Carrier 48DH User Manual

5 (1)
Carrier 48DH User Manual

Number One

r

AirConditioniiX)

 

Maker

 

e

Division of Cairier Corporation

Syracuse New York

Combination Heating/Cooling Units

INTRODUCTION

The 48DH, DL and DM combination heating/ cooling units are complete systems designed for outdoor installation on slab or rooftop.

Installation consists of: rigging and mounting the unit; attaching ductwork; making single gas, electrical and condensate connections; and attach­ ing thermostat leads. A field-furnished filter rack is required in the return air stream.

RECEIVING THE UNIT

Examine the unit carefully for any damage incurred in shipment. If found, file claim with transportation company immediately.

Check unit nameplate to ensure that unit electrical requirements match available power supply, and that unit is designed for use with the proper gas type (natural or liquefied petroleum).

Leave unit on shipping skids until ready for mounting.

INSTALLATION

Check national and local gas and electrical codes and local building codes for any special installation requirements.

Unit Location — Install unit outdoors and as close to building duct openings as possible. Unit may face in any direction since neither the condenser air inlet nor the flue outlet (Fig. 1) are affected by wind. Do not locate unit near sources of con­ taminated air.

Although the unit is weatherproof, position unit so that water and ice from roofs or eaves cannot fall directly on the unit.

SPACE LIMITATIONS - Provide sufficient space for unimpeded air flow and for wiring and servicing unit (Fig. 1).

,CONO UNIT

2-0 OVERHEAD SPACE SECTION

.JSSiiSOc

045 8005

REQ FOR SERVICE AND ACCESS PANEL

 

 

AIR FLOW

;

 

 

002

.

 

 

'O N L Y

 

 

HEATING

SECTION

i ACCESS PANEL

SERVICE ^

^0'

 

 

OPENINGS

 

n DIAM HOLE

 

BOTH

S I D E :

 

® FOR LINE

 

 

 

ACCESS SIDE

 

 

POWER WIRING

 

 

 

FLUE OUTLET

 

—,—X::... ____WIND CAP ASSEMBLY (CONDENSER AIR OUTLET

îLÎÎÎ

002 UNIT ONLY)

COMBUSTION AIR

• DIAM*

(SMTG HOLES)

*This dimension is not applicable to 002 units because there are no mounting rails

Space required for service Design certified by A G.A. for installation on combustible type floor with a minimum ciear-

ta-'iiEiEJ ance space of 1 in. on duct connection side, and 12 in on remaining sides

O'

) Condenser Air

Indoor (Evaporator) Air

Fig. 1 — Physical Data

Table 1 — Base Unit Dimensions (ft-in.)

UNIT

48DL

 

48 DH

48DL

48DL

48 DM

48 DH

48DL

48DL

 

48DH

 

002*

003

 

004

 

Q45

 

005

 

 

 

 

 

 

A

3-10

 

3-10

4- 7

4- 7

3_2

5- 2

5- 2

5- 2

 

5- 7\

В

 

4- 7%

4- 7%

5-2У

5- 2%

5- 2%

5- 2У

 

5- 8У

C

0-1 0V3

 

0 - 1 оу

0-юу

0 - 1 оу

1-ЗУ

1- 5У

1- ЗУ

1- ЗУ

 

1 9

D

0-11 Уз

 

0 - 1 1 у

1- 2

1- 8

1-8

1- 8

1-11

1-11

 

1-11

E

1- 0

 

1- 0

1- 0

1- 0

1-0

1- 0

1- 0

1- 0

 

1- оу

F

2- 2У

 

2- 2%

2- 2У

2- 2У

2-2У

2- 2У

2- 2%

2- 2%

 

2- 2У

G

 

2- 2У

2- 2У

2-4У

2- 2Ув

2- 4У

2- 4У

 

2- 4У

H

0-11У

 

0-11У

0-11У

0-11У

1-4У

1- 4У

1- 4У

1- 4У

 

1- 4У

J

0- 4

 

0- 4

0- 4

0- 4

0-7У

0-11

0- 7У

0- 7У

 

1- 2У

 

 

 

 

 

 

 

 

 

 

 

 

*Refer to Table 2 for differences of these series

Form 48DH-6

Table 2 — Physical Data

UNIT

48DL002

48DH002

 

48DL003

48DL004

 

48 DM004

48DH004

 

48DL045

 

48DL005

 

48DH005

OPERATING WT (lb)

331

343

 

385

411

 

430

438

450

 

476

 

512

REFRIG (22) CHG (Ib-oz)

3.2

3 2

 

3.6

5 1

 

5 1

 

5 2

 

5 1

 

5 1

COMPRESSOR

M27 (1-ph)

M27 (1-ph)

 

M34

M40

 

M40

M40

 

P46

 

P53

 

P53

 

AHbbz^/h(J-ph)

AH5527h(3-ph)

 

 

 

 

 

 

 

 

 

 

 

2

2

 

 

 

 

Cyl inders

2

2

 

2

2

 

2

 

2

 

2

Rpm (60-Hz)

 

 

 

 

 

3500

 

 

 

 

 

 

 

CONDENSER FAN

1700

1700

Propel ler-Type — Direct Drive; Vertical Disc

 

large

 

2700

 

2700

Air Quantity (Cfm)

 

2000

2500

 

2500

2500

2700

 

 

Motor Hp

Vs

Vs

 

Vs

Vs

 

Vs

Vs

 

Vs

 

V,

 

Vs

EVAPORATOR FAN

 

 

Centrifugal —

Direct Drive; Horizontal Discharge

 

Г

 

 

 

 

CAPACITY (1000 Btuh)

 

 

 

 

 

 

 

 

 

 

 

 

48

24

24

30

36

 

36

36

42

 

48

 

Cool in g

 

 

 

Input Heotlng/Bonnet*

56/42

80/60

80/60

80/60

 

110/82 5

125/93 75

100/75

 

110/82 5

 

150/112 5

MAX EXTERNAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STATIC PRESSURE

 

 

 

 

 

40

 

 

 

 

 

 

 

Heating (in. W.C.)

 

 

 

 

 

 

 

 

 

 

 

 

FILTERSt (1-in. thick)

 

 

 

 

 

 

 

1 15x20

 

 

 

1 20x25

 

1 20x25

Disposable — No. ..

 

 

 

 

1 15x20

 

1 15x20

 

 

 

 

Size (in.)

1 .20x25

1 20x25

 

2 15x20

1 20x20

 

1 20x20

1 .20x20

 

2 20x20

 

1 25x25

 

1 .25x25

Permanenti — No. ..

1 15x20

1 15x20

 

1 20x20

1 20x20

 

1 20x20

1 .20x20

 

1 20x25

 

2 15x20

 

2 15x20

Size (in.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT TEMP RISE (F)

35-65

45-75

 

35-65

35-65

 

35-65

45-75

35-65

 

35 65

 

45-75

* Ratings shown for elevations up to 2000 ft above sea level. For ele­

i Recommended field-supplied filter

 

 

 

 

vations above 2000 ft deduct 4% capacity for each 1000 ft above

ifBased on 0.082 in. wg pressure drop or less thru filter at 520 ft/min

sea level

 

 

 

 

face velocity.

 

 

 

 

 

 

 

OUTSIDE AIR LIMITATIONS - Although there are no restrictions on either the percentage or the temperature of the outside air circulated thru the unit, the rate of moisture condensation from the combustion process increases significantly when return air temperature drops below 50 F. Protect the drain holes in the bottom pan against ice buildup if outside air of below freezing tempera­ ture is used

VIBRATION ISOLATION -- The unit compressor, evaporator fan and condenser fan are mounted on isolators to minimize vibration. Additional isola­ tion is not required for slab mounting. With some types of roof construction, however, the use of field-furnished mbber pad type isolators may be advisable.

Unit Rigging

1. Sling the unit perpendicularly to shipping skid mnners. Use spreader bars to prevent damage from sling or cable.

2.Raise unit to desired location and remove shipping skid.

3.Mount and level the unit as indicated in Unit Support and Mounting section.

Unit Support and Mounting

LEVELING THE UNIT — Level the unit from end to end but pitch the unit slightly (3/8 to 1/2 in ) towards the condensate drain on the service access face of the unit (Fig. 1). Use the unit frame as a leveling reference.

SLAB MOUNTING — Mount the unit on a concrete pad, cement blocks, bricks or creosoted wood of sufficient area and strength to support the unit weight (Table 2) without distortion or damage and maintain the drainage pitch recommended above.

A gravel apron will prevent grass and foliage from obstructing the condenser air inlet (Fig. 1).

FLAT OR RECESSED ROOF MOUNTING should be as close as possible to the roof duct opening Place the unit on at least 2 wooden 2x4 in. or 2x6 in. sleepers.

Sleepers may be perpendicular to or parallel to the unit mounting rails, but must span at least 2 roof joists or purlins to distribute unit weight. Set the sleepers in roof cement or mastic. Do not plug drain holes in the compressor or furnace compartment.

Do not support the unit by the ends of the base rails, nor use vibration isolators at these points. Unit will not be properly supported and could sag in the middle.

PITCHED

ROOF

MOUNTING --

Constmct a

s t u r d y

w e l d e d

o r b o l t e d

f r a m e o f

1-1/2 X 1-1/2 X 1/4 in. or larger angle iron, with

%

 

frame members at right angles to unit rails. Make

 

provisions for securing unit to frame. Use roof

 

cement or mastic where frame is in contact with

 

roof.

 

 

Ductwork Installation — For

air duct system design

 

information,

refer to Carrier

System Design

Man­

r

ual, Part 2. System air flow must be within the

range of

temperature rise and external

static

pressure shown on the unit A.G.A. rating plate.

 

Bolt or screw ductwork to unit supply and return air duct flanges and seal joints with sheet metal flashing. Flange location and dimensions are given in Fig. 1 and Table 1. Use flexible connectors between ductwork and unit to dampen vibration. If a single split duct is connected to the unit, use a gasket to prevent air bypass between supply and return sides.

Insulate and weatherproof all external duct­ work. Secure ducts to building structure and weatherproof all duct openings in wall or roof. Ducts passing thru unconditioned spaces must be insulated and provided with a vapor barrier.

Filter Installation (Field-Supplied)

1. Locate filter in return air system. Convenient location for filter is inside building behind return air grille. Size and number of required filters is given in Table 2.

2. Attach filter manufacturer’s instructions to filter rack.

ASSEMBLE WIND CAP AND

COMBUSTION-AIR INLET BOX

Locate — The wind cap assembly, heat-shield collar and combustion-air inlet box (items 1, 2 and 3 of Fig. 2) are shipped within the condenser section of all size 003 thru 005 units except 460 volt unit.

On 460 volt, size 003 thru 005 units, only the combustion-air inlet box is shipped within the condenser section. The heat-shield collar and wind cap assembly are shipped in a separate package.

On size 002 units of any voltage, the combustion-air inlet box is inside the unit behind the heating section access panel (Fig. 1). The heat-shield collar and wind cap assembly are shipped in a separate package.

Remove — On size 002 units, remove the heating section access panel (Fig. 1) and obtain the combustion-air inlet box.

On size 003 thru 005 units, remove 6 sheet metal screws and lift condenser fan, grille and orifice from the top of the condenser section (Fig. 3). Remove and discard metal banding securing the wind cap and/or inlet box and remove the item(s) from the condenser section.

Before replacing the condenser fan, grille and orifice, remove any shipping tape from the con­ denser fan.

Assemble (Fig. 2)

1. Mount the combustion-air inlet box (item 3) by sliding the horizontal box flange under the

retaining clip on the unit top cover. Fasten the inlet box with sheet metal screws provided.

2.Place end of heat-shield collar (item 2) over top cover extrusion.

3.Slide flue pipe into heat-shield collar and secure wind cap assembly (item 1) with 3 sheet metal screws thru wire cage eyelets.

 

WIND CAP

 

ASSEMBLY

FLUE PIPE

£Y£LETS(3)

(PART OF WIND CAP

 

ASSEMSLY)

 

 

■JXHEAT-SHIELC

 

^COLLAR

 

COMBUSTION

 

AIR INLET BOX

 

RETAINJNO

 

CLIP

 

TOP COVER

 

OF UNIT

 

TOP COVER

 

EXTRUSION

 

FLUE BOX

 

EXTRUSION

HEATING SECTION

ACCESS PANEL

Fig. 2 — Wind Cap and Air Inlet Box Assembly

Fig. 3 — Removing Condenser Fan

and Orifice Assembly

PIPING AND WIRING

Gas Piping — Install piping per national and local codes and ANSI Z223.1 entitled “Installation of Gas Appliances and Gas Piping,” (published by American Gas Association, 1515 Wilson Blvd., Arlington (Rosslyn), Va. 22209).

1. Furnish the gas line from the main gas supply to the unit gas valve (Fig. 4).

2.Size the supply pipe for 0.3-in. wg maximum pressure drop and for the volume of gas required (Tables 3, 5 and 6). Pipe size must equal or exceed size of gas connection at unit.

3.Use pipe dope approved for use with liquefied petroleum (LP) gases.

4.Pitch all horizontal pipe runs towards the unit 1/4 in. per 15 ft to prevent trapping condensed

moisture.

5.Support piping to maintain proper pitch, prevent strain on unit controls, and prevent accidental movement of piping.

6.Install a tee for attachment of a dirt and moisture drip pocket (Fig. 4). Tee should be at same level or below gas valve connection. Drip pocket must be protected against freeze-up.

7.Install manual shutoff valve on gas piping per local codes.

8.Provide a ground joint union in the gas supply line near the unit gas valve.

9.Protect gas piping from freezing temperatures.

Gas stoppage can result from failure to insulate pipe against wide or sudden temperature changes.

10. When piping is completed, check entire gas assembly and field piping with soap and water solution.

Never use an open ñame for leak testing.

Fig. 4 — Gas Piping Details

Table 3 — Maximum Pipe Cap. (cfh)^

PIPE

V.

NOMINAL PIPE SIZE

1V4

LENGTH (ft)

V

1

/ 4

10

132

278

520

1050

20

92

190

350

730

30

73

152

285

590

40

63

130

245

500

50

56

115

215

440

60

105

195

400

70

 

96

180

370

80

_

90

170

350

90

84

160

320

100

-

79

150

305

*Cfh — Cu ft/hr based on 0.3 in. wg pressure drop and 0.6 gas specific gravity.

NOTE;

Correction is not necessary for normal number of fittings nor for 0.7 gas specific gravity unless specified.

Table 4 — Electrical Data (60-Hz)

UNIT

 

VOLTAGE

 

 

UNIT

 

COMPR

 

 

OFM

Model

Serie

Norn V/Ph

WSA

FLA

 

ICF

FU

FLA

LRA

 

FLA

48DL,DH

200

 

23 5

19 5

 

83 4

35

16 1

80 0

2 0

 

1 4

300

230/1

21 6

17 9

 

75 4

30

14 5

72 0

2 0

 

1 4

002

 

 

400

208/3

16 8

14 0

 

58 4

20

10 6

55 0

2 0

 

1.4

 

 

 

 

200

208/1

29 8

24 3

 

102.8

40

20.8

99 0

2 4

 

1 4

48DL

300

230/1

27 3

22.3

 

91 8

35

18.8

88.0

2 4

 

1 4

400

208/3

18.8

15 5

 

73 8

25

12 0

70 0

2 4

 

1 4

003

500

230/3

17 4

14 4

 

63.8

25

10 9

60.0

2 4

 

1.4

 

^00

___ 460A3__

8.8

7 4

 

31 9

15

5 5

30 0

2.4

 

1 4

 

300

'^208/l~

39 0

32 4

 

117 9

50

26 5

112,0

3 1 1

 

2.8

48DL,DH,

230/1

35 9

29 9

 

105 9

45

24 0

100 0

3 1

 

2.8

400

208/3

25 0

21 2

 

85 9

30

15 3

80 0

3 1

 

2 8

DM004

 

 

500

230/3

23 3

19 8

 

75 9

20

13 9

70 0

3.1

 

2 8

 

 

 

 

600

460/3

11.3

10.0

 

39.0

15

7 0

35 0

3 1

 

2.8

 

200

208/1

41 0

34 1

 

115 6

60

27 5

109 0

3 8

 

2.8

48DL

300

230/1

36 5

30 5

 

100 6

50

23 9

94 0

3 8

 

2 8

400

208/3

27.4

23 2

 

85.6

35

16 6

79 0

3 8

 

2 8

045

 

 

500

230/3

24 5

20 9

 

73 6

30

14 3

67 0

3 8

 

2.8

 

600^

460/3

12 4

10 6

 

38 3

15

7 3

35 0

3 8

 

2 8

 

200

'208/1^

46 5

38 5

 

132.6

60

31 9

126 0

3 8

 

2.8

48DL,DH

300

230/1

41 5

34 5

 

112 6

50

27 9

106 0

3 8

 

2.8

400

208/3

29 5

24.9

 

93.6

40

18 3

87 0

3 8

 

2 8

005

 

 

500

230/3

25 2

21.5

 

76 6

35

14 9

70 0

3 8

 

2 8

 

 

 

 

600

460/3

13 3

11.3

 

38 3

20

8 0

35 0

3 8

 

2.8

FLA — Full Load Amps

FU — Dual Element Fuse or Circuit Breaker having high inrush capability (max allowable amps)

ICF — Max Instantaneous Current Flow during start-up is the sum of compressor LRA plus the FLA of all other motors in the unit.

IFM Indoor (Evaporator) Fan Motor

LRA Locked Rotor Amps

OFM Outdoor (Condenser) Fan Motor

WSA Wire Sizing Amps per NEC equals 1.25 x FLA of the largest motor plus the sum of all other motors in the unit.

Loading...
+ 9 hidden pages