S i n g l e m o d u l e a n d ‘1 + N’ ( e x p a n d a b l e )
UNINTERRUPTIBLE POWER SYSTEM
U s e r M a n u a l
EMERSON Network Power (India) Pvt. Ltd.
Dear Customer,
Please accept our thanks for giving us the privilege to serve you by choosing a Liebert
make ‘UPS’.
If this is your first Liebert UPS, we hope it is the beginning of a long relationship
which delivers value to your organisation. If you already own and use a Liebert, we are
doubly honoured by your decision of continuing this relationship.
It is our constant endeavour to partner you for the growth and success of your business.
This philosophy is reflected in our Mission statement “To deliver value through Air & Power Quality solutions to achieve customer delight”. Please do give us
feedback to help us realize our Mission.
Emerson Network Power (India) Private Limited
IMPORTANT
This manual contains information concerning the installation, operation and maintenance
of the Series 7400 1Phase Uninterruptible Power System (UPS) for the single module
and one plus one Systems.
All relevant parts of the manual should be read prior to commencing installation.
The UPS must be commissioned by an engineer approved by the manufacturer (or his
agent) before being put into service. Failure to observe this condition will invalidate any
implied warranty.
The Series 7400 1Phase UPS has been designed for Commercial / Industrial use only.
The Series 7400 1Phase UPS is not designed for direct use in any life support
application.
If you encounter any problem with the procedures contained in this manual you should
seek immediate assistance from Emerson Network Power (India) Pvt. Ltd. Sales Office
from whom the equipment was purchased. Alternatively contact the Emerson Network
Power (India) Pvt. Ltd. Customer Service & Support department at the address shown
below:
Emerson Network Power (India) Pvt. Ltd. pursues a policy of continual product development and
reserves the right to change the equipment without notice.
@ Copyright 2001 by Emerson Network Power (India) Pvt. Ltd.
Unauthorized reproduction prohibited
All rights reserved
REGISTERED AND HEAD OFFICEREGISTERED AND HEAD OFFICE
This is a class A UPS product. In a domestic environment, this
product may cause radio interface in which case the user may
be required to take additional measures.
WARNING
HIGH EARTH LEAKAGE CURRENT: EARTH CONNECTIONS IS
ESSENTIAL BEFORE CONNECTING THE INPUT SUPPLY.
This equipment must be earthed in accordance with local
electrical codes.
WARNING
THIS UPS DOES NOT INCORPORATE AUTOMATIC BACKFEED
PROTECTION. A WARNING LABEL MUST BE FITTED TO ALL
EXTERNAL PRIMARY POWER ISOLATIONS STATING.
INSULATE THE UNINTERRUPTIBLE POWER SYSTEM BEFORE
WORKING ON THIS CIRCUIT.
GENERAL
As with other types of high power equipment, dangerous voltages are present within
the UPS and battery enclosure. The risk of contact with these is minimised as the live
component parts are housed behind a hinged, lockable door. Further internal safety
screens make the equipment protected to IP20 standards.
No risk exists to any personnel when operating the equipment in the normal manner,
following the recommended operating procedures.
All equipment maintenance and servicing procedures involve internal access and
should be carried out only by trained personnel.
BATTERIES
Battery manufacturers supply details of the necessary precautions to be observed
when working on, or in the vicinity of a large bank of battery cells. These
precautions should be followed implicitly at all times.
Particular attention should be paid to the recommendations concerning local
environmental conditions and the provision of protective clothing, first-aid and fire
fighting facilities
TEST EQUIPMENT
When the battery is under charge, it is earth-referenced about its mid -point –e.g. if
the battery s being charged at 460V the battery extremities will be at +230V and –
230V with respect to neutral (earth). When using mains -powered test equipment
such as oscilloscopes in the UPS voltage area, always use a differential mode of
operation to disconnect the oscilloscope frame earth.
PERSONNEL
When working inside the UPS (trained personnel only) it is recommended that protection
be worn to prevent eye damage, should an electric ware be struck by mishandling or severe
electrical fault.
Some of the power components are very heavy. If their removal is necessary, ensure that
sufficient manpower is available; otherwise use adequate mechanical handling equipment.
When working in the gene ral area of the UPS where high voltages are present, a second
person should be standing -by to assist and summon help in case of accident.
I N D E X
1 General Description 1
1.1 Introduction 1
1.2 Design Concept 1
1.2.1 Redundant vs Non redundant configuration 1
1.2.2 7400 Module Design 2
1.2.3 Bypass Supplies 3
1.2.4 UPS Power Switch Configuration 4
1.2.5 Battery circuit breaker 4
1.2.6 One plus one parallel control 7
1.2.7 Common Battery 9
1.2.8 Operator Control Panel 10
1.2.9 Battery Circuit Breaker 13
1.2.10 Battery cabinet/ rack 13
1.3 Safety Precautions 14
1.3.1 General 14
1.3.2 Batteries 14
1.3.3 Test Equipment 14
1.3.4 Personnel 14
2 Operating Instructions 15
2.1 Introduction 15
2.1.1 Redundant Module System 15
2.1.2 Non Redundant Module System 15
2.1.3 General Notes 15
3 Installation (Electrical) 21
3.1 Introduction 21
3.1.1 Equipment Positioning and Environmental considerations 22
4.4 Remote Alarm Monitor (RAM) for Single Module and 1+1 UPS System
42
5 Maintenance 47
5.1 Introduction 47
5.2 Safety Precautions 47
5.3 Scheduled Maintenance 47
5.3.1 Daily checks 47
5.3.2 Weekly checks 48
5.3.3 Annual Service 48
5.3.4 Extended Service 49
5.3.5 Battery Maintenance 49
6 Troubleshooting 51
6.1 Troubleshooting UPS systems 51
6.1.1 Operating parameters and limitation s 51
6.1.2 General troubleshooting procedure 51
6.2 Display Panel Message Interpretation 55
ANNEXURE 57
Series 7400 Single Phase 1+N UPS
1.2.1 Redundant vs
Chapter 1Chapter 1
General Description
1.1 Introduction
The Uninterruptible Power Supply system is connected between a
critical load, such as digital drives & automation, distributed digital
Process Control System, telecom equipment, programmable logic
controller, mission critical applications, computer, and its three
phase mains power supply. Being designed to furnish a well
regulated 1 PH output power supply under all rated load and input
supply conditions the system offers the users the following
advantages: -
Increased power quality :
The UPS has its own internal voltage and frequency regulator
circuits which ensure that its output is maintained within close
tolerances independent of voltage and frequency variations on the
mains power lines.
Increased noise rejection :
By rectifying the input AC power to DC power, and then converting
it back to AC, any electrical noise present on the input mains
supply line is effectively isolated from the UPS output, therefore the
critical load sees only clean power.
Power blackout protection:
If the mains power fails, the UPS continues to power the critical
load from its battery source, leaving the load immune from power
disturbances.
1.2 Design Concepts
The one-plus-one system comprises two standard 7400 series UPS
Non-Redundant
configuration
modules which are modified to allow their outputs to be connected
in parallel. These can then be used in a “redundant” or “nonredundant” configuration as explained below.
In a non-redundant module configuration, the system is sized such
that both UPS modules are required to feed the potential load, and
if one of the two modules develops a fault, or is for some reason
shut down, the other module automatically shuts down also.
Note: In such an event the load is transferred to an unprocessed bypass supply as described later.
In a redundant module configuration the system is sized such that
the potential load can be provided by just one of the two modules.
Under normal circumstances both modules are operational and
share the load current equally; but if one module develops a fault,
or is shut down, the second module is able to take over the full load
demand and continue to provide it with processed, backed-up
power. The advantages of a redundant system over a nonredundant system in terms of overall system reliability are selfevident.
Changing a one-plus-one system’s configuration between
redundant and non-redundant is quite straightforward, being
carried out by configuration links on the circuit board, which
governs the modules’ parallel control operation.
1
Series 7400 Single Phase 1+N U PS
Figure 1: Series 7400 UPS Single Module Block Diagram
1.2.2 7400 Module
Design
Bypass
Supply
Mains
Supply
(a.c)(d.c)(a.c)
RECTIFIER
INVERTER
(d.c)
STATIC
SWITCH
UPS
Output
Supply
BATTERY
As previously mentioned, each of the two modules forming the
one-plus-one system is basically a standard single module 7400
series UPS. This section describes an individual module’s
operating principles - the effects of the additional parallel control
facilities on the standard module are described later.
The UPS basically operates as an AC-DC-AC converter (see figure
1). The first conversion stage (from AC to DC) uses a 3 Phase,
fully-controlled SCR bridge rectifier to convert the incoming mains
supply into a regulated 432V DC busbar.
The DC busbar produced by the rectifier provides both battery
charging power and power to the inverter section -which is of a
transistorised / IGBT based pulse width modulation (PWM) design
and provides the second conversion phase; i.e. reconverting the
DC busbar voltage back into an AC voltage waveform.
During normal operation both the rectifier and inverter sections are
active and provides regulated load power whilst simultaneously
float charging the battery. In the event of a mains power failure,
the rectifier becomes inoperative and the inverter is powered solely
from the battery. Critical load power is maintained under these
conditions until the battery is fully discharged, whereupon the UPS
shuts down. The end of battery discharge is assumed when the
battery voltage falls to 320Vdc. In case of 80 to 125 kVA, 1 PH
models the end of discharge is taken as 330Vdc.
The period for which the load can be maintained following a mains
power failure is known as the system’s ‘Autonomy Time’ and is
dependent upon both the battery A/Hr capacity and the applied
percentage load. It is usual in larger installations to provide an
alternative UPS input power source from a stand-by generator
when the mains supply fails. Once such a generator has been
brought on-line, and the UPS input power has been re-established,
the batteries immediately begin to recharge. Modern generators
can be started and brought on-line very quickly and where such a
facility is incorporated into the UPS installation it results in short
battery discharge periods and correspondingly rapid recharge
times.
2
Series 7400 Single Phase 1+N U PS
Figure 2: Series 7400 UPS Isolator configurations
Maintenance Bypass
Isolator
Maintenance Bypass Line
Bypass
Supply
Mains
Supply
Bypass
Supply
Bypass
Isolator
Mains
Supply
1.2.3 Bypass Supplies
Bypass Isolator
Static Bypass Line
Input
Isolator
RECTIFIER
INVERTER
Battery
Breaker
STATIC
SWITCH
Output
Isolator
UPS
Output
Supply
BATTERY
A. BLOCK SCHEMATIC FOR 230V OUTPUT 1PH. UPS SYSTEM
Maintenance Bypass Line
Static Bypass Line
Maintenance Bypass
Isolator
Input
Isolator
RECTIFIER
INVERTER
STATIC
SWITCH
Output
Isolator
UPS
Output
Supply
Battery
Battery
Breaker
Breaker
BATTERY
B. BLOCK SCHEMATIC FOR 110V OUTPUT 1PH. UPS SYSTEM
The circuit block annotated ‘Static Switch’ in figure 2 contains an
electronically controlled switching circuit, which enables the critical
load to be connected either to the Inverter output or to a Bypass
power source via the ‘static bypass line’. Normally, the load is
connected to the inverter; but in the event of a UPS overload, or
inverter failure, it is automatically transferred to the static bypass
line due to static switch action. Note that the Bypass supply should
be in normal condition and enabled.
To provide a clean (no-break) load transfer between the inverter
output and static bypass line, the inverter output and bypass supply
must be fully synchronised during normal operating conditions.
This is achieved through the inverter control electronics which
make the inverter frequency track that of the static bypass supply provided that the bypass remains within an acceptable frequency
window. The synchronising window is pre-selected to 2% of
nominal frequency, giving an acceptable frequency window of
±1Hz.
A warning message [INVERTER UNSYNCHRONIZED] is displayed
on the operator control panel when the inverter and bypass
supplies are not synchronized.
A second, manually controlled, ‘Maintenance bypass’ supply is also
incorporated into the UPS design. Its purpose it to enable the
critical load to be powered from the mains (bypass) supply while
the UPS is shut down for maintenance or troubleshooting.
Note:- The load is unprotected against mains power supply aberrations or
failure when it is connected to either the static bypass or maintenance bypass
supply.
3
Series 7400 Single Phase 1+N U PS
1.2.4 UPS Power
Switch
1.2.5 Battery Circuit
Configuration
Breaker
Figure 2 illustrates what is known as the “Split Bypass”
configuration. This is the standard configuration for all 1PH Models
In the “Split Bypass” configuration the static bypass line is switched
by a separate isolator to a dedicated ‘Bypass’ power source which
also feeds the maintenance bypass line.
The power switch locations in the various 7400 models are shown
in Figure 3.
With the exception of the maintenance bypass isolator, all the
isolators shown must be closed during normal UPS operation.
Although it cannot be classified as a ‘power’, the reset switch may
be used as a part of the UPS operating procedure. Fitted to the
UPS Logic Board, the reset switch is used by the operator to retransfer the load to the inverter following a detected overload or
overtemperature fault.
The battery is connected to the DC Busbar through a circuit
breaker fitted inside the battery Cabinet / Rack or located adjacent
to the batteries where a battery Cabinet / Rack is not used. This
circuit breaker is closed manually, but it contains an undervoltage
release coil which enables it to be tripped from the UPS control
electronics following certain detects for faults. It also has a
magnetic trip facility for overload protection.
4
Series 7400 Single Phase 1+N U PS
Figure 3A: Power Isolator identification for 230V output system
10/ 40 kVA
50 kVA
60/ 80 kVA
105 kVA
I2
Output
Isolator
I3
Maintenance
Bypass
Isolator
830830
I4
Static
Bypass
Isolator
I1
Input
Isolator
I4
I4
Output
Output
Isolator
Isolator
I3
I3
Maintenance
Maintenance
Bypass
Bypass
Isolator
Isolator
900900
I2
I2
Static
Static
Bypass
Bypass
Isolator
Isolator
I1
I1
Input
Input
Isolator
Isolator
I4
Output
Isolator
I3
Maintenance
Bypass
Isolator
I2
Static
Bypass
Isolator
12501250
I1
Input
Isolator
I4
Output
Isolator
I3
Maintenance
Bypass
Isolator
14001400
I2
Static
Bypass
Isolator
I1
Input
Isolator
5
Series 7400 Single Phase 1+N U PS
Figure 3B: Power Isolator identification for 110V output system
10/ 40 kVA
50 kVA
60/ 70 kVA
105 kVA
I2
Output
Isolator
I3
Maintenance
Bypass
Isolator
830830
I1
Input
Isolator
I4
Output
Isolator
I3
Maintenance
Bypass
Isolator
900900
I1
Input
Isolator
I4
Output
Isolator
I3
Maintenance
Bypass
Isolator
12501250
I1
Input
Isolator
I4
Output
Isolator
I3
Maintenance
Bypass
Isolator
14001400
I1
Input
Isolator
6
Series 7400 Single Phase 1+N U PS
1.2.6 One plus One
Parallel
Control
When two of the standard 7400 modules just described are
connected together to form a one-plus-one system, each module
is fitted with an additional circuit board which allows the two
modules to communicate with each other. Communication takes
place via a single ribbon cable connected between the modules as
illustrated in figure 4.
Note: - Modifying a standard module for use with a one-plus-one system also
involves replacing certain other circuit boards with modified versions, and
relocating certain minor assemblies. This means that although it is not
impossible to modify an existing 7400 module to form part of a one-plus-one
system it is not a straightforward proposition.
The inter-module parallel control responsibilities are complex but
can be summarised as follows:
Synchronisation:
As the outputs from both UPS modules are connected together to
provide a single load supply, it is imperative that the inverters are
fully synchronised both in frequency and phase. This is achieved by
digitally locking the two inverter control oscillators. Similarly, as has
already been mentioned, it is necessary for the inverters to be
synchronised to the bypass supply to enable a “no-break” transfer
to be achieved when the static switch transfers the load to the
bypass supply. The inverter control oscillators are therefore not
only locked together but are also made to track the bypass
frequency.
Current sharing:
The parallel control circuit compares the module’s output current
with that of its partner and is thereby able to effect current sharing
between the modules by making fine adjustments of an individual
module’s output voltage.
Redundancy configuration:
A link in the parallel control logic determines whether the one-plusone system operates in a “redundant” or “non-redundant”
configuration. If a non-redundant mode is selected the two static
switch sections are effectively locked together in that both the
static switches are turned off or on by a single control signal. Thus
if one module develops a fault, when running, its static switch
control logic will transfer its output from the inverter to the static
bypass line and simultaneously send a signal to the static switch
control logic in the second module to do likewise. This does not
happen if the system is configured as a redundant system, in
which case the second module is allowed to continue supplying the
load from its inverter when the first module trips its inverter off line.
Reverse current:
A reverse current monitor circuit detects current flowing into, rather
than out of, the module’s output terminals. Such a condition can
arise if a module develops an internal power fault or if for some
reason the two modules become unbalanced, and is liable to
further damage the module and also degrade the load supply. If a
reverse current is detected the inverter on the affected module is
immediately shut down and load transferred to the bypass supply
depending on the system redundancy configuration.
7
Series 7400 Single Phase 1+N U PS
Figure 4: Parallel control in a one-plus-one system
Bypass
Supply
Mains
Supply
Mains
Supply
Bypass
Supply
BATTERY
BATTERY
RECTIFIER
INVERTER
RECTIFIER
INVERTER
Battery charge current sharing:
The illustration in figure 4 shows a dedicated battery installation for
each module; however, it is possible to fit an option kit which allows
the two modules in a one-plus-one system to share a common
battery. Such an installation is shown in figure 5 overleaf.
STATIC
SWITCH
1+1 PARALLEL CONTROL
UPS
Output
Supply
1+1 PARALLEL CONTROL
STATIC
SWITCH
8
Series 7400 Single Phase 1+N U PS
Figure 5: ‘Common Battery’ configuration
Bypass
Supply
Mains
Supply
BATTERY
Mains
Supply
Bypass
Supply
1.2.7 Common Battery
RECTIFIER
INVERTER
Logic
Control
Common Batt. Panel
RECTIFIER
INVERTER
A “Common battery” option kit contains a DCCT (DC Current
Transformers) which are fitted to the battery power lines and
monitored by the parallel control logic. Each module monitors its
battery charge current and compares it with the charge current
provided by the other module. This enables a module to match its
charge current to that of its partner by effecting fine voltage control
over the rectifier section.
The components used by the Common Battery Option are
contained in a separate cabinet known as the Common Battery
Panel.
STATIC
SWITCH
1+1 PARALLEL CONTROL
UPS
Output
Supply
1+1 PARALLEL CONTROL
STATIC
SWITCH
9
Series 7400 Single Phase 1+N U PS
Figure 6: Operator Control Panel
1.2.8 Operator Control
Figure 7: Mimic Panel
Uninterruptible Power System
=
=
The operator control panel is divided into three functional areas;
Panel
‘Mimic indications’, Control switches’, and ‘LCD display panel’.
Uninterruptible Power System
=
LS1LS2LS4LS6
=
MEASUREMENTS
Vo
f
LS3
LS5
ALARM
Io
BON
INVERTEREMERGENCY
OFF
((•))
Mimic Indications
Six LEDs are mounted on a single line
diagram to represent the various UPS
power paths. These LEDs, which are
annotated in figure7, show the current UPS
operational status and should be
interpreted as detailed below.
LSI - Input supply OK / Rectifier operative:
This led illuminates when the input isolator
(I1) is closed, the input supply is within 20%
of nominal voltage, and the rectifier is
operative.
LS2 - Battery volts OK:
This led illuminates when the battery circuit
breaker is closed and the battery voltage is
within the UPS operating range - 320V432V nominal. (330V - 445V* nominal for
the 80 to 125 kVA Models).
LS3 - Bypass supply OK:
This led illuminates when the static bypass
supply in within 10% of its nominal voltage
and the static bypass isolator is closed.
LS4 - Inverter-output OK:
This led illuminates when the inverter is
operating and its output is within a preset
acceptable voltage window.
* - In case of battery on boost, this voltage can go upto 475V.
10
Series 7400 Single Phase 1+N U PS
Figure 8: Control Panel Switches
MEASUREMENTS
Vo
f
ALARM
Io
BON
((•))
INVERTEREMERGENCY
OFF
S2S3S4S5LS7S7LS8S6S8
S1
LS5 - Load on bypass:
This led illuminates when the output isolator is closed and the load
is connected to the bypass via the static switch.
LS6 - Load on Inverter:
This led illuminates when the output isolator is closed and the load
is connected to the inverter via the static switch.
Control switches
Seven tactile switches are located on the Operator Panel, together
with an emergency stop push button which is fitted with a safety
cover to prevent inadvertent operation.
Switch S1 (Vo) - Output volts:
When this switch is pressed, the lower line of the LCD Display
shows the output phase voltage w.r.t neutral.
Switch S2 (Fo) - Output frequency:
When this switch is pressed, the lower line of the LCD Display
shows the output frequency.
Switch S3 (Io) - Output current:
When this switch is pressed, the lower line of the LCD Display
shows the output current.
Switch S4 (B) - Battery:
When this switch is pressed, the lower line of the LCD Display
shows the battery voltage and current. Note that a discharging
current is symbolised by a preceding minus (-) sign, plus autonomy
time is displayed according to % load for SMF batteries.
Switch S5 ((•)) - Alarm reset:
Pressing this switch cancels the audible alarm. The alarm led and
messages will remain active if a detected fault condition is still
present.
Switch S6 - Inverter OFF:
Pressing this switch turns OFF the inverter and causes the load to
be transferred to the static bypass supply.
11
Series 7400 Single Phase 1+N U PS
Switch S7 - Inverter ON:
Pressing this switch activates the inverter and causes the load to
be transferred to the inverter side of the static switch after the
inverter voltage has had time to stabilise.
Switch S8- Emergency Stop:
When the emergency stop switch is pressed it disables the static
switch block entirely (so removing load power). It also disables the
rectifier and inverter, and trips the battery circuit breaker. Under
normal circumstances it does not remove UPS input power since
this is applied through a manually controller isolator; however, if the
UPS input supply is connected via a circuit breaker having an
electrical trip facility the emergency stop signal can be used to
drive the external circuit breaker’s trip circuit.
There are two LEDs contained within the switch panel area:
LS7 Alarm:
This led accompanies the audible alarm warning when any alarm
condition is initiated. The audible warning can be cancelled by the
reset switch (S5) but LS7 will only extinguish after the alarmed
condition has reverted to normal.
LS8 - Inverter status:
This green led situated near the inverter ON switch illuminates
when the inverter is selected ON.
12
Series 7400 Single Phase 1+N U PS
Figure 9: Display messages
1.2.9 Battery Circuit
1.2.10 Battery Cabinet /
*** ALARM *** EMERGENCY STOP
*** ALARM *** INVERTER OFF OR FAILED
*** ALARM *** OVER TEMPERATURE
*** ALARM *** OVERLOAD
*** ALARM *** BATTERY CB OPEN
*** ALARM *** OUTPUT CB OPEN
*** ALARM *** BYPASS CB OPEN
*** ALARM *** RECTIFIER OFF OR FAILED
*** ALARM *** UPS ON MAINTENANCE BYPASS
*** ALARM *** INVERTER UNSYNCHRONISED
*** ALARM *** BATTERY ON LOAD
*** ALARM *** BYPASS OFF OR FAILURE
*** ALARM *** LOAD ON BYPASS
*** ALARM *** LOW BATT: BATT UNDER VOLT.
For all kVA Models battery circuit breaker can be provided either in
Breaker
auxiliary cubicle or in a separate box. This box is designed to be
wall mounted and is connected between the UPS and battery bank.
The batteries associated with the UPS are generally housed in a
Rack
purpose built cabinet / rack located alongside, but not attached to
the main UPS equipment.
It is possible to install batteries of various types and capacities in
the cabinet / rack to obtain required autonomy characteristics.
LCD Display
An LCD display, capable of showing two
rows of 40 characters, is used to indicate the
UPS operating parameters, warnings and
alarms.
A DIP switch fitted to the display
microprocessor board enables the displayed
language to be easily selected to English,
French, Italian, Spanish or German.
The lower row of characters are used to
display metered parameters; which include
output (or bypass) voltage, frequency, or
current together with battery current &
voltage and autonomy time for SMF
batteries only.
Warning and alarm messages are displayed
on the upper row of characters. The ALARM
led and audible warning accompany all
alarm messages but are not activated by
warning messages. In all cases, the
message automatically resets when the
alarmed (or warning ) condition reverts to
normal.
When two (or more) alarm or warning
conditions are active simultaneously, the
appropriate messages are displayed in a
cyclic fashion, with each message appearing
on the display for approximately for 10
seconds.
13
Series 7400 Single Phase 1+N U PS
1.3 Safety Precautions
1.3.1 General
1.3.2 Batteries
1.3.3 Test Equipment
1.3.4 Personnel
In common with other types of high power equipment, dangerous
voltages are present within the UPS and battery enclosure. The risk
of contact with these voltages is minimised as the live component
parts are housed behind a hinged, lockable door. Further internal
safety screens make the equipment protected to IP20 standards.
No risk exists to any personnel when operating the equipment in
the normal manner, following the recommended operating
procedures.
All equipment maintenance and servicing procedures involve
internal access and should be carried only by trained personnel.
Battery manufacturers supply details of the necessary precautions
to be observed when working on, or in the vicinity of, a large bank
of battery cells. These precautions should be followed implicitly at
all times.
Particular attention should be paid to the recommendations
concerning local environmental conditions and the provision of
protective clothing, first aid and fire-fighting facilities.
When the battery is charge it is earth-referenced about it is midpoint -e.g. if the battery is being charged at 432V the battery
extremities will be at +216V and - 216V with respect to neutral
(earth). When using mains-powered test equipment such as
oscilloscopes in the UPS high voltage area, always use a differential
mode of operation to avoid the need to disconnect the oscilloscope
frame earth.
When working inside the UPS (trained personnel only) it is
recommended that protection be worn to prevent eye damage,
should an electrical arc be struck by mishandling or severe
electrical fault.
Some of the power components are very heavy. If their removal is
necessary ensure that sufficient manpower is available, otherwise
use adequate mechanical handling equipment.
When working in the general area of the UPS where high voltages
are present, a second person should be standing-by to assist and
summon help in case of accident.
14
Series 7400 Single Phase 1+N UPS
2.1.1 Redundant
2.1.2 Non - Redundant
Chapter 2Chapter 2
Operating Instructions
2.1 Introduction
Starting and stopping the one-plus-one system is straightforward,
however the modules’ response depends on whether it is
configured as a Redundant or Non-Redundant system. The
operating procedures are the same irrespective of the selected
redundancy mode; in simple terms you start (stop) one module and
then repeat the operation on the second module.
The difference in the system response concerns the point at which
the load is transferred between the bypass and uninterruptible (i.e.
inverter) supplies and is summarised below: -
Starting:
Module System
Module System
2.1.3 General Notes
When starting a redundant module system the load is transferred
from the bypass to the inverter of the first module as soon as the
first module is started and its inverter is brought on line. When the
second module is started its static bypass line is totally inhibited
due to the first module being on line, and the second module will
not be connected to the load until its inverter is operational and fully
synchronised with the first module.
Stopping:
When the first module is stopped its static bypass is inhibited
because the load will be fully maintained by the inverter of the
second module. When shutting down the second module, the
static bypass lines of both modules will be turned on as soon as its
inverter is stopped. That is, both modules will provide load power
through their paralleled bypass lines.
Starting:
In a Non-Redundant module system both modules must be running
before the load is transferred to their paralleled inverters. Therefore
when the first module is started the load will remain connected to
its static bypass line.
Stopping:
The load will be transferred to the static bypass lines in both
modules simultaneously as soon as the inverter stops in the first
module to be shut down.
Note 1: All the user controls and indicators mentioned these in these procedures
are identified in chapter 1.
Note 2: The audible alarm may annunicate at various points in these
procedures. It can be cancelled at any time by pressing the ‘Alarm Reset’
pushbutton.
Note 3: The 7400 series UPS incorporates an optional automatic boost charge
facility which can be used in systems containing non-sealed lead-acid batteries.
If this type of battery is used in your installation you may notice that the battery
charger voltage will be greater than its nominal 432Vdc when the mains supply
returns from a prolonged outage. This is the normal response of the boost
charge facility: the charger voltage should return to normal after a few hours.
15
Series 7400 Single Phase 1+N U PS
The display should indicate a positive (+)
How to turn ON the System from a Shut down condition
(Complete this actions on one module at a time)
This procedure should be followed when turning on the one-plus-one system from a
fully powered down condition - i.e. where the load is not being initially supplied through
the internal Maintenance Bypass supply.
Step Action Response
1. Close the module’s Output Isolator
and check that the UPS input mains
supply (and bypass supply if
separate) is turned on externally.
2. Close the input Isolator (and Static
Bypass Isolator, if separate).
3. Wait 20 seconds then close the
battery circuit breaker: This is
located inside the battery cabinet (if
used) or is otherwise located
adjacent to the battery racks
4. Press the battery metering selector
switch [B].
Mimic panel LEDs LS1 LS3 and LS5
should illuminate immediately, to
indicate that the load is being supplied
through the static bypass line.
(Note: In a Redundant Module system LS5 will
not illuminate on the second module to be
started as its static bypass line is inhibited).
The inverter should start automatically
once the DC Busbar reaches its
working voltage (after about 30
seconds), and when this occurs LS4
(inverter OK) will illuminate followed by
LS6 (load on inverter).
(Note: In a Non-Redundant module system
LS6 will not illuminate on the first module to
be started until you reach this point in starting
the second module.)
Note that LS5 will extinguish when LS6
illuminates.
Mimic panel LED LS2 should illuminate
and LS7 (alarm) should extinguish.
battery charging current.
16
Series 7400 Single Phase 1+N U PS
Close the input isolator (and static
separate. For 110V
systems Static bypass isolator is
Mimic panel LEDs LS1 and LS3 should
illuminate immediately, to indicate that
the input and bypass supplies are
Inverter will not turn ON unless output
Inverter will not turn ON for 1+1
Inverter will not turn ON at this stage with
output isolator open if modules are in
The display should indicate a positive (+)
Mimic panel LED LS5 should illuminate to
indicate that load is connected to the
How to turn ON the System from a Maint. power -down condition
(Complete this action on module at a time)
This procedure should be followed to start the one-plus-one from a MAINTENANCE
power-down condition - i.e. where the load is being initially powered through the
internal maintenance bypass supply.
Step Action Response
1. Check that the UPS mains supply
(and bypass supply, if separate) is
turned on externally.
2.
bypass isolator if
mounted in auxiliary cubicles).
3. Wait 20 seconds then close the
battery circuit breaker.
4. Press the battery metering selector
switch [B] (S4).
5. Press the Inverter OFF pushbutton
(S6).
6. Close the Output Isolator
7. Open the Maintenance Bypass
Isolator on both modules then
Press the Inverter ON switch (S7) on
both modules.
(Note: The inverters of both modules are
inhibited if either modules’ Maintenance
Bypass Isolator is closed).
healthy.
isolator is closed.
configuration at this stage.
1+1 configuration.
Mimic panel LED LS2 should illuminate.
battery charging current.
Mimic panel LED LS4 should extinguish
static bypass line.
(Note: In a Redundant Module system LS5 will
not illuminate on the second module to be
started as its static bypass line is inhibited).
Mimic panel LEDs LS4 (Inverter OK)
and LS6 (Load on Inverter) should
illuminate after approximately 30
seconds. (NB: In a Non-Redundant
Module system LS6 will not illuminate
on the first module to be started until
you reach this point in starting the
second module).
LS5 should extinguish at the same
time as LS6 illuminates.
LS7 (alarm) should extinguish.
17
Series 7400 Single Phase 1+N U PS
Load power through the Maintenance Bypass
Step Action Response
How to turn OFF the System but continue to provide
This procedure should be followed if one-plus-one is to be powered-down while
continuing to supply load through the maintenance bypass line. Note that during this
procedure the load will be unprotected against mains supply disturbances once the
inverter(s) has been switched off.
1. Ensure that LS3 is illuminated on the
mimic panels (indicating that the
static bypass supply is healthy).
2. Press the Inverter OFF switch (S6) on
both modules
3. Close the Maintenance Bypass
Isolator on both modules.
4. Open the Output Isolator on both
modules.
5. On each module - Open the battery
circuit breaker followed by the input
Isolator (and Static Bypass Isolator if
separate. For 110V systems Static
bypass isolator is mounted in
auxiliary cubicles).
6. Isolate the UPS input supply from the
mains distribution panel to make the
UPS safe for work to be carried out
internally.
The following points will be live within the UPS:
- Bypass supply input terminals
- Maintenance Bypass Isolator switch
- Static Bypass Isolator Switch (if fitted)
- UPS output terminals
Mimic panel LEDs LS4 and LS6 should
extinguish on both modules and LS5
should illuminate to show that the load
has been transferred to the static
bypass line.
Note: On a redundant system both Inverter
OFF switches (S6) must be operated before
LS5 illuminates but in a non-redundant system
the Inverter OFF switch must be pressed on
one module only before LS5 illuminates.
However, as the load is transferred to the
static bypass, the second module should be
turned OFF also.
Mimic panel LEDs - No change
Mimic panel LED LS5 should
extinguish on both modules.
All the operator panel led indications
and messages should extinguish as
the mains driven internal power
supplies decay.
WARNING
18
Series 7400 Single Phase 1+N U PS
How to totally Power down the System
This procedure should be followed only if the one-plus-one AND LOAD are to be
completely powered down.
Step Action Response
1. Press the Inverter OFF switch (S6)
on both modules.
2. Open the battery circuit breaker.
3. Open the input isolator (and static
bypass isolator also. For 110V
systems Static bypass isolator is
mounted in auxiliary cubicles).
Mimic panel LEDs - LS4 and LS6 should
extinguish and LS5 should illuminate to
show that the load has been transferred
to the static bypass line.
(Note: In a Non- Redundant Module system LS5
and LS6 will also changeover on the second
module)
Mimic panel LEDs LS2 should
extinguish.
All the operator panel led indications and
messages should extinguish as the
mains driven internal power supplies
decay.
IMPORTANT
The Maintenance Bypass Isolator may be operated at any time when the UPS is
powered down to connect / disconnect each load to the raw maintenance bypass
supply if required.
Emergency Stop
The emergency stop pushbutton is located behind a hinged safety shield to prevent
inadvertent operation. When this switch is pressed both modules are electronically
shut down and both battery circuit breakers are tripped. Power is removed from the
critical load, but pressing the emergency stop pushbutton will not remove the modules’ input mains supply unless an external contactor, controlled via the
emergency stop pushbutton, is fitted in the mains supply line.
19
Series 7400 Single Phase 1+N U PS
20
Series 7400 Single Phase 1+N UPS
Chapter 3Chapter 3
Installation Procedure
3.1 Introduction
WARNING
Do not apply electrical power to the UPS equipment before the arrival of the
commissioning engineer
WARNING
The UPS equipment should be installed by a qualified engineer in accordance
with the information contained in this chapter and the drawing package shipped
inside the UPS cabinet.
WARNING
BATTERY HAZARDS
Ø Special care should be taken when working with the batteries associated
with this equipment. When connected together, the battery terminal voltage
will exceed 400Vdc and is potentially lethal.
Ø Eye protection should be worn to prevent injury from accidental electrical
arcs.
Ø If a ‘sealed’ battery leaks electrolyte, or is otherwise physically damaged, it
should be placed in a container resistant to sulphuric acid and disposed of in
accordance with local regulations.
Ø If electrolyte comes into contact with the skin, the affected area should be
washed immediately.
This chapter contains information regarding the positioning and
cabling of the one-plus-one UPS equipment and batteries.
Because every site has its peculiarities, it is not the aim of this
chapter to provide step-by-step installation instructions, but to act
as guide as to the general procedures and practices that should be
observed by the installing engineer.
21
Series 7400 Single Phase 1+N U PS
3.1.1 Equipment
positioning and
3.1.2 Raised Floor
environmental
considerations
Installation
The UPS cabinets can be moved by fork lift or crane. Fork lift
apertures are provided in the sides of the base plate and are
accessible after removing blanking covers fitted to the side panel
ventilation grills. Roof - mounted eye- bolts are fitted to enable the
cabinet to be crane-handled. These can be removed once the
equipment has been finally positioned.
WARNING
Ø Ensure that the UPS weight is within the designated
S.W.L. of any handling equipment. See the UPS
specification for weight details.
Ø Do not move the battery cabinet with the batteries fitted.
The UPS module should be located in a cool, dry, clean-air
environment with adequate ventilation to keep the ambient
temperature within the specified operating range. If necessary, a
system of extractor fans should be installed to aid cooling-air flow,
and a suitable air filtration system used where the UPS is to
operate in a dirty environment.
Cooling air flow
All the models in the 7400 range are forced-cooled with the aid of
internal fans. Cooling air enters the module through ventilation
grills located at the bottom of the front, back and side panels (and
the door in the case of the 50, 60, 80, 105 & 120 kVA models) and
exhausted through grills located in the equipment roof. When the
equipment is located on a raised floor, and bottom cable entry is
used, additional cooling air also enters the UPS via the floor void.
Clearances
To allow adequate cooling air flow, you should position the
equipment with the following space around the back and sides.
o 25kVA-40kVA 1 PH Models - 100mm required if the UPS is
situated on a solid floor. No space required if situated on a
raised floor.
o 50kVA-125kVA 1 PH Models - 100mm required in all cases.
The UPS modules do not require back-access for maintenance
servicing; but, where space permits, a clearance of approximately
4 feet (1.2 meters) will ease access to some component parts.
Clearance around the front of the equipment should be sufficient to
enable free passage of personnel with the door fully opened.
If the equipment is to be located on a raised floor it should be
mounted on a pedestal suitably designed to accept the equipment
point loading. The installation diagrams in the back of this manual
identifies the location of the holes in the base plate through which
the equipment can be bolted to the floor.
22
Series 7400 Single Phase 1+N U PS
3.1.3 Battery Location
3.2 Preliminary Checks
In 25kVA to 125 kVA module installations the batteries associated
with the UPS equipment are usually contained in a purpose-built
battery cabinet/ rack which sits alongside the main UPS equipment.
Sealed, maintenance-free batteries are normally used in this type
of installation.
Due to their increased capacity, the batteries associated with
larger UPS installations are usually too big to be mounted in a
single cabinet and are either rack mounted or fitted in multiple, or
bespoke, battery cabinets. Such installations may utilise nonsealed lead acid cells, requiring regular attention and impose their
own environmental requirements.
Pedestals are required for the battery cabinets when they are
located on raised floors, in the same way as for the UPS cabinets.
Where battery racks are used, they should be sited and assembled
in accordance with the battery manufacturer’s recommendations.
In general, batteries require a well ventilated, clean and dry
environment at reasonable temperatures to obtain efficient battery
operation.
Battery manufacturers’ literature provide detailed safety measures
to be observed when employing large battery banks and these
should be studied and the proposed battery installation checked to
verify compliance with the appropriate recommendations.
The batteries are connected to the UPS through a circuit breaker
which is manually closed and electronically tripped via the UPS
control circuitry. If the batteries are cabinet-mounted this circuit
breaker is fitted within the cabinet; however, if the batteries are
rack-mounted or otherwise located remote to the main UPS
cabinet then the battery circuit breaker must be mounted as near
as possible to the batteries themselves, and the power and control
cables connected to the UPS using the most direct route possible.
Emerson Network Power (India) Pvt. Ltd. offer a purpose-designed
remote battery circuit breaker box, containing the circuit breaker
and its necessary control board, as a standard option kit.
Before you install the UPS hardware you should carry out the
following preliminary checks:
1. Verify that the UPS room satisfies the environmental conditions
stipulated in the equipment specification, paying particular
attention to the ambient temperature and air exchange system.
2. Remove any packaging devices debris then visually examine
the UPS and battery equipment for transit damage, both
internally and externally. Report any such damage to the
shipper immediately.
3. Verify that the shipment is complete -e.g. that the battery
contains the correct number of cells etc. Report any
discrepancy immediately.
4. When you are satisfied that the equipment is complete and in
good condition move it to its proposed final position.
23
Series 7400 Single Phase 1+N U PS
Note: If ‘side’ cable entry is to be used ensure that the blanking plates are
removed before finally fixing the cabinet position.
5. All UPS models have a stabilising bar fitted to the output
transformer T1 and input choke L1 during shipment. This
should be removed when the UPS has been placed in its final
position. Also PCB door is fixed with z-type clamps which
should be removed.
CAUTION
Ensure the stabilising bar fitted to the output transformer
T1 is removed before proceeding with the installation.
Ensure removal of z-type clamps used for fixing PCB door.
24
Series 7400 Single Phase 1+N U PS
3.3 Connecting UPS Power Cables
Ø Before cabling-up the UPS, ensure that you are aware
of the location and operation of the external isolators
that connect the UPS Input / Bypass supply to the
mains distribution panel.
Ø Check that these supplies are electrically isolated and
post any necessary warning signs to prevent their
inadvertent operation.
3.3.1 Cable Entry
3.3.2 Cable Rating
Cables can enter the UPS modules and battery cabinet either from
below or through either side. Side entry is made possible by
removing blanking pieces fitted in the side ventilation grills to reveal
the cable entry holes. This cable entry method allows the
equipment to be positioned on a solid floor without the need for
cable trenching and also allows cables to pass from one module to
the other when positioned side-by-side.
When connected as a one-plus-one Non Redundant system, the
UPS modules’ input and output cables must be rated to suit the
supported load rather than the individual module’s power rating.
This is due to the possibility of connecting the full load to the mains
via the Maintenance Bypass line of one module.
In a Redundant system this is unnecessary as each module is
individually rated to support the full load, and the input/output
cables can be sized to suit the modules’ rating according to the
table given below.
WARNING
UPS
RATING
105
125
25
40
50
60
80
90
NOMINAL CURRENT (AMPS) 1 PH. UPS
INPUT MAINS BYPASS/ OUTPUT BATTERY
380V 415V 110V 230V
53
85
106
128
167
190
219
261
49
78
98
117
153
173
199
237
227
364
455
546
727
818
955
1136
109
174
217
261
348
391
457
544
68
110
136
163
216
240
279
331
25
Series 7400 Single Phase 1+N U PS
3.3.3 Cable
Connections
3.3.4 Cabling
Procedure
In the 25-40kVA UPS 1 PH models the input mains / bypass cables,
UPS output cables and battery cables are connected to busbars
located behind a safety cover just below the power isolator
switches -as shown in figure 11. A terminal block is used for
connecting the control cables to the battery circuit breaker and the
external emergency stop facility.
For the 50 to 125 kVA 1PH models the power cables are connected
either directly to their respective circuit breakers or to busbars,
which are themselves, connected to the circuit breakers. See figure
12 – 14.
For 110V systems Static bypass isolator is located in auxiliary
cubicles which is usually in scope of Emerson Network Power
(India) Pvt. Ltd. Generally it is mounted in SCVS/ SVR cubicles. The
cable connection details for the same are given in figures 15 – 18.
Once the equipment has been finally positioned and secured,
connect the power cables as described in the following procedure.
Study the connection diagrams in figures 19 & 20 and positively
identify the diagram relevant to your equipment before
commencing cabling.
1. Verify that the UPS equipment is totally isolated from its
external power source and all the UPS isolators are open.
2. On each module, connect the input supply cables between
the mains distribution panel and the UPS input mains
terminals.
- ENSURE CORRECT PHASE ROTATION.
3. Connect the UPS bypass supply cables between the bypass
distribution panel and the UPS bypass supply terminals on
each module.
4. Connect the output terminals of both modules together (in
parallel ).
- ENSURE CORRECT PHASE - PHASE CONNECTION
(R - R & N - N).
Then connect the UPS output cables between the paralleled
UPS output terminals and load distribution panel.
Note: If the UPS is to be commissioned before the load equipment is
ready to receive power then SAFELY isolate the load cables.
5. On each module, connect the battery cables between the
UPS battery terminals and its associated battery circuit
breaker -see figures 19 & 20. As a safety pr ecaution remove
the battery fuse in the module until the arrival of the
commissioning engineer.
- OBSERVE THE BATTERY CABLE POLARITY.
Do not attempt to close the Battery Circuit
Breaker before the equipment has been
commissioned
WARNING
26
Series 7400 Single Phase 1+N U PS
Figure 10: Connecting the parallel interface cables.
6. Connect the safety earth and any necessary bonding earth
cables to the copper earth busbar located on the floor of the
equipment below the power connections.
Note:- The earthing and neutral bonding arrangement must be in
accordance with local and national codes of practice.
7. Connect the battery circuit breaker control cables between
the UPS auxiliary terminal block and battery circuit breaker
controller board as shown in figures 19 & 20.
8. If an external emergency stop facility is to be used then
remove the link between terminals 4 and 5 of the auxiliary
terminal block and connect the ‘normally closed’ remote stop
circuit between these two terminals.
Note:- Terminals 8 and 9 on the auxiliary terminal block are connected to
a pair of ‘normally closed’ contacts on the UPS emergency stop button
and will go open circuit when the emergency stop pushbutton is pressed.
These terminals can be used to control an external circuit breaker
connected in the UPS input mains supply line to isolate the UPS input
power when the emergency stop button is pressed.
9. Connect one-plus-one parallel control ribbon cables between
the Parallel Interface boards of both modules. Connect one
ribbon cable between sockets CN1 on one board and CN2 on
the other, and connect the second ribbon cable between the
remaining CN1 and CN2 sockets. Refer figure 10.
10. Maintenance bypass switch auxiliary wires at terminals 10 &
11 should be connected to other module terminals 10 & 11.
Figure 18: Cable connections for 105 kVA, 230V, 1 Ph.
+ -
31
Series 7400 Single Phase 1+N U PS
40kVA 1Ph UPS
3.5 Battery Circuit Breaker Boxes
A battery circuit breaker box houses the battery circuit breaker and
its controller board and is used to connect the battery to the UPS in
installations where the batteries are not contained in the standard
battery cabinet. It is most likely used with 60–125 kVA UPS models.
Several boxes of various current ratings are available and are
similar in their design and content. These are listed below :
100 Amp C.B. # 0120206014 for use with 25 – 40 kva models.
160 Amp C.B. # 0120206014 for use with 50 – 60 kva models.
250 Amp C.B. # 0120206014 for use with 80 kva models.
400 Amp C.B. # 0120206014 for use with 90 – 125 kva models.
U P S C A B I N E T
B A T T E R Y C A B I N E T
NU RUNI RI SI TINS RS
Figure 19: Battery C.B. box connections for 25-
I1I4I3I2
Battery CB
Battery CB
Interface Bd
Interface Bd
(100202120003)
(100202120003)
1 2 3 4 5
1 2 3 4 5
- +
++
+ ve
- ve
32
Series 7400 Single Phase 1+N U PS
U P S C A B I N E T
Usually the ‘box’ is fitted as close as possible to the batteries.
Figure 19 shows the details of the power and control cable
connections between the circuit breaker box and UPS itself. These
are similar to the connections made to the battery cabinet,
previously described.
As a safety precaution, remove the battery fuse in the UPS before
making the battery circuit breaker power connections.
Note: The polarity of the battery connections in the 25 - 40 kVA UPS cabinets
are reversed for 50 - 125kVA UPS modules.
I4I3I2I1
U2 N2
U3 N3 N1 U1 V1 W1
Figure 20: Battery C/B box connections for a typical 105 kVA 230V 1 PH UPS
+ ve
- ve
B A T T E R Y C A B I N E T
Battery CB
Battery CB
Interface Bd
Interface Bd
(100202120003)
(100202120003)
1 2 3 4 5
1 2 3 4 5
33
Series 7400 Single Phase 1+N U PS
34
Series 7400 Single Phase 1+N UPS
ChChapter 4apter 4
Optional Equipment
Several items of optional equipment are available for fitting to the
7400 series UPS for the use by the customer as required.
These options are:
o IBM AS400 Interface
o IBM AS400 Interface with 4-way output
o Output Interface Board
o Remote Alarms Board.
o Input filter
In addition to these options, it is possible for the customer to use
an RS232 extension of the operator control panel (fitted as
standard) for external indications.
35
Series 7400 Single Phase 1+N U PS
4.1.1 AS400 Interface
4.1.2 Remote Control
4.1 AS400 Interface Board (#100215120003)
The AS400 Interface board connects the five most operationally
critical UPS alarms to an IBM AS400 computer, which is designed
to monitor such alarms and respond to their appearance:
* Mains failure
* Load on inverter
* Low battery and/or battery circuit breaker open
* Load on mains (bypass)
* Load on maintenance bypass
These alarm signals are provided by volt-free relay contacts.
The AS400 Interface Board is fitted to the bottom of the UPS
cabinet door and connected to the UPS control electronics by a
ribbon cable (FC17 in 25-40 kVA modules and FC13 in 50-125 kVA
single phase modules) which is fitted to all modules and normally
stowed in the cable loom when this option is not used.
Two D-type connectors are provided on the Interface Board to
Board Outputs
enable the above signals to be connected to the AS400 computer.
One connector, CN1, has 9 pins and the other, CN2, has 15.
Figure 21 provides pin-out details for these connectors.
Note: Use one connector only -i.e. don’t use both connectors simultaneously.
In addition to the D-type connectors, the AS400 Interface Board
also contains a number of volt-free relays whose contacts provide a
duplicate set of volt-free alarm outputs that are connected to
terminal block M1 -as shown in figure 21. These outputs can be
used to drive an external alarms monitoring device.
Note: When using the above contacts for remote alarm annunciation, the power
supply for the remote indicators must be provided from an external power
source. Under no circumstances should the UPS internal low voltage supplies
be used for this purpose.
The Interface Board has facilities to accept two remote control
Inputs
4.1.3 Calibration
inputs, as shown in figure 21. One remote input allows the inverter
to be shut down (transferring the load to the bypass supply) and the
other enables the inverter synchronisation feature to be inhibited.
This facility is valid only for single module. The inverter
synchronisation inhibit feature is most often used if the UPS is
powered from a standby generator when the input mains supply
fails and the generator frequency is unstable.
The external control signals (12V/ 24V) should be connected to
terminal block M2 as shown in figure 21. Once again, the voltage
supplied to these terminals must be generated by an external
power source and not taken from the UPS internal low voltage
supplies.
When fitting the AS400 interface board to the 7400 series, ensure
that link SH - 1 is in position 1 - 2.
36
Series 7400 Single Phase 1+N U PS
A S 4 0 0 I N T E R F A C E B O A R D
P a r t N o . 1 0 0 2 1 5 1 2 0 0 0 3
RL1-2
RL2-2
RL3-2
SH1
1 2 3
CN1CN2
RL4-2
RL5-2
TB - M2
2
3
4
5
TB - M1
Control Inputs
1
2
Mains or Rectifier
Failure
3
4
5
Load on Inverter
6
7
8
Low Battery
9
10
11
Load on Mains
12
13
14
Load on Maintenance
Bypass
15
Synchro
off
Inverter
off
A S 4 0 0 O u t p u t s
RL1-1
CN1-9
Mains or Rectifier
Failure
CN2-9
RL2-1
CN1-8
Load on Inverter
CN2-2
RL3-1
CN1-7
Low Battery
CN2-10
RL4-1
CN1-6
Load on Mains
CN2-3
RL5-1
CN1-5
Common (0V)
CN2-11
Figure 21: AS400 Interface Board Outputs
37
Series 7400 Single Phase 1+N U PS
4.2.1 Remote Control
4.2 4-WAY AS400 Interface Board (#100201120004)
The 4-way AS-400 Interface board connects fiver critical UPS
alarms to four output terminal blocks M1 - M4 as shown in figure
22. These alarm signals can be connected to a IBM AS 400
computer designed to monitor such alarms, or to a Remote Alarm
Monitor panel.
The alarms monitored are:
* Mains failure
* Load on Inverter
* Low battery and / or battery circuit breaker
* Load on mains (bypass)
* Load on maintenance bypass
The signals commonly interfaced with the AS400 are:
o Mains failure
o Load on inverter or UPS ON
o Low battery
These alarm signals are provided by volt-free relay contacts.
Note: When using the above contacts for remote alarm annuciation, the power
supply for the remote indicators must be provided from an external power
source. Under no circumstances should the UPS internal low voltage supplies
be used for this purpose.
The 4-way AS400 Interface Board is also positioned in the UPS
cabinet (below the power isolators), and connected to the UPS
control electronics by a ribbon cable (FC17 in 25-40 kVA modules
and FC13 in 50-125k VA single phase modules) connected to CN1.
The Interface Board has facilities to accept two remote control
Inputs
inputs, as shown in figure 22. One remote input allows the inverter
to be shut down (transferring the load to the bypass supply) and the
other enables the inverter synchronisation feature to be inhibited.
This facility is valid only for single module. The inverter
synchronisation inhibit feature is most often used if the UPS is
powered from a stand by generator when the input mains supply
fails and the generator frequency is unstable.
The external control signals (12V / 24V) should be connected to the
terminal block M1 as shown in figure 22. Once again, the voltage
applied to these terminals must be generated by an external power
source and not taken from the UPS internal low voltage supplies.
4.2.2 Calibration
When fitting the AS400 interface board to the 7400 series, ensure
that link SH-1 is in position 1-2.
Two remote alarm boards, shown in figure 23 & 24, similar in
function and differing only in their connections to the terminal
blocks M1 - M3, enable the alarm signals generated within the UPS
to be connected by means of volt-free changeover relay contacts
to a remote monitoring device.
Note: When using the above contacts for remote alarm annunciation, the power
supply for the remote indicators must be provided from an external power
source. Under no circumstances should the UPS internal low voltage supplies
be used for this purpose.
Both board have facilities to accept two remote control inputs, as
Inputs
shown in figures 23 and 24. One remote input allows the inverter to
be shut down (transferring the load to the bypass supply) and the
other enables the inverter synchronisation feature to be inhibited.
This facility is valid only for single module. The inverter
synchronisation inhibit feature is most often used if the UPS is
powered from a standby generator when the input mains supply
fails and the generator frequency is unstable.
The external control signals (12V / 24V) should be connected to
terminal block M2 as shown. Once again, the voltage applied to
these terminals must be generated by an external power source
and not taken from the UPS internal low voltage supplies.
SH1
RELAY
RELAY
SYNCHRO INHIBIT
INVERTER ON/OFF
1 2 3
M1
1 2 3 4 5
M3
15
14
LOAD ON BYASS
13
12
BATTERY ON LOAD
11
10
9
MAINS FAILURE
8
7
6
OVERLOAD
5
4
3
OVER TEMPERATURE
2
1
M2
15
LOW BATTERY
14
13
12
11
MAINT. BYPASS ENABLED
10
9
8
INVERTER UNSYNCHRONISED
7
6
5
COMMON ALARM
4
3
2
UPS OK
1
Figure 23: Output Interface Board #100215120007
40
Series 7400 Single Phase 1+N U PS
MAINS VOLTAGE OK
RECTIFIER ACTIVE
BATTERY OK
PRE-ALARM END
OF DISCHARGE
INVERTER OK
SYNCHRO OK
LOAD ON UPS
LOAD ON BYASS
OVER TEMPERATURE
OVERLOAD
MAINT, BYPASS ENABLED
STATIC BYPASS ISOLATOR
CLOSED (SPLIT BYPASS)
OUTPUT SWITCH CLOSED
SYNCHRO INHIBIT
INVERTER ON/OFF
M1
M2
M3
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
RELAY
RELAY
Figure 24: Output Interface Board #10021512002
41
Series 7400 Single Phase 1+N U PS
4.4Remote Alarm Monitor (RAM) for Single Module & “1 + 1” UPS System.
This will contain following items:
1. Remote Alarm Monitor for Single Module #270154000001.
2. Remote Alarm Monitor for 1+1 Module #270154000003.
This unit is always used in conjunction with Alarm interface PCB
#100215120002, only. Remote Alarm Monitor enables the auxiliary
alarm signals to be displayed at a remote station upto 200 meters
from the main equipment.
The RAM is required to be mounted vertically. This is ideally
suitable for wall mounting. However, this also can be mounted
inside a panel. The cut out dimensions for the panel mounting, are
as shown in the clamps provided for wall mounting are required to
be removed. (Refer drawing).
There are total 9 alarms provided on the RAM. Each of the alarm
initiates an audible alarm warning. This is, however, subject to a
short time delay to prevent the warning being activated by transient
conditions. Pressing the reset push button cancels the audible
warning but the alarm indications remain until the condition is
rectified. A test push button is also provided to ensure that all the
LED’s are healthy.
Power Supply
The RAM contains a single-phase 230V a.c. mains driven power
supply. Power is applied through a standard two-pin mains
connector located at the backside of the RAM. This 2 pin malefemale type connector is marked as N L . The supply is rated
to approximately 10 watts and hence can be tapped from any
suitable source. This generates required DC power supply for
functional requirement of the RAM. Once AC power is available to
RAM, “POWER” indicating LED on RAM starts glowing. This
indicates that RAM is ready for operation. This power supply is
used to reproduce UPS mimic and display alarms.
Mimic and Alarm Connections
Refer figure 25 and 26.
For connection of RAM signals to interface PCB two different
connectors are provided marked as RM-1 and RM-2. RM-1 is a six
pin male-female connector and RM-2 is a 10 pin male-female
connector. Both the connectors are with screwed terminals. The
connection diagram of both the terminals with interface PCB is as
shown in connection diagram. 24V d.c.supply is available on RM-3.
This is required to be connected to M3: pin3 of Interface PCB. This
24 volts supply is required to be looped on interface PCB as shown
with star marked connections. For connecting RAM and interface
PCB’s, use multicore 1.5sq.mm. stranded conductor, flexible
copper cable. RAM actually requires 16 such cores. However, it is
advisable to provide spare cores and hence we recommend use of
24-core cable.
For connection diagram of 1+1 UPS system refer figure 27.
42
Series 7400 Single Phase 1+N U PS
Figure 25: Remote alarm monitors for single module and 1+1 configuration
43
Series 7400 Single Phase 1+N U PS
OUTPUT INTERFACE PCB
MOUNTED IN UPS SYSTEM
MAINS OK
(BYPASS)
RECTIFIER
ACTIVE
BATTERY
OK
END OF
DISCHARGE
INVERTER
OK
SYNCHRO
OK
LOAD ON
UPS
LOAD ON
BYPASS
OVER
TEMPERATURE
OVERLOAD
REMOTE ALARM MONITOR
LOCATED AT REMOTE PLACE
M1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
M2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
MIMIC STATUS LED – MAINS (BYPASS) VOLTS OK
MIMIC STATUS LED – LOAD ON BYPASS
MIMIC STATUS LED –RECTIFIER ACTIVE
MIMIC STATUS LED – INVERTER OUTPUT OK
MIMIC STATUS LED – BATTERY OK
MIMIC STATUS LED – LOAD ON INVERTER (UPS)
ALARM SIGNAL LED – PREALARM END OF DISCHARGE
ALARM SIGNAL LED – SYNC. NOT OK
ALARM SIGNAL LED – OVERLOAD
ALARM SIGNAL LED – OVER TEMPERATURE
ALARM SIGNAL LED – INVERTER NOT OK
ALARM SIGNAL LED – RECTIFIER NOT ACTIVE
ALARM SIGNAL LED – BATTERY NOT OK
ALARM SIGNAL LED – MAINS VOLTAGE NOT OK
ALARM SIGNAL LED – LOAD ON MAINT. BYPASS
24 VOLT SUPPLY
N
L
M2
1
M1
2
M2
3
M1
4
M1
5
M1
6
1
M2
2
M2
3
M2
4
M2
5
M1
6
M1
7
M1
8
M1
9
M3
10
TEST
RESET
+ 24 V
230V AC Supply
- 8
- 2
- 5
RM1
- 14
- 5
- 8
- 11
- 1
- 14
- 11
RM2
- 13
- 4
- 7
- 1
- 1
RM3
MAINT. BYP.
ENABLED
STATIC BYPASS
ISOLATOR CLOSED
OUTPUT SWITCH
CLOSED
SYNCHRO INHIBIT
INVERTER ON/OFF
M3
1
2
3
RELAY
RELAY
4
5
6
7
8
9
10
11
12
13
NOTES:
1.Short terminal with the help of suitable wire.
2.Note that if this supply is not available, RAM will not function
3.USF, 24 core, 1.5mm, multistrand cable for interconnection
between RAM and Output interface
4.Status of contacts is shown when relay is ‘Off’. Relay switches
‘On’ when signal is received as per the description
TERMINALS OF INTERFACE PCB
Figure 26: Interconnection diagram for single module RAM & Output Interface PCB
TERMINALS OF RAM
44
Series 7400 Single Phase 1+N U PS
OUTPUT INTERFACE PCB
MOUNTED IN MODULE 1
MAINS OK
(BYPASS)
RECTIFIER
ACTIVE
BATTERY
OK
END OF
DISCHARGE
INVERTER
OK
SYNCHRO
OK
LOAD ON
UPS
LOAD ON
BYPASS
OVER
TEMPERATURE
OVERLOAD
MAINT. BYP.
ENABLED
STATIC BYPASS
ISOLATOR CLOSED
OUTPUT SWITCH
CLOSED
SYNCHRO INHIBIT
INVERTER ON/OFF
RELAY
RELAY
M1
1
MIMIC STATUS LED –MAINS (BYPASS) OK
2
3
4
MIMIC STATUS LED –RECTIFIER ACTIVE
5
6
7
MIMIC STATUS LED –BATT. BREAKER OK
8
9
10
11
12
13
MIMIC STATUS LED –INVERTER OK
14
15
M2
1
2
3
STATUS LED
4
LOAD ON UPS
5
6
STATUS LED
7
LOAD ON BYP.
8
9
10
11
12
13
14
15
M3
1
2
3
4
24V
5
6
7
8
9
10
11
12
13
ALARM SIGNAL LED – SYNCHRO NOT OK
ALARM SIGNAL LED – RECTIFIER 2 NOT ACTIVE
ALARM SIGNAL LED – BATTERY BREAKER 2 NOT OK
ALARM SIGNAL LED – PREALARM END OF DISCHARGE
ALARM SIGNAL LED – INVERTER 2 NOT OK
ALARM SIGNAL LED –MAINS (BYPASS) VOLTAGE NOT OK
ALARM SIGNAL LED –MAINS (BYPASS) VOLTAGE NOT OK
ALARM SIGNAL LED – RECTIFIER 1 NOT ACTIVE
ALARM SIGNAL LED – BATTERY BREAKER 1 NOT OK
ALARM SIGNAL LED – PREALARM END OF DISCHARGE
MIMIC STATUS LED
– INVERTER OK
STATUS LED
LOAD ON UPS
STATUS LED
ALARM SIGNAL LED – SYNCHRO NOT OK
ALARM SIGNAL LED – INVERTER 1 NOT OK
OUTPUT INTERFACE PCB
MOUNTED IN MODULE 2
M1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
M2
1
2
3
4
5
6
LOAD ON
7
BYPASS
8
9
10
11
12
13
14
15
M3
1
2
3
4
24V
5
6
7
8
9
10
11
12
13
RELAY
RELAY
MAINS OK
(BYPASS)
RECTIFIER
ACTIVE
BATTERY
OK
END OF
DISCHARGE
INVERTER
OK
SYNCHRO
OK
LOAD ON
UPS
LOAD ON
BYPASS
OVER
TEMPERATURE
OVERLOAD
MAINT. BYP.
ENABLED
STATIC BYPASS
ISOLATOR CLOSED
OUTPUT SWITCH
CLOSED
SYNCHRO INHIBIT
INVERTER ON/OFF
TERMINALS OF
INTERFACE PCB
TERMINALS OF RAM
ALARM SIGNAL LED – LOAD ON MAINTENANCE BYPASS
RM3RM2RM1
RESET
+ 24 V
10
TEST
123456789
TERMINAL CONNECTION ARE GOING TO
M1
M1
M1
M1
-13
- 7
- 7
-13
- 7
- 7
MODULE 2
MODULE 1
MODULE 2
MODULE 2
MODULE 1
MODULE 2
M1M1M1
M1M1M1
- 4
-13
- 4
-13
MODULE 2
MODULE 1
MODULE 2
MODULE 1
- 14
- 2
- 4
- 14
- 2
- 4
MODULE 1
MODULE 1
M1M2M2M3M1
M1
M1M2M2M3M1
- 8
- 11
- 1
- 8
- 11
- 1
M1
MODULE 1 & 2
N
L123456
NOTES:
230V AC Supply
1.Short terminal with the help of suitable wire.
2.Note that if this supply is not available, RAM will not
M2
M1M2M1
M1
M2
M1M2M1
M1
- 8
- 2
- 5
- 14
- 5
- 8
- 2
- 5
- 14
- 5
function
3.USF, 24 core, 1.5mm, multistrand cable for
interconnection between RAM and Output interface
4.Status of contacts is shown when relay is ‘Off’.
Relay switches ‘On’ when signal is received as per
TERMINALS OF
INTERFACE PCB
ALARM SIGNAL LED – LOAD ON MAINTENANCE BYPASS
the description
Figure 27: Interconnection diagram for single module RAM and UPS Interface PCB 1+1 System
45
Series 7400 Single Phase 1+N U PS
46
Series 7400 Single Phase 1+N UPS
Chapter 5Chapter 5
Maintenance
5.1 Introduction
This chapter contains the procedures necessary to effect general
maintenance of the UPS module and battery. Certain procedures
entail gaining internal access to the UPS, and should only be
undertaken by a competent engineer who is familiar with the
operation and layout of the equipment and understands the areas
of potential hazard. If you have any doubts concerning safety or
the method carrying out any procedure then contact an approved
service agent for assistance or advice. If the locally approved
agent is known to you, then you should contact the Customer
Services & Support department at the address shown at the front
of this manual.
The manufacturer offers customer training, at a nominal fee, if
required. Such training can range from a one-day operator course
to in-depth training on maintenance and troubleshooting lasting
several days, and can be carried out at the manufacturer’s plant or
at the customer premises.
5.2 Safety Precautions
When working on the UPS remember that the equipment contains
live voltages at ALL TIMES unless it is externally isolated from the
mains supply, bypass supply and batteries. It is essential that th e
safety and precautionary notes contained throughout this manual
are read and FULLY UNDERSTOOD before touching any UPS
internal component part.
5.3 Scheduled Maintenance
The UPS utilises solid-state components which are not subject to
wear, with the only moving parts being the cooling fans. Scheduled
maintenance requirements, beyond ensuring that the
environmental conditions remain suitably cool and clean, are
therefore minimal. However, a well documented periodic program
of inspection and preventive maintenance, as suggested below, will
help to ensure optimum equipment performance and may serve to
detect certain minor malfunctions prior to them developing into a
major fault.
5.3.1 Daily Checks
Carry out a daily walk-by inspection of the UPS, checking the
following points:
1. Carry out a spot check of the operator control panel; ensuring
2. Check for obvious signs of overheating.
3. Listen for any noticeable change in audible noise.
4. Ensure that the ventilation grills around the UPS are
5. If possible, log the results of the inspection, noting any
that all mimic LED indications are normal, all metered
parameters are normal and no warning or alarm messages are
present on the display panel.
unobstructed.
discrepancies from the norm.
47
Series 7400 Single Phase 1+N U PS
5.3.2 Weekly Checks
5.3.3 Annual Service
Carry out the following checks from the mimic panel and log the
results:
1. Measure and record the battery float charge voltage.
2. Measure and record the battery charge current.
3. Measure and record the UPS output voltage on all three
phases.
4. Measure and record the UPS output line currents. If these are
significantly different from the values previously logged then, if
possible, record the size, type and location of any additional
load connected to the UPS supply since the previous
inspection. This type of information could prove useful to the
troubleshooting engineer should a problem occur.
If any of the above indications differ greatly from the previously
logged values for no apparent reason then you should contact
the Customer Service & Support Department at the address
given at the front of this manual for advice.
The equipment should be thoroughly cleaned and the following
checks carried out annually. This entails working inside the
equipment in regions containing hazardous voltages.
A manufacturer-trained engineer is fully aware of the hazards
concerned and will carry out this procedure with the load
connected to the maintenance bypass supply; however if the
customer decides to carry out this service procedure himself it is
imperative that the UPS be totally shut down and isolated from the
input mains supply and bypass supplies and batteries using the
procedure given below. We therefore strongly recommend that the
annual service is carried out by trained personnel.
1. Carry out the weekly checks detailed above.
2. Shut down the UPS following the recommended operating
procedure.
3. Isolate the UPS input mains supply externally (also the bypass
supply if a split bypass is in use) and isolate the battery.
4. Ensure that the UPS is totally powered down by checking for
voltage at the mains input terminals, battery connection
terminals, and output terminals (and bypass mains input
terminals in a split bypass configuration).
5. Gain full access to the UPS interior by opening its internal
hinged safety panel.
48
Series 7400 Single Phase 1+N U PS
5.3.4 Extended Service
5.3.5 Battery
Maintenance
6. Carry out a thorough examination of the UPS power
components and sub-assemblies, paying particular attention to
the following -
Electrolytic capacitors - Check for signs of leakage, buckling
etc.
Magnetic components - Check for signs of overheating,
security of fixture and signs of delamination.
Cables and Connections - Check cables for chaffing, fraying or
signs of overheating. Check that all printed circuit board
connectors are secure.
Printed circuit boards - Check the cleanliness and integrity of
the circuit boards and replace if any signs of deterioration are
found.
7. Thoroughly clean inside the equipment enclosure using a
vacuum cleaner and low pressure air to remove any foreign
debris.
8. Reconnect the UPS input mains power.
9. Start the UPS and transfer the load to the inverter following the
appropriate operating procedure.
1. If possible, check the battery autonomy time by opening the
input isolator (I1) with the UPS on-load. Close the input isolator
immediately the DC busbar voltage falls to 325V (note that at
320V the battery circuit breaker will trip and the load will
transfer to bypass). Ensure that the available battery autonomy
time meets the installation specifications.
We recommend that ALL the input/output power cables and their
connections are checked periodically. As this requires the UPS to
be completely shut down such a check should be carried out on an
‘opportunity’ basis but at an interval not exceeding 2 years.
The batteries used with the UPS are generally of a sealed, valveregulated type, and the only maintenance requirement is to ensure
that the cells are kept clean and dry. Maintenance procedures
appropriate to both, valve-regulated and un-sealed batteries vary,
and should be obtained from the battery manufacturer.
49
Series 7400 Single Phase 1+N U PS
50
Series 7400 Single Phase 1+N UPS
6.1.1 Operating
Limitations
6.1.2 General
Procedure
Chapter 6Chapter 6
Troubleshooting
6.1 Troubleshooting UPS systems
The UPS contains complex electronic control circuits that require a
firm understanding in order to carry out comprehensive fault
diagnosis and repair of the equipment. The following information
aims to provide a trained user with sufficient knowledge to
understand the nature of a fault through the correct interpretation
of the accompanying alarms and indications, and to carry out any
necessary first aid repair.
Some of the instructions in the charts at the end of this
chapter involve checking internal fuses. This should be
undertaken (after the equipment has been shut down)
only by a trained electrician who is familiar with the layout
and operation of the equipment and fully conversant with
the areas of potential hazard.
There is no practical way of detecting an impending UPS
Parameters and
Troubleshooting
malfunction. Most problems do not emerge as a gradual
performance degradation; generally the UPS either works correctly
or it will shut down - and transfer the load to the bypass supply if
applicable. However, it is important to maintain a regular record of
the UPS meter indications, as suggested in the maintenance
instructions, in order that any change in the system or load
characteristics are readily identified.
In general, the output voltage should be within 2% of nominal. If the
UPS has not operated on battery power within the previous ten
hours the battery charge current should be typically less than 6A.
If any indication differs significantly from the typical figures given
above the cause should be investigated.
Information concerning prevailing load conditions can prove useful
when discussing problems with the service agent - for example,
details of any particular load being started or shed at the time that
the fault occurred.
Troubleshooting should be carried out methodically using the
following guidelines-
Fault Identification
When first summoned to the scene of a UPS fault, your immediate
action should be to observe and record the displayed messages,
mimic indications, meter indications and the position of the UPS
power isolator switches. This should be completed before you
touch any switch.
WARNING
51
Series 7400 Single Phase 1+N U PS
Corrective Action
When all the indications have been noted, you should refer to the
following fault interpretation charts and carry out the actions
detailed against any led whose status is abnormal. If you are
unsure as to how to undertake the actions detailed - or if several
LED indications are abnormal and you are unable to distinguish
between the likely cause and affects - then seek immediate
assistance from an approved service agent.
Fault Reporting
Irrespective of whether fault rectification is successful or not, report
the fault occurrence to the nearest service agent - who will then
forward the details to the manufacturer. This type of customer
feedback is an important factor in maintaining high product
reliability, and also provides important data concerning the
equipment field performance.
CAUTION
The following diagnostic charts are designed for ‘first aid’
troubleshooting only. If a problem cannot be resolved by
taking the actions given then fully trained assistance should
be sought immediately.
Do not under any circumstances make internal circuit
adjustments or interfere with the circuit boards in any other
way.
Uninterruptible Power System
=
LS1LS2LS4LS6
=
LS3
LS5
52
Series 7400 Single Phase 1+N U PS
LED NORMAL ACTIONS TO BE TAKEN IF ABNORMAL
NUMBER STATE
LS1
LS2
LS3
ON
ON
ON
If this led is OFF it signifies a problem either with the
incoming mains supply or the rectifier section. See
accompanying alarm messages.
Check the following:
a) Input isolator is closed.
b) Input supply voltage is within 20% of nominal
c) Input fuses are O.K.
d) Power supply fuses are OK (Note: LS1 and LS2 on
the AC Power Supply Board will be OFF if either of these
fuses are ruptured).
e) Mains sensing fuses on the High Voltage
Interface board F4, F5, F6 are OK.
f) Check that slide switch I2 on the UPS Logic
Board is closed.
If the above checks prove satisfactory then seek
qualified assistance.
If this led is OFF it signifies that either the battery circuit
breaker is open or that the dc busbar voltage is below
320V dc. (For 80kVA to 125kVA models, this voltage is
330V dc ).
The battery circuit breaker will open automatically if the
dc voltage falls below this level.
Check the following:
a) Battery circuit breaker is closed.
b) DC busbar voltage – if not above 320V then
carry out checks as per LS1 (mains failure)
above. If the dc busbar voltage is greater than
320V ( and 330V dc for 80-125kVA models); If
you are unable to close the battery circuit
breaker, then seek qualified assistance.
c) If the battery circuit breaker trips as soon as
mains power is disconnected then check the dc
power supply fuses.
If this led is OFF it signifies either that the bypass supply
is not within acceptable tolerances or that the bypass
supply isolator is open.
Check that the bypass supply isolator is closed, the
supply is available and within specifications.
53
Series 7400 Single Phase 1+N U PS
LED NORMAL ACTIONS TO BE TAKEN IF ABNORMAL
NUMBER STATE
LS4
LS5**
LS6**
ON
OFF
ON
If this led is OFF it signifies that the inverter is not
producing its correct output voltage.
Check the following:
** Note that in one-plus-one system configured with a redundant
module, it is possible for one of the two modules to shut down (due
to fault for example) without turning on its static switch. In fact
when in a redundant module configuration a module’s static switch
is disabled whenever its partnering module is on line. Therefore in
the event of a fault you are likely to see LS4, LS5 & LS6 all OFF.
a) If [OVERTEMPERATURE] OR [OVERLOAD] alarm
messages are active then (after allowing the
UPS to cool / checking that the load current on
the bypass line is not excessive) press the reset
switch on the UPS Logic Board.
b) Press the Inverter ON pushbutton
c) If the dc busbar is below 320V (330V for 80-125
kVA) then do checks as per LS1 above
d) Check that slide switch I3 is closed on the UPS
Logic Board is closed.
e) If the inverter works OK when mains is available
but not when mains is unavailable then check
the dc power supply fuses.
If the above checks prove unsatisfactory then seek
qualified assistance.
If this led is ON then it signifies that the load has been
transferred to the static bypass supply and the output
circuit breaker is closed. This indication should be
mutually exclusive with LS6 described below - check
out LS6 actions.
If LS4 is also OFF then refer to LS4 checks.
If LS6 is OFF but LS4 is ON then check the following:
a) Ensure that the output isolator is closed then
press the Reset button on the UPS Logic Board.
b) Ensure that slide switch l3 on the Static Switch
Logic Board is in the AUTO position.
If the above checks prove unsatisfactory then seek
qualified assistance.
54
Series 7400 Single Phase 1+N U PS
INVERTER OFF OR
BATTERY C/B OPEN
6.2 Display Panel Message Interpretation
The following table lists the various messages displayed on the
operator panel together with a description of their interpretation.
DISPLAY MESSAGE INTERPRETATION
EMERGENCY STOP
OVERTEMPERATURE
OUTPUT C.B. OPEN
RECTIFIER OFF
FAILED
OVERLOAD
OR
FAILED
This alarm indicates that the UPS was shut down by means of
the local or remote (if fitted) emergency stop pushbutton which
of course is normally due to operator action - investigate why
the emergency stop pushbutton was pressed.
If the emergency stop pushbutton was not pressed then check
the continuity of the remote emergency stop line (if fitted), and
if no remote emergency stop line is fitted then check that a link
is connected between terminals 3 and 4 of the UPS auxiliary
terminal block.
This alarm is active whenever the inverter is not producing its
correct output voltage; either because it has been switched
OFF or due to an internal fault.
The alarm will accompany other alarms such as [OVERLOAD],
[LOAD ON BYPASS]
Overtemperature is sensed by a normally-closed thermostat
(90º C operating) fitted to each inverter heatsink. If an
overtemperature condition arises, the audible alarm will
accompany this message - the inverter stops and load
transfers to bypass after 3 minutes.
The inverter overload has an inverse load/time characteristic i.e. it will accept 125% overload for 10 minutes and 150% for 60
seconds. If this characteristic is exceeded then the load
transfers to the bypass supply, the inverter stops and the
overload alarm annunciates. The [OVERLOAD] alarm will
annunciate as soon as the load exceeds 100 % of the UPS
rating, and the load will transfer to bypass some time later depending on the degree of overload present.
This is a status indication only. Note that UPS if operating with
the battery circuit breaker open and the mains power fails then
the UPS output will also fail together with load power. Also
check battery fuses.
This is a status alarm. This output isolator must be selected
‘CLOSED’ at all times except when operating on the
maintenance bypass supply.
This alarm is active whenever the battery charger (rectifier) is
not producing its correct output voltage; due to either an input
supply failure, an internal fault, or an open input circuit breaker.
55
Series 7400 Single Phase 1+N U PS
DISPLAY MESSAGE INTERPRETATION
UPS ON
MAINTENANCE
BYPASS
INVERTER
UNSYNCHRONISED
BATTERY ON LOAD
MAINS FAILURE
LOAD ON BYPASS
This is a status warning that the load is being powered through
the maintenance bypass line and is unprotected from mains
supply abbreviations. Due to the fact that the UPS power
supplies are fed by the input circuit breaker, this message will
disappear if the input isolator is opened (and bypass isolator
opened on a split bypass system) while the load is on
maintenance bypass supply.
This warns that the inverter is not synchronised with the bypass
supply, which is normally due to a problem with the bypass
supply being outside an acceptable frequency window. Do not
switch OFF the inverter when this alarm is active or the load will
experience a 20-millisecond power break.
This is a status warning that the battery is discharging. It
normally accompanies a [MAINS FAILURE] / [BYPASS FAILURE]
or [RECTIFIER OFF OR FAILED] message.
MAINS FAILURE or mains supply out of specified acceptable
range. Do not switch OFF the inverter while this indication is
active or the load will lose its power.
This is a status warning that the load is being powered through
the static bypass line and is unprotected from mains supply
aberrations.
56
Series 7400 Single Phase 1+N U PS
A N N E X U R E
Inter Connection cable details
Any system essentially needs UPS module. However many
customers need auxiliary cubicles such as Input Isolation
Transformers, Battery Current Sharing Kit, 1+1 Paralleling kit,
Bypass SCVS / SVR or Bypass Line Transformers. In case any of
the auxiliary cubicle or combination of them is required & ordered
by the customer, we would like to recommend following sequence
in which the cubicles shall be located.
SCVS
or
SVR
It should be noted that this is the recommended panel line up &
based on this line up we will provide all interconnection cables. The
interconnecting cables are supplied only if auxiliaries are in ENP’s
scope. ENP is not responsible for supply of these interconnection
cables in case the recommended Line up is altered. It is presumed
that
TXR
Cubicle 1
UPS 1
UPS 2
TXR
Cubicle 2
or
Battery
Sharing Kit
a) All the panels are in single line up.
b) All the panels are placed in such a way that side covers are
touching to each other.
c) Location of UPS panels remain unchanged.
d) In case any of the panel is not ordered its left hand side
panel shall be shifted to ensure no gap between UPS &
other panels i.e. in case Transformer Cubicle is not required
the SCVS or SVR will be placed at the location of
Transformer Cubicle.
We are enclosing the typical interconnection diagram which will
remain unchanged for all permutations & combinations of various
options.
57
Series 7400 Single Phase 1+N U PS
58
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.