Xylem MM 316E User Manual

Series 47 and 247 Mechanical Water Feeders
Series 47-2 and 247-2 Combination Mechanical
INSTRUCTION MANUAL
MM-316E
Water Feeder/Low Water Cut-Off
Applications:
For steam and hot water boilers with cold water feed, to maintain a minimum safe water level independent of electrical service.
• Before using this product read and understand instructions.
CAUTION
WARNING
• Save these instructions for future reference.
• All work must be performed by qualified personnel trained in the proper application, instal­lation, and maintenance of plumbing, steam, and electrical equipment and/or systems in
accordance with all applicable codes and ordinances.
• To prevent serious burns, the boiler must be cooled to 80˚F (27˚C) and the pressure must be 0 psi (0 bar) before servicing.
• To prevent electrical shock, turn off the electrical power before making electrical connections.
• The low water cut-off switch must be installed in series with all other limit and operating controls installed on the boiler. After installation, check for proper operation of all of the limit and operating controls, before leaving the site.
• We recommend that secondary (redundant) Low Water Cut-Off controls be installed on all steam boilers with heat input greater than 400,000 BTU/hour or operating above 15 psi
steam pressure. At least two controls should be connected in series with the burner
control circuit to provide safety redundancy protection should the boiler experience a low-water condition. Moreover, at each annual outage, the low water cutoffs should be dismantled, inspected, cleaned, and checked for proper calibration and performance.
• Boiler manufacturer schematics should always be followed. In the event that the boiler manufacturer's schematic does not exist, or is not available from the boiler manufacturer,
refer to the schematics provided in this document.
• To prevent a fire, do not use this low water cut-off to switch currents over 10.2A, 1/2 HP at 120 VAC or 5.1A, 1/2 HP at 240 VAC, unless a starter or relay is used in conjunction with it.
California Proposition 65 warning! This product contains chemicals known to the
state of California to cause cancer and birth defects or other reproductive harm. Previous controls should never be installed on a new system. Always install new
controls on a new boiler or system.
Series 47-2 Combination Water Feeder Low Water
WARNING
!
!
Series 47
Water Feeder
Cut-Off
Series 247
Water Feeder
Series 247-2 Combination
Water Feeder Low Water
Cut-Off
Water Feeder Closing Level
Low
Water Cut-Off
Burner Starts
2
1
/4" (57mm)
37/16" (87mm)
23/4" (70mm)
Feeder keeps water level 37/16" (87mm) above center of lower gauge glass tapping
If extreme priming or foaming causes water line to fall 13/16" (30mm) below feeder closing level, cut-off switch stops the burner
When water level is restored 1/2" (13mm) above emergency. Cut-off switch starts burner and the water feeder resumes control
Motor Switch Rating (Amperes)
Voltage Full Load Locked Rotor Pilot Duty
120 VAC 10.2 61.2
125 VA at 120
240 VAC 5.1 30.6
or 240 VAC, 60 Hz
OPERATION
Series 47/47-2 Operating Levels
All Models
Maximum Water Pressure: 150 psi (10.5 kg/cm2)
Maximum Water Temp: 120˚F (49˚C)
Water Connection Size:
1
/2” NPT
47/47-2
Maximum Boiler Pressure: 25 psi (1.76 kg/cm2)
247/247-2
Maximum Boiler Pressure: 30 psi (2.1 kg/cm
2
)
Electrical Ratings
Series 47 Water Feeders and Series 47-2 Combination Water Feeder/Low Water Cut-Off maintain minimum water level in the boiler during normal operation.
Series 47-2 Combination Water Feeder/Low Water Cut-Off allows the burner to operate on demand as the water level is restored to its proper level.
Series 47-2 Combination Water Feeder/Low Water Cut-Off shuts off the burner if the boiler water level drops 1 3/16” (30mm) below the water feeder’s closing level.
2
Failure to follow this warning could cause property damage, personal inj ury or death.
CAUTION:
A more frequent replacement interval may be necessary based on the condition of the unit at time of inspection. McDonnell Miller s warranty is one (1) year from date of installation or two (2) years from the date of manufacture.
&
'
11
7
/8"
PARALLEL TO BOILER
OUT
IN
11
7
/8"
10
5
/8"
OUT
IN
(alternate water equalizing tapping used)
OUT
IN
10
5
/8"
13
5
/8"
9"
9"
13
5
/8"
(alternate water equalizing tapping used)
IN OUT
10
5
/8"
RIGHT ANGLED TO BOILER
RIGHT ANGLED TO BOILER
WITH TURNED Y FITTINGS
PARALLEL TO BOILER
WITH TURNED Y FITTINGS
3
STEP 1 - Determine Best Position to Install the Water Feeder
(to clear obstructions that may be encountered on the side of the boiler).
INSTALLATION –
TOOLS NEEDED:
Two (2) pipe wrenches, and one (1) flathead screwdriver.
Series 247 and 247-2 Operating Level
Water feeder figures are +/- 1/4" (6.4mm) Burner figures are +/- 1/8" (3.2mm)
TOP VIEWS
Valve Off -7/16" (11.1mm) Casting Line - 0"
Burner On - 1/4" (6.4mm) Burner Off - 3/4" (19mm)
E
F
D
10-5/8"
(270mm)
G
d. Determine the position of the black "Y" casting (F).
If gauge glass tappings (D) and (E) are less than 10
5
8" (270 mm) apart, install the black "Y" casting (F) as depicted in the diagram to the top right.
OR
If gauge glass tappings (D) and (E) are greater than 10
5
8" (270 mm) apart, invert the black "Y" casting (F) as depicted in the diagram to the bottom right.
OR
If gauge glass tappings (D) and (E) are greater than 14" (356 mm) apart, invert the black "Y" casting (F) as depicted in the diagram to the bottom right and install a longer nipple (G).
4
STEP 2 - Preparation (Installing Quick Hook-up Fittings to Water Feeder)
a. Turn the boiler off.
A
b. Drain the water in the boiler until the level falls below the lower
gauge glass connection (A). Allow the boiler to cool to 80˚F (27 ˚C) and allow the pressure to release to 0 psi (0 bar).
B
C
c. Remove the water glass (B) and gauge glass connections (C)
from the boiler.
OFF
ON
INVERTED “Y” CASTING
Note:
F
Reverse union nuts, packing and plug.
G
Tighten top nut securely.
F
G
g. Slide the black "Y" (F) casting over the nipple (G)
in accordance with Step 2d, but do not tighten.
L
F
M
N
L
P
U
U
K
Q
Q
h. 1). Apply sealant to the external threads of the nipple (L)
of the upper "Y" connection. Using a pipe wrench, tighten the nipple (L) into the 1/2" (15 mm) NPT tapping (M) of the black "Y" casting (F). Slide union nut (U) over nipple (L). Using a pipe wrench tighten the upper “Y” connection (N) to nipple (L). Tighten to 54 ft
lb (74 Nm).
2). Apply sealant to the external threads of the tailpiece (P) of the lower "Y" connection. Slide union nut (U) over tailpiece (P). Using a pipe wrench, tighten the tailpiece (P) into the 1/2” (15 mm) NPT tapping (Q) in the lower half of body (K). Tighten to 54 ft
lb (74 Nm).
5
J
H
K
e. Remove the plug (H) from the 1/2" (15 mm) NPT
tapping (J) in the top of the feeder body (K).
J
G
K
No Threads
f. Apply thread sealant to the external threads. Using
a pipe wrench, tighten the 1/2" (15 mm) NPT nipple (G) into the tapping (J) on the top of the feeder (K) to approximately 54 ft
lb (74 Nm).
Note: Nipple (G) is only threaded on one end.
Upper “Y”
Lower “Y”
When using pipe or tape sealant on the external threads of pipes or fittings, follow the manufacturers instructions. Use sparingly and do not place on the first thread.
!
IMPORTANT
6
STEP 3 - Installing Series 47 Water Feeder or Series 47-2 Combination Water
Feeder/Low Water Cut-Off with Quick Hook-Up Fittings to Boiler
a. Apply thread sealant to the external threads
of the "Y" fittings (T). Using the pipe wrench, install them in the boiler gauge glass tappings (S), and tighten to approximately 54 ft
lb (74 Nm).
Tighten both union nuts (U).
b. Reinstall water glass and gauge connections to “Y”
fittings (T).
When using pipe or tape sealant on the external threads of pipes or fittings, follow the manufacturers instructions. Use sparingly and do not place on the first thread.
!
IMPORTANT
U
N
L
U
U
T
S
R
i. Using the pipe wrench, tighten the furnished pipe
plug into the open tapping (R) on the lower half of the feeder float body in accordance with the position diagrams in Step 1. Tighten the plug to approximately 20 ft
lb (27.3 Nm).
STEP 4 - Installing Series 247/247-2 Water Feeder to Boiler
Burner
Boiler
City Water Supply
Return
Header
Series 247 Water Feeder
Casting Line
ByPass
Valve
Pipe the Series 247/247-2 water feeder so that the line on the casting is 3" (76mm) above the minimum safe operating level as specified by the boiler manufacturer.
Recommended Piping
STEP 5 - Piping the valve on the Models 47/47-2 and 247/247-2
TO BOILER
By-Pass
Valve
Swing Check
STEP 6 - Electrical Wiring (Only for Series 47-2 & 247-2)
AA
a. Using the flathead screwdriver, loosen the two
(2) screws that secure the switch cover (AA).
Remove cover.
7
!
IMPORTANT
Boiler manufacturer schematics should always be followed. In the event that the boiler manufacturer's schematic does not exist, or is not available from the boiler manufacturer, refer to the schematics provided in this document.
a. Follow the drawing to the right for piping the valve
to the boiler and city water supply. When piping the valve, remember to leave room for servicing the valve.
b. Piping the valve this way will aid in troubleshooting
the valve and piping in the future.
8
STEP 7 - Testing and Inspection
V
CLOSING
LEVEL
INSTALLATION COMPLETE
C.
Line
Load
N.
N.C.
O.
C.
Load
or Burner Circuit
Low Water Alarm
N.
N.C.
Neutral
120 V.A.C.
or 24 V.A.C.
Supply
HOT
O.
b. Based on the mode of operation required for
your application, complete the appropriate corresponding step.
When the water feeder is used as a low water cut-off switch and/or a low water alarm
, connect the "Hot" wire to the "Common" contact. Using a flat head screw driver, tighten the screw. Connect the low water alarm to the “Normally Open” contact and tighten the screw. Connect the burner or load circuit wire to the “Normally Closed” contact and tighten the screw.
OR
When the water feeder is used as a pilot switch to a holding coil of a motor starter or relay,
connect as shown in the diagram to the right.
Low water cut-off switch and/or low water alarm
Pilot switch for motor starter or relay
The feeder should be blown down after initial installation before leaving site. It should also be blown down as recommended in the Maintenance section of these instructions.
• Burner should be on and water level above 'closing level' of feeder.
Slowly open the water feeder blow down valve 'V' which will lower the water level in the float chamber. As water flows out the blow down pipe, you should begin to hear the feeder valve open.
• If the feeder has a #2 switch, the burner should stop.
• Close the water feeder blow down valve 'V'. The water level should return to a safe operating level and the burner should turn on.
To prevent serious personal injury from steam pipe blow down, connect a drain pipe to the control opening to avoid exposure to steam discharge.
Failure to follow this caution could cause personal injury.
!
CAUTION
Blow Down of Feeder
9
X
Z
TO BOILER
Feed
Valve
By-Pass
Valve
Check Valve
WATER
SUPPLY
Make sure that the water level in the boiler is above the closing level of the feeder.
Close valve 'X' and slowly open union 'Z' to determine if valve is leaking.
• If water is leaking from the union, the valve needs to be serviced.
• If no water leaks from the union, the feeder operation is not the cause of the flooding.
Broken Union Test
E
D
B
H
x 4
A. Using a 1/2" socket wrench, unscrew the four (4) hex-head
bolts (B) that secure the strainer basket (H) to the valve assembly (E).
B. Using a 13/16" socket wrench, unscrew the cartridge (D)
and remove.
C. Clean any debris (scale, rust, etc.) from strainer and cartridge.
Poppet inside cartridge must move freely. Replace if debris cannot be removed or poppet does not move freely.
D. Lubricate cartridge o-rings using silicone type lubricant and
re-install.
E. Re-install strainer basket.
Removal of cartridge and strainer for inspection and cleaning
10
TROUBLESHOOTING
The following is intended as a guide to determine why the feeder may not be operating as intended. Please note that there can be system and installation issues that can affect the operation of the feeder. This includes but is not limited to the following:
• Piping not installed properly • Priming and foaming of boiler water
• Faulty check valve in return header • Delay in condensate returning to boiler
• Tankless coil leaking
Boiler is getting too much water.
a) Cause: There is something preventing the valve
(cartridge poppet) from completely closing.
Test: Perform broken union test.
Solution: Remove and inspect cartridge. Clean or
replace as necessary.
b) Cause: By-pass valve is leaking.
Test: Perform broken union test.
Solution: Repair or replace valve.
c) Cause: Float chamber clogged with sediment.
Test: Open blow-down valve. If there is little or no
water flow, the chamber may be clogged with sediment.
Solution: Remove bottom of float chamber. Clean sediment from chamber, float and bellows mechanism. Replace control if necessary.
d) Cause: Float has filled with water.
Solution: Replace float.
e) Cause: Equalizing piping is plugged.
Solution: Clean or replace piping.
f) Cause: Water supply is above 150 psi.
Solution: Install pressure reducing valve to reduce water pressure.
Boiler is not getting enough water.
a) Cause: There is something preventing the valve
(cartridge poppet) from fully opening.
Test: Perform broken union test.
Solution: Remove and inspect cartridge. Clean or
replace as necessary.
b) Cause: Strainer clogged with sediment.
Test: Perform broken union test.
Solution: Remove and inspect strainer. Clean or
replace as necessary.
c) Cause: Float chamber clogged with sediment.
Test: Open blow-down valve. If there is little or no water flow, the chamber may be clogged with sediment.
Solution: Remove bottom of float chamber and clean sediment from chamber, float and bellows mechanism. Replace control if necessary.
d) Cause: Feed line between valve and boiler is partially
plugged.
Test: Perform broken union test. With union broken, there should be water flowing through the piping from the boiler.
Solution: Clean or replace piping.
e) Cause: Feed line between valve and city water supply
is plugged.
Solution: Clean or replace piping.
f) Cause: Water supply pressure is less than boiler
pressure.
Solution: Reduce boiler pressure or convert to pumped return.
11
MAINTENANCE
SCHEDULE:
Weekly
• Blow down when boiler is in operation.
Annually
• Disassemble and inspect/clean strainer screen.
Replace if screen is torn or not able to be cleaned.
• Remove and inspect/clean cartridge. Replace if
poppet does not move freely or debris cannot be removed.
• Remove lower float chamber and inspect internal parts. Clean out all mud, silt, sediment and debris from
chamber, float mechanism and other waterside components.
• Inspect equalizing piping. Clean or replace as required.
• Check all wires for brittle or worn insulation.
• Check for leaks at gasket surfaces and solder joints.
Replace entire unit including equalizing piping every 10 years.
More frequent cleaning or replacement may be required if used in locations where water treatment is required or in applications with high make-up water requirements.
NOTE
Use clean water to rinse components and surfaces. DO NOT use sharp objects to scrape off any accumulations
of sediment or debris.
Unit is making noise.
a) Cause: Under certain system conditions, there may be
a vibration when the valve mechanism (cartridge poppet) is slightly open.
Solution: Install a pressure reducing valve, such as the Bell & Gossett B-38, in the inlet water line before the feeder valve.
Burner switch not working. a) Cause: Cam worn or broken.
Solution: Replace cam assembly (CO-106/302900).
b) Cause: Linkages not transferring float movement
to switch.
Solution:
• Linkage pins may be worn or broken which would require purchasing a new valve assembly (SA47-101-102/341600).
• Float may be damaged, sediment may have accumulated in chamber or equalizing piping may be plugged. Perform testing to determine what the problem may be and correct.
Water leaking from bellows
a) Cause: Continuous exposure to chemicals or water with
pH higher than 9.0 can cause the solder to deteriorate. Solution: Remove source of chemicals or consider
replacing control with one that is suitable for the application.
TROUBLESHOOTING (cont'd)
Xylem
1) The tissue in plants that brings water upward from the roots;
2) a leading global water technology company.
We’re 12,000 people unified in a common purpose: creating innovative solutions to meet our world’s water needs. Developing new technologies that will improve the way water is used, conserved, and re-used in the future is central to our work. We move, treat, analyze, and return water to the environment, and we help people use water efficiently, in their homes, buildings, factories and farms. In more than 150 countries, we have strong, long-standing relationships with customers who know us for our powerful combination of leading product brands and applications expertise, backed by a legacy of innovation.
For more information on how Xylem can help you, go to www.xyleminc.com
Xylem Inc.
8200 N. Austin Avenue Morton Grove, Illinois 60053 Phone: (847) 966-3700 Fax: (847) 965-8379 www.xyleminc.com/brands/mcdonnellmiller
McDonnell & Miller is a trademark of Xylem Inc. or one of its subsidiaries.
© 2013 Xylem Inc. MM-316E July 2013 Part No. 210386
Loading...