Emerson 850 User Manual

Page 1
Installation Instructions for
Heating & Cooling
Digital Model 850
5/1/1 Day Programmable
Thermostat
CONTENTS
Preparations.................................................. 1
Thermostat Details ........................................ 1
Mounting and Wiring ..................................... 2
Check Thermostat Operation........................ 4
Specifications ................................................ 7
Troubleshooting ............................................ 7
Y OUR THERMOST AT REPLACES
Description 850
Standard Heat & Cooling Systems – 4 or 5 wires Yes Standard Heat Only Systems Yes Millivolt Heat Only Systems – Floor or Wall Furnaces Yes Standard Central Air Conditioning Yes Gas or Oil Heat Yes Electric Furnace Yes Hydronic (Hot Water) Zone Heat – 2 Wires Yes Hydronic (Hot Water) Zone Heat – 3 Wires No Heat Pump (No Aux or Emergency Heat) Yes Heat Pump (with Aux or Emergency Heat) No Baseboard Electric Heating or Line Voltage (120 or 240 volt) No
THERMOSTAT DETAILS
2
Screw anchors
PREPARATIONS
1
Assemble tools required as shown below.
FLAT BLADE SCREWDRIVER
HAND OR POWER DRILL WITH 3/16 INCH DRILL BIT, IF NEEDED
SPIRIT LEVEL OR PLUMB BOB AND LINE (OPTIONAL)
Failure to follow and read all instructions carefully before installing or operating this control could cause personal injury and/or property damage.
REMOVING OLD THERMOSTAT
3
CAUTION
!
To prevent electrical shock and/or equipment damage, disconnect electrical power to the system at the main fuse or circuit breaker until installation is complete.
WIRE CUTTER/STRIPPER
Mounting
holes
Electric/Gas
switch
Figure 1. Thermostat base
Mounting
holes
Before removing wires from old thermostat’s switching subbase,
label each wire with the terminal designation it was removed from.
1. Remove Old Thermostat: A standard heat/cool thermostat
consists of three basic parts: a. The cover, which may be either a snap-on or hinge type. b. The base, which is removed by loosening all captive screws. c. The switching subbase, which is removed by unscrewing
the mounting screws that hold it on the wall or adaptor plate.
2. Shut off electricity at the main fuse box until installation is complete. Ensure that electrical power is disconnected.
3. Remove the front cover of the old thermostat. With wires still attached, remove wall plate from the wall. If the old thermostat
has a wall mounting plate, remove the thermostat and the wall mounting plate as an assembly.
4. Identify each wire attached to the old thermostat using the labels enclosed with the new thermostat.
5. Disconnect the wires from the old thermostat one at a time. DO NOT LET WIRES FALL BACK INTO THE WALL.
6. Install new thermostat using the following procedures.
White-Rodgers is a division
of Emerson Electric Co.
www.white-rodgers.com
PART NO. 37-6295B
Replaces 37-6295A
0514
Page 2
REMOVING OLD THERMOSTAT
TERMINAL CROSS REFERENCE CHART
New Thermostat
Terminal Designation
Other Manufacturers’ Terminal Designation
RH RC
G
W
Y
4 R
G
W
Y
RH
R G
W
Y
M
V
F H C
R5
-
G
4
Y6
R
-
G
W
Y
**
* These are four-wire, single-transformer systems. Factory installed jumper wire between the RH and RC terminals must remain in place.
3
CONTINUED FROM FIRST PAGE
ATTENTION! This product does not contain mercury. How­ever, this product may replace a unit which contains mercury.
Do not open mercury cells. If a cell becomes damaged, do not touch any spilled mercury. Wearing non-absorbent gloves, take up the spilled mercury and place into a container which can be sealed. If a cell becomes damaged, the unit should be discarded.
Mercury must not be discarded in household trash. When the unit this product is replacing is to be discarded, place in a suitable container and return to White-Rodgers for proper disposal.
MOUNTING AND WIRING
4
WARNING
!
Do not use on circuits exceeding specified voltage. Higher voltage will damage control and could cause shock or fire hazard.
Do not short out terminals on gas valve or primary control to test. Short or incorrect wiring will damage thermostat and could cause personal injury and/or property damage.
Thermostat installation and all components of the sys­tem shall conform to Class II circuits per the NEC code.
Electric Heat or Single Stage
Heat Pump Systems
This thermostat is configured from the factory to operate a heat/ cool, fossil fuel (gas, oil, etc.), forced air system. It is configured correctly for any system that DOES NOT require the thermostat to energize the fan on a call for heat. If your system is an electric or heat-pump system that REQUIRES the thermostat to turn on the fan on a call for heat, locate the GAS/ELECTRIC switch (see fig. 1) and switch it to the ELECTRIC position. This will allow the thermostat to energize the fan immediately on a call for heat. If you are unsure if the heating/cooling system requires the thermostat to control the fan, contact a qualified heating and air conditioning service person.
Hydronic (Hot Water or Steam)
Heating Systems
This thermostat is set to operate properly with a forced-air heating system. If you have a hydronic heating system (a system that heats with hot water or steam), you must set the thermostat to operate properly with your system. Change the second option in the configuration menu to SL (see CONFIGURATION MENU, page 5).
CAUTION
!
Take care when securing and routing wires so they do not short to adjacent terminals or rear of thermostat. Personal injury and/or property damage may occur.
Attach Thermostat Base to Wall
1. Remove the packing material from the thermostat. Gently pull the cover straight off the base. Forcing or prying on the thermostat will cause damage to the unit. If necessary, move the electric heat switch (see ELECTRIC HEAT SYSTEMS, above).
2. Connect wires beneath terminal screws on base using appro­priate wiring schematic (see figs. 2 through 7).
3. Place base over hole in wall and mark mounting hole locations on wall using base as a template.
4. Move base out of the way. Drill mounting holes.
5. Fasten base loosely to wall, as shown in fig. 1, using two mounting screws. Place a level against bottom of base, adjust until level, and then tighten screws. (Leveling is for appear­ance only and will not affect thermostat operation.) If you are using existing mounting holes, or if holes drilled are too large and do not allow you to tighten base snugly, use plastic screw anchors to secure base.
6. Push excess wire into wall and plug hole with a fire-resistant material (such as fiberglass insulation) to prevent drafts from affecting thermostat operation.
Battery Location
This thermostat requires 2 “AA” alkaline batteries to operate. If the word LO BATTERY is displayed, the batteries are low and should be replaced with fresh “AA” Energizer® alkaline batteries. To replace the batteries, install the batteries along the top of the base (see fig. 1). The batteries must be installed with the positive(+) ends to the right.
www.white-rodgers.com
Page 3
MOUNTING AND WIRING
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Figure 5. Typical wiring diagram for
heat/cool, 5-wire, two-transformer systems
HEATING
TRANSFORMER
Heating
System
Fan
Relay
Cooling System
RC
24 VAC
120 VAC
Hot
Neutral
COOLING TRANSFORMER
OBC
‡
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Figure 6. Typical wiring diagram for heat pump
with reversing valve energized in COOL
TRANSFORMER
Reversing
Valve*
RCOBC
‡
JUMPER
WIRE
Compressor
Contactor
JUMPER
WIRE
* Reversing valve is energized when the system switch is in the COOL position
Fan
Relay
RH
Y
24 VAC
120 VAC
Hot
Neutral
THERMOSTAT
SYSTEM
G W
Figure 7. Typical wiring diagram for heat pump
with reversing valve energized in HEAT
TRANSFORMER
Reversing
Valve*
RCO
B
C
‡
JUMPER
WIRE
Compressor
Contactor
JUMPER
WIRE
* Reversing valve is energized when the system switch is in the HEAT position
Fan
Relay
4
CONTINUED FROM SECOND PAGE
‡
NOTE
For 2-wire Heat only, attach to RH and W
heat only, 3-wire, single transformer systems
‡
C
cool only, 3-wire, single transformer systems
YC
OB
G W
Fan
Relay
Heating System
Figure 2. Typical wiring diagram for
Y
Cooling System
G W
Fan
Relay
Figure 3. Typical wiring diagram for
JUMPER
RC
JUMPER
RCOB
WIRE
WIRE
24 VAC
THERMOSTAT
RH
SYSTEM
24 VAC
TRANSFORMER
THERMOSTAT
RH
SYSTEM
TRANSFORMER
Hot
120 VAC
Neutral
Hot
120 VAC
Neutral
RED jumper wire (provided with thermostat) must be connected between thermostat RH and RC terminals for proper thermostat operation with this system.
Y
OC‡B
Cooling System
G W
Fan
Relay
Heating System
Figure 4. Typical wiring diagram for
heat/cool, 4-wire, single transformer systems
NOTE
‡
The 24 Volt neutral connection to terminal C on the thermostat is not required if the batteries are replaced once a year with fresh “AA” Energizer® alkaline batteries.
JUMPER
WIRE
RH
RC
24 VAC
THERMOSTAT
SYSTEM
Hot 120 VAC
Neutral
TRANSFORMER
www.white-rodgers.com
Page 4
CHECK THERMOST A T OPERA TION
5
If at any time during testing your system does not operate properly, contact a qualified service person.
Turn on power to the system.
Fan Operation
If your system does not have a G terminal connection, skip to Heating System.
1. Move FAN switch to ON position. The blower should begin to operate.
2. Move FAN switch to AUTO position. The blower should stop immediately.
Heating System
1. Move SYSTEM switch to HEAT position. If the heating system has a standing pilot, be sure to light it.
2. Press ture. The heating system should begin to operate.
3. Press ture. The heating system should stop operating.
to adjust thermostat setting above room tempera-
to adjust temperature setting below room tempera-
Cooling System
CAUTION
!
To prevent compressor and/or property damage, if the outdoor temperature is below 50°F, DO NOT operate the cooling system.
1. Move SYSTEM switch to COOL position.
2. Press ture. The blower should come on immediately on high speed,
followed by cold air circulation
3. Press ture. The cooling system should stop operating.
Before you begin programming your thermostat, you should be familiar with its features and with the display and the location and operation of the thermostat buttons. Your thermostat consists of two parts: the thermostat cover and the base. To remove the cover, pull it straight out from the base. To replace the cover, line up the cover with the base and press until the cover snaps onto the base.
to adjust thermostat setting below room tempera-
to adjust temperature setting above room tempera-
The Thermostat Buttons and Switches
1
Raises temperature setting.
Lowers temperature setting.
2
TIME button.
3
PRGM (program) button.
4 5
RUN (run program) button.
6
HOLD temperature button.
7
FAN switch (ON, AUTO). SYSTEM switch (COOL, OFF, HEAT).
8
The Display
9
Indicates day of the week. Flame icon ( ) is displayed when the SYSTEM switch is in
10
the HEAT position. Snowflake icon ( flashing) when the SYSTEM switch is in the COOL position. Snowflake is displayed (flashing) if the thermostat is in lockout mode to prevent the compressor from cycling too quickly.
11
Displays “BATT” when the 2 “AA” batteries are low and should be replaced. Only “BATT” with “LO” in the minutes field are displayed when batteries are low with no system power.
Alternately displays current time and temperature. Displays
12
“LO” in the minutes field when batteries are low.
13
The word “HOLD” is displayed when the thermostat is in the HOLD mode. “HOLD” is displayed flashing when the ther­mostat is in a temporary HOLD Mode.
14
Displays currently programmed set temperature (this is blank when SYSTEM switch is in the OFF position).
15
Displays FLTR when the system has run for the programmed filter time period as a reminder to change or clean your air filter.
)is displayed (non-
CONFIGURATION MENU
The configuration menu allows you to set certain thermostat operating characteristics to your system or personal require­ments.
Press RUN to make sure the thermostat is in the run program mode, then press PRGM and RUN at the same time to enter the configuration menu. The display will show the first item in the configuration menu.
The configuration menu table summarizes the configuration options. An explanation of each option follows.
Press HOLD to change to the next menu item or press TIME to go backwards to the previous item in the menu. To exit the menu and return to the program operation, press RUN. If no keys are pressed within fifteen minutes, the thermostat will revert to normal operation.
www.white-rodgers.com
Page 5
CHECK THERMOST A T OPERA TION
5
CONTINUED FROM FOURTH PAGE
1) Select Temporary Hold Time - The thermostat can hold any temperature you set it to for the amount of time you select on this option. Your choices are 0:00 to 8:00 hours in 15 minute increments. 0:00 disables the function
Example:
1. You have selected 3:00 hours for the Temporary Hold time period.
2. With the thermostat set to HEAT or COOL, press HOLD for approximately five seconds until “HOLD” time (3:00 indicating 3 hours) appears as a setting reminder.
3. After releasing the button, “HOLD” on the display will blink.
4. Use The thermostat will maintain this temperature setting for 3 hours with “HOLD” blinking to remind you it is in Tempo­rary Hold. After 3 hours the thermostat will go back to the program temperature and “HOLD” will no longer blink or display.
2) Select FA or SL (Fast or Slow) Heating Cycle Rate - The FA setting is frequently used for gas, oil or electric heat. The SL setting produces a longer heating cycle which is normally for hot water or steam (hydronic) systems. Both settings produce very accurate temperature control and can be set to your personal preference. FA cycles the system just under 1°F and the SL setting cycles at approximately 1.5°F.
3) Select backlit display - The display backlight improves display contrast in low lighting conditions. Selecting backlight ON will keep the light on for a short period of time after any key is pressed. Selecting OFF will keep the light off.
4) Select Energy Management Recovery OFF or ON - Energy Management Recovery (EMR) causes the thermostat to start heating or cooling early to make the building temperature reach the program setpoint at the time you specify. Heating will start 5 minutes early for every 1° of temperature required to reach setpoint.
Example: You select EMR and have your heating pro­grammed to 65° at night and 70° at 7 AM. If the building temperature is 65° the difference between 65° and 70° is 5°. Allowing 5 minutes per degree the thermostat setpoint will change to 70° at 6:35 AM. Cooling allows more time per degree because it takes longer to reach temperature.
or to set the temperature to your preference.
5) Select filter replacement run time - The thermostat will display “FLTR” after a set time of operation. This is a reminder to change or clean your air filter. This time can be set from 0 to 1950 hours in 50 hour increments. A selection of 000 will cancel this feature. When “FLTR” is displayed, you can clear it by pressing HOLD and RUN at the same time. This resets the timer and starts counting the hours until the next filter change. Changing the time in the menu also resets the timer.
6) Select Compressor Lockout LOC OFF or ON - Selecting LOC ON will cause the thermostat to wait 5 minutes before turning on the compressor if the heating and cooling system loses power. It will also wait 5 minutes minimum between cooling cycles. This is intended to help protect the compres­sor from short cycling. Some newer compressors already have a time delay built in and do not require this feature. Your compressor manufacturer can tell you if the feature is already present in their system. When the compressor time delay occurs it will flash the (snowflake icon) for about five minutes then turn on the compressor.
7) Select Temperature Display Adjustment 4 LO to 4 HI ­Allows you to adjust the room temperature display 4° higher or lower. Your thermostat was accurately calibrated at the factory but you have the option to change the display tem­perature to match your previous thermostat.
8) Select F° or C° Readout - Changes the display readout to Centigrade or Fahrenheit as required.
OPERATING FEATURES
Now that you are familiar with the thermostat buttons and display, read the following information to learn about the many features of the thermostat.
• SIMULTANEOUS HEATING/COOLING PROGRAM STOR­AGE — When programming, you can enter both your heating
and cooling programs at the same time. There is no need to reprogram the thermostat at the beginning of each season.
• TEMPERATURE OVERRIDE — Press display shows the temperature you want. The thermostat will override current programming and keep the room tempera­ture at the selected temperature until the next program period begins. Then the thermostat will automatically revert to the program.
or until the
Configuration Menu
Step
* Press
Press Button(s)
1 2 3 4 5 6 7 8 9
HOLD to advance to next item or TIME to move backwards to previous item
PRGM and RUN
HOLD* HOLD* HOLD* HOLD* HOLD* HOLD* HOLD*
RUN
Displayed
(Factory Default)
HOLD (0:00)
(FA)
d-L (ON)
E (ON)
Filter (000)
LOC (OFF)
0 HI (0)
(F)
Press or to select:
0 to 8 hrs (in 15 minute increments)
0 to 1950 hours (in 50 hour increments)
www.white-rodgers.com
SL OFF OFF
ON
4 LO to 4 HI
C
Comments
Select temporary Hold time Select FA or SL (Fast or Slow) heating cycle rate Select display backlight OFF or ON Select Energy Management Recovery OFF or ON Select filter replacement run time Select compressor lockout OFF or ON Select temperature display adjustment higher or lower Select temperature display to F or C Returns to normal operation
Page 6
CHECK THERMOST A T OPERA TION
5
CONTINUED FROM FIFTH PAGE
Set Current Time and Day
1. Press TIME button once. The display will show the hour only.
• HOLD TEMPERATURE — The thermostat can hold any temperature within its range for an indefinite period without reverting to the programmed temperature. Momentarily press HOLD button. HOLD will be displayed. Then choose the desired temperature by pressing
or . The thermostat will hold the room temperature at the selected setting until you press RUN button to start program operation again.
• CONFIGURATION MENU — Allows you to customize cer­tain thermostat options.
PROGRAMMING Y OUR THERMOST A T
6
This section will help you plan your thermostat’s program to meet your needs. For maximum comfort and efficiency, keep the following guidelines in mind when planning your program.
• When heating (cooling) your building, program the tempera­tures to be cooler (warmer) when the building is vacant or during periods of low activity.
• During early morning hours, the need for cooling is usually minimal.
Look at the factory preprogrammed times and temperatures shown below. If this program will suit your needs, simply press the RUN button to begin running the factory preset program. If you want to change the preprogrammed times and tempera­tures, follow these steps. Determine the time periods and temperatures for your weekday and weekend programs. You must program four periods for both the weekday and weekend program. However, you may use the same heating and cooling temperatures for consecutive time periods. You can choose start times, heating temperatures, and cooling temperatures independently for both weekday and week­end programs (for example, you may select 5:00 AM and 70° as the weekday 1st period heating start time and temperature, and also choose 7:00 AM and 76° as the weekday 1st period cooling start time and temperature). Use the table at the bottom of the page to plan your program time periods and the temperatures you want during each period. You may also want to look at the sample program table to get an idea of how the thermostat can be programmed.
Entering Your Program
Follow these steps to enter the heating and cooling programs you have selected.
EXAMPLE:
PM
2. Press and hold either or until you reach the correct hour and AM/PM designation (AM begins at midnight; PM begins at noon).
3. Press TIME once. The display window will show the minutes only.
EXAMPLE:
4. Press and hold either or until you reach the correct minutes.
5. Press TIME once. The display will show the day of the week.
6. Press or until you reach the current day of the week.
7. Press RUN once. The display will show the correct time and room temperature alternately.
Enter Heating Program
1. Move the SYSTEM switch to HEAT.
2. Press PRGM once. “MO TU WE TH FR” (indicating weekday program) will appear in the display. Also displayed are the currently programmed start time for the 1st heating period and the currently programmed temperature (flashing).
MO TU WE TH FR
EXAMPLE:
This display window shows that for the 1st weekday period, the start time is 6:00 AM, and 70° is the programmed tempera­ture (this example reflects factory preprogramming).
3. Press or to change the displayed temperature to your selected temperature for the 1st heating program period.
4. Press TIME once (the programmed time will flash). Press or until your selected time appears. The time will change in 15 minute increments. When your selected time is dis­played, press TIME again to return to the change temperature mode.
5. Press PRGM once. The currently programmed start time and setpoint temperature for the 2nd heating program period will appear.
6. Repeat steps 3 through 5 to select the start time and heating temperature for the 2nd heating program period.
AM
Heating/Cooling Schedule Plan (Factory Program)
WEEKDAY (5 DAY)
Period
1ST 6:00 AM 70˚F 6:00 AM 70˚F 6:00 AM 70˚F 2ND 8:00 AM 62˚F 8:00 AM 62˚F 8:00 AM 62˚F 3RD 5:00 PM 70˚F 5:00 PM 70˚F 5:00 PM 70˚F 4TH 10:00 PM 62˚F 10:00 PM 62˚F 10:00 PM 62˚F 1ST 6:00 AM 78˚F 6:00 AM 78˚F 6:00 AM 78˚F 2ND 8:00 AM 85˚F 8:00 AM 85˚F 8:00 AM 85˚F
COOL HEAT
3RD 5:00 PM 78˚F 5:00 PM 78˚F 5:00 PM 78˚F 4TH 10:00 PM 82˚F 10:00 PM 82˚F 10:00 PM 82˚F
Start Time Temperature
SAMPLE
SATURDAY (1 DAY)
Start Time Temperature
SUNDAY (1 DAY)
Start Time Temperature
Period
1ST 2ND 3RD 4TH 1ST 2ND
COOL HEAT
3RD 4TH
www.white-rodgers.com
Heating/Cooling Schedule Plan (Factory Program)
WEEKDAY (5 DAY)
Start Time Temperature
SAMPLE
SATURDAY (1 DAY)
Start Time Temperature
SUNDAY (1 DAY)
Start Time Temperature
Page 7
PROGRAMMING Y OUR THERMOST A T
6
CONTINUED FROM SIXTH PAGE
1. Move SYSTEM switch to COOL position.
2. Follow the procedure for entering your heating program, using your selected cooling times and temperatures.
7. Repeat steps 3 through 5 for the 3rd and 4th heating program periods. Weekday heating programs are now complete.
8. Press PRGM once. “SA” will appear in the display, along with the start time for the 1st heating period and the currently programmed temperature for Saturday.
9. Repeat steps 3 through 7 to complete Saturday heating programming.
10.Press PRGM once. “SU” will appear on the display along with start time and currently programmed temperature for the 1st heating period for Sunday. Repeat steps 3 through 7 to complete Sunday heating programming.
11. When you have completed entering your heating program, press RUN.
Enter Cooling Program
If the outside temperature is below 50°F, disconnect power to the cooling system before programming. En­ergizing the air conditioner compressor during cold weather may cause personal injury or property damage.
SPECIFICATIONS
7
ELECTRICAL DATA Electrical Rating:
0 to 30 VAC 50/60 Hz. or D.C.
0.05 to 1.2 Amps (Load per terminal)
1.5 Amps Maximum Total Load (All terminals combined)
Check Your Programming
Follow these steps to check your thermostat programming one final time before beginning thermostat operation.
1. Move SYSTEM switch to HEAT position.
2. Press PRGM to view the 1st weekday heating period time and temperature. Each time you press PRGM, the next heating period time and temperature will be displayed in sequence for weekday, then weekend program periods (you may change any time or temperature during this procedure).
3. Press RUN.
4. Move SYSTEM switch to COOL position.
5. Repeat step 2 to check cooling temperatures.
6. Press RUN to begin program operation.
YOUR THERMOSTAT IS NOW COMPLETELY PROGRAMMED AND READY TO AUTOMATICALLY PROVIDE MAXIMUM COM­FORT AND EFFICIENCY!
THERMAL DATA Setpoint Temperature Range:
45°F to 90°F (7°C to 32°C)
Operating Ambient Temperature Range:
32°F to 105°F
Operating Humidity Range:
0 to 90% RH (non-condensing)
Shipping Temperature Range:
-40°F to 150°F
TROUBLESHOOTING
8
Reset Operation
If a voltage spike or static discharge blanks out the display or causes erratic thermostat operation you can reset the thermostat by pressing thermostat to the factory defaults. If the thermostat has power,
, and TIME at the same time. This resets the
has been reset and still does not function correctly contact your heating/cooling service person or place of purchase.
Batteries
For optimum performance, we recommend replacing batteries once a year with fresh “AA” Energizer
®
alkaline batteries.
Symptom Possible Cause Corrective Action
No Heat/No Cool/No Fan 1. Blown fuse or tripped circuit breaker. Replace fuse or reset breaker. (common problems) 2. Furnace power switch to OFF. Turn switch to ON.
3. Furnace blower compartment door or Replace door panel in proper position to engage panel loose or not properly installed. safety interlock or door switch.
No Heat 1. Pilot light not lit. Re-light pilot.
2. SYSTEM Switch not set to HEAT. Set SYSTEM Switch to HEA T and raise temper ature
above room temperature.
3. Loose connection to thermostat or system. Verify thermostat and system wires are securely
attached.
4. Furnace Lock-Out Condition. Heat may also Many furnaces have safety devices that shut be intermittent. down when a lock-out condition occurs. If the
heat works intermittently contact the furnace manufacturer or local service person for assistance.
www.white-rodgers.com
Page 8
TROUBLESHOOTING
8
CONTINUED FROM SEVENTH PAGE
Symptom Possible Cause Corrective Action
No Heat (continued) 5. Heating system requires service or Diagonistic: Set SYSTEM Switch to HEAT and
thermostat requires replacement. raise the setpoint above room temperature. Within
a few seconds the thermostat should make a soft click sound. This sound usually indicates the thermostat is operating properly. If the thermostat does not click, try the reset operation listed below . If the thermostat does not click after being reset contact your heating and cooling service person or place of purchase for a replacement. If the thermostat clicks, contact the furnace manufacturer or a service person to verify the heating is operating correctly.
No Cool 1. SYSTEM Switch not set to COOL. Set SYSTEM Switch to COOL and lower temperature
below room temperature.
2. Loose connection to thermostat or system. Verify thermostat and system wires are securely
attached.
3. Cooling system requires service or Same procedure as diagnostic for No Heat thermostat requires replacement. condition except set the thermostat to COOL and
lower the setpoint below the room temperature. There may be up to a five minute delay before the thermostat clicks in Cooling.
Heat, Cool or Fan Runs Constantly. 1. FAN Switch set to Fan ON. Check each wire connection to verify they are not
2. Possible short in wiring. shorted or touching together. No bare wire should
3. Possible short in thermostat. stick out from under terminal screws. Try resetting
4. Possible short in heat/cool/fan system. the thermostat as described below. If the condition
persists the manufacturer of your system or service person can instruct you on how to test the Heat/Cool system for correct operation. If the system operates correctly, replace the thermostat.
Furnace Cycles Too Fast or Too Slow 1. The location of the thermostat and/or the Digital thermostats normally provide precise (narrow or wide temperature swing) size of the Heating System may be temperature control and may cycle faster than
influencing the cycle rate. some older mechanical models. A faster cycle
rate means the unit turns on and off more frequently but runs for a shorter time so there is no increase in energy use. If you would like to increase the cycle time, clip Jumper W-905 as mentioned in the instructions for Hydronic Heating Systems. It is not possible to shorten the cycle time. If an acceptable cycle rate is not achieved as received or by clipping W-905 contact a local service person for additional suggestions.
Cooling Cycles Too Fast or Too Slow 1. The location of the thermostat and the size The cycle rate for cooling is fixed and can not be (narrow or wide temperature swing) of the Cooling System can influence the adjusted. Contact a local service person for
cycle rate. suggestions.
Thermostat Setting and Thermostat 1. Thermostat thermometer setting requires The thermometer can be adjusted +/- 3 degrees. Thermometer Disagree adjustment. See Temperature Display Adjustment in the
Operation section.
Thermostat Does Not Follow Program 1. AM or PM set incorrectly in program. Check current clock and program settings
2. AM or PM set incorrectly on the clock. including the AM or PM designations for each
3. Voltage spike or static discharge. time period. If a voltage spike or a static discharge
occurs use the Reset Operation listed below.
Blank Display and/or Keypad 1.Voltage spike or static discharge. Replace batteries and check heat/cool system Not Responding 2. Battery change required. for proper operation. If a voltage spike occurs use
the Reset Operation listed below.
The Emerson logo is a trademark and a service mark of Emerson Electric Co.
www.white-rodgers.com
Loading...