only be ensured if it is used and serviced according to the conditions given in this manual. The maximum values specified in this manual must never be exceeded.
Page 9 of 36
®
Type kg Refer.
Q
Manuf. N
H m
t
emp. °C
Satndard
Type
Engine
Type
Q
m3/h
H m
%
P
KW
MEN USER INSTRUCTIONS ENGLISH 71576288 – 11-09
3.2 Nomenclature
Characteristics shown on the nameplate fixed on the pump are as shown below: Each pump is supplied with the following nameplate:
Pump
m3/h
Max/min
Bearing rad/thrust
Year + Manuf. N
min-1 Max pr.
bar
Unit
Year +
Power Nom.
Power Max.
Pump Type
100%
KW for
KW for
min-1
min-1
130%
Each pump unit is supplied with the following nameplate:
Mass of the set:
Eff.
Page 10 of 36
®
NF E 27 811
MEN USER INSTRUCTIONS ENGLISH 71576288 – 11-09
4 INSTALLATION
4.1 Location
The pump should be located to allow room for access, ventilation, maintenance and inspection with ample headroom for lifting and should be as close as practicable to the supply of liquid to be pumped, and to the venting system.
Disconnect the switching enclosure support from the pump support by removing the fastening bolts. The switching enclosure support must be off-set with respect to the pump motor base.
4.2 Foundation
There are many methods of installing pump units to their foundations. The correct method depends on the size of the pump unit, its location and noise vibration limitations. Non-compliance with the provision of correct foundation and installation may lead to failure of the pump and, as such, would be outside the terms of the warranty. The base plate should be mounted onto a firm foundation, either an appropriate thickness of quality concrete or sturdy steel framework. It should NOT be distorted or pulled down onto the surface of the foundation, but should be supported to maintain the original alignment.
Anchor bolts must be in accordance with the foot bolt holes. Use anchor bolts of accepted standards and sufficient to ensure safe fitting in the foundation. Particularly, this applies to individual plates where the anchor bolts have to withstand the driving torque.
Provide sufficient space in the foundation to accommodate the anchor bolts. If necessary, provide concrete risers.
4.2.1 Setting the base plate for anchoring
- Clean the foundation surface thoroughly.
- Put shims on the foundation surface (approx 20-25 mm thick), one on each side of the bolt hole (as an alternative, leveling screws can be used).
- Lay the base plate and level in both directions with extra shims. The base plate should be level to within
0.5 mm per 1 m.
If anchor bolts have been pre-cast in the foundation slightly tighten the anchor bolts. Otherwise let them hang in the foundation holes.
4.3 Grouting
4.3.1 Base plate grouting
Prepare the site for grouting. Before grouting clean the foundation surface thoroughly and provide external barriers as shown:
barriers
Prepare grouting product (concrete, resin) in accordance with manufacturers' instructions.
Page 11 of 36
Loading...
+ 25 hidden pages