Carrier 48HJD005-007 User Manual

0 (0)

48HJD005-007, 48HJE/HJF004-007 48HJL/HJM/HJN/HJG/HJH/HJK004-006 (LOW NOx)

Single-Package Rooftop Heating/Cooling

Installation, Start-Up and

Service Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . 1 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-28

Step 1 — Provide Unit Support . . . . . . . . . . . . . . . . . . . 1

ROOF CURB

SLAB MOUNT

Step 2 — Field Fabricate Ductwork . . . . . . . . . . . . . . .

3

Step 3 — Install External Trap for

 

Condensate Drain. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3

Step 4

— Rig and Place Unit . . . . . . . . . . . . . . . . . . . . .

3

• POSITIONING

 

Step 5

— Install Flue Hood . . . . . . . . . . . . . . . . . . . . . . .

4

Step 6

— Install Gas Piping . . . . . . . . . . . . . . . . . . . . . .

4

Step 7

— Make Electrical Connections . . . . . . . . . . .

4

FIELD POWER SUPPLY

FIELD CONTROL WIRING

HEAT ANTICIPATOR SETTINGS

Step 8 — Adjust Factory-Installed Options . . . . . . . 8

MOISTUREMISER DEHUMIDIFCATION PACKAGE

APOLLO CONTROL

DISCONNECT SWITCH

OPTIONAL DURABLADE ECONOMIZER

OPTIONAL ECONOMI$ER

Step 9 — Adjust Evaporator-Fan Speed . . . . . . . . . 19

• BELT-DRIVE MOTORS

PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29-32 SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-38 TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . . 39-45 START-UP CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . CL-1

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.

Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the literature, tags and labels attached to the unit, and other safety precautions that may apply.

Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.

Before performing service or maintenance operations on unit, turn off main power switch to unit and install lockout tag. Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate. Electrical shock could cause personal injury.

Disconnect gas piping from unit when leak testing at pressure greater than 1/2 psig. Pressures greater than 1/2 psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater than 1/2 psig, it must be replaced before use. When pressure testing field-supplied gas piping at pressures of 1/2 psig or less, a unit connected to such piping must be isolated by manually closing the gas valve(s).

INSTALLATION

Unit is shipped in the vertical discharge configuration. To convert to horizontal discharge application, remove duct opening covers. Using the same screws, install covers on duct openings in basepan of unit with insulation-side down. Seals around openings must be tight.

NOTE: Any combination of supply and return ducting is permissible, i.e., vertical supply combined with horizontal return.

Step 1 — Provide Unit Support

ROOF CURB — Assemble and install accessory roof curb in accordance with instructions shipped with curb. See Fig. 1. Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb, not to the unit.

If electric control power or gas service is to be routed through the basepan, attach the accessory thru-the-bottom service connections to the basepan in accordance with the accessory installation instructions. Connections must be installed before unit is set on roof curb.

IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 1. Improperly applied gasket can result in air leaks and poor unit performance.

Curb should be level. Unit leveling tolerances are shown in Fig. 2. This is necessary for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.

SLAB MOUNT (Horizontal Units Only) — Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of condenser-coil air inlet to prevent grass and foliage from obstructing airflow.

NOTE: Horizontal units may be installed on a roof curb if required.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book

1

4

PC 111

Catalog No. 534-767

Printed in U.S.A.

Form 48HJ-18SI

Pg 1

9-00

Replaces: 48HJ-17SI

Tab

1a

6a

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

UNIT SIZE

B

C

D ALT

“E”

“F”

“G”

CONNECTOR

DRAIN HOLE

GAS

POWER

CONTROL

PKG. ACCY.

 

 

 

 

 

 

 

3

3/4″ [19] NPT

1

CRBTMPWR001A00

 

 

 

 

/4

 

/2

 

 

 

1′-911/16

1′-4″

13/4

[19] NPT

11/4″ [31.7]

[12.7] NPT

CRBTMPWR002A00

48HJD004-007

1/2

3/4″ [19] NPT

 

 

CRBTMPWR003A00

50HJF004-007

[551]

[406]

[44.5]

[12.7] NPT

 

1/2

 

 

 

 

 

3/4

11/4″ [31.7]

[12.7] NPT

CRBTMPWR004A00

 

 

 

 

[19] NPT

 

 

 

 

 

 

 

 

 

 

NOTES:

1.Roof curb accessory is shipped disassembled.

2.Insulated panels.

3. Dimensions in [ ] are in millimeters.

4.Roof curb: galvanized steel.

5.Attach ductwork to curb (flanges of duct rest on curb).

6. Service clearance 4 ft on each side.

7. Direction of airflow.

8.Connector packages CRBTMPWR001A00 and 002A00 are for thru-the-curb connections. Packages CRBTMP003A00 and 004A00 are for thru-the-bottom connections.

2

ROOF CURB

 

 

“A”

UNIT SIZE

ACCESSORY

 

 

48/50HJ

 

 

 

 

 

CRRFCURB001A00

1′-2″ [356]

004-007

CRRFCURB002A00

2′-0″ [610]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 1 — Roof Curb Details

MAXIMUM ALLOWABLE

DIFFERENCE (in.)

A-B

B-C

A-C

0.5

1.0

1.0

Fig. 2 — Unit Leveling Tolerances

Step 2 — Field Fabricate Ductwork — Secure all ducts to roof curb and building structure on vertical discharge units. Do not connect ductwork to unit. For horizontal applications, field-supplied isolation flanges should be attached to horizontal discharge openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.

Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.

If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.

A minimum clearance is not required around ductwork. Cabinet return-air static shall not exceed –.35 in. wg with Durablade economizer, or –.30 in. wg with EconoMi$er, or –.45 in. wg without economizer.

These units are designed for a minimum continuous returnair temperature in heating of 50 F (dry bulb), or an intermittent operation down to 45 F (dry bulb), such as when used with a night setback thermostat.

Step 3 — Install External Trap for Condensate Drain — The unit’s 3/4-in. condensate drain connections are located on the bottom and side of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.

When using the standard side drain connection, ensure the plug (Red) in the alternate bottom connection is tight before installing the unit.

To use the bottom drain connection for a roof curb installation, relocate the factory-installed plug (Red) from the bottom connection to the side connection. See Fig. 3. The piping for the condensate drain and external trap can be completed after the unit is in place.

All units must have an external trap for condensate drainage. Install a trap 4-in. deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection (3/4 in.).

Step 4 — Rig and Place Unit — Inspect unit for transportation damage, and file any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit, and rollers may be used to move unit across a roof. Level by using unit frame as a

CONDENSATE PAN (SIDE VIEW)

DRAIN PLUG

NOTE: Drain plug is shown in factory-installed position.

Fig. 3 — Condensate Drain Pan

reference. See Table 1 and Fig. 4 for additional information. Operating weight is shown in Table 1 and Fig. 4.

Lifting holes are provided in base rails as shown in Fig. 5. Refer to rigging instructions on unit.

All panels must be in place when rigging and lifting.

POSITIONING — Maintain clearance around and above unit to provide minimum distance from combustible materials, proper airflow, and service access. See Fig. 5. A properly positioned unit will have the following clearances between unit and roof curb; 1/4-in. clearance between roof curb and base rails on each side and duct end of unit; 1/4 in. clearance between roof curb and condenser coil end of unit. (See Fig. 1, section C-C.)

Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contaminated air.

Be sure that unit is installed such that snow will not block the combustion intake or flue outlet.

Unit may be installed directly on wood flooring or on Class A, B, or C roof-covering material when roof curb is used.

Although unit is weatherproof, guard against water from higher level runoff and overhangs.

Locate mechanical draft system flue assembly at least 48 in. from any opening through which combustion products could enter the building, and at least 48 in. from an adjacent building. When unit is located adjacent to public walkways, flue assembly must be at least 7 ft above grade.

NOTE: When unit is equipped with an accessory flue discharge deflector, allowable clearance is 18 inches.

Flue gas can deteriorate building materials. Orient unit such that flue gas will not affect building materials.

Adequate combustion-air space must be provided for proper operation of this equipment. Be sure that installation complies with all local codes and Section 5.3, Air for Combustion and Ventilation, NFGC (National Fuel Gas Code), ANSI (American National Standards Institute) Z223.1-1984 and addendum Z223.1a-1987. In Canada, installation must be in accordance with the CAN1.B149.1 and CAN1.B149.2 installation codes for gas burning appliances.

Flue vent discharge must have a minimum horizontal clearance of 4 ft from electric and gas meters, gas regulators, and gas relief equipment.

After unit is in position, remove shipping materials and rigging skids.

3

NOTES:

1.

Place unit on curb as close as possible to the duct end.

2.

Dimension in ( ) is in millimeters.

3.Hook rigging shackles through holes in base rail as shown in detail ‘‘A.’’ Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.

4.Weights include base unit without economizer. See Table 1 for unit operating weights with accessory economizer.

All panels must be in place when rigging.

UNIT

MAX

“A”

“B”

“C”

WEIGHT

48HJ

 

 

 

 

 

 

lb

kg

in.

mm

in.

mm

in.

mm

 

004

530

240

73.69

1872

35.50

902

33.31

847

005

540

245

73.69

1872

35.50

902

33.31

847

006

560

254

73.69

1872

35.50

902

33.31

847

007

615

279

73.69

1872

35.50

902

33.31

847

Fig. 4 — Rigging Details

Step 5 — Install Flue Hood — Flue hood is shipped screwed to the burner compartment access panel. Remove from shipping location and, using screws provided, install flue hood in location shown in Fig. 5 and 6.

For units being installed in California Air Quality Management Districts which require NOx emissions of 40 nanograms/ joule or less, kit CRLOWNOX001A00 must be installed.

Step 6 — Install Gas Piping — Unit is equipped for use with type of gas shown on nameplate. Refer to local building codes, or in the absence of local codes, to ANSI Z223.1-1984 and addendum Z223.1A-1987 entitled National Fuel Gas Code. In Canada, installation must be in accordance with the CAN1.B149.1 and CAN1.B149.2 installation codes for gas burning appliances.

For natural gas applications, gas pressure at unit gas connection must not be less than 4 in. wg or greater than 13 in. wg while the unit is operating. On 48HJ005-007 high-heat units, the gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13 in. wg while the unit is operating. For propane applications, the gas pressure must not be less than 5 in. wg or greater than 13 in. wg at the unit connection.

Size gas supply piping for 0.5 in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connection.

Support gas piping as shown in the table in Fig. 7. For example, a 3/4-in. gas pipe must have one field-fabricated support beam every 8 ft. Therefore, an 18-ft long gas pipe would have a minimum of 3 support beams, and a 48-ft long pipe would have a minimum of 6 support beams.

See Fig. 7 for typical pipe guide and locations of external manual gas shutoff valve.

Step 7 — Make Electrical Connections

Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA (National Fire Protection Association), latest edition, and local electrical codes. Do not use gas piping as an electrical ground. Failure to follow this warning could result in the installer being liable for personal injury of others.

FIELD POWER SUPPLY — All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by moving the black wire from the 230-v terminal on the transformer and connecting it to the 200-v terminal from the transformer.

Refer to unit label diagram for additional information. Pigtails are provided for field service. Use factory-supplied splices or UL (Underwriters’ Laboratories) approved copper connector.

When installing units, provide a disconnect per NEC.

All field wiring must comply with NEC and local requirements.

4

Table 1 — Physical Data

BASE UNIT 48

 

HJE/F/H/K/M/N004

 

HJD/E/F/G/H/K/L/M/N005

 

HJD/E/F/G/H/K/L/M/N006

 

HJD/HJE/HJF007

NOMINAL CAPACITY

 

3

 

4

 

5

 

6

OPERATING WEIGHT (lb)

 

 

 

 

 

 

 

 

Unit

 

530

 

540

 

560

 

615

With Durablade Economizer

 

564

 

574

 

594

 

649

With EconoMi$er

 

577

 

587

 

607

 

662

With MoistureMiser Dehumidification Package

 

548

 

558

 

578

 

633

Roof Curb

 

115

 

115

 

115

 

115

COMPRESSOR

 

 

 

 

 

Scroll

 

Quantity

 

1

 

1

 

1

 

1

 

 

 

 

Oil (oz)

 

42

 

53

 

50

 

60

REFRIGERANT TYPE

 

 

 

 

 

R-22

 

Operating Charge (lb-oz)

 

 

 

 

 

 

 

 

Standard Unit

 

5- 8

 

8-6

 

10- 0

 

9-10

 

 

 

 

Unit With MoistureMizer Dehumidification Package

 

8-13

 

11-2

 

12-13

 

13- 6

CONDENSER FAN

 

 

 

 

Propeller

 

Quantity...Diameter (in.)

 

1...22

 

1...22

 

1..22

 

1...22

 

 

 

 

Nominal Cfm

 

3500

 

3500

 

4100

 

4100

Motor Hp...Rpm

 

1/4...825

 

1/4...825

 

1/4...1100

 

1/4...1100

Watts Input (Total)

 

180

 

180

 

320

 

320

CONDENSER COIL

 

 

 

Enhanced Copper Tubes, Aluminum Lanced Fins

 

Standard Unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rows...Fins/in.

 

1...17

 

2..17

 

2...17

 

2...17

Total Face Area (sq ft)

 

14.6

 

16.5

 

16.5

 

16.5

Unit with MoistureMiser Dehumidification Package

 

 

 

 

 

 

 

 

Rows...Fins/in.

 

1...17

 

1...17

 

1...17

 

1...17

Total Face Area (sq ft)

 

3.9

 

3.9

 

3.9

 

3.9

EVAPORATOR FAN

 

 

 

Centrifugal Type, Belt Drive

 

Quantity...Size (in.)

 

1...10 x 10

 

1...10 x 10

 

1...10 x 10

 

1...10 x 10

 

 

 

 

Nominal Cfm

 

1200

 

1600

 

2000

 

2400

Maximum Continuous Bhp

Std

1.20

 

1.20

 

1.30/2.40*

 

2.40

 

Hi-Static

2.40

 

2.40

 

2.90

 

2.90

Motor Frame Size

Std

48

 

48

 

48/56*

 

56

 

Hi-Static

56

 

56

 

56

 

56

Fan Rpm Range

Std

760-1090

 

840-1185

 

1020-1460/1120-1585*

 

1120-1585

Motor Bearing Type

Hi-Static

1075-1455

 

1075-1455

 

1300-1685

 

1300-1685

 

Ball

 

Ball

 

Ball

 

Ball

Maximum Fan Rpm

 

2100

 

2100

 

2100

 

2100

Motor Pulley Pitch Diameter

Std

1.9/2.9

 

1.9/2.0

 

2.4/3.4

 

2.4/3.4

A/B (in.)

Hi-Static

2.8/3.8

 

2.8/3.8

 

3.4/4.4

 

3.4/3.4

Nominal Motor Shaft Diameter (in.)

Std

1/2

 

1/2

 

5/8

 

5/8

Fan Pulley Pitch Diameter (in.)

Hi-Static

5/8

 

5/8

 

5/8

 

5/8

Std

4.5

 

4.0

 

4.0

 

4.0

 

Hi-Static

4.5

 

4.0

 

4.5

 

4.5

Belt — Type...Length (in.)

Std

1...A...33

 

1...A...33

 

1....4...40

 

1...A...38

Pulley Center Line Distance (in.)

Hi-Static

1...A...39

 

1...A...39

 

1...A...40

 

1...A...40

 

10.0-12.4

 

10.0-12.4

 

14.7-15.5

 

14.7-15.5

Speed Change per Full Turn of

Std

65

 

70

 

75

 

95

Movable Pulley Flange (rpm)

Hi-Static

65

 

65

 

60

 

60

Movable Pulley Maximum Full

Std

5

 

5

 

6

 

5

Turns from Closed Position

Hi-Static

6

 

6

 

5

 

5

Factory Setting — Full Turns Open

Std

3

 

3

 

3

 

3

Factory Speed Setting (rpm)

Hi-Static

31/2

 

31/2

 

31/2

 

31/2

Std

890

 

980

 

1240

 

1304

Fan Shaft Diameter at Pulley (in.)

Hi-Static

1233

 

1233

 

1396

 

1396

 

5/8

 

5/8

 

5/8

 

5/8

EVAPORATOR COIL

 

Enhanced

Copper Tubes, Aluminum Double-Wavy Fins, Acutrol™ Metering Device

Rows...Fins/in.

 

2...15

 

2...15

 

4...15

 

4...15

 

 

 

 

Total Face Area (sq ft)

 

5.5

 

5.5

 

5.5

 

5.5

LEGEND

 

 

 

*Single phase/three phase.

 

Bhp —

Brake Horsepower

†Indicates automatic reset.

**48HJD005-007 and 48HJE004 (72,000 Btuh heat input) units have 2 burners.

 

 

 

 

48HJE005-007 and 48HJF004 (115,000 Btuh heat input) units and 48HJF005-

 

 

007 (150,000 Btuh Heat input) units have 3 burners.

 

 

††An LP kit is available as an accessory.

 

 

||Three-phase standard models have heating inputs as shown. Single-phase

 

 

standard models have one-stage heating with heating input values as follows:

 

 

48HJE004, 48HJD005,006 — 72,000 Btuh

 

 

48HJF004, 48HJE005,006 — 115,000 Btuh

 

 

48HJF005,006 — 150,000 Btuh

 

 

***California compliant three-phase models.

 

 

†††California SCAQMD compliant low NOx models have combustion products that

 

 

are controlled to 40 nanograms per joule or less.

5

Table 1 — Physical Data (cont)

BASE UNIT 48

HJE/F/H/K/M/N004

HJD/E/F/G/H/K/L/M/N005

 

HJD/E/F/G/H/K/L/M/N006

HJD/HJE/HJF007

FURNACE SECTION

 

 

 

 

 

 

 

 

Rollout Switch Cutout Temp (F)†

195

 

195

 

 

195

 

195

Burner Orifice Diameter (in. ...drill size)**

 

 

 

 

 

 

 

 

Natural Gas — Std

HJE .113...33

HJD .113...33

 

HJD .113...33

HJD .113...33

 

HJF .113...33

HJE .113...33

 

HJE .113...33

HJE .113...33

 

HJF .129...30

 

HJF .129...30

HJF .129...30

 

HJH .113...33

HJG .113...33

 

HJG .113...33

 

 

HJK .113...33

HJH .113...33

 

HJH .113...33

 

 

HJK .129...30

 

HJK .129...30

 

 

HJM .102...38

HJL .102...38

 

HJL .102...38

 

 

HJN .102...38

HJM .102...38

 

HJM .102...38

 

 

HJN .116...32

 

HJN .116...32

 

Liquid Propane — Alt††

HJE .089...43

HJD .089...43

 

HJD .089...43

HJD .089...43

 

HJF .089...43

HJE .089...43

 

HJE .089...43

HJE .089...43

 

HJF .102...38

 

HJF .102...38

HJF .102...38

 

HJH .082...45

HJG .089...43

 

HJG .089...43

 

 

HJK .082...45

HJH .089...43

 

HJH .089...43

 

 

HJK .102...38

 

HJK .102...38

 

 

HJM .082...45

HJL .082...45

 

HJL .082...45

 

 

HJN .082...45

HJM .082...45

 

HJM .082...45

 

Thermostat Heat Anticipator Setting (amps) 208/230/460 v

HJN .094...42

 

HJN .094...42

 

 

 

 

 

 

 

 

 

First Stage

.14

 

.14

 

 

.14

 

.14

Second Stage

.14

 

.14

 

 

.14

 

.14

Gas Input (Btuh)

 

 

 

 

 

 

 

 

First Stage/Second Stage

HJE|| 50,000/ 72,000

HJD||

50,000/ 72,000

 

HJD||

50,000/ 72,000

HJD||

50,000/ 72,000

 

HJF|| 82,000/115,000

HJE||

82,000/115,000

 

HJE||

82,000/115,000

HJE||

82,000/115,000

 

HJF|| 120,000/150,000

 

HJF|| 120,000/150,000

HJF|| 120,000/150,000

 

HJH*** —/ 72,000

HJG*** —/ 72,000

 

HJG*** —/ 72,000

 

 

HJK***—/115,000

HJH*** —/115,000

 

HJH*** —/115,000

 

 

HJK*** —/150,000

 

HJK*** —/150,000

 

 

HJM††† —/ 60,000

HJL††† —/ 60,000

 

HJL††† —/ 60,000

 

 

HJN††† —/ 90,000

HJM††† —/ 90,000

 

HJM†††—/ 90,000

 

 

HJN††† —/120,000

 

HJN††† —/120,000

 

Efficiency (Steady State) (%)

HJE 82

HJD 82

 

HJD 82

HJD 82

 

HJF 81

HJE 81

 

HJE 81

HJE 81

 

HJF 80

 

HJF 80

HJF 80

 

HJH 82

HJG 82

 

HJG 82

 

 

HJK 81

HJH 81

 

HJH 81

 

 

HJK 80

 

HJK 80

 

 

HJM 81

HJL 81

 

HJL 81

 

 

HJN 81

HJM 81

 

HJM 81

 

 

HJN 82

 

HJN 82

 

Temperature Rise Range

HJE 15-45

HJD 15-45

 

HJD 15-45

HJD 15-45

 

HJF 55-85

HJE 35-65

 

HJE 35-65

HJE 35-65

 

HJF 50-80

 

HJF 50-80

HJF 50-80

 

HJH 15-45

HJG 15-45

 

HJG 15-45

 

 

HJK 55-85

HJH 35-65

 

HJH 35-65

 

 

HJK 50-80

 

HJK 50-80

 

 

HJM 20-50

HJL 20-50

 

HJL 20-50

 

 

HJN 30-60

HJM 30-60

 

HJM 30-60

 

Manifold Pressure (in. wg)

HJN 40-70

 

HJN 40-70

 

 

 

 

 

 

 

 

 

Natural Gas — Std

3.5

 

3.5

 

 

3.5

 

3.5

Liquid Propane — Alt††

3.5

 

3.5

 

 

3.5

 

3.5

Maximum Static Pressure (in. wg)

1.0

 

1.0

 

 

1.0

 

1.0

Field Gas Connection Size (in.)

1/2

 

1/2

 

 

1/2

 

1/2

HIGH-PRESSURE SWITCH (psig)

 

 

 

 

 

 

 

 

Standard Compressor Internal Relief

 

 

450 ± 50

 

 

 

Cutout

 

 

 

428

 

 

 

Reset (Auto.)

 

 

 

320

 

 

 

LOSS-OF-CHARGE SWITCH/LOW-PRESSURE

 

 

 

 

 

 

 

 

SWITCH (Liquid LIne) (psig)

 

 

 

 

 

 

 

 

Cutout

 

 

 

7 ± 3

 

 

 

Reset (Auto.)

 

 

22 ± 5

 

 

 

FREEZE PROTECTION THERMOSTAT

 

 

 

 

 

 

 

 

Opens (F)

 

 

30 ± 5

 

 

 

Closes (F)

 

 

45 ± 5

 

 

 

OUTDOOR-AIR INLET SCREENS

 

 

Cleanable

 

 

 

Quantity...Size (in.)

 

 

1...20 x 24 x 1

 

 

 

RETURN-AIR FILTERS

 

 

Throwaway

 

 

 

Quantity...Size (in.)

 

 

2...16 x 25 x 2

 

 

 

LEGEND

Bhp — Brake Horsepower

*Single phase/three phase. †Indicates automatic reset.

**48HJD005-007 and 48HJE004 (72,000 Btuh heat input) units have 2 burners. 48HJE005-007 and 48HJF004 (115,000 Btuh heat input) units and 48HJF005007 (150,000 Btuh Heat input) units have 3 burners.

††An LP kit is available as an accessory.

||Three-phase standard models have heating inputs as shown. Single-phase standard models have one-stage heating with heating input values as follows:

48HJE004, 48HJD005,006 — 72,000 Btuh

48HJF004, 48HJE005,006 — 115,000 Btuh 48HJF005,006 — 150,000 Btuh

***California compliant three-phase models.

†††California SCAQMD compliant low NOx models have combustion products that are controlled to 40 nanograms per joule or less.

6

Carrier 48HJD005-007 User Manual

 

STANDARD

DURABLADE

 

 

CORNER

CORNER

CORNER

CORNER

BOTTOM POWER CHART, THESE HOLES REQUIRED FOR

UNIT

ECONOMI$ER

USE WITH ACCESSORY PACKAGES — CRBTMPWR001A00

UNIT

ECONOMIZER

WEIGHT

WEIGHT

WEIGHT

WEIGHT

WEIGHT

THROUGH CRBTMPWR004A00

48HJ

WEIGHT

WEIGHT

 

 

 

(A)

(B)

(C)

 

(D)

 

 

 

 

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

Lb

Kg

THREADED

WIRE

REQURED

004

530

240

34

15.4

47

21.3

127

57.6

122

55.3

138

62.6

143

64.9

CONDUIT SIZE

USE

HOLE SIZES (MAX.)

005

540

245

34

15.4

47

21.3

129

58.5

124

56.2

141

64.0

146

66.2

1/2

24 V

7/8[22.2]

006

560

254

34

15.4

47

21.3

134

60.8

129

58.5

146

66.2

151

68.5

3/4

Power*

11/8[28.4]

007

615

279

34

15.4

47

21.3

147

66.7

142

64.4

160

72.6

166

75.3

11/4

Power*

13/4[44.4]

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1/2″ NPT

Gas†

11/4[31.8]

 

CONNECTION SIZES

 

 

 

 

 

 

 

 

 

 

3/4″ NPT

Gas†

15/8[41.3]

A

13/8Dia [35] Field Power Supply Hole

 

 

 

 

 

 

 

 

 

*Select either 3/4″ or 11/4″ for power, depending on wire size.

B

2Dia [51] Power Supply Knockout

 

 

 

 

 

 

 

 

 

 

†Select either 1/2″ or 3/4″ for gas depending on gas connection.

C

13/4Dia [44] Charging Port Hole

 

 

 

 

 

 

 

 

 

 

 

 

 

D

7/8Dia [22] Field Control Wiring Hole

 

 

 

 

NOTES:

 

 

 

 

 

E

3/4-14 NPT Condensate Drain

 

 

 

 

 

1.

Dimensions in [

] are in millimeters.

 

 

F

5/8-14 NPT Gas Connection

 

 

 

 

 

2.

 

Center of gravity.

 

 

 

G

21/2Dia [64] Power Supply Knockout

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.

 

Direction of airflow.

 

 

 

 

 

 

 

 

 

 

 

 

 

4. On vertical discharge units, ductwork to be attached to accessory roof curb only. For horizontal dis-

 

 

 

 

 

 

 

 

 

 

 

charge units, field-supplied flanges should be attached to horizontal discharge openings, and all

 

 

 

 

 

 

 

 

 

 

 

ductwork should be attached to the flanges.

 

 

 

 

 

 

 

 

 

 

 

 

5. Minimum clearance (local codes or jurisdiction may prevail):

 

 

 

 

 

 

 

 

 

 

 

 

a. Between unit, flue side and combustible surfaces, 48 inches. (18 in. when using accessory flue

 

 

 

 

 

 

 

 

 

 

 

 

discharge deflector.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

b. Bottom of unit to combustible surfaces (when not using curb), 1 inch.

 

 

 

 

 

 

 

 

 

 

 

 

Bottom of base rail to combustible surfaces (when not using curb) 0 inches.

 

 

 

 

 

 

 

 

 

 

 

c. Condenser coil, for proper airflow, 36 in. one side, 12 in. the other. The side getting the greater

 

 

 

 

 

 

 

 

 

 

 

 

clearance is optional.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

d. Overhead, 60 in. to assure proper condenser fan operation.

 

 

 

 

 

 

 

 

 

 

 

 

e. Between units, control box side, 42 in. per NEC (National Electrical Code).

 

 

 

 

 

 

 

 

 

 

 

f. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.

 

 

 

 

 

 

 

 

 

 

 

g. Between unit and block or concrete walls and other grounded surfaces, control box side, 42 in.

 

 

 

 

 

 

 

 

 

 

 

 

per NEC.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

h. Horizontal supply and return end, 0 inches.

 

 

 

 

 

 

 

 

 

 

 

 

6. With the exception of the clearance for the condenser coil and combustion side as stated in notes

 

 

 

 

 

 

 

 

 

 

 

5a, b and c, a removable fence or barricade requires no clearance.

 

 

 

 

 

 

 

 

 

 

 

7. Units may be installed on combustible floors made from wood or Class A, B, or C roof covering

 

 

 

 

 

 

 

 

 

 

 

material if set on base rail.

 

 

 

 

 

 

 

 

 

 

 

 

 

8. The vertical center of gravity is 1′-6″ [457] up from the bottom of the base rail.

Fig. 5 — Base Unit Dimensions — 48HJ004-007

7

Fig. 6 — Flue Hood Details

LEGEND

NFGC — National Fuel Gas Code *Field supplied.

NOTE: Follow all local codes.

SPACING OF SUPPORTS

STEEL PIPE

SPACING OF SUPPORTS

NOMINAL DIAMETER

X DIMENSION

(in.)

(ft)

1/2

6

3/4 or 1

8

11/4 or larger

10

Fig. 7 — Gas Piping Guide (With Accessory Thru-the-Curb Service Connections)

Install conduit through side panel openings indicated in Fig. 5. Route power lines through connector to terminal connections as shown in Fig. 8.

Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (also see Tables 2A-2D). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in Tables 2A-2D, Note 2 to determine the percent voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Carrier warranty.

NOTE: If accessory thru-the-bottom connections and roof curb are used, refer to the Thru-the-Bottom Accessory Installation Instructions for information on power wiring and gas connection piping. The power wiring, control wiring and gas piping can be routed through field-drilled holes in the basepan. The basepan is specially designed and dimpled for drilling the access connection holes.

FIELD CONTROL WIRING — Install a Carrier-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature in accordance with thermostat installation instructions.

Route thermostat cable or equivalent single leads of colored wire from subbase terminals through connector on unit to lowvoltage connections (shown in Fig. 9).

Connect thermostat wires to matching screw terminals of low-voltage connection board. See Fig. 9.

NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft, use no. 16 AWG insulated wire (35 C minimum). For over 75 ft, use no. 14 AWG insulated wire (35 C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.

Pass the control wires through the hole provided in the corner post; then feed wires through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. See Fig. 10. The raceway provides the UL required clearance between highand low-voltage wiring.

HEAT ANTICIPATOR SETTINGS — Set heat anticipator settings at .14 amp for first stage and .14 for second stage heating, when available.

Step 8 — Adjust Factory-Installed Options

MOISTUREMISER DEHUMIDIFICATION PACKAGE — MoistureMiser package operation can be controlled by field installation of a Carrier-approved humidistat (Fig. 11). To install the humidistat:

1.Route humidistat cable through hole provided in unit corner post.

2.Feed wires through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. See Fig. 10. The raceway provides the UL-required clearance between highand low-voltage wiring.

3.Use a wire nut to connect humidistat cable into lowvoltage wiring as shown in Fig. 12.

APOLLO CONTROL — The optional Apollo control is used to actively monitor all modes of operation as well as indoor (evaporator) fan status, filter status, and indoor-air quality. The Apollo control is designed to work with Carrier TEMP and VVT® systems.

The thermostat must be wired to the Apollo Control before starting the unit. Refer to the Apollo Control installation instructions for information on installing the thermostat.

DISCONNECT SWITCH — The optional disconnect switch is non-fused. The switch has the capability of being locked in place for safety purposes.

8

 

LEGEND

C

Contactor

COMPS — Compressors

EQUIP

Equipment

GND

Ground

IFC

Indoor (Evaporator)

 

Fan Contactor

NEC

National Electrical Code

TB

Terminal Block

Fig. 8 — Power Wiring Connections

RACEWAY LOW VOLTAGE

 

INTEGRATED GAS UNIT

 

 

 

 

CONNECTIONS

 

CONTROLLER (IGC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LEGEND

 

AHA —

Adjustable Heat Anticipator

HOLE IN END PANEL (HIDDEN)

CC

Cooling Compensator

 

TC — Thermostat-Cooling

Fig. 10 — Field Control Wiring Raceway

TH

Thermostat-Heating

 

 

Field Wiring

 

Factory Wiring

NOTE: Connect Y2 when unit is equipped with an integrated economizer.

Fig. 9 — Low-Voltage Connections With or

Without Economizer

9

Table 2A — 48HJ Electrical Data Standard Motor (Units Without Electrical Convenience Outlet)

 

 

NOMINAL

VOLTAGE

COMPRESSOR

OFM

IFM

COMBUSTION

POWER

MINIMUM UNIT

UNIT

SUPPLY

DISCONNECT

VOLTAGE

RANGE

FAN MOTOR

48HJ

 

 

 

 

WITH OUTLET

SIZE*

(V-Ph-Hz)

 

 

 

 

 

 

 

 

 

Min

Max

RLA

LRA

FLA

FLA

FLA

MCA

MOCP†

FLA

LRA

 

 

 

 

 

208/230-1-60

187

254

16.0

88.0

0.7

4.9

.57

25.6/25.6

35/35

25/25

101/101

004

 

208/230-3-60

187

254

10.3

77.0

0.7

4.9

.57

18.5/18.5

25/25

18/18

90/ 90

(3 Tons)

 

460-3-60

414

508

5.1

39.0

0.4

2.2

.30

9.0

15

9

46

 

 

575-3-60

518

632

4.2

31.0

0.4

2.2

.30

7.3

15

7

36

 

 

208/230-1-60

187

254

23.7

129.0

0.7

4.9

.57

35.2/35.2

45/45

34/34

142/142

005

 

208/230-3-60

187

254

13.5

99.0

0.7

4.9

.57

22.5/22.5

30/30

22/22

112/112

(4 Tons)

 

460-3-60

414

508

7.4

49.5

0.4

2.2

.30

11.9

15

12

56

 

 

575-3-60

518

632

5.8

40.0

0.4

2.2

.30

9.3

15

9

45

 

 

208/230-1-60

187

254

28.8

169.0

1.5

8.8

.57

46.3/46.3

60/60

45/45

216/216

006

 

208/230-3-60

187

254

17.3

123.0

1.5

5.8

.57

28.9/28.9

35/35

28/28

168/168

(5 Tons)

 

460-3-60

414

508

9.0

62.0

0.8

2.6

.30

14.7

20

14

84

 

 

575-3-60

518

632

7.1

50.0

0.8

2.6

.30

11.6

15

11

67

007

 

208/230-3-60

187

254

20.5

156.0

1.4

5.8

.57

32.8/32.8

40/40

32/32

200/200

 

460-3-60

414

508

9.6

70.0

0.6

2.6

.30

15.2

20

15

92

(6 Tons)

 

 

575-3-60

518

632

7.7

56.0

0.6

2.6

.30

12.2

15

13

78

 

 

Table 2B — 48HJ Electrical Data Standard Motor (Units With Electrical Convenience Outlet)

 

 

NOMINAL

VOLTAGE

 

 

 

 

COMBUSTION

POWER

MINIMUM UNIT

UNIT

COMPRESSOR

OFM

IFM

SUPPLY

DISCONNECT

VOLTAGE

RANGE

FAN MOTOR

48HJ

 

 

 

 

WITH OUTLET

SIZE*

(V-Ph-Hz)

 

 

 

 

 

 

 

 

 

Min

Max

RLA

LRA

FLA

FLA

FLA

MCA

MOCP†

FLA

LRA

 

 

 

 

 

208/230-1-60

187

254

16.0

88.0

0.7

4.9

.57

31.6/31.6

40/40

30/30

106/106

004

 

208/230-3-60

187

254

10.3

77.0

0.7

4.9

.57

24.5/24.5

30/30

24/24

95/95

(3 Tons)

 

460-3-60

414

508

5.1

39.0

0.4

2.2

.30

11.7

15

11

48

 

 

575-3-60

518

632

4.2

31.0

0.4

2.2

.30

9.5

15

9

38

 

 

208/230-1-60

187

254

23.7

129.0

0.7

4.9

.57

41.2/41.2

50/50

39/39

147/147

005

 

208/230-3-60

187

254

13.5

99.0

0.7

4.9

.57

28.5/28.5

35/35

27/27

117/117

(4 Tons)

 

460-3-60

414

508

7.4

49.5

0.4

2.2

.30

14.6

20

14

58

 

 

575-3-60

518

632

5.8

40.0

0.4

2.2

.30

11.5

15

11

47

 

 

208/230-1-60

187

254

28.8

169.0

1.5

8.8

.57

52.3/52.3

60/60

50/50

221/221

006

 

208/230-3-60

187

254

17.3

123.0

1.5

5.8

.57

34.9/34.9

40/40

34/34

173/173

(5 Tons)

 

460-3-60

414

508

9.0

62.0

0.8

2.6

.30

17.4

20

17

86

 

 

575-3-60

518

632

7.1

50.0

0.8

2.6

.30

13.8

20

13

69

007

 

208/230-3-60

187

254

20.5

156.0

1.4

5.8

.57

38.8/38.8

45/45

37/37

205/205

 

460-3-60

414

508

9.6

70.0

0.6

2.6

.30

17.9

20

17

94

(6 Tons)

 

 

575-3-60

518

632

7.7

56.0

0.6

2.6

.30

14.3

20

15

79

 

 

LEGEND

FLA — Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration

IFM — Indoor (Evaporator) Fan Motor

LRA — Locked Rotor Amps

MCA — Minimum Circuit Amps

MOCP— Maximum Overcurrent Protection

NEC — National Electrical Code

OFM — Outdoor (Condenser) Fan Motor

RLA — Rated Load Amps

UL — Underwriters’ Laboratories

*Used to determine minimum disconnect per NEC.

†Fuse or HACR circuit breaker.

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

= 100 x

max voltage deviation from average voltage

average voltage

 

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

Average Voltage = 452 + 464 + 455 3

=

1371

3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance= 100 x

7

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

10

Table 2C — 48HJ High-Static Motor Units Without Electrical Convenience Outlet

 

NOMINAL

VOLTAGE

COMPRESSOR

 

 

COMBUSTION

POWER

MINIMUM UNIT

UNIT

OFM

IFM

DISCONNECT

VOLTAGE

RANGE

(each)

FAN MOTOR

SUPPLY

48HJ

 

 

 

SIZE*

(V-Ph-Hz)

 

 

 

 

 

 

 

 

 

 

 

Min

Max

RLA

LRA

FLA

FLA

RLA

MCA

MOCP†

FLA

 

LRA

 

 

 

 

208/230-3-60

187

254

10.3

77.0

0.7

5.8

0.6

19.4/19.4

25/25

19/19

 

120/120

004

460-3-60

414

508

5.1

39.0

0.4

2.6

0.3

9.4

15

9

 

60

 

575-3-60

518

632

4.2

31.0

0.4

2.6

0.3

7.7

15

8

 

48

 

208/230-3-60

187

254

13.5

99.0

0.7

5.8

0.6

23.4/23.4

30/30

23/23

 

142/142

005

460-3-60

414

508

7.4

49.5

0.4

2.6

0.3

12.3

15

12

 

71

 

575-3-60

518

632

5.8

40.0

0.4

2.6

0.3

9.7

15

9

 

57

 

208/230-3-60

187

254

17.3

123.0

1.5

7.5

0.6

30.6/30.6

35/35

30/30

 

187/187

006

460-3-60

414

508

9.0

62.0

0.8

3.4

0.3

15.5

20

15

 

94

 

575-3-60

518

632

7.1

50.0

0.8

3.4

0.3

12.2

15

12

 

76

 

208/230-3-60

187

254

20.5

156.0

1.4

7.5

0.6

30.6/30.6

35/35

30/30

 

187/187

007

460-3-60

414

508

9.6

70.0

0.6

3.4

0.3

15.5

20

15

 

94

 

575-3-60

518

632

7.7

56.0

0.6

3.4

0.3

12.2

15

12

 

76

Table 2D — 48HJ High-Static Motor Units With Electrical Convenience Outlet

 

NOMINAL

VOLTAGE

COMPRESSOR

 

 

COMBUSTION

POWER

MINIMUM UNIT

UNIT

OFM

IFM

DISCONNECT

VOLTAGE

RANGE

(each)

FAN MOTOR

SUPPLY

48HJ

 

 

 

SIZE*

(V-Ph-Hz)

 

 

 

 

 

 

 

 

 

 

 

Min

Max

RLA

LRA

FLA

FLA

RLA

MCA

MOCP†

FLA

LRA

 

 

 

208/230-3-60

187

254

10.3

77.0

0.7

5.8

0.6

25.4/25.4

30/30

25

124/124

004

460-3-60

414

508

5.1

39.0

0.4

2.6

0.3

12.1

15

12

63

 

575-3-60

518

632

4.2

31.0

0.4

2.6

0.3

9.8

15

10

50

 

208/230-3-60

187

254

13.5

99.0

0.7

5.8

0.6

29.4/29.4

35/35

29

146/146

005

460-3-60

414

508

7.4

49.5

0.4

2.6

0.3

15.0

20

14

73

 

575-3-60

518

632

5.8

40.0

0.4

2.6

0.3

11.8

15

11

59

 

208/230-3-60

187

254

17.3

123.0

1.5

7.5

0.6

36.6/36.6

40/40

36

192/192

006

460-3-60

414

508

9.0

62.0

0.8

3.4

0.3

18.2

20

18

96

 

575-3-60

518

632

7.1

50.0

0.8

3.4

0.3

14.4

20

14

77

 

208/230-3-60

187

254

20.5

156.0

1.4

7.5

0.6

40.5/40.5

45/45

39

224/224

007

460-3-60

414

508

9.6

70.0

0.6

3.4

0.3

18.7

25

18

104

 

575-3-60

518

632

7.7

56.0

0.6

3.4

0.3

15.0

20

15

89

LEGEND

FLA — Full Load Amps

HACR — Heating, Air Conditioning and Refrigeration

IFM — Indoor (Evaporator) Fan Motor

LRA — Locked Rotor Amps

MCA — Minimum Circuit Amps

MOCP— Maximum Overcurrent Protection

NEC — National Electrical Code

OFM — Outdoor (Condenser) Fan Motor

RLA — Rated Load Amps

UL — Underwriters’ Laboratories

*Used to determine minimum disconnect per NEC.

†Fuse or HACR circuit breaker.

NOTES:

1.In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker. UL, Canada units may be fuse or circuit breaker.

2.Unbalanced 3-Phase Supply Voltage

Never operate a motor where a phase imbalance in supply voltage is greater than 2%. Use the following formula to determine the percent of voltage imbalance.

= 100 x

max voltage deviation from average voltage

average voltage

 

Example: Supply voltage is 460-3-60.

AB = 452 v BC = 464 v AC = 455 v

Average Voltage = 452 + 464 + 455 3

=

1371

3

= 457

Determine maximum deviation from average voltage. (AB) 457 – 452 = 5 v

(BC) 464 – 457 = 7 v (AC) 457 – 455 = 2 v

Maximum deviation is 7 v.

Determine percent of voltage imbalance.

% Voltage Imbalance= 100 x

7

457

= 1.53%

This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.

IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.

11

OPTIONAL DURABLADE ECONOMIZER — The optional economizer hood assembly is packaged and shipped in the filter section. Damper blades and control boards are installed at the factory and the economizer is shipped in the vertical discharge position.

NOTE: Horizontal discharge block-off plate is shipped with the air hood package. If unit is to be used for vertical discharge application, discard this plate.

Assembly:

1.Determine if ventilation air is required in building. If so, determine the minimum amount to be supplied by each unit and record quantity of ventilation air needed for use in Step 7.

2.Remove filter access panel by raising panel and swinging panel outward. Panel is now disengaged from track and can be removed. No tools are required to remove filter access panel. Remove outdoor-air opening panel. Save panels and screws. See Fig. 13. Remove economizer, and remove optional outdoor-air damper hood package from filter section (located behind economizer).

3.Assemble outdoor-air hood top and side plates as shown in Fig. 14. Install seal strips on hood top and sides. Put aside screen retainer and retainer screw for later assembly. Do not attach hood to unit at this time.

4.Slide economizer into unit and secure with screws. See Fig. 15.

NOTE: Be sure to engage rear economizer flange under tabs in vertical return-air opening.

5.To convert to horizontal discharge application:

a.Rotate economizer 90 degrees until the economizer motor faces the condenser section (see Fig. 16).

b.Remove tape and shipping screw, rotate the barometric relief damper cover 90 degrees.

 

 

 

LEGEND

C

Contactor (Compressor)

CCH

Crankcase Heater

COMP

Compressor

FU

Fuse

HU

Humidistat

IFM

Indoor (Evaporator) Fan Motor

LLSV

Liquid Line Solenoid Valve

S-LPS

Low-Pressure Switch (Subcooler Only)

TRAN

Transformer

 

 

 

Factory Wiring

 

 

 

Accessory or Optional Wiring

 

 

 

c.Install horizontal discharge block-off plate over the opening on the access panel. (Block-off plate MUST be installed before installing hood assembly.) See Fig. 17.

6.Remove 12-pin blue and yellow wire jumper plug from factory wiring harness and store. Insert economizer plug into 12-pin plug of factory wiring harness. Remove tape and shipping screw from barometric relief damper. See Fig.18.

7.If ventilation air is not required, proceed to Step 8. If ventilation air is required, determine minimum position setting for required airflow. See Fig. 19. Adjust minimum position setting by adjusting the screws on the position setting bracket. Slide bracket until the top screw is in the position determined by Fig. 19. Tighten screws.

8.Remove tape from outdoor-air thermostat (OAT). Fasten OAT to inside of hood using screws and speed clips provided. See Fig. 20. Make sure OAT terminals are positioned up.

MOISTUREMISER

% RELATIVE HUMIDITY

Fig. 11 — Accessory Field-Installed Humidistat

Fig. 12 — Typical MoistureMiser Dehumidification Package Humidistat Wiring

(208/230-V Unit Shown)

12

9.Replace outdoor-air opening panel using screws from Step 2. Replace filter access panel. Ensure the filter access panel slides along the tracks and is securely engaged.

10.Fasten hood top and side plate assembly (Fig. 14) to outdoor-air opening panel with screws provided.

11.Place knob supplied with economizer on OAT. See Fig. 20. Set for 3° F below indoor room thermostat setting. If accessory enthalpy control (EC) is used in place of OAT, see instructions shipped with EC for installation and adjustment. See Fig. 20.

12.Connect OAT per Fig. 21.

13.Slide outdoor-air inlet screen into screen track on hood side plate. While holding screen in place, fasten screen retainer to hood using screws provided.

NOTE: Refer to Fig. 22 for economizer barometric relief damper characteristics.

FILTER

OUTDOOR-AIR

COMPRESSOR

ACCESS

ACCESS

PANEL

OPENING

PANEL

Fig. 13 — Typical Access Panel Locations

Fig. 14 — Outdoor-Air Hood Details

ECONOMIZER

ECONOMIZER

ECONOMIZER

TOP

CONTROL BOARD

PLUG

MOTOR

SCREW

SHIPPING

SCREW

Fig. 15 — Durablade Economizer Installed in Unit

ECONOMIZER

CONTROL

BOARD

BAROMETRIC

RELIEF

DAMPER

ECONOMIZER

PLUG

ECONOMIZER

MOTOR

Fig. 16 — Horizontal Durablade Economizer

Installation

BLOCK-OFF PLATE

Fig. 17 — Horizontal Discharge Block-Off Plate

13

U-SHAPED HOLE

(NOT SHOWN)

ECONOMIZER

PLUG

WIRING

HARNESS

Fig. 18 — Typical Durablade Economizer and

 

OAT

Wiring Harness

 

TOP

(TERMINALS ARE UP)

 

 

UNIT

OUTSIDE AIR

SCREEN

Example:

Given —

Negative Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . .0.1 in. wg

Outdoor Airflow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1100 cfm

Determine —

Setting = 6

Fig. 19A — Durablade Economizer Damper

Minimum Position Setting

0

1

2

3

4

5

6

7

8

9

Fig. 19B — Durablade Economizer Minimum

Position Damper Setting

ENTHALPY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTROL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

RE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

V

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

.

 

OPEN

 

 

 

POSITIONMINIMUM

 

 

 

 

 

 

 

 

 

 

 

B

 

 

 

 

 

 

 

 

 

 

 

 

S

C

TR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

O

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

 

 

 

 

 

T

 

3

 

 

1

 

 

 

 

 

 

 

 

 

P

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HOOD

 

 

 

T1

 

4

 

 

2

 

 

5

 

 

 

 

 

 

P1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T ID

 

 

 

 

8 S

CONT

OR

CONT

 

 

 

 

 

 

 

 

 

 

 

 

%

 

1 R

 

 

 

 

 

 

 

 

 

Y

 

 

IMUH

 

9 U

 

UNPOWERED

 

 

 

 

 

 

 

 

 

 

 

 

90

 

 

C

 

A

 

 

 

 

 

 

 

 

30

60

70

 

 

8

T

ACT

 

CTS

3

 

 

ENTHALPY

 

 

 

60

 

DAMPER

 

 

1

A

5A

TE

 

2

 

 

 

 

 

 

 

 

 

 

m

 

 

 

 

 

 

10

 

 

 

 

D

CW

A

2

RA

 

SHO

 

TR

 

 

 

 

50

 

 

 

 

C

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

TINGS:

 

 

 

 

 

 

 

 

OUTDOOR

65

 

 

 

 

 

SETPOINTS

 

M

ST

HIGH

 

 

C

 

 

 

 

 

 

 

 

 

 

 

 

 

24V

 

 

 

 

55

 

OPEN

 

 

B

 

 

3 .

 

WN

 

 

A

 

 

 

 

 

 

 

 

 

A

 

 

 

1

A

IN

 

 

 

CONTROL

 

 

F

5

 

 

 

 

 

 

 

A

RUN,

 

 

1

TR1

 

 

 

°

7

 

 

 

 

 

 

 

.

 

ENTHALPY

 

 

 

 

 

 

 

 

 

 

 

 

 

1

IN

 

 

 

 

 

 

 

TEMP

 

 

 

 

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

IN

5A

 

 

 

 

 

 

 

 

.

70

 

 

 

 

 

CCW

 

1

 

 

 

 

 

 

 

 

 

 

 

CLOSED DAMPER

 

 

T

3

 

 

 

 

 

 

 

 

 

8

 

 

 

 

 

VDC

.

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

85

REV.

 

97-3672

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 20 — Outdoor-Air Thermostat/

Enthalpy Control Installation

Fig. 21 — Wiring Connections for Outdoor-Air Thermostat

14

 

0.90

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.80

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

wg)(in.

0.70

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.60

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DROP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRESSURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.40

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.00

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100

200

300

400

500

600

700

800

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

 

 

Fig. 22 — Durablade Economizer Barometric

Relief Damper Characteristics

OPTIONAL ECONOMI$ER — See Fig. 23 for EconoMi$er component locations.

1.To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. Remove the indoor coil access panel and discard. See Fig. 24.

If installing an optional Power Exhaust Assembly, refer to the EconoMi$er Power Exhaust Installation Instructions.

Controller should be mounted in vertical position as shown in Fig. 23.

2.Assemble the hood assembly as follows:

Remove the EconoMi$er hood from its packaging. Remove shipping brackets holding hood package to EconoMi$er. Locate the outdoor-air opening panel. See Fig. 25. Remove hood assembly shipping brackets located on the back (sloped) side of the EconoMi$er assembly. These brackets are used to retain the hood assembly during shipping only.

3.Install the 1/8 x 3/4-in. seal strip on the exhaust air hood side panels and the bottom bracket. Assemble the exhaust air hood to the outdoor-air opening panel as shown in Fig. 25, using the screws provided. Do not attach hood assembly to unit at this time.

4.Install the 1/8 x 3/4 in. seal strip on the outdoor-air hood top and side panels. Assemble the outdoor-air hood to the outdoor-air opening panel as shown in Fig. 26, using the screws provided. Do not attach hood assembly to the unit at this time.

5.Slide the outdoor-air inlet screens into the screen track on the hood side panels. While holding the screens in place, fasten the screen retainer to the hood using the screws provided. Repeat the process for the barometric exhaust air screen. Do not attach completed (Fig. 27) hood assembly to unit at this time.

6.Install the EconoMi$er assembly into the rooftop unit. See Fig. 28 and 29.

NOTE: Be sure to engage rear EconoMi$er flange under tabs in return-air opening of the unit base. See Fig. 28.

7.Install the outdoor-air block-off plate, then secure the EconoMi$er with the screws provided. See Fig. 29.

8.Remove and discard the 12-pin jumper plug from the unit wiring harness located int he upper left corner and insert

the EconoMi$er plug into the unit wiring harness. Refer to wiring diagram Fig. 30 and 31. Also refer to Fig. 32 if installing an accessory power exhaust.

9.Install the complete hood assembly on the unit and secure using the screws provided.

10.Remove the indoor fan motor access panel. See Fig. 33.

11.Mount the supply-air temperature sensor to the lower left

portion of the indoor blower housing with the two

(2) screws provided (see Fig. 34). Connect the violet and pink wires to the corresponding connections on the supply-air temperature sensor. Replace the indoor fan motor access panel.

ECONOMI$ER

CONTROLLER

PLUG

GEAR-DRIVEN

 

 

DAMPER

OUTDOOR AIR

TEMPERATURE

SENSOR

ACTUATOR

BAROMETRIC RELIEF DAMPERS

Fig. 23 — Economizer Component Locations

OUTDOOR-AIR

FILTER ACCESS

OPENING PANEL

PANEL

Fig. 24 — Typical Access Panel Locations

OUTDOOR AIR

OPENING PANEL EXHAUST AIR HOOD TOP

SCREEN

RETAINER

 

EXHAUST AIR

SEAL STRIP

HOOD SIDES

 

EXHAUST AIR SCREEN

EXHAUST AIR BOTTOM BRACKET

Fig. 25 — Exhaust Air Hood Assembly

15

Loading...
+ 33 hidden pages