Carrier 48LJD User Manual

0 (0)
Carrier 48LJD User Manual

HEATING & COOLING

48LJE/LJF004 48L J D/L J E/L J F005-007 Single-Package Rooftop Heating/Cooling Units

Installation, Start-Up, and Service Instructions

 

CONTENTS

 

 

 

Page

SAFETY CONSIDERATIONS ...

 

INSTALLATION .......................................................

1 19

Step 1 — Provide Unit Support................................

1

ROOF CURB

 

SLAB MOUNT

 

Step 2 — Field Fabricate Ductwork .........................

Step 3 — Install External Trap for

Condensate Drain ..................................................

Step 4 — Rig and Place Unit ....................................

• POSITIONING

Step 5 — Install Flue Hood........................................

Step 6 — Install Gas Piping .....................................

Step 7 — Make Electrical Connections...................

FIELD POWER SUPPLY

FIELD CONTROL WIRING

HEAT ANTICIPATOR SETTINGS

Step 8 - Make Outdoor-Air Adjustments and

 

 

Install Outdoor-Air Hood.......................................

10

• MANUAL OUTDOOR-AIR DAMPER

 

• TWO-POSITION DAMPER

 

OPTIONAL ECONOMIZER

 

Step 9 — Adjust Evaporator-Fan Speed..................

13

DIRECT DRIVE MOTORS

 

BELT DRIVE MOTORS

 

START-UP................

20,21

SERVICE ..................

21-25

TROUBLESHOOTING

26-31

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical com­ ponents. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance func­ tions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service per­ sonnel. When working on air-conditioning equipment, ob­ serve precautions in the literature, tags and labels attached to the unit, and other safety precautions that apply.

Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.

A WARNING

Disconnect gas piping from unit when leak testing at pressure greater than V2 psig. Pres­ sures greater than ’/2 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than ■ /2 psig, it must be replaced before use. When pressure testing field-supplied gas piping at pressures of V2 psig or less, a unit connected

i to such piping must be isolated by manually closing the gas valve(s).

A WARNING

Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury.

INSTALLATION

Unit is shipped in the vertical discharge configuration. To convert to horizontal configuration, remove screws from side duct opening covers and remove covers. Using the same screws, install covers on vertical duct openings with the insulation-side down. Seals around duct openings must be tight. See Fig. 1.

IMPORTANT: An external filter kit MUST be used or the filters MUST be field-installed outside the unit on horizontal discharge applications with optional econ­ omizer. Otherwise, the economizer must be partially removed to access the filters. The area of the fieldinstalled filters should be equal to the area of the factoryinstalled filters.

Step 1 — Provide Unit Support

ROOF CURB — Assemble and install accessory roof curb in accordance with instructions shipped with curb. See Fig. 2. Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb, not to the unit. If gas, electric power, or control power is to be routed through the curb, attach the accessory thm-the-curb service connection plates to the roof curb in accordance with the accessory installation instmctions. Connection plates must be installed before unit can be set on roof curb.

IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket sup­ plied with the roof curb as shown in Fig. 2. Improp­ erly applied gasket can result in air leaks and poor unit performance.

Curb should be level. Unit leveling tolerances are shown in Fig. 3. This is necessary for unit drain to function prop­ erly. Refer to Accessory Roof Curb Installation Instruc­ tions for additional information as required.

SLAB MOUNT (Horizontal Units Only) — Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of condenser coil air inlet to prevent grass and foliage from obstructing airflow.

NOTE: Horizontal units may be installed on a roof curb if required.

Step 2 — Field Fabricate Ductwork — Secure all ducts to roof curb and building structure on vertical units.

Do not connect ductwork to unit. For horizontal applica­ tions, field-supplied flanges should be attached to horizon­ tal discharge openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external duct­ work, joints, and roof openings with counter flashing andmastic in accordance with applicable codes.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obiigations.

Book|1 |4

PC 111

Catalog No. 564-987

Printed in U S A

Form 48LJ-7SI

Pg 1

4-93

Replaces: 48LJ-5SI

Tab la 6a

 

 

 

 

 

 

 

Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with ap­ plicable fire codes.

A minimum clearance is not required around ductwork. Cabinet return air static shall not exceed —.35 in. wg with economizer or — .45 in. wg without economizer.

Step 3 — Install External Trap for Condensate Drain — All units must have an external trap added for condensate drainage. A y4-in. NPT connection is located on the side of the unit. Use a trap at least 4-in. deep and protect against freeze-up.

If drain line is run to a drain, pitch line away from unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection. See Fig. 4 for more details.

Step 4 — Rig and Place Unit — Inspect unit for transportation damage. File any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit. Rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and Fig. 5 for additional infor­ mation. Operating weight is shown in Table 1 and Fig. 5.

Lifting holes are provided in base rails as shown in Fig. 6. Refer to rigging instructions on unit.

A CAUTION

I______ All panels must be in place when rigging._________ |

POSITIONING — Maintain clearance around and above unit to provide minimum distance from combustible mate­ rials, proper airflow, and service access. See Fig. 6. A prop­

erly positioned unit will have the following clearances between unit and roof curb: 'A-in. clearance between roof curb and base rails on each side and front of unit; U/32-in. clearance between roof curb and rear of unit. (See Fig. 2, section C-C.)

Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of con­ taminated air.

Be sure that unit is installed such that snow will not block the combustion intake or flue outlet.

Unit may be installed directly on wood flooring or on Class A, B, or C roof-covering material when roof curb is used.

Although unit is weatherproof, guard against water from higher level runoff and overhangs.

Locate mechanical draft system flue assembly at least 48 in. from any opening through which combustion prod­ ucts could enter the building, and at least 48 in. from an adjacent building. When unit is located adjacent to public walkways, flue assembly must be at least 7 ft above grade.

Flue vent discharge must have a minimum horizontal clear­ ance of 4 ft from electric and gas meters, gas regulators, and gas relief equipment.

Flue gas can deteriorate building materials. Orient unit such that flue gas will not affect building materials.

Adequate combustion-air space must be provided for proper operation of this equipment. Be sure that installation complies with all local codes and Section 5.3, Air for Com­ bustion and Ventilation, NFGC (National Fuel Gas Code), ANSI (American National Standards Institute) Z223.1- 1984 and addendum Z223.la-1987. In Canada, instal­ lation must be in accordance with the CAN LB 149.1 and CAN1.B149.2 installation codes for gas burning appliances.

 

 

ROOF CURB

A

UNIT SIZE

 

 

ACCESSORY

 

 

 

 

c

 

50DJ900771

1 '-2”

 

 

[356]

48LJE/LJF004

!J

- 1

50DJ900781

2"-0'

48UD/LJE/UF005-007

 

—1

 

[610]

 

 

 

 

 

NOTES:

1.Roof curb accessory is shipped unassembled

2.Insulated panels.

3 Dimensions in [ ] are in millimeters

4. Roof Curb: galvanized steel

5Attach ductwork to curb (Flanges of duct rest on curb.)

6Service clearance is 4 ft on each side.

Direction of airflow

UNIT SIZE

“E”

“F”

“G”

CONNECTOR

GAS

POWER

CONTROL

PKG ACY

 

48LJE/LJF004

%" [19] NPT

%" [19] NPT

3/4" [19] NPT

50DJ900791

48LJD/LJE/LJF005-007

 

 

 

 

Fig. 2 — Roof Curb Dimensions

MAXIMUM ALLOWABLE

DIFFERENCE (in.)

A-B

B-C

A-C

0.5

1.0

1.0

Fig. 3 — Unit Leveling Tolerances

/■

NOTE: Trap should be deep enough to offset maximum unit static difference, A 4-in. trap is recommended.

Fig. 4 — External Trap Condensate Drain

PLACE ALL SEAL STRIPS

 

IN PLACE BEFORE PLACING

 

UNIT ON ROOF CURB.

DETAIL "A"

SEE DETAIL DUCT END

 

"A"

 

NOTES:

1. Dimensions in ( ) are in miilimeters

2Hook rigging shackles through holes in base rail, as shown in de­ tail “A.” Holes in base rails are centered around the unit center of gravity Use wooden top skid when rigging to prevent rigging straps from damaging unit

3 Unit weights do not include economizer. See Table 1 for economizer weights.

A CAUTION

All panels must be in place when rigging.

 

MAX

 

 

A

 

B

 

C

UNIT

WEIGHT

 

 

 

 

 

 

 

 

 

 

 

 

 

Lb

 

Kg

in.

 

mm

in.

 

mm

in.

 

mm

48LJE/LJF004

530

 

240

 

 

 

 

 

 

 

 

 

48LJD/LJE/LJF005

540

 

245

73.69

 

1872

35.5

 

902

32.52

 

826

48LJD/LJE/LJF006

560

 

254

 

 

 

 

 

 

 

 

 

 

 

 

 

48LJD/LJE/LJF007

615

 

279

 

 

 

 

 

 

 

 

 

Fig. 5 — Rigging Details

Table 1 — Physical Data

BASE UNIT 48

 

LJE/LJF004

 

LJD/LJE/LJF005

 

LJD/LJE/LJF006

LJD/LJE/LJF007

NOMINAL CAPACITY (tons)

 

3

 

4

 

5

6

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

Unit

 

530

 

540

 

560

615

Economizer

 

34

 

34

 

34

34

Roof Curb

 

115

 

115

 

115

115

COMPRESSOR

 

Reciprocating

 

 

Scroil

Reciprocating

Quantity

 

1

 

1

1

1

Oil (oz)

 

55

 

55

70

65

REFRIGERANT TYPE

 

 

 

 

 

R-22

 

Operating Charge (Ib-oz)

 

6-0

7-6

8-3

9-12

CONDENSER FAN

 

 

 

 

Propeiier Type

 

Quantity...Diameter (in.)

 

1 ..26.0

 

1 ..26.0

 

1...26.0

1 . 26.0

Nominal Cfm

 

4600

 

4600

 

4100

4i00

Motor Hp...Rpm

 

Уз 850

 

Уз...850

 

У3...850

Уз . 850

CONDENSER COIL

 

 

 

Enhanced Copper Tubes, Aiuminum Lanced Fins

 

Rows...Fins/in.

 

1.. 17

2.. 17

2.. 17

2.. 17

Total Face Area (sq ft)

 

12 25

12.25

12.25

12.25

EVAPORATOR FAN

 

 

 

10 X 10

Centrifugai Type

 

Size (in.)

Std

10 X 10

 

 

10 X 10

10 X 10

Type Drive

Direct

 

Direct

 

Beit

Beit

 

Alt

Direct

 

Beit

 

Nominal Cfm

Std

1200

 

1600

 

2000

2400

Maximum Continuous Bhp

34

 

.81

 

1 80

2 40

 

Alt

81

 

1 20

 

Motor Frame

Std

48

 

48

 

56

56

 

Alt

48

 

56

 

Nominal Rpm High/Low

Std

860/845

 

1080/970

 

 

Ait

1080/970

 

 

Fan Rpm Range

Std

 

_

 

900-1300

1070-1460

 

Alt

 

970-1310

 

Motor Bearing Type

 

Baii

 

Bali

 

Baii

Bail

Maximum Fan Rpm

 

2100

 

2100

 

2100

2100

Motor Pulley Pitch Diameter A/B (in.)

Std

 

 

2 4/3 4

2.8/3.8

 

Alt

 

1 9/2 9

 

Fan Pulley Pitch Diameter (in.)

Std

 

 

4.5

45

 

Alt

 

3.5

 

Belt — Type...Length (in.)

Std

 

 

A 39

A 39

 

Alt

 

A 31

 

Pulley Center Line Distance (in.)

Std

 

 

14 7-15.5

14 7-15 5

 

Alt

 

14 7-15 5

 

Speed Change Per Full Turn of

Std

 

 

80

79

Moveable Pulley Flange (rpm)

Alt

 

68

 

 

Movable Pulley Maximum Full Turns

Std

 

 

5

5

From Closed Position

Alt

 

5

 

_

Factory Setting — Full Turns Open

Std

 

 

3

3

 

Alt

 

3

 

Factory Speed Setting (rpm)

std

 

 

1060

1230

 

Alt

 

1110

 

Fan Shaft Diameter at Pulley (in.)

 

 

5/8

 

У2

Ув

EVAPORATOR COIL

 

 

Enhanced Copper Tubes, Aluminum Doubie Wavy Fins, Acutroi'“ Feed Device

Rows...Fins/in.

 

2. 15

 

2.. 15

 

3.. 15

4...15

Total Face Area (sq ft)

 

4 17

 

55

 

55

5.5

FURNACE SECTION

 

 

 

 

 

 

 

Burner Orifice Diameter (in. ...drill size)*

 

 

 

113. 33/113 33/129 30

 

113. 33/113 33/129. 30

 

Natural Gas — Std

 

113 33

 

 

113 33/113 33/.129.30

Liquid Propane — Alt

 

089 43

 

.089.. 43/089 .43/.102 .38

 

089 43/089 43/102 38

089 43/089 43/102 38

Thermostat Heat Anticipator Setting (amps)

 

 

 

 

 

 

 

208/230/460 V

 

 

 

.14

 

14

 

First Stage

 

.14

 

 

14

Second Stage

 

-/14

 

-/-/14

 

-/-/14

-/-/14

Gas Input

 

 

 

 

 

 

 

First Stage

 

74,000/82,000

 

74,000/115,000/120,000

 

74,000/115,000/120,000

74,000/115,000/120,000

Second Stage

 

-/115,000

 

-/-/150,000

 

-/-/150,000

-/-/150,000

Efficiency (Steady State) (%)

 

80

 

80

 

80

80

Temperature Rise Range

 

25-55/55-85

 

25-55/35-65/50-80

 

25-55/35-65/50-80

25-55/35-65/50-80

Manifold Pressure (in. wg)

 

 

 

35

 

 

 

Natural Gas — Std

 

35

 

 

35

3.5

Liquid Propane — Alt

 

3.5

 

3.5

 

3.5

3.5

Field Gas Connection Size (in.)

 

.5

 

.5

 

.5

.5

HIGH-PRESSURE SWITCH (psig)t

 

 

 

 

 

 

 

Standard Compressor Internal Relief

 

 

 

 

625

 

Cutout

 

 

 

 

428

 

Reset (Auto.)

 

 

 

 

320

 

LOSS-OF-CHARGE/LOW-PRESSURE SWITCHf

 

 

 

 

 

 

 

(liquid Line) (psig)

 

 

 

 

 

 

 

Cutout

 

 

 

 

7 ± 3

 

Reset (Auto.)

 

 

 

 

22 ± 7

 

FREEZE PROTECTION THERMOSTATf

 

 

 

 

30 ± 5

 

Opens (F)

 

 

 

 

 

Closes (F)

 

 

 

 

45 ± 5

 

OUTDOOR-AIR INLET SCREENS

 

 

 

 

 

Cieanabie

 

Qty...Size (in.)

 

 

 

 

1 ..20 X 24 X 1

 

RETURN-AIR FILTERS

 

 

 

 

 

Throwaway

 

Qty...Size (in.)

 

 

 

 

2.. 16 X 25 X 2

 

LEGEND

Bhp — Brake Horsepower

*The 48LJD005-007 and 48LJE004 (74,000 Btuh) units have 2 burners The 48LJE005-007 and 48LJF004 (115,000 Btuh) units and the 48LJF005-007 (150,000 Btuh) units have 3 burners

flndioates a FlOP (Factory-instalied Option) that requires a control kit.

RIGHT SIDE

'Indicates horizontal center of gravity flndicates vertical center of gravity

NOTES:

1. Dimensions in [ ] are in millimeters.

Center of Gravity.

3

Direction of airflow

4.On vertical discharge units, ductwork is to be attached to accessoiy roof curb only. For hor­ izontal discharge units, field-supplied flanges should be attached to horizontal discharge openings and all ductwork should be at­ tached to the flanges.

5Minimum clearances are as follows (local codes or jurisdiction may prevail):

NOTE: When installing these units, use the maximum clearance stated for your application

aBetween unit, flue side, and combustible surfaces, 36 inches. (Minimum clearance to combustibles, flue side, is 18 in for units with accessory flue discharge deflector.)

b.Bottom to combustible surfaces (when not using curb), 0 in. for LJD,LJE units and

1in. for LJF units.

c.Condenser coil for proper airflow, 36-in one side, 12 in the other The side getting the greater clearance is optional

d.Overhead, 60 in to assure proper con­ denser fan operation

e.Horizontal supply and return end, 0 inches

f Between units, control box side, 42 in per NEC (National Electrical Code),

g Between unit and ungrounded surfaces, con­ trol box side, 36 in. per NEC.

h.Between unit and block or concrete walls and other grounded surfaces, control box

side, 42 in. per NEC.

6. With the exception of the clearance for the condenser coil and combustion side, as stated in Notes 5a, b, and c, a removable fence or barricade requires no clearance

7Units may be instailed on combustible floors made from wood or class A, B, or C roof cov­ ering material

 

STD UNIT

 

ECONOMIZER

CORNER

CORNER

UNIT

 

WEIGHT

 

WEIGHT

WEIGHT (A)

WEIGHT (B)

 

 

Lb

 

Kg

 

Lb

Kg

Lb

Kg

Lb

Kg

48LJE/LJF004

530

 

240

 

34

 

15.4

 

104

47.2

97

44.0

48LJD/LJE/UF005

540

 

245

 

34

 

15.4

 

106

48 1

98

44.5

48UD/UE/UF006

560

 

254

 

34

 

154

 

110

49.9

102

46 3

48UD/UE/UF007

615

 

279

 

34

 

154

 

120

54.4

112

50.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CORNER

 

CORNER

 

 

 

UNIT

 

WEIGHT (C)

 

WEIGHT (D)

 

 

 

 

 

Lb

 

 

 

Kg

 

Lb

 

Kg

 

 

 

48LJE/LJF004

 

159

 

 

72.1

 

171

 

77.6

 

 

 

48LJD/LJE/LJF005

 

162

 

 

73.5

 

174

 

78.9

 

 

 

48LJD/LJE/LJF006

 

168

 

 

76.2

 

180

 

81.6

 

 

 

48LJD/LJE/LJF007

 

185

 

 

83.9

 

198

 

89.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FRONT

 

Connection Sizes

A

1%" Dia [351 Field Power Supply Hole

B

2" Dia [50.51 Power Supply Knockout

c

2¥i6" Dia [551 Charging-Port Hole

D

%" [221 Field Control Wiring Hole

E

%" Condensate Drain

F

V2"-14 NPT Gas Connection

O'-O 3/B r’OJ

LEFT SIDE

FRONT

L

Fig. 6 — Base Unit Dimensions

 

Step 5 — Install Flue Hood — Flue hood and screen

 

are shipped screwed to the burner compartment access panel.

 

Remove from shipping location and using screws provided,

 

install flue hood and screen in location shown in Fig. 7.

i '

Step 6 — Install Gas Piping — Unit is equipped for

 

use with type of gas shown on nameplate. Refer to local

 

building codes, or in the absence of local codes, to ANSI

 

Z223.1-1984 and addendum Z223-1A-1987 entitled Na­

 

tional Fuel Gas Code. In Canada, installation must be in

 

accordance with the CANl.B 149.1 and CAN1.B149.2 in­

 

stallation codes for gas burning appliances.

 

For natural gas applications, gas pressure at unit gas con­

 

nection must not be less than 4 in. wg or greater than

 

13.0 in. wg while unit is operating. On 48LJ005,006,007

 

high heat units, the gas pressure at unit gas connection must

 

not be less than 5 in. wg or greater than 13 in. wg while the

 

unit is operating. For propane applications, the gas pressure

 

must not be less than 5 in. wg or greater than 13 in. wg at

 

the unit connection.

 

Size gas supply piping for 0.5 in. wg maximum pressure

 

drop. Do not use supply pipe smaller than unit gas connec­

 

tion. Support gas piping as shown in the table in Fig. 8. For

 

example, a %-in. gas pipe must have one field-fabricated

 

support beam every 8 ft. Therefore, an 18-ft long gas pipe

 

would have a minimum of 2 support beams, a 48-ft long

 

pipe would have a minimum of 6 support beams.

 

See Fig. 8 for typical pipe guide and locations of exter­

 

nal manual main shutoff valve.

 

9” MINIMUM CLEARANCE

 

 

 

FOR PANEL REMOVAL

 

 

 

MANUAL GAS

GAS

 

 

I SHUTOFF VALVE* REGUUTOR*

 

48" MINIMUM -

 

 

 

 

DRIP LEG PER NFGC

 

 

ROOF CURB

FIELD-

FABRICATED*

 

 

 

 

 

 

 

7

FROM GAS METER

 

 

SUPPORT

 

 

 

 

 

 

LEGEND

 

SPACING OF SUPPORTS

NFGC — National Fuel Gas Code

 

 

 

 

STEEL PIPE

X

"Field supplied.

 

 

NOMINAL

 

DIMENSIONS

NOTE: Follow all local codes

 

DIAMETER

 

(feet)

 

 

 

(In.)

 

 

 

 

 

 

 

 

 

%

 

6

 

 

 

*/4or 1

 

8

 

 

1’/4 or larger

10

 

 

 

 

 

 

Fig. 8 — Gas Piping Guide (With Accessory

Thru-the-Curb Service Connections)

Step 7 — Make Electrical Connections

A WARNING

Unit cabinet must have an uninterrupted, unbroken elec­ trical ground to minimize the possibility of personal in­ jury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for elec­ trical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA (National Fire Protection Association), latest edition, and local elec­ trical codes. Do not use gas piping as an electrical ground.

Failure to follow this warning could result in the in­ staller being liable for personal injury of others.

FIELD POWER SUPPLY - All units except 208/230-v units are factory wired for the voltage shown on the name­ plate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by moving the black wire from the 230-v orange wire on the trans­ former and connecting it to the 200-v red wire from the transformer. The end of the orange wire must then be insulated.

Refer to unit label diagram for additional information. Wiring leads are provided for field service. Use copper con­ ductors only when splice connectors are used.

When installing units, provide a disconnect per NEC.

All field wiring must comply with NEC and local require­ ments. In Canada, electrical connections must be in accor­ dance with CSA (Canadian Standards Association) C22.1 Canadian Electrical Code Part 1.

Install conduit through side panel openings indicated in Fig. 6. Route power lines through connector to terminal connections as shown in Fig. 9.

Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (also see Table 2). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in the legend for Table 2, Note 2 to determine the percent voltage imbalance. Operation on im­ proper line voltage or excessive phase imbalance consti­ tutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.

FIELD CONTROL WIRING - Install a Carrier-approved accessory thermostat assembly according to installation in­ structions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature in accordance with thermostat instal­ lation instmctions. Connect thermostat wires to terminal board.

Route thermostat cable or equivalent single leads of col­ ored wire from subbase terminals through connector on unit to low-voltage connections (shown in Fig. 10).

Connect thermostat wires to matching screw terminals of low-voltage connection board. See Fig. 10.

NOTE; For wire runs up 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C min­ imum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.

Pass the control wires through the hole provided in the end panel; then feed wires through the raceway built into the comer post to the 24-v barrier located on the left side of the control box. See Fig. 11. The barrier provides the UL (Underwriters’ Laboratories) required clearance between highand low-voltage wiring.

Table 2 — Electrical Data

 

NOMINAL

IFM

VOLTAGE

COMPR

OFM

IFM

COMBUSTION

POWER SUPPLY

DISCONNECT SIZE

UNIT

RANGE

(each)

FAN MOTOR

 

V-PH-HZ

TYPE

 

 

 

 

 

 

 

 

 

 

 

 

Min

Max

RLA

LRA

FLA

FLA

FLA

MCA

MOCP*

FLA

LRA

 

 

 

 

208/230-1-60

Std

187

254

179

93

1 9

2.8

57

27 1/27 1

35/35

26/26

105/105

 

Alt

3.8

28.1/28 1

35/35

27/27

107/107

 

 

 

 

 

 

 

 

 

208/230-3-60

Std

187

254

11 2

80

1 9

28

.57

18 7/18.7

25/25

18/18

92/92

48LJE/LJF004

Alt

38

19 7/19.7

25/25

19/19

94/94

 

 

 

 

 

 

 

(3 Tons)

460-3-60

Std

414

508

6 1

40

1 0

1 5

30

101

15

10

46

 

Alt

1.9

105

15

10

46

 

 

 

 

 

 

 

 

 

575-3-60

Std

518

632

45

29

1 9

2.8

57

7.5

15

7

34

 

Alt

38

7.9

15

8

34

 

 

 

 

 

 

 

 

 

208/230-1-60

Std

187

254

24 8

127

1 9

38

57

36 7/36.7

45/45

35/35

141/141

 

Alt

57

38.6/38 6

45/45

37/37

144/144

 

 

 

 

 

 

 

 

48LJD/LJE/LJF

208/230-3-60

Std

187

254

157

99

1.9

3.8

57

25 3/25.3

30/30

25/25

113/113

Alt

5.7

27 2/27.2

35/35

27/27

116/116

 

 

 

 

 

 

 

005

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Std

 

 

 

 

1 0

1 9

 

126

15

12

56

(4 Tons)

460-3-60

 

414

508

78

50

 

.30

 

 

 

 

Alt

2.8

13.5

20

13

58

 

 

 

 

 

 

 

 

 

575-3-60

Std

518

632

55

40

1.9

38

57

9.2

15

9

45

 

Alt

5.7

9.9

15

10

47

 

 

 

 

 

 

 

 

48LJD/LJE/LJF

230-1-60

 

187

254

27.8

135

1 9

85

.57

45 2

60

44

164

208/230-3-60

Std

187

254

19.2

105

1 9

8.5

.57

34.4/34.4

40/40

34/34

134/134

006

 

 

 

 

 

 

 

 

 

 

 

 

460-3-60

414

508

96

55

1 0

4.5

30

17.5

20

17

81

(5 Tons)

 

 

575-3-60

 

518

632

83

45

1 9

85

.57

14.5

20

14

57

48LJD/LJE/LJF

208/230-3-60

 

187

254

21 9

142

1 9

5.8

57

35.1/35.1

40/40

34/34

188/188

007

460-3-60

Std

414

508

104

72

1 0

2.6

30

16.6

20

16

95

(6 Tons)

575-3-60

 

518

632

96

58 5

1 9

11 0

57

172

20

17

81

IMPORTANT: Optional, alternate evaporator-fan motor and drive are not available for 48LJ006,007 units. Contact your local Carrier representative for more information about field-installed motors

 

LEGEND

COMPR

Compressor

FLA

Full Load Amps

HACR

Heating, Air Conditioning and Refrigeration

IFM

Indoor (Evaporator) Fan Motor

LRA

Locked Rotor Amps

MCA

Minimum Circuit Amps

MOCP

Maximum Overcurrent Protection

OFM

Outdoor (Condenser) Fan Motor

RLA

Rated Load Amps

*Fuse or HACR circuit breaker

NOTES:

1.In compliance with NEC (National Electrical Code) requirements for multi­ motor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shali be fuse or HACR breaker Canadian Standards Association (CSA) units may be fuse or circuit breaker

2 Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalanoe in supply voltage is greater than 2% Use the following formula to determine the percent voltage im­ balance.

% Voltage Imbalance

max voltage deviation from average voltage

100 X

average voltage

Example: Supply voltage is 460-3-60.

AB = 452V ABC BC = 464v

AC = 455V

452 4- 464 4- 455

Average Voltage

_ 1371 3

= 457

NOTE: The 575-v units are CSA only

Determine maximum deviation from average voltage (AB) 457 - 452 = 5 V

(BC) 464 - 457 = 7 V

(AC) 457 - 455 = 2 V

Maximum deviation is 7 v.

Determine % voltage imbalance

7 % Voltage Imbalance = 100 x -----------

457

= 1 53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately

c

LEGEND

 

Contactor

 

COMP

Compressor

TO

EQUIP

Equipment

 

GND

Ground

 

IFC

Indoor (Evaporator) Fan Contactor

 

NEC

National Electrical Code

 

 

208 / 230-3-60

FIELD POWER SUPPLY

 

460-3-60

 

(SIZES 004-006)

DISCONNECT

 

575-3-60

 

(SIZES 004-007)

PER NEC

Fig. 9 — Power Wiring Connections

c

 

LEGEND

 

AHA

Adjustable Heat

TH — Thermostat-Heating

CC

Anticipator

--------- Field Wiring

Cooling Compensator

---------- Factory Wiring

TC

Thermostat-Cooling

 

NOTE: Connect Y2 when unit is equipped with an economizer.

CONNECTION BOARD LED

INTEGRATED GAS UNIT

CONTROLLER (IGC)

 

RACEWAY

HOLE IN END

PANEL---

(HIDDENV

LED — Light-Emitting Diode

Fig. 11 — Fieid Control Wiring Raceway

Fig. 10 - Low-Voitage Connections

HEAT ANTICIPATOR SETTINGS - Set heat anticipator settings at. 14 amp for the first stage and . 14 amp for secondstage heating, when available.

Step 8 - Make Outdoor-Air Adjustments and

Install Outdoor-Air Hood

MANUAL OUTDOOR-AIR DAMPER - The outdoor-air hood and screen are attached to the basepan at the bottom of the unit for shipping.

Assembly:

1.Determine quantity of ventilation required for building. Record amount for use in Step 8.

2.Remove and save evaporator coil access panel and screws. See Fig. 12.

3.Separate hood and screen from basepan by removing the 4 screws securing them. Save all screws.

EVAPORATOR

COIL ACCESS ?

PANEL \

SCREWS (SIDE) “

MANUAL

OUTDOOR-AIR »

ADJUSTMENT

SCREWS

POSITION

SETTING SCALE

Fig. 12 — Damper Panel with Manual Outdoor-Air Damper Installed

4.Replace evaporator coil access panel.

5.Place hood on front of evaporator coil access panel. See Fig. 13 for hood details. Secure top of hood with the 4 screws removed in Step 3. See Fig. 14.

6.Remove and save 6 screws (3 on each side) from sides of the manual outdoor-air damper.

7.Align screw holes on hood with screw holes on side of manual outdoor-air damper. See Fig. 13 and 14. Secure hood with 6 screws from Step 6.

8.Adjust minimum position setting of the damper blade by adjusting the manual outdoor air adjustment screws on the front of the damper blade. See Fig. 12. Slide blade vertically until it is in the appropriate position deter­ mined by Fig. 15. Tighten screws.

9.Remove and save screws currently on sides of hood. In­ sert screen. Secure screen to hood using the screws. See Fig. 14.

SCREW HOLES (TOP)

HOOD

HOOD

SCREEN LOCATION (SCREEN NO SHOWN)

Fig. 14 Outdoor-Air Damper with Hood Attached

OUTDOOR AIRFLOW (cfm x 100)

Fig. 15 - Position Setting

10

Loading...
+ 23 hidden pages