Technical Bulletin

Identification:

All cooling equipment

Bulletin no:

VTX2004-08

Date:

11-11-04

Issuer:

Customer Support Dept.

Factory:

Villotta (Italy)

Subject:

How to check if a PROBE is working or not

Model:

All appliances.

 

 

 

Problem:

The display doesn’t show any temperature or a wrong

 

 

temperature.

 

 

 

Reason:

The probe is bad connected or out of service

 

Action in

All the appliances are tested at the end of the product line

Factory:

before packaging.

 

 

 

Action in

The service should be able to do a quick diagnostic and

Field:

understand if the probe has faulted or not (see details below).

 

 

 

 

 

 

 

 

 

 

W H A T

T O

D O

 

 

 

 

 

 

 

 

check the electrical connection into the

 

check the connection between the probe

check the position of the probe; check if

 

check the resistance (Ω) of the probe with a

and the connector of the dgt (or electronic)

 

electrical box;

 

the real probe position is according to its

 

check if the dgt (or electronic) control has

multimeter (values according to the

control: if the terminal wirings of the probe

label (def=defrost=evaporator; cell=inside

 

a good connection to the power supply

amb.temp. -see the attached table-)

aren't well insulated and properly

the cell; cond=condenser; etc.)

 

 

connected, a short-circuit can happen

 

 

 

 

 

 

blank (with alarm on)

 

 

 

 

 

DISPLAY

wrong temperature

 

 

 

 

 

(with no alarms running)

 

 

 

 

 

 

 

 

 

 

 

 

wrong temperature

 

 

 

 

 

 

(with alarm on)

 

 

 

 

 

 

R

E

A

S

O

N

bad connection

probe miscalibrated,

short-circuit in probe

wrong installation

open-circuit in probe

 

 

 

 

 

 

 

ELECTROLUX PROFESSIONAL

 

p. 1 of 4

VIA 1° MAGGIO, 2 – 33089 VILLOTTA (PN) – ITALY

 

 

TELEPHONE:

TELEFAX:

E-MAIL:

+ 39 0434 637609

+ 39 0434 630 472

gabriele.dal-bianco@electrolux.it

Technical Bulletin

Identification:

All cooling equipment

Bulletin no:

VTX2004-08

Date:

11-11-04

Issuer:

Customer Support Dept.

Factory:

Villotta (Italy)

Instruments requested for diagnostic: digital multimeter and a standard tool-box.

“Resistance – Temperature” table (*)

Appliance type

Cabinet&counters, BC&F and cold self-service

hot self-service

Probe type

2K7

10K

10K SEMITEC 103AT

NTC M891 22K

Temperature [°C]

Ohm [Ω]

Ohm [kΩ]

Ohm [kΩ]

Ohm [kΩ]

-40

100÷86

340÷320

196÷181

---

-30

53÷45

188÷165

115÷107

---

-20

30÷23

103÷91

70÷65

258÷247

-10

18÷13

59÷52

44÷41

144÷135

0

11÷8

36÷31

28÷26

81÷76

10

6÷4

20÷18

19÷17

50÷44

20

3.5÷3.0

13÷11

13÷11

29÷27

25

3.0÷2.5

11÷9

11÷9

23÷21

30

2.5÷2.0

9÷7

9÷7

18÷16

40

---

---

---

12÷10

50

---

---

---

8÷6

When ambient temperature is around 25°C, a good (10K Semitec 103AT) probe should have a resistance around 10 kΩ, it means that the multimeter has to show a value of about 9÷11 kΩ

(according to the resolution of the instrument and to the real ambient temperature).

(*) see the following table to find the probe properties.