60-480 Watts

ADN Series

 

Total Power:

60 - 480 Watts

 

Input Voltage:

115/230 VAC

 

# of Outputs:

One

 

 

 

 

 

 

Electrical Specs

Special Features

• Power Factor Correction

• Auto Select 115/230 VAC, 50/60 Hz Input

• All Single Phase models meet SEMI F47 Sag Immunity

• Class 1, Div 2 Hazardous Locations

• DC OK Signal

• Adjusable Voltage

• Industrial grade design (no derating to 60°C)

• User-friendly front panel

• Single and three phase inputs available

• Highly efficent >90% switching technology

• High MTBF and reliability

• Peak current capability 2x rated current for 2 seconds

• Three year warranty

• NEC Class 2 on models <100W

Environmental

Storage/Shipment

-25°C to +85°C

Operating (convection)

-10° C to +60° C (derate

 

to 50% at +70° C)

Humidity

<90% RH noncondensing per

 

IEC 68-2-2, 68-2-3

 

IP20 (EN60529), protection

 

from moisture & condensation

Input

Nominal voltage

115/230 VAC auto select

Power factor (PFC)

EN61000-3-2

AC Input range

85-123 / 176-264VAC

DC Input range

210-375VDC

Frequency

47-63 Hz, 500 Hz

Output

Nominal voltage

24V (22.5-28.5VDC Adj.)

Holdup time

> 20ms at full load (25°C)

Tolerance

< ±2 % overall

 

(combination line/load/time/temp)

Tolerance

< ±2 % overall

Line regulation

<0.5%

Load regulation

<0.5%

Time & temp. drift

<1%

Initial voltage setting

24.5V ± 1%

Ripple

< 50mVpp

Power back immunity

> 35V

Parallel Operation

 

ADN20-24-1PM

Switch selectable

All others

Jumper selectable via front panel

Over voltage protection

< 33VDC

 

EMC

Safety

 

 

 

 

 

 

 

Emissions

EN 61000-6-3, Class B EN55011, EN55022 Radiated

 

 

 

Conducted including Annex A

 

 

 

Immunity

EN 61000-6-2, EN61000-4-2 Level 4, EN61000-4-3

 

 

Level 3, EN61000-4-6 Level 3, EN61000-4-4 Level 4

 

 

 

 

input and level 3 output. EN61000-4-5 Isolation class

 

 

4, EN61000-4-11, Transient protection according to

 

 

 

 

VDE 0160/W2 over entire load range.

 

Approvals

EN60950, UL508 Listed, cULus, UL 60950, cURus, CE

 

 

 

(LVD 73/23 & 93/68/EEC), (EMC 89/336 & 93/68/EEC).

 

 

 

 

EN61000-3-2, EN60079-15 (Class 1, Division 2

 

 

hazardous location, Groups A, B, C, D w/ T3 temp

 

 

 

 

class up to 60°C Ambient.) SEMIF47 Sag Immunity.

 

 

For models <100W, UL60950 testing to include

 

 

 

 

approval as NEC Class 2 power supply acc. To NFPA 70

 

 

art. 725-41 (a)(2).

 

 

 

Protection

Class 1 (IEC536), degree of protection

 

 

 

SELV rated per EN60950

190

Technical Support: (888) 41ASTEC or (407) 241-2752

 

 

 

Americas: (760) 930-4600

Europe (UK) 44 (1384) 842-211

Asia (HK) 852-2437-9662

 

rev 09.08.05